ABB ACS880-01 Series Quick Installation Manual

Type
Quick Installation Manual
English . . . . . . . . .3
English – USA . . .9
Dansk . . . . . . . . .17
Deutsch . . . . . . .23
Español . . . . . . .29
Suomi. . . . . . . . .35
Français. . . . . . .41
Italiano. . . . . . . .47
Nederlands . . . .53
Polski . . . . . . . . .59
Português . . . . .65
Русский . . . . . . .71
Svenska . . . . . . .77
Türkçe . . . . . . . .83
中文. . . . . . . . . . .89
ABB INDUSTRIAL DRIVES
ACS880-01 drives
Frames R1 to R3
Quick installation guide
3AUA0000085966 Rev H MUL
EFFECTIVE: 2019-05-
08
EN
USA
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
List of related manuals
You can find manuals and other product documents in PDF format on the Internet. See
section Document library on the Internet on the inside of the back cover. For manuals
not available in the Document library, contact your local ABB representative.
The code below opens an online listing of the manuals applicable to the product:
Drive hardware manuals and guides Code (English)
ACS880-01 hardware manual 3AUA0000078093
ACS880-01 quick installation guide for frames
R1 to R3
3AUA0000085966
ACS880-01 quick installation guide for frames
R4 and R5
3AUA0000099663
ACS880-01 quick installation guide for frames
R6 to R9
3AUA0000099689
ACS880-01 +P940 drives for cabinet
installation supplement
3AUA0000145446
ACS880-01 assembly drawings for cable entry
boxes of IP21 frames R5 to R9
3AUA0000119627
ACS-AP-x assistant control panels user’s
manual
3AUA0000085685
Vibration dampers for ACS880-01 drives
(frames R4 and R5, option +C131) installation
guide
3AXD50000010497
Vibration dampers for ACS880-01 drives
(frames R6 to R9, option +C131) installation
guide
3AXD50000013389
ACS880-01 +C132 marine type-approved drives
supplement
3AXD50000010521
ACS880-01 +N7502 drives for SynRM motors
(0.8 to 200
kW) supplement
3AXD50000029482
Drive firmware manuals and guides
ACS880 primary control program firmware
manual
3AUA0000085967
Quick start-up guide for ACS880 drives with
primary control program
3AUA0000098062
Option manuals and guides
Manuals and quick guides for I/O extension
modules, fieldbus adapter, etc.
ACS880-01 manuals
EN – Quick installation guide 3
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
EN – Quick installation guide
This guide instructs briefly how to install the drive. For more detailed instructions,
engineering guide lines, technical data and complete safety instructions, see the
hardware manual (www.abb.com/drives
: Select Document Library and search for
document number 3AUA0000078093 [English]).
Obey the safety instructions
The floor material below the drive must be non-flammable.
Check if capacitors need to be reformed
Reform the capacitors if the drive has not been powered (either in storage or unused)
for a year or more.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY: 17, 18, 19, … for 2017, 2018, 2019,
WW: 01, 02, 03, … for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur:
Only qualified electrical professionals are allowed to install and maintain the
drive.
Never work on the drive, motor cable or motor when main power is applied. If
the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
Never work on the control cables when power is applied to the drive or to the
external control circuits.
Always ground the drive, the motor and adjoining equipment to the protective
earth (PE) bus of the power supply.
Make sure that debris from borings and grindings does not enter the drive when
installing.
Do not connect the drive to a voltage higher than what is marked on the type
designation label.
3AUA0000085966 Rev H
4 EN – Quick installation guide
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
(3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Typical power cable sizes are listed in table J on page 100. For the conditions of the
sizing, see the hardware manual.
Ensure the cooling
See table B on page 97 for the losses and the cooling air flow through the drive. The
allowed operating temperature range of the drive without derating is -15 to +40 °C.
Protect the drive and input power cable
See table B on page 97. Check that the operating time of the fuse is below 0.5
seconds.
Install the drive on the wall
See figure A on page 97.
Check the compatibility with IT (ungrounded), corner-
grounded delta, midpoint-grounded delta and TT systems
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. For other systems, see the hardware manual
and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [English]).
EN – Quick installation guide 5
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
.
A = TN-S system, B1 = Corner-grounded system, B2 = Midpoint-grounded system, C = IT system
WARNING! Do not install the drive with EMC filter options +E200 and +E202
connected to a system that the filter is not suitable for. This can cause danger,
or damage the drive.
WARNING! Do not install the drive with the ground-to-phase varistor
connected to a system that the varistor is not suitable for. If you do, the varistor
circuit can be damaged. See the drive hardware manual.
Note: With option +E201, remove EMC AC, EMC DC and VAR screws in for systems
other than TN-S if not removed at the factory. For more information, contact ABB.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before you
connect it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure F on page 98. Measure the insulation resistance between
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
6 EN – Quick installation guide
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
please consult the manufacturer’s instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
Attach the warning stickers in local languages
Connect the power cables
See figures C, D, E and G. Use symmetrical shielded cable for motor cabling.
1. Undo the mounting screws at the sides of the front cover.
2. Remove the cover by sliding it forward.
3. Attach the residual voltage warning sticker in the local language to the control
panel mounting platform.
4. Remove the rubber grommets from the lead-through plate for the cables to be
connected.
5. IP21 units
: Fasten the cable connectors (included in the delivery in a plastic bag)
to the cable lead-through plate holes.
6. Prepare the ends of the input power and motor cables as illustrated in the figure.
7. Ground the cable shields 360 degrees in the cable connectors (IP21 units) or
under the clamps (IP55 units).
8. Connect the twisted shield of the input cable to the PE terminal.
9. Connect the PE conductor of the input cable to the additional PE terminal.
10. Connect the twisted shield of the motor cable and resistor cable (if present) to the
grounding terminal.
11. Connect the phase conductors of the input, motor and resistor cables. Tighten the
screws.
12. Install the control cable grounding shelf in the cable entry box.
13. Secure the cables mechanically outside the drive.
14. Ground the motor cable shield at the motor end. For minimal interference, make a
360-degree grounding at the cable lead-through, or keep the pig tail short.
Connect the control cables
See figure H.
EN – Quick installation guide 7
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
1. Cut adequate holes into the rubber grommets and slide the grommets onto the
cables. Slide the cables through the holes of the bottom plate and attach the
grommets to the holes.
2. Strip the cable ends and cut to suitable length (note the extra length of the
grounding conductors).
3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in
the cable entry box.
4. Ground the pair-cable shields to the grounding clamp. Leave the other end of the
shields unconnected or ground them indirectly via a high-frequency capacitor with
a few nanofarads, eg, 3.3 nF / 630 V.
5. Connect the conductors to the appropriate terminals of the control board (see
page 8).
6. Wire the optional modules if included in the delivery.
7. Reinstall the front cover.
Note for fieldbus cabling. See figure I.
1. Install the additional grounding shelf.
2. Ground the outer shields of the cables 360 degrees at a grounding clamp.
3. Knock out holes in the cable entry box cover for the cables to be installed. Install
the cable entry box cover.
4. Plug the connector to the fieldbus module.
Default I/O connections
The default I/O connections of the Factory macro of the ACS880 primary control
program are shown below.
8 EN – Quick installation guide
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
XPOW External power input
1 +24VI
24 V DC, 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF -10 V DC, R
L
1…10 kohm
3 AGND Ground
4 AI1+ Speed reference 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+
By default not in use. 0(4)…20 mA, R
in
=
100 ohm
7 AI2-
J1 J1 AI1 current/voltage selection jumper
J2 J2 AI2 current/voltage selection jumper
XAO Analog outputs
1 AO1 Motor speed rpm 0…20 mA, R
L
<
500 ohm
2 AGND
3 AO2
Motor current 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Drive-to-drive link
1 B
Drive-to-drive link
2 A
3 BGND
J3 J3 Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
11 NC
Ready
250 V AC / 30 V DC
2 A
12 COM
13 NO
21 NC
Running
250 V AC / 30 V DC
2 A
22 COM
23 NO
31 NC
Faulted(-1)
250 V AC / 30 V DC
2 A
32 COM
33 NO
XD24 Digital interlock
1 DIIL Run enable
2 +24VD +24 V DC 200 mA
1)
3 DICOM Digital input ground
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Digital input/output ground
J6 Ground selection switch
XDIO Digital input/outputs
1 DIO1 Output: Ready
2 DIO2 Output: Running
XDI Digital inputs
1 DI1 Stop (0) / Start (1)
2 DI2 Forward (0) / Reverse (1)
3 DI3 Reset
4 DI4 Acceleration & deceleration select
5 DI5 Constant speed 1 (1 = On)
6 DI6 By default not in use.
XSTO Safe torque off
1 OUT1
Safe torque off. Both circuits must be
closed for the drive to start.
2 SGND
3 IN1
4 IN2
X12 Safety functions module connection
X13 Control panel connection
X205 Memory unit connection
Wire sizes:
0.5 … 2.5 mm
2
(24…12 AWG)
Tightening
torques: 0.5 N·m
(5 lbf·in) for both
stranded and
solid wiring.
1)
Total load
capacity of these
outputs is 4.8 W
(200 mA / 24 V)
minus the power
taken by DIO1 and
DIO2.
Fault
EN – USA quick installation guide 9
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
EN – USA quick installation guide
This guide instructs briefly how to install the drive. For more detailed instructions,
engineering guide lines, technical data and complete safety instructions, see the
hardware manual (www.abb.com/drives
: Select Document Library and search for
document number 3AUA0000078093 [English]).
Obey the safety instructions
The floor material below the drive must be non-flammable.
Check if capacitors need to be reformed
Reform the capacitors if the drive has not been powered (either in storage or unused)
for a year or more.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY: 17, 18, 19, … for 2017, 2018, 2019,
WW: 01, 02, 03, … for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur:
Only qualified electrical professionals are allowed to install and maintain the
drive.
Never work on the drive, motor cable or motor when main power is applied. If
the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
Never work on the control cables when power is applied to the drive or to the
external control circuits.
Always ground the drive, the motor and adjoining equipment to the protective
earth (PE) bus of the power supply.
Make sure that debris from borings and grindings does not enter the drive when
installing.
Do not connect the drive to a voltage higher than what is marked on the type
designation label.
10 EN – USA quick installation guide
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
(3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
Select the power cables
Select the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Typical power cable sizes are listed in table J on page 100. For the conditions of the
sizing, see the hardware manual.
Ensure the cooling
See table B on page 101 for the losses and the cooling air flow through the drive. The
allowed operating temperature range of the drive without derating is -5 to +104 °F.
Protect the drive and input power cable
See table B on page 101. Check that the operating time of the fuse is below 0.5
seconds.
Install the drive on the wall
See figure A on page 101.
Check the compatibility with IT (ungrounded), corner-
grounded delta, midpoint-grounded delta and TT systems
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. For other systems, see the hardware manual
and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [English]).
EN – USA quick installation guide 11
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
A = TN-S system, B1 = Corner-grounded system, B2 = Midpoint-grounded system, C = IT system
WARNING! Do not install the drive with EMC filter options +E200 and +E202
connected to a system that the filter is not suitable for. This can cause danger,
or damage the drive.
WARNING! Do not install the drive with the ground-to-phase varistor
connected to a system that the varistor is not suitable for. If you do, the varistor
circuit can be damaged. See the drive hardware manual.
Note: With option +E201, remove EMC AC, EMC DC and VAR screws in for systems
other than TN-S if not removed at the factory. For more information, contact ABB.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before you
connect it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure F on page 102. Measure the insulation resistance between
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 C
B2
PE
L2
L3
L1
N
A
12 EN – USA quick installation guide
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
please consult the manufacturer’s instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
Connect the power cables
See figures C, D and E on page 101 and 102.
1. Undo the two mounting screws at the sides of the front cover.
2. Remove the cover by sliding it forward.
3. Attach the residual voltage warning sticker in the local language to the control
panel mounting platform.
4. Remove the rubber grommets from the lead-through plate for the cables to be
connected.
5. Fasten the cable conduits to the cable lead-through plate holes. Strip the cable
ends. Slide the cables through the connectors.
6. Connect the grounding conductors to the grounding terminals.
7. Connect the phase conductors of the input and motor cables. Tighten the screws.
8. Units with option +D150:
Connect the brake resistor cable conductors to the R+
and R- terminals.
9. Install the control cable grounding shelf in the cable entry box.
10. Connect the motor cable at the motor end.
Connect the control cables
See figure G on page 102.
1. Fasten the cable conduits to the cable lead-through plate holes. Slide the cables
through the connectors.
2. Strip the cable ends and cut to suitable length (note the extra length of the
grounding conductors).
3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in
the cable entry box.
EN – USA quick installation guide 13
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
4. Ground the pair-cable shields to the grounding clamp. Leave the other end of the
shields unconnected or ground them indirectly via a high-frequency capacitor with
a few nanofarads, eg, 3.3 nF / 630 V.
5. Connect the conductors to the appropriate terminals of the control board (see
page 14).
6. Wire the optional modules if included in the delivery. For fieldbus cabling, see
page 99.
7. Reinstall the front cover.
Default I/O connections
The default I/O connections of the Factory macro of the ACS880 primary control
program are shown below.
14 EN – USA quick installation guide
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
XPOW External power input
1 +24VI
24 V DC, 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF -10 V DC, R
L
1…10 kohm
3 AGND Ground
4 AI1+ Speed reference 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+
By default not in use. 0(4)…20 mA, R
in
=
100 ohm
7 AI2-
J1 J1 AI1 current/voltage selection jumper
J2 J2 AI2 current/voltage selection jumper
XAO Analog outputs
1 AO1 Motor speed rpm 0…20 mA, R
L
<
500 ohm
2 AGND
3 AO2
Motor current 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Drive-to-drive link
1 B
Drive-to-drive link
2 A
3 BGND
J3 J3 Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
11 NC
Ready
250 V AC / 30 V DC
2 A
12 COM
13 NO
21 NC
Running
250 V AC / 30 V DC
2 A
22 COM
23 NO
31 NC
Faulted(-1)
250 V AC / 30 V DC
2 A
32 COM
33 NO
XD24 Digital interlock
1 DIIL Run enable
2 +24VD +24 V DC 200 mA
1)
3 DICOM Digital input ground
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Digital input/output ground
J6 Ground selection switch
XDIO Digital input/outputs
1 DIO1 Output: Ready
2 DIO2 Output: Running
XDI Digital inputs
1 DI1 Stop (0) / Start (1)
2 DI2 Forward (0) / Reverse (1)
3 DI3 Reset
4 DI4 Acceleration & deceleration select
5 DI5 Constant speed 1 (1 = On)
6 DI6 By default not in use.
XSTO Safe torque off
1 OUT1
Safe torque off. Both circuits must be
closed for the drive to start.
2 SGND
3 IN1
4 IN2
X12 Safety functions module connection
X13 Control panel connection
X205 Memory unit connection
Wire sizes:
0.5 … 2.5 mm
2
(24…12 AWG)
Tightening
torques: 0.5 N·m
(5 lbf·in) for both
stranded and
solid wiring.
1)
Total load
capacity of these
outputs is 4.8 W
(200 mA / 24 V)
minus the power
taken by DIO1 and
DIO2.
Fault
EN – USA quick installation guide 15
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
UL checklist
The drive must be installed in clean air according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically
conductive dust. (IP55)- UL Type 12 enclosure. This enclosure provides
protection from airborne dust and light sprays or splashing water from all
directions.
The maximum ambient air temperature is 40 °C (104 °F) at rated current. The
current is derated for 40 to 55 °C (104 to 131 °F).
The drive is suitable for use in a circuit capable of delivering not more than
100,000 rms symmetrical amperes, 500 V maximum. The ampere rating is based
on tests done according to UL 508C.
The cables located within the motor circuit must be rated for at least 75 °C
(167 °F) in UL-compliant installations.
The input cable must be protected with fuses. Circuit breakers must not be used
without fuses in the USA. Suitable IEC (class aR) fuses and UL (class T) fuses
are listed in the hardware manual. For suitable circuit breakers, contact your local
ABB representative.
For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local
codes. To fulfill this requirement, use the UL classified fuses.
For installation in Canada, branch circuit protection must be provided in
accordance with the Canadian Electrical Code and any applicable provincial
codes. To fulfill this requirement, use the UL classified fuses.
The drive provides overload protection in accordance with the National Electrical
Code (NEC).
16 EN – USA quick installation guide
DA
USA
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
DA – Hurtig installationsvejledning 17
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
DA – Hurtig installationsvejledning
Denne guide er en kortfattet vejledning i, hvordan du installerer frekvensomformeren.
Hvis du vil have mere detaljerede instruktioner, tekniske retningslinjer, tekniske data
og komplette sikkerhedsinstruktioner, kan du se hardwaremanualen
(www.abb.com/drives
: Vælg Document Library, og søg efter dokumentnummer
3AUA0000078093 (på engelsk).
Overhold sikkerhedsinstruktionerne
Gulvmaterialet under frekvensomformeren skal være ikke-brandbart.
Kontrollér, om det er nødvendigt at reformere
kondensatorerne
Reformér kondensatorerne, hvis frekvensomformeren ikke har været tilsluttet strøm i
over et år (opbevaret eller ikke anvendt).
Du kan bestemme produktionsdatoen ud fra serienummeret, som du finder på
mærkatet med typebetegnelse på frekvensomformeren. Serienummeret har formatet
MYYWWRXXXX. YY og WW angiver produktionsåret og ugen på følgende måde:
YY: 17, 18, 19, … for 2017, 2018, 2019,
WW: 01, 02, 03, … for uge 1, uge 2, uge 3,
ADVARSEL! Følg disse instruktioner. Hvis de ignoreres, kan det resultere i
personskader, dødsfald eller skade på udstyret:
Kun autoriserede elinstallatører må udføre installation og vedligeholdelse af
frekvensomformeren.
Undlad at arbejde med frekvensomformeren, motorkablet eller motoren, når
tilslutning til nettet er foretaget. Hvis frekvensomformeren allerede er tilsluttet
netforsyningen, skal du vente 5 minutter efter frakobling af netspændingen.
Du må aldrig arbejde med signalkablerne, når netspændingen er tilsluttet
frekvensomformeren eller de eksterne styrekredse.
Frekvensomformeren, motoren og tilstødende udstyr skal altid jordes med
strømforsyningens beskyttelsesjordbus (PE).
Undgå, at der trænger smuds fra boringer og sliberester ind i
frekvensomformeren under installation.
Frekvensomformeren må ikke tilsluttes til en spænding, der er højere end den,
der er angivet på mærkatet med typebetegnelse.
3AUA0000085966 Rev H
18 DA – Hurtig installationsvejledning
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
Oplysninger om reformering af kondensatorer findes i Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 (på engelsk)), som findes på internettet på
www.abb.com/drives/documents
.
Vælg effektkabler
Vælg en størrelse til kablerne i henhold til lokale forskrifter til at bære den nominelle
strøm, der er anført på mærkatet med typebetegnelsen på din frekvensomformer.
Typiske størrelser på effektkabler er vist i tabellen J på side 100. Se
hardwaremanualen for oplysninger om betingelserne for størrelse.
Sørg for kølingen
Se tabel B på side 97 for tabene og frekvensomformerens gennemstrømning af
kølende luft. Frekvensomformerens tilladte driftstemperaturområde uden reduktion er
-15 til +40 °C.
Beskyt frekvensomformeren og forsyningskabel
Se tabellen B på side 97. Ud fra sikringens smeltekurve kontrolleres, at smeltetiden
er under 0,5 sekunder.
Installer frekvensomformeren på væggen
Se figur A på side 97.
Kontrollér kompatibiliteten med IT-net (ujordede),
hjørnejordede delta-, midtpunktsjordet delta- og
TT-systemer
Standardfrekvensomformeren med tilsluttet jord-til-fase-varistorer kan installeres
sammen med et symmetrisk jordet TN-S-system. Oplysninger om andre systemer
finder du i hardwaremanualen samt i ACS880 frames R1 to R11 EMC filter and
ground-to-phase varistor disconnecting instructions (3AUA0000125152 (på
engelsk)).
DA – Hurtig installationsvejledning 19
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
A = TN-S-system, B1 = Hjørnejordet system, B2 = Midtpunktsjordet system, C = IT-system
ADVARSEL! Installer ikke en frekvensomformer med tilsluttet EMC-filter
ekstraudstyr +E200 og +E202 til et system, hvortil filtret ikke er egnet. Dette
kan medføre fare eller ødelægge frekvensomformeren.
ADVARSEL! Installer ikke frekvensomformeren med tilsluttet jord-til-fase-
varistor til et system, hvortil varistoren ikke er egnet. Hvis du gør det, kan
varistorkredsløbet tage skade. Se frekvensomformerens hardwaremanual.
Bemærk! Hvis du anvender ekstraudstyr +E201, skal du fjerne EMC AC-, EMC DC-
og VAR-skruerne i andre systemer end TN-S, hvis de ikke allerede er fjernet på
fabrikken. Kontakt ABB for at få yderligere oplysninger.
Kontroller isoleringen på forsynings- og motorkabel samt
motoren
Kontrollér, at isoleringen af forsyningskablet er i overensstemmelse med de nationale
forskrifter, inden du tilslutter det til frekvensomformeren.
Kontrollér isoleringen af motorkabel og motor, når kablet er koblet fra
frekvensomformeren. Se figur F på side 98. Mål isolationsmodstanden mellem hver
faseleder og beskyttelsesjordens leder med en målespænding på 1000 V DC.
Isolationsmodstanden på en ABB-motor skal være større end 100 Mohm
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
20 DA – Hurtig installationsvejledning
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
(referenceværdi ved 25 °C eller 77 °F). Se producentens instruktioner for at få
oplysninger om isolationsmodstanden på andre motorer. Bemærk! Fugt inden i
motorhuset reducerer isolationsmodstanden. Hvis der er mistanke om fugt, skal
motoren tørres, og målingen gentages.
Fastgør advarselsmærkaterne på de lokale sprog
Tilslut effektkablerne.
Se figurerne C, D, E og G. Anvend et skærmet symmetrisk kabel til motoren.
8. Løsn monteringsskruerne i siderne af frontdækslet.
9. Fjern dækslet ved at skubbe det fremad.
10. Fastgør advarselsmærkatet om restspænding på det lokale sprog på
betjeningspanelets monteringsplatform.
11. Fjern gummimufferne fra gennemføringspladen, så kablerne kan tilsluttes.
12. IP21-enheder
: Fastspænd kabelstikkene (inkluderet i leveringen i en plastikpose)
via hullerne i kablets gennemføringsplade.
13. Forbered enderne på forsynings- og motorkablet som vist på figuren.
14. Jord kabelskærmene 360 grader i kabelstikkene (IP21-enheder) eller under
bøjlerne (IP55-enheder).
15. Forbind den snoede del af forsyningskablets skærm med PE-terminalen.
16. Forbind forsyningskablets PE-leder med den ekstra PE-terminal.
17. Forbind den snoede skærm i motorkablet og i modstandskablet (hvis det findes) til
jordterminalen.
18. Forbind faselederne på forsynings-, motor- og modstandskablerne. Stram
skruerne.
19. Installér medfølgende jordingsterminal for styrekabler i kabelsektionen.
20. Fastgør kablerne mekanisk uden for frekvensomformeren.
21. Tilslut motorkablets skærm i motoren. Opnå minimal interferens ved at lave en
360 graders jording ved kabelgennemføringen eller holde den snoede
kobberskærm kort.
DA – Hurtig installationsvejledning 21
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
Tilslut styrekablerne
Se figur H.
1. Klip passende huller i gummimufferne, og skub mufferne på kablerne. Før
kablerne gennem hullerne på bundpladen, og sæt mufferne fast i hullerne.
2. Afisoler kabelenderne, og skær dem af i en passende længde (bemærk
jordledernes ekstra længde).
3. Jord de ydre skærme på alle kabler 360 grader ved en jordingsklemme i
kabelsektionen.
4. Jord skærmene på de parsnoede kabler til jordingsklemmen. Lad den anden
ende af skærmene være frakoblet, eller slut dem indirekte til jord med en
højfrekvenskondensator på nogle få nanofarad (f.eks. 3,3 nF / 630 V).
5. Forbind kablets ledere til de korrekte klemmer på styrekortet (se side 22).
6. Forbind de valgfrie moduler, hvis de indgår i leverancen.
7. Genmonter frontdækslet.
Bemærkning til kabelføring for fieldbuskommunikation. Se figur I.
1. Montér den ekstra jordingsterminal.
2. Jord de udvendige skærme på kabler 360 grader ved en jordingsklemme.
3. Lav huller i kabelindgangskassens dæksel til de kabler, der skal installeres.
Monter kabelindgangskassens dæksel.
4. Tilslut stikket til fieldbusmodulet.
I/O-standardtilslutninger
I/O-standardtilslutninger til fabriksmakroen for det primære styreprogram for ACS880
er vist herunder.
22 DA – Hurtig installationsvejledning
EN
DA
DA
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
XPOW Ekstern strømforsyning
1 +24VI
24 V DC, 2 A
2 GND
XAI Referencespænding og analoge indgange
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF -10 V DC, R
L
1…10 kohm
3 AGND Jord
4 AI1+ Hastighedsreference 0(2)…10 V,
R
in
> 200 kohm
5 AI1-
6 AI2+
Som standardindstilling ubenyttet.
0(4)…20 mA, R
in
= 100 ohm
7 AI2-
J1 J1 AI1-jumper til valg af strøm/spænding
J2 J2 AI2-jumper til valg af strøm/spænding
XAO Analoge udgange
1 AO1 Motorhastighed o/min 0…20 mA,
R
L
< 500 ohm
2 AGND
3 AO2
Motorstrøm 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Drev-til-drev-forbindelse
1 B
Drev-til-drev-forbindelse
2 A
3 BGND
J3 J3 Afbryder til drev-til-drev-forbindelse
XRO1, XRO2, XRO3 Relæudgange
11 NC
Startklar
250 V AC / 30 V DC
2 A
12 COM
13 NEJ
21 NC
Kører
250 V AC / 30 V DC
2 A
22 COM
23 NEJ
31 NC
Fejl(-1)
250 V AC / 30 V DC
2 A
32 COM
33 NEJ
XD24 Digital interlock
1 DIIL Start frigiv
2 +24VD +24 V DC 200 mA
1)
3 DICOM Jording af digital indgang
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Jording af digital indgang/udgang
J6 Afbryder til valg af jord
XDIO Digitale indgange/udgange
1 DIO1 Udgang: Startklar
2 DIO2 Udgang: Kører
XDI Digital indgang
1 DI1 Stop (0) / Start (1)
2 DI2 Forlæns (0) / Baglæns (1)
3 DI3 Nulstil
4 DI4 Acceleration og deceleration vælg
5 DI5 Konstant hastighed 1 (1 = Til)
6 DI6 Som standardindstilling ubenyttet.
XSTO Safe torque off
1 OUT1
Safe torque off. Begge kredse skal være
lukkede, for at frekvensomformeren kan
starte.
2 SGND
3 IN1
4 IN2
X12 Modulforbindelse med sikkerhedsfunktioner
X13 Tilslutning til betjeningspanel
X205 Tilslutning til hukommelsesenhed
Lednings-
størrelse:
0,5 … 2,5 mm
2
(24…12 AWG)
Fastspændings-
momenter:
0,5 N·m (5 lbf·in)
til både
trådledere og
stive ledere.
1)
Den totale
belastningskapa-
citet for disse
udgange er 4,8 W
(200 mA / 24 V)
minus den strøm,
der benyttes af
DIO1 og DIO2.
Fejl
DE – Kurzanleitung für die Installation 23
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
DE – Kurzanleitung für die Installation
Diese Kurzanleitung beschreibt die Installation des Frequenzumrichters. Weitere
Informationen, Planungsrichtlinien, technische Daten und die vollständigen
Sicherheitsvorschriften finden Sie im Hardware-Handbuch. (www.abb.com/drives
:
Wählen Sie Document Library und suchen Sie die Dokumentennummer
3AUA0000078093 [Englisch]).
Befolgen Sie die Sicherheitsvorschriften
Der Boden unterhalb des Geräts muss aus nicht entflammbarem Material bestehen.
Prüfen Sie, ob Kondensatoren nachformiert werden
müssen
Die Kondensatoren müssen neu formiert werden, wenn der Frequenzumrichter für
mehr als ein Jahr nicht eingeschaltet wurde (entweder gelagert oder nicht benutzt
wurde).
Das Herstellungsdatum kann anhand der Seriennummer bestimmt werden, welche
auf dem am Frequenzumrichter angebrachten Typenschild angegeben ist. Die
Seriennummer hat das Format MJJWWRXXXX. JJ und WW geben das
Herstellungsjahr und die -woche an:
WARNUNG! Befolgen Sie diese Anweisungen. Wenn diese nicht befolgt
werden, können Verletzungen, tödliche Unfälle oder Schäden an den
Geräten auftreten:
Installation und Wartung des Frequenzumrichters dürfen nur von qualifiziertem
Fachpersonal ausgeführt werden.
Am Frequenzumrichter, dem Motorkabel oder dem Motor dürfen keinerlei
Arbeiten ausgeführt werden, solange die Netzspannung anliegt. Wenn der
Frequenzumrichter bereits an die Spannungsversorgung angeschlossen
ist/war, warten Sie 5 Minuten nach der Trennung von der Eingangsspannung.
Führen Sie keine Arbeiten an den Steuerkabeln durch, wenn Spannung am
Frequenzumrichter oder den externen Steuerkreisen anliegt.
Erden Sie immer den Frequenzumrichter, den Motor und die benachbarten
Geräte über die PE-Sammelschiene der Spannungsversorgung.
Stellen Sie sicher, dass bei der Installation keine Bohrspäne und Staub in den
Frequenzumrichter eindringen.
Am Frequenzumrichter keine Spannung anlegen, die höher ist, als auf dem
Typenschild angegeben.
3AUA0000085966 Rev H
24 DE – Kurzanleitung für die Installation
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
JJ: 17, 18, 19, … für 2017, 2018, 2019,
WW: 01, 02, 03, … für Woche 1, Woche 2, Woche 3,
Informationen zum Formieren der Kondensatoren enthält die Anleitung Converter
modules with electrolytic DC capacitors in the DC link capacitor reforming
instructions (3BFE64059629 [Englisch], 3AUA0000044714 [Deutsch]), verfügbar im
Internet unter www.abb.com/drives/documents
.
Auswahl der Leistungskabel
Die Leistungskabel müssen nach den örtlichen Vorschriften für den auf dem
Typenschild des Frequenzumrichters angegebenen Nennstrom ausreichend
bemessen sein.
Typische Kabelgrößen sind in Tabelle J auf Seite 100 aufgelistet. Bedingungen der
Dimensionierung siehe Hardware-Handbuch).
Ausreichende Kühlung sicherstellen
Verluste und Kühlluftstrom durch den Frequenzumrichter siehe Tabelle B auf
Seite 97. Der zulässige Betriebstemperaturbereich für den Frequenzumrichter ohne
Leistungsminderung beträgt -15 bis +40 °C.
Schutz des Frequenzumrichters und der Einspeisekabel
Siehe Tabelle B auf Seite 97. Prüfen Sie, ob die Ansprechzeit der Sicherungen
weniger als 0,5 Sekunden beträgt.
Wandmontage des Frequenzumrichters
Siehe Abbildung A auf Seite 97.
Prüfung der Kompatibilität mit (ungeerdeten) IT-,
asymmetrisch geerdeten, mittelpunktgeerdeten und
TT-Netzen
Der Standard-Frequenzumrichter mit angeschlossenem Erde-Phase-Varistor kann an
ein symmetrisch geerdetes TN-S-Netz angeschlossen werden. Andere Netze siehe
Hardware-Handbuch und ACS880 frames R1 to R11 EMC filter and ground-to-phase
varistor disconnecting instructions (3AUA0000125152 [Englisch]).
DE – Kurzanleitung für die Installation 25
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
A = TN-S-Netz, B1 = asymmetrisch geerdetes Netz, B2 = mittelpunktgeerdetes Netz, C = IT-Netz
WARNUNG! Installieren Sie den Frequenzumrichter mit angeschlossenem
EMV-Filteroptionen +E200 und +E202 nicht an einem Netz, für das der Filter
nicht geeignet ist. Dadurch können Gefahren entstehen oder der Frequenzumrichter
kann beschädigt werden.
WARNUNG! Installieren Sie den Frequenzumrichter mit angeschlossenem
Erde-Phase-Varistor nicht an einem Netz, für das der Varistor nicht geeignet
ist. Dann kann die Varistorschaltung beschädigt werden. Siehe das entsprechende
Hardware-Handbuch des Frequenzumrichters.
Hinweise: Entfernen Sie mit Option +E201 die EMV AC-, EMV DC- und VAR-
Schrauben für andere Netze als TN-S, falls dies nicht bereits ab Werk geschehen ist.
Für weitere Informationen setzen Sie sich mit ABB in Verbindung.
Prüfen Sie die Isolierung der Einspeise- und Motorkabel
und des Motors.
Prüfen Sie, ob die Isolation des Netzanschlusskabels den örtlichen Vorschriften
entspricht, bevor es an den Frequenzumrichter angeschlossen wird.
Prüfen Sie die Isolation des Motorkabels und des Motors, wenn das Motorkabel vom
Frequenzumrichter getrennt wird, siehe Abbildung F auf Seite 98. Messen Sie die
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
26 DE – Kurzanleitung für die Installation
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
Isolationswiderstände zwischen jeder Phase und der Schutzerde mit einer
Messspannung von 1000 V DC. Der Isolationswiderstand eines ABB-Motors muss
100 MOhm überschreiten (Referenzwert bei 25 °C bzw. 77 °F). Die
Isolationswiderstände anderer Motoren entnehmen Sie bitte der Anleitung des
Herstellers. Hinweis: Feuchtigkeit innerhalb des Motorgehäuses reduziert den
Isolationswiderstand. Bei Verdacht auf Feuchtigkeit muss der Motor getrocknet und
die Messung wiederholt werden.
Bringen Sie die Warnaufkleber in der Landessprache an
Anschluss der Leistungskabel
Siehe Abbildungen C, D, E und G. Ein symmetrisch geschirmtes Motorkabel
verwenden.
5. Die Befestigungsschrauben auf den Seiten der Frontabdeckung lösen.
6. Die Abdeckung durch Vorschieben abnehmen.
7. Den Restspannungs-Warnaufkleber in der erforderlichen lokalen Sprache auf der
Bedienpanel-Halterung anbringen.
8. Die Gummi-Kabeldurchführungen für die anzuschließenden Kabel vom
Durchführungsblech abnehmen.
9. IP21 Einheiten
: Die Kabelschellen (mitgeliefert, in einem Plastikbeutel) an den
Bohrungen des Durchführungsblechs befestigen.
10. Die Enden der Einspeise- und Motorkabel wie in der Abbildung gezeigt
vorbereiten.
11. Die Kabelschirme 360 Grad an den Kabelanschlüssen (IP21 Einheiten) oder
unter den Schellen (IP55 Einheiten) erden.
12. Den verdrillten Schirm des Einspeisekabels an die Erdungsklemme anschließen.
13. Den Erdungsleiter (PE) des Einspeisekabels an die zusätzliche Erdungsklemme
anschließen.
14. Die verdrillten Schirme des Motor- und Widerstandskabels (falls vorhanden) an
die Erdungsklemme anschließen.
15. Die Phasenleiter des Einspeise-, Motor- und Widerstandskabels anschließen.
Ziehen Sie die Schrauben fest.
16. Die Steuerkabel-Erdungsschellenschiene im Kabelanschlusskasten installieren.
17. Die Kabel außerhalb des Frequenzumrichters mechanisch sichern.
18. Die Motorkabelschirme motorseitig an Erde/PE anschließen. Um eine geringe
Interferenz sicherzustellen, eine 360-Grad-Erdung an der Kabeldurchführung
vornehmen oder den verdrillten Schirm kurz halten.
DE – Kurzanleitung für die Installation 27
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
Die Steuerkabel anschließen
Siehe Abbildung H.
1. Eine passende Öffnung in die Gummi-Kabeldurchführungen schneiden und die
Kabeldurchführungen auf die Kabel schieben. Die Kabel durch die Öffnungen des
unteren Abschlussblechs stecken und die Kabeldurchführungen in die Öffnungen
drücken.
2. Die Kabelenden abisolieren und auf die passende Länge abschneiden (beachten
Sie die zusätzliche bei den Erdleitern benötigte Länge).
3. Für die äußeren Schirme aller Steuerkabel im Kabelanschlusskasten eine
360-Grad-Erdung an einer Erdungsschelle herstellen.
4. Den Kabelschirm an der Erdungsklemme erden. Das andere Ende der Schirme
nicht anschließen oder indirekt über einen Hochfrequenz-Kondensator mit
wenigen Nanofarad (z.B. 3,3 nF / 630 V) erden.
5. Schließen Sie die Leiter an die entsprechenden Anschlüsse der Regelungseinheit
an (siehe Seite 28).
6. Die Optionsmodule, falls im Lieferumfang enthalten, verdrahten.
7. Die Frontabdeckung wieder anbringen:
Hinweis zur Feldbusverkabelung. Siehe Abbildung I.
1. Installieren Sie die zusätzliche Erdungsschellenschiene.
2. Die äußeren Schirme der Kabel 360 Grad unter der Erdungsschelle erden.
3. Für die zu installierenden Kabel die Abdeckungen aus den Öffnungen im
Kabelanschlusskasten brechen. Die Abdeckung des Kabelanschlusskastens
installieren.
4. Den Stecker an das Feldbus Modul anschließen.
Standard E/A-Anschlüsse
Die Standard-E/A-Anschlüsse des Makros Werkseinstellung des ACS880
Hauptregelungsprogramms sind nachfolgend dargestellt.
28 DE – Kurzanleitung für die Installation
EN
DA
DE
DE
FI
FR
IT
NL
PT
RU
SV
TR
CN
XPOW Eingang für externe Spannungsversorgung
1 +24VI
24 V DC, 2 A
2
GND/Masse
XAI Referenzspannungsausgänge und Analogeingänge
1 +VREF 10 V DC, R
L
1…10 kOhm
2 -VREF -10 V DC, R
L
1…10 kOhm
3 AGND Masse
4 AI1+ Drehzahl-Sollwert 0(2)…10 V,
R
in
> 200 kOhm
5 AI1-
6 AI2+
Standardmäßig nicht benutzt.
0(4)...20 mA, R
in
= 100 Ohm
7 AI2-
J1 J1
AI1 Steckbrücke für Auswahl Strom/Spannung I/U
J2 J2
AI2 Steckbrücke für Auswahl Strom/Spannung I/U
XAO Analogausgänge
1 AO1 Motordrehzahl U/min 0…20 mA,
R
L
< 500 Ohm
2 AGND
3 AO2 Motorstrom 0…20 mA,
R
L
< 500 Ohm
4 AGND
XD2D Umrichter-Umrichter-Verbindung (D2D)
1 B
Umrichter-Umrichter-Verbindung (D2D)
2 A
3 BGND
J3 J3
Schalter für Abschluss der D2D-Verbindung
XRO1, XRO2, XRO3 Relaisausgänge
11 NC
Bereit
250 V AC / 30 V DC
2 A
12 COM
13 NO
21 NC
Läuft
250 V AC / 30 V DC
2 A
22 COM
23 NO
31 NC
Störung (-1)
250 V AC / 30 V DC
2 A
32 COM
33 NO
XD24 Digital-Startsperre
1 DIIL Reglerfreigabe
2 +24 VD +24 V DC 200 mA
1)
3 DICOM Digitaleingang Masse
4 +24 VD +24 V DC 200 mA
1)
5 DIOGND Digitaleingang/-ausgang Masse
J6 Schalter Masse-Auswahl
XDIO Digitaleingänge/-ausgänge
1 DIO1 Ausgang: Startbereit
2 DIO2 Ausgang: In Betrieb
XDI Digitaleingänge
1 DI1 Stop (0) / Start (1)
2 DI2 Vorwärts (0) /Rückwärts (1)
3 DI3 Störungsquittierung
4 DI4 Auswahl Beschl./Verzög.-Rampen
5 DI5 Konstantdrehzahl 1 (1 = Ein)
6 DI6 Standardmäßig nicht benutzt.
XSTO Sicher abgeschaltetes Drehmoment
1 OUT1
Sicher abgeschaltetes Drehmoment
(STO). Beide Kreise müssen für den
Start des Antriebs geschlossen sein.
2 SGND
3 IN1
4 IN2
X12 Sicherheitsfunktionsmodul-Anschluss
X13 Bedienpanel-Anschluss
X205 Anschluss für Memory Unit
Leitergrößen:
0,5 … 2,5 mm
2
(24…12 AWG)
Anzugsmomente:
0,5 Nm (5 lbf·in)
für Litzen und
einadrige Leiter.
1)
Die Gesamtbe-
lastbarkeit dieser
Ausgänge beträgt
4,8 W (200 mA /
24 V) minus der
Energie, die von
DIO1 und DIO2
verbraucht wird.
Störung
ES – Guía rápida de instalación 29
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
ES – Guía rápida de instalación
Esta guía ofrece unas breves instrucciones para la instalación del convertidor de
frecuencia. Para obtener instrucciones más detalladas, directrices de ingeniería,
datos técnicos y unas instrucciones de seguridad completas, véase el Manual de
hardware (www.abb.com/drives
: seleccione Biblioteca de documentos y busque el
número de documento 3AUA0000078093).
Siga estrictamente las instrucciones de seguridad
El material del suelo situado bajo el convertidor debe ser de un material ignífugo.
Compruebe si es necesario reacondicionar los
condensadores
Reacondicione los condensadores si el convertidor no ha sido alimentado (por estar
almacenado o sin usar) durante un año o más.
Puede determinar la fecha de fabricación a partir del número de serie, que
encontrará en la etiqueta de designación de tipo adherida al convertidor. El número
de serie tiene el formato MAASSRXXXX. AA y SS indican el año y la semana de
fabricación, de la forma siguiente:
AA: 17, 18, 19… para 2017, 2018, 2019
SS: 01, 02, 03… para semana 1, semana 2, semana 3
ADVERTENCIA: Siga estrictamente estas instrucciones. Si no lo hace, se
pueden producir daños en el equipo o en las personas, e incluso causar la
muerte:
Sólo podrán efectuar la instalación y el mantenimiento del convertidor
electricistas cualificados.
No intente trabajar con el convertidor, el cable de motor o el motor con la
alimentación principal conectada. Si el convertidor está conectado a la potencia
de entrada, espere 5 minutos tras desconectarlo.
Nunca manipule los cables de control mientras el convertidor o los circuitos de
control externo reciban alimentación.
Conecte siempre el convertidor, el motor y los equipos auxiliares al embarrado
de conexión a tierra (PE) de la fuente de alimentación.
Asegúrese de que los restos de polvo y virutas resultantes de practicar orificios y
rectificaciones no entren en el convertidor de frecuencia durante la instalación.
No conecte el convertidor a una tensión superior a la indicada en la etiqueta de
designación de tipo.
3AUA0000085966 Rev H
30 ES – Guía rápida de instalación
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
Para más información sobre el reacondicionamiento de los condensadores,
consulte el documento Converter modules with electrolytic DC capacitors in the DC
link capacitor reforming instructions (3BFE64059629 [Inglés]), disponible en
Internet en www.abb.com/drives/documents
.
Seleccione los cables de potencia
Dimensione los cables de potencia de conformidad con los reglamentos locales para
el transporte de la intensidad nominal indicada en la etiqueta de designación de tipo
de su convertidor de frecuencia.
Puede ver los tamaños de cables de potencia más habituales en la tabla J de la
página 100. Consulte en el Manual de hardware las condiciones de los tamaños de
los cables.
Garantice la refrigeración
Véase la tabla B de la página 97 para conocer las pérdidas y el caudal de aire de
refrigeración a través del convertidor de frecuencia. El rango de temperatura de
funcionamiento permitido para el convertidor de frecuencia sin pérdidas de potencia
es de -15 a +40 °C.
Protección del convertidor y el cable de potencia de
entrada
Véase la tabla B en la página 97. Compruebe que el tiempo de fusión del fusible sea
inferior a 0,5 segundos.
Monte el convertidor de frecuencia en la pared
Véase la figura A de la página 97.
Compruebe la compatibilidad con redes IT (sin conexión a
tierra), redes en triángulo conectadas a tierra en un vértice
o en el punto medio y redes TT
Los convertidores estándar con varistores tierra-fase conectados se pueden instalar
en una red TN-S conectada a tierra simétricamente. Para otros sistemas, véase el
Manual de hardware y ACS880 frames R1 to R11 EMC filter and ground-to-phase
varistor disconnecting instructions (3AUA0000125152 [Inglés]).
ES – Guía rápida de instalación 31
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
A = Red TN-S, B1 = Red conectada a tierra en un vértice, B2 = Red conectada a tierra en el punto medio,
C = Red IT
ADVERTENCIA: No instale el convertidor de frecuencia con los opcionales de
filtro EMC +E200 y +E202 conectados a un sistema para el cual el filtro no es
adecuado. Esto puede entrañar peligro o provocar daños en el convertidor.
ADVERTENCIA: No instale el convertidor de frecuencia con un varistor tierra-
fase conectado en un sistema para el cual no sea adecuado el varistor. Si lo
hace, el circuito del varistor podría resultar dañado. Consulte el manual de hardware
del convertidor.
Nota: Con el opcional +E201, si no se han quitado en la fábrica, retire los tornillos
EMC AC, EMC DC y VAR para todas las redes excepto TN-S. Para más información,
póngase en contacto con ABB.
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
32 ES – Guía rápida de instalación
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
Compruebe el aislamiento de los cables de entrada y motor
y del propio motor
Compruebe el aislamiento del cable de entrada conforme a las normativas locales
antes de conectar el convertidor a la red.
Compruebe el aislamiento del cable de motor y del motor mientras el cable está
desconectado del convertidor, véase la figura F en la página 98. Mida la resistencia
de aislamiento entre cada conductor de fase y el conductor de protección a tierra con
una tensión de medición de 1000 V CC. La resistencia de aislamiento de un motor
ABB debe ser superior a los 100 Mohmios (valor de referencia a 25 °C o 77 °F).
En cuanto a la resistencia de aislamiento de otros motores, véanse las instrucciones
del fabricante. Nota: La humedad en el interior de la carcasa del motor reduce la
resistencia de aislamiento. Si sospecha de la presencia de humedad, seque el motor
y repita la medición.
Fije las etiquetas de advertencia disponibles en los
idiomas locales
Conecte los cables de potencia
Véanse las figuras C, D, E y G. Use cable apantallado simétrico para el cableado al
motor.
5. Afloje los tornillos de montaje situados a los lados de la cubierta frontal.
6. Retire la cubierta deslizándola hacia delante.
7. Pegue el adhesivo de advertencia de tensión residual en el idioma local a la
plataforma de montaje del panel de control.
8. Retire las arandelas de goma de la placa pasacables para los cables que desee
conectar.
9. Unidades IP21
: Sujete los conectores de cables (incluidos en el suministro dentro
de una bolsa de plástico) a los orificios de la placa pasacables.
10. Prepare los extremos de los cables de potencia de entrada y de motor de la
forma mostrada en la figura.
11. Conecte a tierra los apantallamientos de los cables a 360 grados a los conectores
de cable (unidades IP21) o debajo de las abrazaderas (unidades IP55).
12. Conecte el apantallamiento trenzado del cable de entrada al terminal PE.
13. Conecte el conductor de conexión a tierra del cable de potencia de entrada al
terminal PE.
14. Conecte la pantalla trenzada del cable de motor y del cable de resistencia (si lo
hubiese) al terminal de conexión a tierra.
ES – Guía rápida de instalación 33
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
15. Conecte los conductores de fase de los cables de entrada, motor y resistencia.
Apriete los tornillos.
16. Instale la pletina de conexión a tierra para cables de control en la caja de entrada
de cables.
17. Sujete los cables mecánicamente al exterior del convertidor.
18. Conecte a tierra la pantalla del cable de motor en el extremo del motor. Para unas
mínimas interferencias, realice una conexión a tierra a 360 grados en el
pasacables o mantenga el mallado corto.
Conexión de los cables de control
Véase la figura H.
1. Practique orificios adecuados en las arandelas de goma y haga pasar los cables
a través de ellas. Deslice los cables a través de los orificios del panel inferior y fije
las arandelas a los orificios.
2. Pele los extremos de los cables y corte a una longitud adecuada (recuerde la
longitud adicional de los conductores de conexión a tierra).
3. Conecte a tierra los apantallamientos exteriores de todos los cables de control a
360 grados a la abrazadera de conexión a tierra de la caja de entrada de cables.
4. Conecte a tierra el apantallamiento del par de cables en la abrazadera de tierra.
Deje el otro extremo de las pantallas sin conectar o conéctelas a tierra de forma
indirecta a través de un condensador de alta frecuencia de unos pocos
nanofaradios, por ejemplo, 3,3 nF / 630 V.
5. Conecte los conductores a los terminales adecuados de la tarjeta de control
(véase la página 34).
6. Cablee los módulos opcionales si están incluidos en el suministro.
7. Vuelva a colocar la cubierta frontal.
Nota para el cableado de bus de campo. Véase la figura I.
1. Instale la pletina adicional de conexión a tierra.
2. Conecte a tierra las pantallas exteriores de los cables a 360 grados en una
abrazadera de conexión a tierra.
3. Practique orificios en la cubierta de la caja de entrada de cables para los cables
que se van a instalar. Instale la cubierta de la caja de entrada de cables.
4. Enchufe el conector al módulo de bus de campo.
Conexiones de E/S por defecto
A continuación se muestran las conexiones de E/S por defecto de la macro de
fábrica del programa de control primario ACS880.
34 ES – Guía rápida de instalación
ES
DA
DE
ES
ES
FR
IT
NL
PT
RU
SV
TR
CN
XPOW Entrada de alimentación externa
1 +24 VI
24 V CC, 2 A
2 GND
XAI Tensión de referencia y entradas analógicas
1 +VREF 10 V CC, R
L
1…10 kohmios
2 -VREF -10 V CC, R
L
1…10 kohmios
3 AGND Tierra
4 AI1+ Ref. de velocidad 0(2)…10 V, R
in
>
200 kohmios
5 AI1-
6 AI2+
Por defecto no se usa. 0(4)…20 mA, R
in
= 100 ohmios
7 AI2-
J1 J1
Puente de selección de Tensión/Corriente AI1
J2 J2
Puente de selección de Tensión/Corriente AI2
XAO Salidas analógicas
1 AO1 Régimen de motor rpm 0…20 mA,
R
L
< 500 ohmios
2 AGND
3 AO2 Intensidad de motor 0…20 mA,
R
L
< 500 ohmios
4 AGND
XD2D Enlace de convertidor a convertidor
1 B
Enlace de convertidor a convertidor
2 A
3 BGND
J3 J3
Terminador de enlace de convertidor a convertidor
XRO1, XRO2, XRO3 Salidas de relé
11 NC
Listo
250 V CA / 30 V CC
2 A
12 COM
13 NO
21 NC
En marcha
250 V CA / 30 V CC
2 A
22 COM
23 NO
31 NC
Fallo(-1)
250 V CA / 30 V CC
2 A
32 COM
33 NO
XD24 Bloqueo de marcha
1 DIIL Permiso de marcha
2 +24 VD +24 V CC 200 mA
1)
3 DICOM Tierra de entrada digital
4 +24 VD +24 V CC 200 mA
1)
5 DIOGND Tierra de entrada/salida digital
J6 Interruptor de selección de tierra
XDIO Entradas/salidas digitales
1 DIO1 Salida: Listo
2 DIO2 Salida: En marcha
XDI Entradas digitales
1 DI1 Paro (0) / Marcha (1)
2 DI2 Avance (0) / Retroceso (1)
3 DI3 Restaurar
4 DI4 Selección de aceleración y deceleración
5 DI5 Velocidad constante 1 (1 = activado)
6 DI6 Por defecto no se usa.
XSTO Safe Torque Off
1 OUT1
Safe Torque Off. Ambos circuitos deben
estar cerrados para que el convertidor
pueda ponerse en marcha.
2 SGND
3 IN1
4 IN2
X12 Conexión de módulo de funciones de seguridad
X13 Conexión del panel de control
X205 Conexión de la unidad de memoria
Tamaños de hilos:
0,5 … 2,5 mm
2
(24…12 AWG)
Pares de apriete:
0,5 N·m (5 lbf·in)
tanto para los
cables flexibles
como para los
sólidos.
1)
La capacidad de
carga total de estas
salidas es de 4,8 W
(200 mA / 24 V)
menos la potencia
consumida por
DIO1 y DIO2.
Fallo
FI – Asennuksen pikaopas 35
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
FI – Asennuksen pikaopas
Tässä oppaassa on taajuusmuuttajan lyhyet asennusohjeet. Yksityiskohtaisemmat
ohjeet, suunnitteluohjeet, tekniset tiedot ja täydelliset turvaohjeet löytyvät
laiteoppaasta (www.abb.com/drives
: valitse Document Library ja kirjoita
hakukenttään dokumentin numero 3AUA0000078093 [englanninkielinen]).
Noudata turvaohjeita
Taajuusmuuttajan alla olevan lattiamateriaalin tulee olla palamatonta.
Tarkista, täytyykö kondensaattorit elvyttää
Elvytä kondensaattorit, jos taajuusmuuttajaan ei ole kytketty virtaa vähintään vuoteen
(laite on ollut varastoituna tai käyttämättä).
Voit selvittää valmistusajankohdan sarjanumeron perusteella. Sarjanumero on
taajuusmuuttajaan kiinnitetyssä tyyppikilvessä. Sarjanumero on muotoa
MYYWWRXXXX. YY ja WW ilmaisevat valmistusvuoden ja -viikon seuraavasti:
YY: 17, 18, 19,…, mikä tarkoittaa vuotta 2017, 2018, 2019,…
WW: 01, 02, 03,…, mikä tarkoittaa viikkoa 1, 2, 3,…
Lisätietoja kondensaattorien elvyttämisestä on Converter modules with electrolytic
DC capacitors in the DC link capacitor reforming instructions -oppaassa
VAROITUS! Noudata näitä ohjeita. Ohjeiden laiminlyönti voi aiheuttaa
fyysisen vamman tai hengenvaaran tai vahingoittaa laitteistoa.
Taajuusmuuttajan asennus- ja huoltotyöt saa suorittaa vain valtuutettu
sähköalan ammattilainen.
Tee kaikki taajuusmuuttajan, moottorikaapelin ja moottorin asennus- ja
huoltotyöt jännitteen ollessa katkaistuna. Jos taajuusmuuttaja on jo kytketty
syöttöverkkoon, kytke se irti verkosta ja odota 5 minuuttia.
Älä käsittele ohjauskaapeleita, kun taajuusmuuttajaan tai ulkoisiin
ohjauspiireihin on kytketty jännite.
Maadoita taajuusmuuttaja, moottori ja niihin liittyvät laitteet aina syötön
suojamaakiskoon (PE).
Varmista, ettei poraus- tai hiomajäte pääse laitteen sisään asennuksen
yhteydessä.
Älä kytke taajuusmuuttajaa tyyppikilpeen merkittyä jännitettä suurempaan
jännitteeseen.
3AUA0000085966 Rev. H
36 FI – Asennuksen pikaopas
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
(3BFE64059629, englanninkielinen), joka on saatavana osoitteesta
www.abb.com/drives/documents.
Valitse tehokaapelit
Mitoita tehokaapelit taajuusmuuttajan tyyppikilvessä ilmoitetun nimellisvirran mukaan.
Noudata paikallisia määräyksiä.
Tyypilliset tehokaapelien koot on esitetty taulukossa J sivulla 100. Mitoitukseen
liittyvät ehdot on kerrottu laiteoppaassa.
Varmista jäähdytys
Katso tiedot lämpöhäviöistä ja taajuusmuuttajan läpi virtaavasta jäähdytysilmasta
sivulla 97 olevasta taulukosta B. Taajuusmuuttajan sallittu käyttölämpötila-alue ilman
kuormitettavuuden alennusta on –15...+40 °C.
Suojaa taajuusmuuttaja ja syöttökaapeli
Katso taulukko B sivulla 97. Varmista, että sulakkeen toiminta-aika on alle 0,5
sekuntia.
Asenna taajuusmuuttaja seinälle
Katso kuva A sivulla 97.
Tarkista yhteensopivuus maadoittamattomien IT-verkkojen,
epäsymmetrisesti ja keskipisteestä maadoitettujen
kolmioverkkojen sekä TT-verkkojen kanssa
Vakiomallinen taajuusmuuttaja, johon on liitetty maajohtimen ja vaihejohtimen väliset
varistorit, voidaan asentaa symmetrisesti maadoitettuun TN-S-verkkoon. Katso
muiden verkkojen osalta laiteopas sekä opas ACS880 frames R1 to R11 EMC filter
and ground-to-phase varistor disconnecting instructions (3AUA0000125152,
englanninkielinen).
FI – Asennuksen pikaopas 37
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
.
A = TN-S-verkko, B1 = epäsymmetrisesti maadoitettu verkko,
B2 = keskipisteestä maadoitettu verkko, C = IT-verkko
VAROITUS! Älä asenna taajuusmuuttajaa, johon on liitetty EMC-suodin
(lisävarusteet +E200 ja +E202), verkkoon, johon suodin ei sovellu. Tämä voi
aiheuttaa vaaratilanteen tai vahingoittaa taajuusmuuttajaa.
VAROITUS! Älä asenna taajuusmuuttajaa, johon on liitetty maajohtimen ja
vaihejohtimen välinen varistori, verkkoon, johon varistori ei sovellu. Muussa
tapauksessa varistoripiiri voi vahingoittua. Lisätietoja on taajuusmuuttajan
laiteoppaassa.
Huomaa: Jos järjestelmässä on lisävaruste +E201, poista EMC AC-, EMC DC- ja
VAR-ruuvit muita kuin TN-S-verkkoja varten, jos niitä ei ole poistettu tehtaalla.
Lisätietoja on saatavana ABB:ltä.
Tarkista syöttö- ja moottorikaapelien sekä moottorin
eristys
Tarkista syöttökaapelin eristys paikallisten määräysten mukaisesti ennen kaapelin
kytkemistä taajuusmuuttajaan.
Tarkista moottorikaapelin ja moottorin eristys, kun kaapeli on irti taajuusmuuttajasta.
Katso kuva F sivulla 98. Mittaa jokaisen vaihejohtimen ja suojamaajohtimen (PE)
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
38 FI – Asennuksen pikaopas
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
välinen eristysvastus 1 000 V DC:n mittausjännitteellä. ABB:n moottoreiden
eristysvastuksen tulee olla yli 100 megaohmia (ohjearvo lämpötilassa 25 °C).
Lisätietoja muiden moottorien eristysvastuksista on valmistajan ohjeissa.
Huomautus: Moottorin kotelon sisällä oleva kosteus pienentää eristysvastusta. Jos
epäilet, että kotelon sisällä on kosteutta, kuivata moottori ja toista mittaus.
Kiinnitä tarrat, joissa varoitukset on annettu paikallisilla
kielillä
Kytke tehokaapelit
Katso kuvat C, D, E ja G. Käytä suojattua symmetristä moottorikaapelia.
5. Avaa etukannen sivuilla olevat kiinnitysruuvit.
6. Irrota kansi vetämällä sitä eteenpäin.
7. Kiinnitä oikeankielinen jäännösjännitteen varoitustarra ohjauspaneelin
kiinnitysalustaan.
8. Irrota kumitiivisteet läpivientilevystä kytkettäviä kaapeleita varten.
9. IP21-yksiköt
: Kiinnitä kaapeliliittimet (ovat toimitukseen kuuluvassa
muovipakkauksessa) kaapelien läpivientilevyn reikiin.
10. Valmistele syöttö- ja moottorikaapelien päät kuvassa esitetyllä tavalla.
11. Maadoita kaapelin suojavaipat 360 astetta kaapeliliittimissä (IP21-yksiköt) tai
kiinnikkeiden alla (IP55-yksiköt).
12. Kytke syöttökaapelin kierretty suojavaippa PE-liittimeen.
13. Kytke syöttökaapelin PE-johdin PE-lisäliittimeen.
14. Kytke moottorikaapelin ja mahdollisen vastuskaapelin kierretty suojavaippa
maadoitusliittimeen.
15. Kytke syöttö-, moottori- ja vastuskaapelien vaihejohtimet. Kiristä ruuvit.
16. Asenna ohjauskaapelin maadoitushylly kaapelin läpivientikoteloon.
17. Kiinnitä taajuusmuuttajan ulkopuolella olevat kaapelin osat mekaanisesti.
18. Maadoita moottorikaapelin suojavaippa moottorin päästä. Jotta häiriöt voitaisiin
minimoida, tee kaapelin läpiviennissä 360 asteen maadoitus tai pidä kierretty
johdin lyhyenä.
FI – Asennuksen pikaopas 39
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
Kytke ohjauskaapelit
Katso kuva H.
1. Leikkaa kumitiivisteisiin sopivan kokoiset aukot ja vedä kumitiivisteet kaapeleihin.
Vie kaapelit pohjalevyssä olevien reikien läpi ja kiinnitä kumitiivisteet reikiin.
2. Kuori kaapelien päät ja leikkaa ne sopivaan pituuteen (huomaa
maadoitusjohtimien ylimääräinen pituus).
3. Maadoita kaikkien ohjauskaapelien ulkovaipat 360 astetta kaapelien
läpivientikotelossa olevan maadoituskiinnikkeen kohdalla.
4. Maadoita parikaapelien vaipat maadoituskiinnikkeeseen. Jätä suojavaippojen
toiset päät maadoittamatta tai maadoita ne epäsuorasti muutaman nanofaradin
suurtaajuuskondensaattorilla, esim. 3,3 nF / 630 V.
5. Liitä johtimet oikeisiin ohjauskortin liittimiin (katso sivu 40).
6. Kytke myös lisävarustemoduulit, mikäli niitä sisältyy toimitukseen.
7. Asenna etukansi takaisin paikalleen.
Kenttäväyläkaapeleita koskeva huomautus: Katso kuva I.
1. Asenna lisämaadoitushylly.
2. Maadoita kaapelien ulommat suojavaipat 360 astetta maadoitusliittimen kohdalla.
3. Avaa kaapelien läpivientikotelon kanteen aukot asennettaville kaapeleille. Asenna
kaapelien läpivientikotelon kansi.
4. Kiinnitä liitin kenttäväylämoduuliin.
Oletusarvoiset I/O-ohjauskytkennät
ACS880-perusohjausohjelman tehdasmakron oletusarvoiset I/O-ohjauskytkennät on
esitetty seuraavassa kaaviossa.
40 FI – Asennuksen pikaopas
EN
DA
DE
ES
FI
FI
IT
NL
PT
RU
SV
TR
CN
XPOW Ulkoinen syöttö
1 +24VI
24 V DC, 2 A
2 GND
XAI Ohjejännite ja analogiatulot
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF –10 V DC, R
L
1…10 kohm
3 AGND Maa
4 AI1+ Nopeusohje 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+
Oletusasetuksena ei käytössä.
0(4)…20 mA, R
in
= 100 ohm
7 AI2-
J1 J1 AI1 (virran/jännitteen valinnan siirtoliitin)
J2 J2 AI2 (virran/jännitteen valinnan siirtoliitin)
XAO Analogialähdöt
1 AO1 Moottorin nopeus (rpm) 0…20 mA, R
L
< 500 ohm
2 AGND
3 AO2 Moottorin virta 0…20 mA, R
L
<
500 ohm
4 AGND
XD2D Taajuusmuuttajien välinen liitäntä
1 B
Taajuusmuuttajien välinen liitäntä
2 A
3 BGND
J3 J3 Liitännän päätevastuksen valintakytkin
XRO1, XRO2, XRO3 Relelähdöt
11 NC
Valmis
250 V AC / 30 V DC
2 A
12 COM
13 NO
21 NC
Käy
250 V AC / 30 V DC
2 A
22 COM
23 NO
31 NC
Vika(-1)
250 V AC / 30 V DC
2 A
32 COM
33 NO
XD24 Digitaalinen lukitus
1 DIIL Käyntilupa
2 +24VD +24 V DC 200 mA
1)
3 DICOM Digitaalitulon maa
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Digitaalitulon/-lähdön maa
J6 Maadoituksen valintakytkin
XDIO Digitaalitulot/-lähdöt
1 DIO1 Lähtö: Valmis
2 DIO2 Lähtö: Käy
XDI Digitaalitulot
1 DI1 Seis (0) / Käy (1)
2 DI2 Eteen (0) / Taakse (1)
3 DI3 Kuittaus
4 DI4 Kiihdytyksen ja hidastuksen valinta
5 DI5 Vakionopeus 1 (1 = Käytössä)
6 DI6 Oletusasetuksena ei käytössä.
XSTO Safe torque off -toiminto
1 OUT1
Safe torque off -toiminto. Molempien
piirien on oltava suljettuina, jotta
taajuusmuuttaja käynnistyy.
2 SGND
3 IN1
4 IN2
X12 Turvatoimintomoduulin liitäntä
X13 Ohjauspaneelin liitäntä
X205 Muistiyksikön liitäntä
Johdinkoot:
0,5 … 2,5 mm
2
(24…12 AWG)
Kiristysmomen-
tit: 0,5 Nm yksi-
lankaisille ja
kerratuille johti-
mille.
1)
Näiden lähtöjen
kokonaiskapasiteetti
on 4,8 W (200 mA /
24 V), josta vähenne-
tään DIO1- ja DIO2-
liitäntöjen kuluttama
teho.
Vika
FR – Guide d'installation 41
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
FR – Guide d'installation
Ce guide vous explique brièvement comment installer le variateur. Pour des
consignes détaillées, des directives d'ingénierie, les caractéristiques techniques ou
les consignes de sécurité complètes, reportez-vous au manuel d'installation
(www.abb.com/drives
: Sélectionnez Document Library (vous devrez peut-être
afficher la page en anglais pour voir cette rubrique) et recherchez le document
anglais de référence 3AUA0000078093.
Consignes de sécurité
La surface (sol) sous l'appareil doit être en matériau ininflammable.
Vérification des condensateurs
Si le variateur est resté plus d'un an sans être mis sous tension (en stockage ou non
utilisé), vous devez réactiver les condensateurs.
Pour connaître la date de fabrication, consultez le numéro de série, qui se trouve sur la
plaque signalétique de l'appareil. Le numéro de série est au format MAASSRXXXX,
avec AA et SS indiquant respectivement l’année et la semaine de fabrication :
AA : 17, 18, 19, … = 2017, 2018, 2019,
etc.
SS : 01, 02, 03, … = semaine 1, semaine 2, semaine 3, ...
ATTENTION ! Vous devez suivre les consignes de sécurité à la lettre. Leur
non-respect est susceptible de provoquer des blessures graves, voire
mortelles, ou des dégâts matériels.
Seuls des électriciens qualifiés sont autorisés à procéder à l’installation et la
maintenance du variateur.
N'intervenez jamais sur le variateur, le moteur ou son câblage sous tension. S’il
est déjà raccordé au réseau, vous devez attendre 5 minutes après
sectionnement de l’alimentation avant d’intervenir.
Vous ne devez jamais intervenir sur les câbles de commande lorsque le
variateur ou les circuits de commande externes sont sous tension.
Le variateur ainsi que le moteur et les équipements annexes doivent être mis à
la terre en permanence via le bus PE de l'alimentation.
En cas de perçage ou de rectification d’un élément, évitez toute pénétration de
débris dans le variateur.
Vous ne devez pas alimenter le variateur avec une tension supérieure à la
valeur figurant sur sa plaque signalétique.
3AUA0000085966 Rév H
42 FR – Guide d'installation
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
Pour la procédure de réactivation, cf. document anglais Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629), disponible sur Internet (www.abb.com/drives/documents
).
Sélection des câbles de puissance
Les câbles de puissance doivent être dimensionnés en fonction de la réglementation
locale pour supporter le courant nominal indiqué sur la plaque signalétique du
variateur.
Le tableau J page 100 indique les sections typiques des câbles de puissance.
Reportez-vous au manuel d'installation pour le calcul du dimensionnement.
Refroidissement
Cf. tableau B page 97 pour les pertes et le débit d'air de refroidissement dans le
variateur. Sans déclassement, la plage de température de fonctionnement admissible
va de -15 à +40 °C.
Protection du variateur et du câble réseau
Cf. tableau B page 97. Vérifiez que le temps de manœuvre du fusible est inférieur à
0,5 seconde.
Montage mural du variateur
Cf. figure A page 97.
Vérification de la compatibilité avec les réseaux en régime
IT (neutre isolé ou impédant), TT, et en couplage triangle
avec mise à la terre asymétrique ou centrale (« high leg
delta »)
En standard (varistance phase-terre branchée), le variateur peut être raccordé sur un
réseau en régime TN-S (mise à la terre symétrique). Autres exécutions : reportez-
vous au manuel d'installation ainsi qu’au document anglais ACS880 frames R1 to
R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152).
FR – Guide d'installation 43
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
A = réseau en régime TN-S, B1 = mise à la terre asymétrique, B2 = mise à la terre centrale, C = réseau en
régime IT
ATTENTION ! Il est interdit de raccorder un variateur équipé du filtre RFI
(options +E200 et +E202) sur un réseau non prévu pour cet usage, ce qui peut
s’avérer dangereux ou endommager l’appareil.
ATTENTION ! Il est interdit de raccorder un variateur équipé de la varistance
phase-terre sur un réseau non prévu pour cet usage, car cela risque
d’endommager le circuit des varistances. Cf. manuel d’installation du variateur.
Nota : Avec l’option +E201, lorsque le variateur est raccordé à un réseau autre que
TN-S, retirez les vis EMC AC, EMC DC et VAR si cela n’a pas déjà été effectué en
usine. Pour en savoir plus, contactez ABB.
Mesurez la résistance d'isolement du câble réseau, du
moteur et de son câblage
Mesurez la résistance d’isolement du câble réseau avant de le brancher sur le
variateur conformément à la réglementation en vigueur.
Mesurez la résistance d'isolement du moteur et de son câblage lorsqu'il est sectionné
du variateur : cf. figure F page 98. Mesurez la résistance d’isolement du câble moteur
entre chaque phase et la terre de protection (PE) avec une tension de mesure de
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
44 FR – Guide d'installation
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
1000 Vc.c. Les valeurs mesurées sur un moteur ABB doivent être supérieures à
100 Mohm (valeur de référence à 25 °C ou 77 °F). Pour la résistance d'isolement des
autres moteurs, prière de consulter les consignes du fabricant. Nota : La présence
d’humidité à l’intérieur de l’enveloppe du moteur réduit sa résistance d’isolement. Si
vous soupçonnez la présence d’humidité, séchez le moteur et recommencez la
mesure.
Fixation des étiquettes de mise en garde dans votre langue
Raccordement des câbles de puissance
Cf. figures C, D, E et G. Utilisez un câble moteur symétrique blindé.
5. Retirez les vis de fixation sur les côtés du capot avant.
6. Démontez le capot en le faisant glisser vers l'avant.
7. Vous devez fixer une étiquette de mise en garde contre les tensions résiduelles
dans votre langue sur le logement de la micro-console.
8. Sur la plaque passe-câbles, retirez les passe-câbles en caoutchouc des câbles à
raccorder.
9. Appareils IP21
: Fixez les connecteurs de câbles (joints à la livraison dans un
sachet en plastique) à la plaque passe-câbles.
10. Préparez les extrémités des câbles d'alimentation et moteur comme l'illustre la
figure.
11. Effectuez une reprise de masse sur 360 degrés au niveau des connecteurs
(appareils IP21) ou sous les colliers (appareils IP55).
12. Raccordez le blindage torsadé du câble réseau à la borne PE.
13. Raccordez le conducteur PE du câble réseau à la borne PE supplémentaire.
14. Raccordez les blindages torsadés des câbles moteur et de la résistance (si
présent) à la borne de terre.
15. Raccordez les conducteurs de phase des câbles réseau, moteur et de la
résistance. Serrez les vis.
16. Montez la platine de mise à la terre des câbles de commande dans le boîtier
d'entrée des câbles.
17. Fixez les câbles mécaniquement à l’extérieur du variateur.
18. Mettez à la terre le blindage du câble moteur du côté moteur. Pour minimiser les
interférences, effectuez une reprise de masse sur 360 degrés au niveau du
passe-câbles ou faites une queue de cochon aussi courte que possible.
FR – Guide d'installation 45
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
Raccordement des câbles de commande
Cf. figure H
1. Découpez des trous de diamètre adéquat dans les passe-câbles en caoutchouc
pour les glisser sur les câbles. Insérez les câbles dans les trous de la plaque
inférieure et fixez-y les passe-câbles.
2. Dénudez les extrémités de câbles et coupez à la longueur adéquate (vous
remarquerez que les conducteurs de terre sont plus longs).
3. Effectuez une reprise de masse sur 360° des blindages extérieurs de tous les
câbles de commande au niveau du collier de mise à la terre du boîtier d'entrée de
câbles.
4. Mettez à la masse des blindages de câbles au niveau du collier de mise à la terre.
L'autre extrémité des blindages doit être laissée non connectée ou être reliée à la
terre indirectement par le biais d’un condensateur haute fréquence de quelques
nanofarads (ex., 3,3 nF/630 V).
5. Raccordez les conducteurs aux bornes correspondantes de la carte de
commande. (cf. page 46).
6. Raccordez les modules optionnels, si inclus à la livraison.
7. Remontez le capot avant.
Nota : Pour les câbles du bus de terrain, cf. figure I.
1. Montez la platine de mise à la terre supplémentaire.
2. Effectuez une reprise de masse sur 360° des blindages externes sous le collier
de terre.
3. Percez les ouvertures dans le capot du boîtier d'entrée des câbles pour le
passage des câbles. Montez le capot du boîtier d'entrée des câbles.
4. Raccordez le connecteur au module coupleur réseau.
Raccordement des signaux d’E/S (préréglages)
Le schéma suivant présente les préréglages usine des signaux d’E/S du
macroprogramme Usine du programme de commande standard de l'ACS880
46 FR – Guide d'installation
EN
DA
DE
ES
FI
FR
FR
NL
PT
RU
SV
TR
CN
XPOW Entrée alimentation externe
1 +24VI
24 Vc.c., 2 A
2 GND
XAI Tension de référence et entrées analogiques
1 +VREF 10 Vc.c., R
L
1…10 kohm
2 -VREF -10 Vc.c., R
L
1…10 kohm
3 AGND Terre
4 AI1+ Référence vitesse 0(2)…10 V, R
en
>
200 kohm
5 AI1-
6 AI2+
Non utilisée par défaut. 0(4)…20 mA,
R
en
= 100 ohm
7 AI2-
J1 J1
Sélection courant/tension AI1 par cavalier
J2 J2
Sélection courant/tension AI2 par cavalier
XAO Sorties analogiques
1 AO1 Vitesse moteur tr/min 0…20mA, R
L
<
500 ohm
2 AGND
3 AO2 Courant moteur 0…20 mA, R
L
<
500 ohm
4 AGND
XD2D Liaison multivariateurs (D2D)
1 B
Liaison multivariateurs
2 A
3 BGND
J3 J3
Commutateur de terminaison de la liaison D2D
XRO1, XRO2, XRO3 Sorties relais
11 NC
Prêt
250 Vc.a. / 30 Vc.c.
2 A
12 COM
13 NO
21 NC
En marche
250 Vc.a. / 30 Vc.c.
2 A
22 COM
23 NO
31 NC
Défaut(-1)
250 Vc.a. / 30 Vc.c.
2 A
32 COM
33 NO
XD24 Verrouillage logique
1 DIIL Validation Marche
2 +24VD +24 Vc.c. 200 mA
1)
3 DICOM Masse entrées logiques
4 +24VD +24 Vc.c. 200 mA
1)
5 DIOGND Masse entrées/sorties logiques
J6 Commutateur de sélection de masse
XDIO Entrées/sorties logiques
1 DIO1 Sortie : Prêt
2 DIO2 Sortie : En marche
XDI Entrées logiques
1 DI1 Arrêt (0) / Démarrage (1)
2 DI2 Avant (0) / Arrière (1)
3 DI3 Réarmement
4 DI4 Sélection accélération & décélération
5 DI5 Vitesse constante 1 (1 = On)
6 DI6 Non utilisée par défaut
XSTO Interruption sécurisée du couple STO
1 OUT1
Interruption sécurisée du couple STO.
Les deux circuits doivent être fermés
pour autoriser le démarrage du
variateur.
2 SGND
3 IN1
4 IN2
X12 Raccordement module de fonctions de sécurité
X13 Raccordement micro-console
X205 Raccordement unité mémoire
Section des fils :
0,5 … 2,5 mm
2
(24…12 AWG)
Couples de
serrage : 0,5 N·m
(5 lbf·in) pour
câbles à brins
multiples toronnés
et monobrin.
1)
La capacité de
charge totale des
sorties est de
4,8 W (200 mA /
24 V) moins la
puissance
consommée par
DIO1 et DIO2.
Défaut
IT – Guida rapida all'installazione 47
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
IT – Guida rapida all'installazione
Questa guida illustra brevemente la procedura di installazione del convertitore di
frequenza. Per istruzioni più dettagliate, linee guida ingegneristiche, dati tecnici e
norme di sicurezza complete, si rimanda al Manuale hardware (www.abb.com/drives
:
selezionare Document Library e cercare il numero del documento 3AUA0000078093
[inglese]).
Rispettare le norme di sicurezza
Il pavimento sottostante all'unità deve essere di materiale non infiammabile.
Ricondizionamento dei condensatori
I condensatori devono essere ricondizionati se il convertitore è fermo da oltre un
anno (perché è rimasto inutilizzato oppure in magazzino).
La data di fabbricazione si legge dal numero di serie riportato sull'etichetta
identificativa del convertitore. Il formato del numero di serie è MYYWWRXXXX. YY e
WW indicano rispettivamente l'anno e la settimana di produzione, nel modo
seguente:
YY: 17, 18, 19, … per 2017, 2018, 2019,
WW: 01, 02, 03, … per settimana 1, settimana 2, settimana 3,
Per informazioni sul ricondizionamento dei condensatori, vedere Converter
Modules with Electrolytic DC Capacitors in the DC Link Capacitor Reforming
AVVERTENZA! Rispettare le seguenti norme di sicurezza. La mancata
osservanza di queste norme può mettere in pericolo l'incolumità delle
persone, con rischio di morte, e danneggiare le apparecchiature:
L'installazione e la manutenzione del convertitore di frequenza devono essere
eseguite solo da elettricisti qualificati.
Non operare mai sul convertitore, sul cavo motore o sul motore quando è
inserita l'alimentazione. Se il convertitore è già collegato all'alimentazione,
disinserirla e attendere 5 minuti.
Non lavorare mai sui cavi di controllo quando il convertitore o i circuiti di
controllo esterni sono alimentati.
Mettere sempre a terra il convertitore, il motore e le apparecchiature adiacenti
collegandoli al bus di terra (PE) dell'alimentazione.
Assicurarsi che i detriti generati da forature e smerigliature non si infiltrino
nell'unità durante l'installazione.
Non collegare il convertitore a una tensione superiore al valore indicato
sull'etichetta di identificazione dell'unità.
3AUA0000085966 Rev H
48 IT – Guida rapida all'installazione
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
Instructions (3BFE64059629 [inglese]), disponibile in Internet al sito
www.abb.com/drives/documents.
Selezione dei cavi di potenza
Dimensionare i cavi di potenza in base alle normative locali. I cavi devono essere
adatti a condurre la corrente nominale indicata sull'etichetta identificativa del
convertitore.
Le dimensioni tipiche dei cavi di potenza sono riportate nella tabella J a pag. 100. Per
le regole di dimensionamento, vedere il Manuale hardware.
Raffreddamento
Vedere la tabella B a pag. 97 per i dati relativi alle perdite e al flusso d'aria attraverso
il convertitore di frequenza. Il range di temperatura operativa del convertitore, senza
declassamento, è -15 ... +40 °C.
Protezione del convertitore e del cavo di alimentazione di
ingresso
Vedere la tabella B a pag. 97. Verificare che il tempo di intervento del fusibile sia
inferiore a 0.5 secondi.
Montaggio del convertitore di frequenza a parete
Vedere la figura A a pag. 97.
Verifica della compatibilità con sistemi IT (senza messa a
terra), sistemi a triangolo con una fase a terra, a triangolo
con messa a terra nel punto mediano e sistemi TT
Il convertitore standard, con i varistori fase-terra collegati, può essere installato in un
sistema TN-S con messa a terra simmetrica. Per gli altri sistemi, vedere il Manuale
hardware e ACS880 Frames R1 to R11 EMC Filter and Ground-to-Phase Varistor
Disconnecting Instructions (3AUA0000125152 [inglese]).
IT – Guida rapida all'installazione 49
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
A = sistema TN-S, B1 = sistema con una fase a terra, B2 = sistema con messa a terra nel punto mediano,
C = sistema IT
AVVERTENZA! Non installare il convertitore con il filtro EMC collegato
(opzioni +E200 e +E202) in un sistema che non consente l'uso del filtro.
Questo può determinare una situazione di pericolo o danneggiare l'unità.
AVVERTENZA! Non installare il convertitore con il varistore fase-terra
collegato in un sistema che non consente l'uso del varistore, poiché così
facendo si può danneggiare il circuito del varistore. Vedere il Manuale
hardware del convertitore.
Nota: con l'opzione +E201, rimuovere le viti EMC AC, EMC DC e VAR per i sistemi di
tipo diverso da TN-S, se le viti non sono state rimosse in fabbrica. Per ulteriori
informazioni, contattare ABB.
Controllo dell'isolamento di cavo di ingresso, motore e
cavo motore
Verificare che l'isolamento del cavo di ingresso sia conforme alle normative locali
prima di collegarlo al convertitore di frequenza.
Controllare l'isolamento del cavo motore e del motore quando il cavo è scollegato dal
convertitore; vedere la figura F a pag. 98. Misurare la resistenza di isolamento tra
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
50 IT – Guida rapida all'installazione
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
ogni conduttore di fase e il conduttore di protezione di terra (PE) con una tensione di
misura di 1000 Vcc. La resistenza di isolamento dei motori ABB deve essere
superiore a 100 Mohm (valore di riferimento a 25 °C o 77 °F). Per la resistenza di
isolamento di altri motori, consultare le istruzioni del produttore. Nota: la presenza di
umidità all'interno dell'alloggiamento del motore riduce la resistenza di isolamento. In
caso di umidità, asciugare il motore e ripetere la misurazione.
Applicazione degli adesivi di avvertenza nelle lingue locali
Collegamento dei cavi di potenza
Vedere le figure C, D, E e G. Utilizzare un cavo schermato di tipo simmetrico per il
motore.
5. Svitare le viti di montaggio ai lati del coperchio anteriore.
6. Rimuovere il coperchio facendolo scorrere in avanti.
7. Applicare l'adesivo con il messaggio di avvertenza per tensione residua (nella
lingua locale) sulla piastra di fissaggio del pannello di controllo.
8. Rimuovere i gommini dalla piastra passacavi per il passaggio dei cavi che si
intendono collegare.
9. Unità IP21
: applicare i connettori dei cavi (inclusi nella fornitura, all'interno di un
sacchetto di plastica) sui fori della piastra passacavi.
10. Preparare le estremità del cavo di alimentazione e del cavo motore come
illustrato nella figura.
11. Mettere a terra a 360° le schermature dei cavi in corrispondenza dei connettori
dei cavi (unità IP21) o sotto i morsetti (unità IP55).
12. Collegare la schermatura intrecciata del cavo di ingresso al morsetto PE.
13. Collegare il conduttore PE del cavo di ingresso al morsetto PE supplementare.
14. Collegare le schermature intrecciate del cavo del motore e del cavo della
resistenza (se presente) al morsetto di terra.
15. Collegare i conduttori di fase del cavo di ingresso, del cavo del motore e del cavo
della resistenza. Serrare le viti.
16. Installare la piastra di messa a terra dei cavi di controllo nella cassetta di ingresso
dei cavi.
17. Fissare i cavi meccanicamente all'esterno del convertitore di frequenza.
18. Mettere a terra la schermatura del cavo del motore sul lato motore. Per ridurre al
minimo le interferenze, eseguire una messa a terra a 360° in corrispondenza
della piastra passacavi, o ridurre al minimo la lunghezza del fascio intrecciato.
IT – Guida rapida all'installazione 51
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
Collegamento dei cavi di controllo
Vedere la figura H.
1. Praticare fori di dimensioni idonee nei gommini e fare scivolare i gommini sui cavi.
Inserire i cavi nei fori della piastra inferiore e fissare i gommini ai fori.
2. Spellare le estremità dei cavi e tagliarle a una lunghezza adeguata (tenendo
conto della lunghezza extra dei conduttori di terra).
3. Mettere a terra le schermature esterne di tutti i cavi di controllo a 360° sotto un
morsetto di terra nella cassetta di ingresso dei cavi.
4. Mettere a terra le schermature dei doppini sotto il morsetto di terra. Lasciare
scollegata l'altra estremità delle schermature o metterla a terra indirettamente
utilizzando un condensatore ad alta frequenza di pochi nanofarad (es. 3.3 nF /
630 V).
5. Collegare i conduttori ai morsetti corrispondenti della scheda di controllo (vedere
pag. 52).
6. Collegare i moduli opzionali, se inclusi nella fornitura.
7. Reinstallare il coperchio anteriore.
Nota per il cablaggio del bus di campo. Vedere la figura I.
1. Installare la piastra supplementare di messa a terra.
2. Mettere a terra le schermature esterne dei cavi a 360° in corrispondenza del
morsetto di terra.
3. Aprire dei fori nel coperchio della cassetta di ingresso cavi, in corrispondenza dei
cavi da installare. Installare il coperchio della cassetta di ingresso cavi.
4. Inserire il connettore nel modulo bus di campo.
Collegamenti di I/O di default
Di seguito sono illustrati i collegamenti degli I/O di default della macro Fabbrica del
programma di controllo primario dell'ACS880.
52 IT – Guida rapida all'installazione
IT
DA
DE
ES
FI
FR
IT
IT
PT
RU
SV
TR
CN
XPOW Ingresso alimentazione esterna
1 +24VI
24 Vcc, 2 A
2 GND
XAI Ingressi analogici e tensione di riferimento
1 +VREF 10 Vcc, R
L
1…10 kohm
2 -VREF -10 Vcc, R
L
1…10 kohm
3 AGND Terra
4 AI1+
Riferimento velocità 0(2)…10 V, R
in
> 200 kohm
5 AI1-
6 AI2+
Di default non utilizzati. 0(4)…20 mA, R
in
=
100 ohm
7 AI2-
J1 J1 Ponticello di selezione corrente/tensione AI1
J2 J2 Ponticello di selezione corrente/tensione AI2
XAO Uscite analogiche
1 AO1
Velocità motore rpm 0…20 mA, R
L
< 500 ohm
2 AGND
3 AO2
Corrente motore 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Collegamento drive-to-drive
1 B
Collegamento drive-to-drive
2 A
3 BGND
J3 J3
Interruttore terminazione collegamento drive-to-drive
XRO1, XRO2, XRO3 Uscite relè
11 NC
Pronto
250 Vca / 30 Vcc
2 A
12 COM
13 NO
21 NC
In marcia
250 Vca / 30 Vcc
2 A
22 COM
23 NO
31 NC
Guasto(-1)
250 Vca / 30 Vcc
2 A
32 COM
33 NO
XD24 Interblocco digitale
1 DIIL Abilitazione marcia
2 +24VD +24 Vcc 200 mA
1)
3 DICOM Terra ingressi digitali
4 +24VD +24 Vcc 200 mA
1)
5 DIOGND Terra ingressi/uscite digitali
J6 Interruttore di selezione terra
XDIO Ingressi/uscite digitali
1 DIO1 Uscita: pronto
2 DIO2 Uscita: in marcia
XDI Ingressi digitali
1 DI1 Arresto (0) / Avviamento (1)
2 DI2 Avanti (0) / Indietro (1)
3 DI3 Reset
4 DI4 Selezione accelerazione e decelerazione
5 DI5 Velocità costante 1 (1 = On)
6 DI6 Di default non utilizzato.
XSTO Safe Torque Off
1 OUT1
Safe Torque Off. Per avviare il convertitore
entrambi i circuiti devono essere chiusi.
2 SGND
3 IN1
4 IN2
X12 Collegamento modulo funzioni di sicurezza
X13 Collegamento pannello di controllo
X205 Collegamento unità di memoria
Dimensioni fili:
0.5 … 2.5 mm
2
(24…12 AWG)
Coppie di
serraggio:
0.5 N·m
(5 lbf·in) per
cavi intrecciati
e pieni.
1)
La capacità
di carico
totale di
queste uscite
è 4.8 W
(200 mA /
24 V) meno
la potenza
assorbita da
DIO1 e DIO2.
Guasto
NL – Beknopte installatiegids 53
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
NL – Beknopte installatiegids
Deze gids geeft een beknopte beschrijving van het installeren van de omvormer. Zie,
voor nadere instructies, technische richtlijnen, technische gegevens en complete
veiligheidsinstructies, de hardwarehandleiding (www.abb.com/drives
: Kies Document
Library en zoek document nummer 3AUA0000078093 [Engels]).
Volg de veiligheidsvoorschriften
Het materiaal van de vloer onder de omvormer dient onbrandbaar te zijn.
Controleer of condensatoren opnieuw geformeerd moeten
worden
Formeer de condensatoren opnieuw als de omvormer een jaar of langer niet aan
geweest is (in de opslag of niet gebruikt).
U kunt de fabricagedatum bepalen uit het serienummer, dat op het typeplaatje,
bevestigd aan de omvormer, te vinden is. Het serienummer heeft het formaat
MYYWWRXXXX. YY en WW bepalen als volgt het jaar en de week van fabricage:
YY: 17, 18, 19, … voor 2017, 2018, 2019,
WW: 01, 02, 03, … voor week 1, week 2, week 3,
WAARSCHUWING! Volg deze instructies. Indien u deze negeert, kan dit
lichamelijk letsel of de dood tot gevolg hebben, of er kan schade aan de
apparatuur ontstaan:
De installatie en het onderhoud van de omvormer mag uitsluitend worden
uitgevoerd door gekwalificeerde elektrotechnische vakmensen.
Voer nooit werkzaamheden uit aan de frequentie-omvormer, de motorkabel of
de motor als ze onder spanning staan. Als de omvormer al is aangesloten op
het voedingsnet, ontkoppelt u de omvormer en wacht u 5 minuten.
Voer nooit werkzaamheden uit aan de besturingskabels als de omvormer of
externe besturingscircuits onder spanning staan.
Aard de omvormer, de motor en bijbehorende apparatuur altijd aan de
veiligheidsaarde (PE) -bus van de voeding.
Zorg bij de installatie dat er geen boor- of slijpafval in de omvormer
binnendringt.
Sluit de omvormer niet op een spanning aan die hoger is dan die vermeld is op
het typeplaatje.
3AUA0000085966 Rev H
54 NL – Beknopte installatiegids
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
Zie, voor informatie over het opnieuw formeren van de condensatoren, Converter
modules with electrolytic DC capacitors in the DC link capacitor reforming
instructions (3BFE64059629 [Engels]), dat op internet te vinden is op
www.abb.com/drives/documents
.
Kies de vermogenskabels
Dimensioneer de vermogenskabels volgens de plaatselijke regelgeving om de
nominale stroom te voeren die gegeven is op het typeplaatje van uw omvormer.
Typische vermogenskabel-afmetingen zijn te vinden in tabel J op pagina 100. Zie,
voor de voorwaarden van de afmetingen, de hardwarehandleiding.
Zorg voor de koeling
Zie tabel B op pagina 97 voor de verliezen en de koelluchtstroom door de omvormer.
Het toegestane bedrijfstemperatuurbereik van de omvormer zonder derating is -15 tot
+40 °C.
Beveilig de omvormer en de voedingskabel
Zie tabel B op pagina 97. Controleer dat de aanspreektijd van de zekering korter is
dan 0,5 seconde.
Installeer de omvormer aan de wand
Zie figuur A op pagina 97.
Controleer de compatibiliteit met IT (ongeaarde), corner-
grounded delta, midpoint-grounded delta, en TT systemen
De standaard omvormer met aangesloten aarde-naar-fase varistors kan
geïnstalleerd worden in een symmetrisch geaard TN-S systeem. Zie voor andere
systemen de hardwarehandleiding en ACS880 frames R1 to R11 EMC filter and
ground-to-phase varistor disconnecting instructions (3AUA0000125152 [Engels]).
NL – Beknopte installatiegids 55
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
A = TN-S systeem, B1 = Corner-grounded systeem, B2 = Midpoint-grounded systeem, C = IT systeem
WAARSCHUWING! Installeer de omvormer niet met aangesloten EMC-filter
opties +E200 en +E202 in een systeem waarvoor het filter niet geschikt is. Dit
kan gevaar opleveren of de omvormer beschadigen.
WAARSCHUWING! Installeer de omvormer niet met aangesloten aarde-naar-
fase varistor in een systeem waarvoor de varistor niet geschikt is. Indien u dit
wel doet, kan het varistor-circuit beschadigd worden. Zie de hardwarehandleiding van
de omvormer.
Opmerking: Verwijder bij optie +E201 de EMC AC, EMC DC en VAR schroeven voor
andere systemen dan TN-S systemen indien ze nog niet in de fabriek verwijderd zijn.
Neem voor meer informatie contact op met ABB.
Controleer de isolatie van de ingangs- en motorkabels en
van de motor
Controleer de isolatie van de ingangskabel volgens plaatselijke regelgeving alvorens
u deze aansluit op de omvormer.
Controleer de isolatie van de motorkabel en motor wanneer de kabel losgekoppeld is
van de omvormer, zie figuur F op pagina 98. Meet de isolatieweerstand tussen elke
fasegeleider en de veiligheidsaardegeleider door een meetspanning van 1000 V DC
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
56 NL – Beknopte installatiegids
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
te gebruiken. De isolatieweerstand van een ABB-motor moet hoger zijn dan
100 Mohm (referentiewaarde bij 25 °C of 77 °F). Voor de isolatieweerstand van
andere motors moet u de instructies van de fabrikant raadplegen. Opmerking: Vocht
in de motorbehuizing zal de isolatieweerstand verlagen. Als u vocht vermoedt, moet u
de motor drogen en de meting herhalen.
Bevestig de waarschuwingsstickers in plaatselijke talen
Sluit de vermogenskabels aan
Zie figuren C, D, E en G. Gebruik symmetrisch afgeschermde kabel voor de
motorbekabeling.
5. Draai de montageschroeven aan de zijkanten van de frontkap los.
6. Verwijder de kap door deze naar voren te schuiven.
7. Bevestig de waarschuwingssticker tegen restspanning in de plaatselijke taal op
het montageplatform voor het bedieningspaneel.
8. Verwijder de rubberen doorvoertules van de doorvoerplaat zodat de kabels
aangesloten kunnen worden.
9. IP21 units
: Bevestig de kabelconnectoren (meegeleverd in een plastic zak) in de
gaten van de kabeldoorvoerplaat.
10. Maak de uiteinden van de voedings- en motorkabels gereed zoals in de figuur
geïllustreerd.
11. Aard de kabelafschermingen over 360 graden in de kabelconnectoren
(IP21 units) of onder de klemmen (IP55 units).
12. Sluit de getwiste afscherming van de ingangskabel aan op de PE-klem.
13. Sluit de PE-geleider van de ingangskabel aan op de extra PE-klem.
14. Sluit de getwiste afscherming van de motorkabel en weerstandskabel (indien
aanwezig) aan op de aardingsklem.
15. Sluit de fasegeleiders van de ingangs-, motor- en weerstandskabels aan. Draai
de schroeven vast.
16. Installeer de aardingsplaat voor de besturingskabels in het kabelingangsblok.
17. Zet de kabels buiten de omvormer mechanisch vast.
18. Aard de motorkabelafscherming aan de motorzijde. Maak, om interferentie te
minimaliseren, een aarding van 360 graden bij de kabeldoorvoer, of houd de
pigtail kort.
NL – Beknopte installatiegids 57
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
Sluit de besturingskabels aan
Zie figuur H.
1. Snij voldoende grote gaten in de rubberen doorvoertules en schuif de
doorvoertules op de kabels. Schuif de kabels door de gaten van de bodemplaat
en maak de doorvoertules in de gaten vast.
2. Strip de kabeluiteinden en snijd deze tot een geschikte lengte (houd rekening met
de extra lengte van de aardgeleiders).
3. Aard de buitenste afschermingen van alle besturingskabels over 360 graden aan
een aardingsklem in het kabelinvoerblok.
4. Aard de kabelpaar-afschermingen aan de aardklem. Sluit het andere uiteinde van
de afschermingen niet aan of aard deze indirect via een hoogfrequente
condensator van enkele nanofarad, bijvoorbeeld 3,3 nF / 630 V).
5. Sluit de geleiders op de juiste klemmen van de besturingskaart aan (zie pagina 58).
6. Bedraad de optionele modules indien deze bij de levering bijgevoegd zijn.
7. Zet de frontkap terug?
Opmerking voor?veldbus-bekabeling. Zie figuur I.
1. Installeer de extra aardingsplaat.
2. Aard de buitenste afscherminen van de kabels over 360 graden bij de aardklem.
3. Druk gaten in het deksel van het kabelingangsblok uit zodat de kabels
geïnstalleerd kunnen worden. Installeer het deksel van het kabelingangsblok.
4. Plug de connector in de veldbusmodule.
Standaard I/O aansluitingen
De standaard I/O-aansluitingen voor de Fabrieksmacro van het ACS880 primair
besturingsprogramma worden hieronder getoond.
58 NL – Beknopte installatiegids
EN
DA
DE
ES
FI
FR
IT
NL
NL
RU
SV
TR
CN
XPOW Externe hulpspanningsingang
1 +24VI
24 V DC, 2 A
2 GND
XAI Referentiespanning en analoge ingangen
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF -10 V DC, R
L
1…10 kohm
3 AGND Aarde
4 AI1+ Toerentalreferentie 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+
Standaard niet in gebruik. 0(4)…20 mA,
R
in
= 100 ohm
7 AI2-
J1 J1 AI1 stroom/spanning selectiejumper
J2 J2 AI2 stroom/spanning selectiejumper
XAO Analoge uitgangen
1 AO1 Motortoerental rpm 0…20 mA, R
L
<
500 ohm
2 AGND
3 AO2
Motorstroom 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Drive-to-drive link
1 B
Drive-to-drive link
2 A
3 BGND
J3 J3 Afsluitingsjumper drive-to-drive link
XRO1, XRO2, XRO3 Relaisuitgangen
11 NC
Gereed
250 V AC/30 V DC
2 A
12 COM
13 NO
21 NC
In bedrijf
250 V AC/30 V DC
2 A
22 COM
23 NO
31 NC
Fout(-1)
250 V AC/30 V DC
2 A
32 COM
33 NO
XD24 Digitale blokkering
1 DIIL Runvrijgave
2 +24VD +24 V DC 200 mA
1)
3 DICOM Aarde digitale ingang
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Aarde digitale ingang/uitgang
J6 Aarde selectiejumper
XDIO Digitale ingang/uitgangen
1 DIO1 Uitgang: Gereed
2 DIO2 Uitgang: In bedrijf
XDI Digitale ingangen
1 DI1 Stop (0) / Start (1)
2 DI2 Voorwaarts (0) / Achterwaarts (1)
3 DI3 Reset
4 DI4 Acceleratie & deceleratie keuze
5 DI5 Constant toerental 1 (1 = Aan)
6 DI6 Standaard niet in gebruik.
XSTO Safe torque off
1 OUT1
Safe torque off. Beide circuits moeten
gesloten zijn voordat de omvormer kan
starten.
2 SGND
3 IN1
4 IN2
X12 Aansluiting veiligheidsfuncties-module
X13 Aansluiting bedieningspaneel
X205 Aansluiting geheugenunit
Ader-
afmetingen:
0,5 … 2,5 mm
2
(24…12 AWG)
Aanhaalmoment
en: 0,5 N·m
(5 lbf·in) voor
zowel
gevlochten als
massieve
bedrading.
1)
Totale belas-
tingscapaciteit van
deze uitgangen is
4,8 W (200 mA /
24 V) minus het
vermogen opgeno-
men door DIO1 en
DIO2.
Fout
PL — Skrócona instrukcja montażu 59
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
PL — Skrócona instrukcja montażu
Ten dokument zawiera skrócon instrukcj montau przemiennika czstotliwoci.
Bardziej szczegóowe wskazówki, wytyczne i dane techniczne oraz pene instrukcje
bezpieczestwa zawiera podrcznik uytkownika (www.abb.com/drives
: naley
wybra opcj Document Library [Biblioteka dokumentów] oraz wyszuka dokument
wjzyku angielskim o numerze 3AUA0000078093).
Należy przestrzegać instrukcji bezpieczeństwa
Materia znajdujcy si na pododze pod przemiennikiem czstotliwoci musi by
niepalny.
Sprawdzenie, czy kondensatory wymagają formowania
Jeli przemiennik czstotliwoci nie by wczany od ponad roku (by w magazynie
lub nie by uywany), naley wykona formowanie kondensatorów.
Dat produkcji mona okreli na podstawie numeru seryjnego, który jest widoczny na
tabliczce znamionowej przymocowanej do przemiennika czstotliwoci. Numer seryjny ma
format MRRTTRXXXX. RR i TT okrelaj rok i tydzie produkcji w nastpujcy sposób:
RR: 17, 18, 19, … oznacza 2017, 2018, 2019,
TT: 01, 02, 03, … to 1. tydzie, 2. tydzie, 3. tydzie,
OSTRZEŻENIE!
Naley przestrzega tych instrukcji. Nieprzestrzeganie instruk-
cji moe skutkowa obraeniami, mierci lub uszkodzeniem urzdzenia:
Do montau i konserwacji przemiennika czstotliwoci uprawnieni s wycznie
wykwalifikowani elektrycy.
Nie mona wykonywa adnych prac przy przemienniku czstotliwoci, kablu
silnika ani silniku, jeli podczone jest ródo zasilania. Jeli przemiennik cz-
stotliwoci jest ju podczony do zasilania, naley odczeka 5 minut po jego
odczeniu.
Nie wolno nigdy wykonywa adnych prac przy kablach sterowania, jeli do
przemiennika czstotliwoci lub zewntrznych obwodów sterowania doprowa-
dzone jest zasilanie.
Zawsze uziemi przemiennik czstotliwoci, silnik oraz pobliskie urzdzenia. do
szyny uziemiajcej (PE) zasilania.
Podczas montau naley uwaa, aby opiki powstajce w trakcie wiercenia
i szlifowania nie przedostay si do wntrza przemiennika czstotliwoci.
Nie mona podcza przemiennika czstotliwoci do napicia wyszego ni
podane na tabliczce znamionowej.
3AUA0000085966 wersja H
60 PL — Skrócona instrukcja montażu
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
Wicej informacji na temat formowania kondensatorów zawiera dokument
Converter modules with electrolytic DC capacitors in the DC link capacitor
reforming instructions (3BFE64059629 [j.ang.]), który jest dostpny na stronie
internetowej www.abb.com/drives/documents
.
Dobór kabli zasilania
Kable zasilania naley zwymiarowa zgodnie z obowizujcymi przepisami
lokalnymi, tak aby zapewni przepyw prdu znamionowego, którego warto jest
podana na tabliczce znamionowej przemiennika czstotliwoci.
Typowe rozmiary kabli zasilania wymieniono w tabeli J na stronie 100. Warunki
dotyczce dobierania rozmiarów mona znale w podrczniku oprogramowania
przemiennika czstotliwoci.
Zapewnianie chłodzenia
W tabeli B na stronie 97 zawarto informacje o stratach oraz przepywie powietrza
chodzcego przez przemiennik czstotliwoci. Dozwolony zakres temperatury pracy
przemiennika czstotliwoci bez obnienia jego wartoci znamionowych wynosi od -
15 do +40°C.
Ochrona przemiennika częstotliwości i kabla zasilania
wejściowego
Odpowiednie informacje zawiera tabela B na stronie 97. Naley upewni si, e czas
zadziaania bezpiecznika wynosi mniej ni 0,5 s.
Montaż przemiennika częstotliwości na ścianie
Patrz rysunek A na stronie 97.
Sprawdzanie zgodności z sieciami IT (bez uziemienia), typu
trójkąt z uziemieniem wierzchołkowym i centralnym oraz TT
Standardowy przemiennik czstotliwoci z podczonymi warystorami uziemienie-
faza mona poczy z uziemion symetrycznie sieci TN-S. W przypadku innych
sieci informacji naley szuka w podrczniku uytkownika i dokumencie ACS880
frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152 [j. ang.]).
PL — Skrócona instrukcja montażu 61
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
.
A = sie TN-S, B1 = sie uziemiona wierzchokowo, B2 = sie uziemiona centralnie, C = sie IT
OSTRZEŻENIE! Nie naley instalowa przemiennika czstotliwoci z podczo-
nymi opcjami +E200 i +E202 filtra EMC w sieci, dla której ten filtr jest nieodpo-
wiedni. Moe to spowodowa zagroenie lub uszkodzi przemiennik czstotliwoci.
OSTRZEŻENIE! Nie naley instalowa przemiennika czstotliwoci z podczo-
nym warystorem uziemienie-faza w sieci, dla której ten warystor jest nieodpo-
wiedni. Moe to uszkodzi obwód warystora. Wicej informacji znajduje si
w podrczniku uytkownika przemiennika czstotliwoci.
Uwaga: W przypadku opcji +E201 naley wykrci wkrty EMC AC, EMC DC i VAR
dla sieci innych ni TN-S (o ile nie zostay wykrcone w fabryce). Wicej informacji na
ten temat mona uzyska od firmy ABB.
Sprawdzenie izolacji wejściowego kabla zasilania i kabla
silnika oraz samego silnika
Przed podczeniem wejciowego kabla zasilania do przemiennika czstotliwoci
naley sprawdzi, czy jego izolacja jest zgodna z lokalnymi przepisami.
Izolacj silnika oraz kabla silnika i silnika naley sprawdzi, gdy kabel jest odczony
od przemiennika czstotliwoci; patrz rysunek F na stronie 98. Zmierzy rezystancj
izolacji pomidzy poszczególnymi przewodami fazowymi a przewodem uziomowym
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
62 PL — Skrócona instrukcja montażu
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
przy uyciu napicia pomiarowego 1000 V DC. Rezystancja izolacji silnika ABB musi
przekracza 100 M (warto zadana przy temperaturze 25 °C lub 77 °F). Wymaga-
nia dotyczce rezystancji izolacji innych silników zostay podane w instrukcjach
dostarczonych przez producenta. Uwaga: Wilgo wewntrz obudowy silnika zmniej-
sza rezystancj izolacji. Jeli istnieje prawdopodobiestwo obecnoci wilgoci, naley
wysuszy silnik i powtórzy pomiar.
Mocowanie nalepek ostrzegawczych w językach lokalnych
Podłączanie kabli zasilania
Patrz rysunki C, D, E i G. W okablowaniu silnika naley uywa symetrycznego kabla
ekranowanego.
5. Odkrci wkrty montaowe po bokach osony przedniej.
6. Usun oson, przesuwajc j do przodu.
7. Przyklei naklejk z ostrzeeniem o napiciu szcztkowym w odpowiednim
jzyku do platformy montaowej panelu sterowania.
8. Wyj gumowe dawiki z pyty przepustowej w miejscach, w których maj zosta
wprowadzone kable.
9. Jednostki IP21:
Zamocowa czniki kablowe (znajdujce si w torebce foliowej
w opakowaniu) w otworach na kable w pycie.
10. Przygotowa kocówki kabli zasilania oraz silnika w sposób przedstawiony na
rysunku.
11. Uziemi ekrany kabli na caym obwodzie w cznikach kablowych (jednostki IP21)
lub pod zaciskami (jednostki IP55).
12. Podczy skrcany ekran kabla wejciowego do zacisku ochronnego.
13. Podczy przewód ochronny kabla wejciowego do dodatkowego zacisku
ochronnego.
14. Podczy skrcony ekran kabla silnika i kabla rezystora (jeli jest uywany) do
zacisku uziemienia.
15. Podczy przewody fazowe kabla wejciowego, kabla silnika i kabla rezystora.
Dokrci wkrty.
16. Zamontowa listw uziomow kabla sterowania w skrzynce kablowej.
17. Zabezpieczy kable mechanicznie na zewntrz przemiennika czstotliwoci.
18. Uziemi ekran kabla silnika po stronie silnika. W celu ograniczenia zakóce
naley uziemi ekran na caym obwodzie kabla na przepucie kabla lub postara
si, aby jego kocówka bya jak najkrótsza.
PL — Skrócona instrukcja montażu 63
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
Podłączanie kabli sterowania
Patrz rysunek H.
1. Wyci odpowiednie otwory w gumowych dawikach i nasun je na kable.
Przecign kable przez otwory w pycie dolnej i zamocowa dawiki w tych
otworach.
2. cign izolacj z kocówek kabli i przyci je do odpowiedniej dugoci
(pamitajc o wikszej dugoci przewodów uziomowych).
3. Wykona uziemienia zewntrznych ekranów wszystkich kabli sterowania na
caym obwodzie przy uyciu zacisku uziomowego w skrzynce kablowej.
4. Uziemi ekrany kabli dwuyowych przy uyciu zacisku uziomowego. Drugi
koniec ekranu powinien pozosta niepodczony lub uziemiony porednio przez
kondensator wysokoczstotliwociowy o pojemnoci kilku nanofaradów, np.
3,3 nF/630 V.
5. Podczy przewody do odpowiednich zacisków tablicy rozdzielczej (patrz
strona 64).
6. Podczy moduy opcjonalne, jeli s
czci dostawy.
7. Zaoy oson przedni.
Uwaga dotycząca okablowania magistrali komunikacyjnej. Patrz rysunek I.
1. Zamontowa dodatkow listw uziemiajc.
2. Uziemi obwodowo zewntrzne ekrany kabli pod zaciskiem uziemiajcym.
3. Przygotowa w osonie skrzynki kablowej otwory dla kabli, które bd
podczane. Zainstalowa pokryw skrzynki kablowej.
4. Podczy zcze do moduu magistrali komunikacyjnej.
Domyślne połączenia we/wy
Poniej przedstawiono domylne poczenia we/wy makra fabrycznego dla
standardowego oprogramowania przemiennika czstotliwoci ACS880.
64 PL — Skrócona instrukcja montażu
EN
DA
DE
ES
FI
FR
IT
NL
PT
PL
SV
TR
CN
XPOW Wejcie zasilania zewntrznego
1 +24VI
24 V DC, 2 A
2 GND
XAI Napicie odniesienia i wejcia analogowe
1 +VREF 10 V DC, R
L
1…10 k
2 -VREF -10 V DC, R
L
1…10 k
3 AGND Uziemienie
4 AI1+ Wartość zadana prędkości 0(2)…10 V,
R
in
> 200 k
5 AI1-
6 AI2+
Domylnie nieuywane. 0(4)…20 mA,
R
in
= 100
7 AI2-
J1 J1
Zworka wyboru trybu pracy wejcia AI1 (prdowe/napiciowe)
J2 J2
Zworka wyboru trybu pracy wejcia AI2 (prdowe/napiciowe)
XAO Wyjcia analogowe
1 AO1 Prędkość silnika w obrotach na
minutę 0…20mA, R
L
< 500
2 AGND
3 AO2
Prąd silnika 0…20mA, R
L
< 500
4 AGND
XD2D cze drive-to-drive
1 B
cze drive-to-drive
2 A
3 BGND
J3 J3
Przecznik terminacji cza drive-to-drive
XRO1, XRO2, XRO3 Wyjcia przekanikowe
11 NC
Stan gotowości
250 V AC / 30 V DC
2 A
12 COM
13 NO
21 NC
Bieg
250 V AC / 30 V DC
2 A
22 COM
23 NO
31 NC
Błąd (-1)
250 V AC / 30 V DC
2 A
32 COM
33 NO
XD24 Blokada cyfrowa
1 DIIL Zezwolenie na bieg
2 +24VD +24 V DC 200 mA
1)
3 DICOM Masa wejcia cyfrowego
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Masa wejcia/wyjcia cyfrowego
J6 Przecznik wyboru masy
XDIO Wejcia/wyjcia cyfrowe
1 DIO1 Wyjcie: Stan gotowoci
2 DIO2 Wyjcie: Bieg
XDI Wejcia cyfrowe
1 DI1 Stop (0)/Start (1)
2 DI2 Do przodu (0)/Do tyu (1)
3 DI3 Reset
4 DI4
Wybór czasów przyspieszenia i zwolnienia
5 DI5 Staa prdko 1 (1 = W.)
6 DI6 Domylnie nieuywane.
XSTO Bezpieczne wyczanie momentu
1 OUT1
Bezpieczne wyczanie momentu (STO).
Oba obwody musz by zamknite, aby
byo moliwe uruchomienie
przemiennika czstotliwoci.
2 SGND
3 IN1
4 IN2
X12 Zcze moduu funkcji bezpieczestwa
X13 Zcze panelu sterowania
X205 Zcze moduu pamici
Rozmiary
przewodów:
0.5 … 2,5 mm
2
(24…12 AWG)
Momenty
dokrcania:
0,5 N m dla kabli
jedno- i
wieloyowych.
1)
Cakowita
obcialno tych
wyj wynosi
4,8 W (200 mA /
24 V) minus moc
pobierana przez
zcza DIO1
iDIO2.
Bd
PT - Guia rápido de instalação 65
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
PT - Guia rápido de instalação
Este guia contém instruções sobre como instalar o acionamento. Para instruções
mais detalhadas, indicações de engenharia, dados técnicos e instruções de
segurança completas, consulte o manual de hardware em (www.abb.com/drives
:
Selecione Document Library e aceda ao documento número 3AUA0000078093
[Inglês]).
Cumpra as instruções de segurança
O material do piso por baixo do acionamento deve ser não inflamável.
Verificar se é necessário reformar os condensadores
Deve beneficiar os condensadores se o acionamento não tiver sido ligado (estiver
armazenado ou não tiver sido usado) durante um ou mais anos.
É possível determinar a data de fabrico a partir do número de série, que se encontra
na etiqueta de designação de tipo colada no acionamento. O número de série é do
formato MYYWWRXXXX. YY e WW indicam o ano e a semana de fabrico como se
segue:
YY: 17, 18, 19, … para 2017, 2018, 2019,
WW: 01, 02, 03, … para semana 1, semana 2, semana 3,
AVISO! Cumprir estas instruções. Se ignorar as mesmas, podem ocorrer
ferimentos ou morte, ou danos no equipamento:
Apenas profissionais eletricistas qualificados estão autorizados a instalar e a
reparar o acionamento.
Nunca trabalhe no acionamento, no cabo do motor ou no motor com a
alimentação aplicada. Se o acionamento já estiver ligado à entrada de
alimentação, aguarde 5 minutos depois de desligar a alimentação de entrada.
Nunca manipule os cabos de controlo quando a alimentação está aplicada ao
acionamento ou aos circuitos de controlo externos.
Ligue sempre o acionamento, o motor e o equipamento circundante ao
barramento da terra de proteção (PE) da alimentação de potência.
Certifique-se que as poeiras das perfurações não entram no acionamento
durante a instalação.
Não ligue o acionamento a uma tensão superior à assinalada na etiqueta de
designação de tipo.
3AUA0000085966 Rev H
66 PT - Guia rápido de instalação
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
Para informações sobre a beneficiação de condensadores, consulte Converter
modules with electrolytic DC capacitors in the DC link capacitor reforming
instructions (3BFE64059629 [Inglês]), disponível na Internet em
www.abb.com/drives/documents
.
Selecionar os cabos de potência
Dimensione os cabos de potência de acordo com os regulamentos locais para
cumprimento da corrente nominal apresentada na etiqueta de designação tipo do
seu acionamento.
Os tamanhos típicos do cabo de potência estão listados na tabela J na página 100.
Sobre as condições de dimensionamento, consulte o manual de hardware.
Assegurar a refrigeração
Consulte a tabela B na página 97 sobre as perdas e o fluxo de ar de refrigeração
através do acionamento A gama de temperatura de operação permitida para o
acionamento sem desclassificação é -15 para +40 °C.
Proteger o acionamento e o cabo de entrada de potência
Veja a tabela B na página 97. Verifique se o tempo de operação do fusível é inferior a
0.5 segundos.
Instalar o acionamento na parede
Veja a figura A na página 97.
Verificar a compatibilidade com sistemas IT (sem ligação à
terra), sistemas de redes flutuantes e delta de ponto médio
e sistemas TT
Um acionamento com varístores terra-para-fase ligados pode ser instalado num
sistema TN ligado à terra simetricamente. Sobre outros sistemas, consulte o manual
de hardware e ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [Inglês]).
PT - Guia rápido de instalação 67
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
A = Sistemas TN-S, B1 = Sistemas de redes flutuantes, B2 = delta de ponto médio, C = Sistema IT
AVISO! Não instale o acionamento com filtro EMC opções +E200 e +E202
ligado a um sistema cujo filtro não seja o adequado. Isto pode ser perigoso ou
danificar o acionamento.
AVISO! Não instale o acionamento com o varístor terra-para-fase ligado a um
sistema cujo varístor não seja o adequado. Se o fizer, o circuito de varístores
pode ser danificado. Consulte o manual de hardware do acionamento.
Nota: Com a opção +E201, remova os parafusos EMC AC, EMC DC e VAR para
sistemas diferentes de TN-S, se não tiverem sido removidos na fábrica. Para mais
informações, contacte a ABB.
Verificar o isolamento do cabo de entrada e dos cabos do
motor
Verifique o isolamento do cabo de entrada de acordo com os regulamentos locais
antes de o ligar ao acionamento.
Verifique o isolamento do cabo do motor e do motor quando o cabo estiver desligado
do acionamento, veja a figura F na página 98. Meça a resistência de isolamento
entre cada condutor de fase e o condutor de Proteção à Terra usando a tensão de
medida de 1000 V CC. A resistência de isolamento de um motor da ABB deve
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
68 PT - Guia rápido de instalação
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
exceder 100 Mohm (valor de referência a 25 °C ou 77 °F). Para a resistência do
isolamento de outros motores, consulte as instruções do fabricante. Nota: A
presença de humidade no interior da caixa do motor reduz a resistência do
isolamento. Se suspeitar da presença de humidade, seque o motor e volte a efetuar
a medição.
Colocar os autocolante de aviso nos idiomas locais
Ligar os cabos de alimentação
Veja as figuras C, D, E e G. Usar cabo de motor blindado simétrico para a cablagem
do motor.
5. Desaperte os parafusos de montagem nos lados da tampa frontal.
6. Remova a tampa fazendo a mesma deslizar para a frente.
7. Cole o autocolante de aviso de tensão residual no idioma local à plataforma de
contagem da consola de programação.
8. Remova os bucins de borracha da placa guia para os cabos serem ligados.
9. Unidades IP21
: Aperte os conectores de cabo (incluídos na entrega num saco
plástico) aos orifícios da placa guia de cabos.
10. Prepare as extremidades dos cabos de entrada de potência e do motor como
ilustrado na figura.
11. Ligue à terra as blindagens de cabo a 360-graus nos conectores de cabo
(unidades IP21) ou por baixo dos grampos (unidades IP55).
12. Ligue a blindagem entrançada do cabo ao terminal PE.
13. Ligue o condutor PE do cabo de entrada ao terminal PE adicional.
14. Ligue as blindagens entrançadas do cabo de entrada e o cabo da resistência (se
presente) ao terminal de ligação à terra.
15. Ligue os condutores de fase dos cabos de entrada, motor e resistência. Aperte os
parafusos.
16. Instale a prateleira de ligação à terra do cabo de controlo na caixa de entrada de
cabos.
17. Fixe mecanicamente os cabos no exterior do acionamento.
18. Ligue à terra a blindagem do cabo do motor no lado do motor. Para interferência
mínima, efetue uma ligação à terra a 360 graus na placa guia de cabos, ou
mantenha a espiral curta.
PT - Guia rápido de instalação 69
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
Ligar os cabos de controlo
Ver a figura H.
1. Faça os furos adequados nos bucins de borracha e faça os mesmos deslizar
sobre os cabos. Passe os cabos através dos orifícios da placa inferior e fixe os
bucins aos orifícios.
2. Descarne as extremidades do cabo e corte ao comprimento pretendido
(considerar o comprimento extra dos condutores de ligação à terra).
3. Ligue à terra as blindagens exteriores de todos os cabos de controlo a 360 graus
no grampo de ligação à terra na caixa da entrada de cabo.
4. Ligue à terra as blindagens do par de cabo ao grampo de ligação à terra. Deixe a
outra extremidade das blindagens desligadas ou ligue-as à terra indiretamente
através de um condensador de alta frequência com alguns nano farads,
ex.: 3.3 nF / 630 V.
5. Ligue os condutores aos terminais apropriados da placa de controlo (consulte a
página 70).
6. Ligue os módulos opcionais, se incluídos na entrega.
7. Reinstale a tampa frontal.
Nota para cabos de fieldbus: Veja a figura I.
1. Instale a prateleira de ligação à terra adicional.
2. Ligue à terra as blindagens exteriores dos cabos 360 graus ao grampo de ligação
à terra.
3. Faça os furos na tampa da caixa de entrada de cabos para os cabos a instalar.
Instale a tampa da caixa de entrada de cabos.
4. Ligue o conector ao módulo de fieldbus.
Ligações E/S de fábrica
As ligações de E/S por defeito da macro Factory do programa de controlo primário do
ACS800, são apresentadas abaixo.
70 PT - Guia rápido de instalação
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
PT
TR
CN
XPOW Entrada de potência externa
1 +24VI
24 V CC, 2 A
2 GND
XAI Tensão de referência e entradas analógicas
1 +VREF 10 V CC, R
L
1…10 kohm
2 -VREF -10 V CC, R
L
1…10 kohm
3 AGND Terra
4 EA1+ Referência de velocidade 0(2)…10 V,
R
in
> 200 kohm
5 EA1-
6 EA2+
Por defeito não usada. 0(4)…20 mA, R
in
= 100 ohm
7 EA2-
J1 J1
Jumper de seleção de corrente/tensão EA1
J2 J2
Jumper de seleção de corrente/tensão EA2
XAO Saídas analógicas
1 SA1 Rpm velocidade do motor 0…20 mA,
R
L
< 500 ohm
2 AGND
3 SA2 Corrente motor 0…20 mA, R
L
<
500 ohm
4 AGND
XD2D Ligação acionamento-para-acionamento
1 B
Ligação acionamento-para-acionamento
2 A
3 BGND
J3 J3
Interruptor de ligação de terminação acionamento-para-acionamento
XRO1, XRO2, XRO3 Saídas a relé
11 NF
Pronto
250 V CA / 30 V CC
2 A
12 COM
13 NA
21 NF
Operação
250 V CA / 30 V CC
2 A
22 COM
23 NA
31 NF
Falha (-1)
250 V CA / 30 V CC
2 A
32 COM
33 NA
XD24 Interlock digital
1 DIIL Permissão func
2 +24VD +24 V CC 200 mA
1)
3 DICOM Terra entrada digital
4 +24VD +24 V CC 200 mA
1)
5 DIOGND Terra entrada/saída digital
J6 Interruptor de seleção de terra
XDIO Entradas/saídas digitais
1 ESD1 Saída: Pronto
2 ESD2 Saída: Operação
XDI Entradas digitais
1 ED1 Parar (0) / Arrancar (1)
2 ED2 Direto (0) / Inverso (1)
3 ED3 Rearme
4 ED4 Seleção aceleração & desaceleração
5 ED5 Velocidade constante 1 (1 = On)
6 ED6 Por defeito não usada.
XSTO Binário seguro off
1 OUT1
Binário de segurança off. Ambos os
circuitos devem estar fechados para o
acionamento arrancar.
2 SGND
3 IN1
4 IN2
X12 Ligação do módulo de funções de segurança
X13 Ligação da consola de programação
X205 Ligação da unidade de memória
Tamanho cabos:
0.5 … 2.5 mm
2
(24…12 AWG)
Binários de
aperto: 0.5 N·m
(5 lbf·in) para
cablagem
entrançada e
rígida.
1)
A capacidade de
carga total destas
saídas é 4.8 W
(200 mA / 24 V)
menos a potência
tomada por EDS1
e EDS2.
Falha
RU — Краткое руководство по монтажу 71
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN
RU — Краткое руководство по монтажу
       .
  ,  ,  
     .   
  (www.abb.com/drives
:  Document Library
   3AUA0000078093 ( . ).
Следуйте указаниям по технике безопасности
 ,    ,   .
Проверьте, не требуется ли формовка конденсаторов
      (     
)     ,  
.
      ,   
   .    
MYYWWRXXXX. YY WW    , :
ПРЕДУПРЕЖДЕНИЕ!
   .
       
      .
     
 .
  -    ,
      .   
  ,     5  
 .
  -   
       .
   ,  -
      (PE) 
.
    ,  

 ,     
.
      
  .
3AUA0000085966 . H
72 RU — Краткое руководство по монтажу
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN
YY: 17, 18, 19, …  2017, 2018, 2019,
WW: 01, 02, 03, …  1- , 2- , 3- ,
   .  Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(   3BFE64059629),    
  www.abb.com/drives/documents
.
Выберите силовые кабели
       
   ,     .
      J  . 100.
       
.
Обеспечьте надлежащее охлаждение
     .  B  . 97.
    ,   
  ,   –15  +40 °C.
Защитите привод и входной силовой кабель
от повреждений
.  B  . 97. ,    
  0,5 .
Закрепите привод на стене
. . A  . 97.
Проверьте совместимость с системами IT
(незаземленные сети), системами с заземленной
вершиной треугольника, системами с заземленной
средней точкой треугольника и системами TT
    «-»  
    TN-S.  
 .      
ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting
instructions (   3AUA0000125152).
RU — Краткое руководство по монтажу 73
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN
A =  TN-S, B1 =    , B2 =  
  , C =  IT
ПРЕДУПРЕЖДЕНИЕ!
   
  (  +E200 +E202) ,
    .    
    .
ПРЕДУПРЕЖДЕНИЕ!
   
 «-» ,     -
.      .
.      .
Примечание.     +E201 
 EMC AC, EMC DC VAR   ,  TN-S,    
   .    
 ABB.
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
74 RU — Краткое руководство по монтажу
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN
Проверьте изоляцию питающего кабеля, кабеля
двигателя и самого двигателя
       
  .
    ,   
 , . . F  . 98.    
     , 
  1000 =.    ABB
  100  (
  25 °C). 
    .  .
Примечание.       
 .     , 
  .
Прикрепите предупреждающие наклейки на местных
языках
Подключите силовые кабели
. . C, D, E G.     
 .
5.        .
6.  ,   .
7.      
(  )     .
8.       
 
.
9.  IP21
.    (  ,
  )    
.
10.         
.
11.       
( IP21)    ( IP55).
12.     
 
.
13.
      
  .
14.       
 ( )  .
RU — Краткое руководство по монтажу 75
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN
15.     ,  
.  .
16.        .
17.      .
18.       .  
        
  
  .
Подключите кабели управления
. . H.
1.       
  .      
  .
2.         
 (   ,     
)
3. 
        
    .
4.      .  
       
     
, : 3,3 /630 .
5.      
(
. . 76).
6.
  ,     .
7.     .
Обратите внимание на проводку Fieldbus. . . I.
1.    .
2.        (360 )
 .
3.        .
    .
4.    Fieldbus.
Стандартные подключения входов/выходов
       /
     ACS880.
76 RU — Краткое руководство по монтажу
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
RU
CN

XPOW   
1 +24VI
24 =, 2
2 GND
XAI    
1 +VREF 10 =, R
L
1…10 
2 -VREF -10 =, R
L
1…10 
3 AGND 
4 AI1+ Задание скорости 0(2)…10 ,
R
in
> 200 
5 AI1-
6 AI2+    .
0(4)…20 , R
in
= 100 
7 AI2-
J1 J1
  / AI1
J2 J2
  / AI2
XAO  
1 AO1 Скорость двигателя, об/мин
0…20 , R
L
< 500 
2 AGND
3 AO2
Ток двигателя 0…20 , R
L
< 500 
4 AGND
XD2D   -
1 B
  -
2 A
3 BGND
J3 J3
  
  -
XRO1, XRO2, XRO3  
11 NC
Готов
250 ~ / 30 =
2
12 COM
13 NO
21 NC
В работе
250 ~ / 30 =
2
22 COM
23 NO
31 NC
Отказ (-1)
250 ~ / 30 =
2
32 COM
33 NO
XD24   
1 DIIL  
2 +24VD +24 =, 200 
1)
3 DICOM   
4 +24VD +24 =, 200 
1)
5 DIOGND   /
J6   
XDIO  /
1 DIO1 : 
2 DIO2 : 
XDI  
1 DI1  (0) /  (1)
2 DI2  (0) /  (1)
3 DI3 
4 DI4   
5 DI5   1 (1 = )
6 DI6    .
XSTO    
1 OUT1
  
 .  
   
.
2 SGND
3 IN1
4 IN2
X12    
X13   
X205   

:
0,5 … 2,5 
2

: 0,5 ·
 
,
 

.
1)


 

 4,8 
 ,


/
 DIO1
DIO2.
SV – Snabbguide för installation 77
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
SV – Snabbguide för installation
Denna guide beskriver i korthet hur frekvensomriktaren installeras. För mera detalje-
rade instruktioner, konstruktionsriktlinjer, tekniska data och fullständiga säkerhetsin-
struktioner, se hårdvaruhandledning (www.abb.com/drives
: Välj Dokumentbibliotek
och sök efter dokumentnummer 3AUA0000078093 [engelska]).
Följ säkerhetsinstruktionerna
Golvet/ytan under frekvensomriktaren måste vara av icke brännbart material.
Kontrollera om kondensatorerna måste reformeras
Reformera kondensatorerna om frekvensomriktaren har förvarats i mer än ett år.
Tillverkningsdatumet kan fastställas med serienumren som finns på märkskylten på
frekvensomriktaren. Serienumret är i formatet MÅÅVVRXXXX. ÅÅ och VV visar till-
verkningsår och -vecka enligt följande:
ÅÅ: 17, 18, 19, … för 2017, 2018, 2019,
VV: 01, 02, 03, … för vecka 1, vecka 2, vecka 3,
För information om reformering av kondensatorer, se Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 [engelska]), på Internet på www.abb.com/drives/documents.
VARNING! Följ dessa instruktioner. Om instruktionerna inte följs kan det
orsaka personskador eller dödsfall eller skador på utrustningen:
Endast kvalificerad elektriker får installera och underhålla frekvensomriktaren.
Arbeta aldrig med frekvensomriktaren, motorkabeln eller motorn när nätspän-
ning är ansluten. Om frekvensomriktaren är ansluten till matningsspänning,
vänta 5 minuter efter att den har frånskilts.
Arbeta aldrig med styrkablarna om frekvensomriktaren eller dess externa styrk-
retsar är spänningssatta.
Jorda alltid frekvensomriktaren, motorn och ansluten utrustning till strömförsörj-
ningens skyddsjordledare (PE).
Var noga med att inga borr- eller slipspån kommer in i frekvensomriktaren i
samband med installationen.
Anslut inte frekvensomriktaren till en spänning som är högre än angivelsen på
märkskylten.
3AUA0000085966 Rev H
78 SV – Snabbguide för installation
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
Val av kraftkablar
Dimensionera kraftkablarna enligt lokala föreskrifter och den märkström som anges
på frekvensomriktarens märkskylt.
Typiska kraftkabeldimensioner anges i tabellen J på sidan 100. För förhållanden för
dimensionering, se hårdvaruhandledningen.
Kontrollera att kylningen är tillfredsställande
Se tabell B på sidan 97 för information om förlusteffekt och kylluftflöde genom frek-
vensomriktaren. Tillåtet driftstemperaturområde för frekvensomriktaren utan ned-
stämpling är -15 till +40°C.
Skydd för frekvensomriktaren och matningskabeln
Se tabell B på sid 97. Kontrollera att säkringens utlösningstid understiger 0,5 sekun-
der.
Installera frekvensomriktaren på vägg
Se figur A på sidan 97.
Kontrollera kompatibilitet med IT-system (icke-
direktjordade system), hörnjordade deltasystem,
mittpunktjordade deltasystem och TT-system
Standardfrekvensomriktare med jord till fas-varistorer anslutnga kan installeras i ett
symmetriskt jordat TN-S-system. För övriga system, se hårdvaruhandledningen och
ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting
instructions (3AUA0000125152 [engelska]).
SV – Snabbguide för installation 79
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
.
A = TN-S-system, B1 = hörnjordade system, B2 = mittpunktsjordade system, C = IT-system
VARNING! Installera inte frekvensomriktaren med EMC-filtret tillval +E200 och
+E202 anslutet till ett system som filtret inte passar till. Detta kan orsaka fara
eller skada frekvensomriktaren.
VARNING! Installera inte frekvensomriktaren med jord till fas-varistorn anslu-
ten till ett system som varistorn inte passar till. I så fall kan varistorkretsen ska-
das. Se frekvensomriktarens hårdvaruhandledning.
Obs! Med tillval +E201, ta bort EMC AC-, EMC DC- och VAR-skruvarna för andra
system än TN-S om de inte borttagna från fabrik. För ytterligare information, kontakta
ABB.
Kontrollera isolationen hos nätkabel, motor och
motorkabel
Kontrollera ingångskabelns isolation enligt lokala föreskrifter innan du ansluter den till
frekvensomriktaren.
Kontrollera isolationen hos motorkabel och motor när kabeln är frånkopplad frånfrek-
vensomriktaren, se figur F på sidan 98. Mät isolationsresistansen mellan varje fas
och skyddsjordledare med en mätspänning på 1000 V DC. Isolationsresistansen hos
en ABB-motor måste överskrida 100 Mohm (referensvärde vid 25 °C). För isolations-
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
80 SV – Snabbguide för installation
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
resistans hos andra motorer, se respektive tillverkares instruktioner. Obs! Fukt inuti
motorkapslingen minskar isolationsresistansen. Om fukt misstänks, torka motorn och
upprepa mätningen.
Sätt fast varningsetiketten på det lokala språket
Anslut matningskablarna
Se figurerna C, D, E och G. Använd symmetrisk skärmad kabel för motoranslutning.
5. Lossa fästskruvarna på sidorna av frontkåpan.
6. Ta av kåpan genom att dra den framåt.
7. Sätt en varningsetikett på lokalt språk på manöverpanelens monteringsplatta.
8. Ta bort gummikragarna från genomföringsplåten för kablar som ska anslutas.
9. IP21-enheter
: Montera kabelförskruvningarna (medföljer leveransen i en plast-
påse) vidi kabelingångslådans hål.
10. Förbered de inkommande ändarna av matnings- och motorkablarna så som illus-
treras i figuren.
11. Jorda ledarskärmarna 360° runtom i genomföringarna (IP21-enheterna) eller
runtom under jordningsöverfallet (IP55-enheter).
12. Anslut den tvinnade skärmen för ingångskabeln till jordplinten.
13. Anslut ledaren för skyddsjord för den inkommande kabeln till den extra jordplin-
ten.
14. Anslut den tvinnade skärmen för motorkabeln och motståndskabeln (i förkom-
mande fall) till jordplinten.
15. Anslut fasledarna för ingångs-, motor- och motståndskablarna. Dra åt skruvarna.
16. Montera styrkablarnas jordningsskena i kabelingångslådan.
17. Fixera kablarna mekaniskt utanför enheten.
18. Jorda motorkabelskärmen vid motoränden. För att minimera störningarna, gör en
360° runtomgående jordning vid skåpgenomföringen, eller håll skärmstumpen
kort.
SV – Snabbguide för installation 81
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
Anslut styrkablarna
Se figur H.
1. Skär lämpliga hål i gummikragarna i kabelingångslådans underdel och skjut upp
kragarna på kablarna. För kablarna genom hålen i bottenplattan och fäst kragarna
i hålen.
2. Skala ledarändarna och kapa ledarna till lämplig längd. Observera att jordledarna
behöver vara något längre.
3. Jorda alla yttre skärmar på styrkablar 360° runtom vid en jordklämma i kabelin-
gångslådan.
4. Anslut ledarparens skärmar till jordklämman. Lämna skärmarnas motsatta ändar
oanslutna, eller jorda dem indirekt via en högfrekvenskondensator på några få
nanofarad, t.ex. 3,3 nF/630 V).
5. Anslut ledarna till respektive plintar på styrkortet (se sid 82).
6. Anslut tillvalsmodulerna om de har medföljt leveransen.
7. Sätt tillbaka frontkåpan.
Not för fältbusskablar: Se figur I.
1. Montera den extra jordningsplåten.
2. Jorda den yttre kabelskärmen 360 grader vid jordningsklämman.
3. Öppna de förberedda hålen i kabelingångslådan för kablarna som ska installeras.
Installera kabelingångslådan.
4. Anslut kontaktdonet till fältbussmodulen.
Förvalda I/O-anslutningar
De förvalda I/O-anslutningarna för makrot FABRIK i ACS880 standardprogramvara
visas nedan.
82 SV – Snabbguide för installation
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
SV
XPOW Extern matning
1 +24VI
24 V DC, 2 A
2 GND
XAI Referensspänning och analoga ingångar
1 +VREF 10 V DC, R
L
1…10 kohm
2 -VREF -10 V DC, R
L
1…10 kohm
3 AGND Jord
4 AI1+
Varvtalsreferens 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+ Används normalt ej. 0(4)…20 mA, R
in
=
100 ohm
7 AI2-
J1 J1 AI1 ström/spänning, valbygel
J2 J2 AI2 ström/spänning, valbygel
XAO Analoga utgångar
1 AO1
Motorvarvtal 0…20 mA, R
L
< 500 ohm
2 AGND
3 AO2
Motorström 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Drift till drift-buss
1 B
Drift till drift-buss
2 A
3 BGND
J3 J3 Bygel för terminering av drift till drift-buss
XRO1, XRO2, XRO3 Reläutgångar
11 NC
Driftklar
250 V AC/30 V DC
2 A
12 COM
13 NO
21 NC
Drift
250 V AC/30 V DC
2 A
22 COM
23 NO
31 NC
Fel (-1)
250 V AC/30 V DC
2 A
32 COM
33 NO
XD24 Digital förregling
1 DIIL Driftfrigivning
2 +24VD +24 V DC 200 mA
1)
3 DICOM Jord för digitala ingångar
4 +24VD +24 V DC 200 mA
1)
5 DIOGND Jord för digitala in-/utgångar
J6 Omkopplare för val av jord
XDIO Digitala in-/utgångar
1 DIO1 Utgång: Driftklar
2 DIO2 Utgång: Drift
XDI Digitala ingångar
1 DI1 Stopp (0)/Start (1)
2 DI2 Fram (0)/Back (1)
3 DI3 Felåterställning
4 DI4 Val av accelerations-/retardationsramp
5 DI5 Konstant varvtal 1 (1 = På)
6 DI6 Används normalt ej.
XSTO Safe torque off
1 OUT1
Safe torque off. Båda kretsarna måste
vara slutna för att frekvensomriktaren
skall starta.
2 SGND
3 IN1
4 IN2
X12 Anslutning för säkerhetsfunktionsmodul
X13 Anslutning för manöverpanel
X205 Anslutning för minnesenhet
Ledardimensio-
ner:
0,5 … 2,5 mm
2
(24…12 AWG)
åtdragningsmo-
ment: 0,5 Nm för
både mångtrå-
diga och enkel-
ledare.
1)
Total belastning-
skapacitet för
dessa utgångar är
4,8 W (200 mA /
24 V) minus den
effekt som krävs av
DIO1 och DIO2.
Fel
TR – Hızlı montaj kılavuzu 83
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
TR – Hızlı montaj kılavuzu
Bu kılavuz sürücüyü nasıl kuracaınız hakkında kısa talimatlar verir. Daha ayrıntılı
talimatlar, mühendislik kılavuzları, teknik veriler ve eksiksiz güvenlik talimatları için
lütfen donanım kılavuzuna bakın (www.abb.com/drives
: Document Library (Belge
Kütüphanesi)'ni seçin ve 3AUA0000078093 [ngilizce] numaralı belgeyi arayın).
Güvenlik talimatlarına uyun
Sürücünün altındaki zemin malzemesi yanmaz nitelikte olmalıdır.
Kondansatörlerin yenilenmesinin gerekip gerekmediğini
kontrol edin
Sürücüye bir yıl veya daha uzun süre güç verilmemise (sürücü depolanmısa veya
kullanılmıyorsa) kondansatörler yenilenmelidir.
Üretim tarihini, sürücünün üzerindeki tip tanımlama etiketinde bulabileceiniz seri
numarasından belirleyebilirsiniz. Seri numarası MYYWWRXXXX biçimindedir. YY ile
WW üretim yılını ve haftasını gösterir.
YY: 2017, 2018, 2019,
için 17, 18, 19, …
WW: hafta 1, hafta 2, hafta 3, … için 01, 02, 03,
Kondansatörlerin yenilenmesi ile ilgili bilgi için, bkz. Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 [ngilizce]), nternet'te www.abb.com/drives/documents
adresinde
bulunmaktadır.
UYARI! Bu talimatlara uyun. Bunlara uymamanız halinde ölüm ya da
yaralanma söz konusu olabilir veya ekipman zarar görebilir.
Sürücünün kurulumu ve bakımı sadece yetkili elektrik uzmanları tarafından
yapılmalıdır.
Enerji verildiinde sürücü, motor kablosu ve motor üzerinde hiçbir ilem
yapmayın. Sürücü zaten giri gücüne balıysa giri gücü balantısını kestikten
sonra 5 dakika bekleyin.
Sürücü veya harici kontrol devrelerine enerji verilirken kontrol kabloları üzerinde
asla çalıma yapmayın.
Sürücüyü, motoru ve bitiik ekipmanları her zaman güç kaynaının koruyucu
topraklama (PE) barasına topraklayın.
Delme ve talama kalıntılarının kurulum sırasında sürücü içine girmemesine
dikkat edin.
Sürücüyü tip tanımlama etiketinde belirtilenden daha yüksek bir gerilime
balamayın.
3AUA0000085966 Rev H
84 TR – Hızlı montaj kılavuzu
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
Güç kablolarını seçin
Sürücünüzün tip belirleme etiketinde verilen nominal akımı taımak için güç
kablolarını yerel yönetmeliklere uygun olarak boyutlandırın.
Tipik güç kablosu boyutları sayfa 100‘da J tablosunda listelenmitir. Boyutlandırma
ilgili koullar için lütfen donanım kılavuzuna bakın.
Soğutmayı sağlayın
Kayıplar ve sürücünün içinden geçen soutma hava akıı için bkz. tablo B sayfa 97.
Deer kaybı olmadan sürücünün izin verilen iletim sıcaklıı aralıı -15 ile +40°C
arasındadır.
Sürücüyü ve giriş güç kablosunu koruyun
Bkz. tablo B, sayfa 97. Sigortaların çalıma süresinin 0,5 saniyenin altında
olduundan emin olun.
Sürücüyü duvara monte edin
Bkz. ekil A, sayfa 97.
IT (topraklamasız), köşe topraklamalı delta, orta nokta
topraklamalı delta ve TT sistemlerle uyumluluğu kontrol
edin
Toprak-faz varistörü balı olan standart sürücü, simetrik topraklamalı bir TN-S
sistemine takılabilir. Dier sistemler için bkz. donanım kılavuzu ve ACS880 frames R1
to R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152 [ngilizce])
TR – Hızlı montaj kılavuzu 85
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
A = TN-S sistemi, B1 = Köe topraklamalı sistem, B2 = Orta nokta topraklamalı sistem, C = IT sistemi
UYARI! EMC filtresi opsiyonları +E200 ve +E202 balı olan bir sürücüyü
filtrenin uygun olmadıı bir sisteme monte etmeyin. Bu, tehlikeye veya
sürücüde hasara neden olabilir.
UYARI! Toprak-faz varistörü balı olan bir sürücüyü varistörün uygun olmadıı
bir sisteme monte etmeyin. Aksi halde, varistör devresi hasar görebilir. Sürücü
donanım kılavuzuna bakın.
Not:
+E201 opsiyonunda, TN-S dıındaki sistemlerde bulunan EMC AC, EMC DC ve VAR
vidalarını fabrikada sökülmemilerse sökün. Daha fazla bilgi için, ABB ile irtibata geçin.
Giriş ve motor kabloları ile motorun yalıtımını kontrol edin
Sürücüye balamadan önce yerel yasalara uygun olarak giri kablosunun yalıtımını
kontrol edin.
Motor kablosu sürücüden ayrılmı durumdayken, motor kablosu ve motorun
yalıtımını kontrol edin, bkz. ekil F, sayfa 98. 1000 VDC ölçüm gerilimi kullanarak her
bir faz iletkeni ile motor Koruyucu Topraklama iletkeni arasındaki yalıtım direncini
ölçün. ABB motorunun yalıtım direnci 100 Mohm'u geçmelidir (referans deer, 25°C
veya 77°F'de). Dier motorların yalıtım direnci için, lütfen üreticinin talimatlarına
bavurun. Not: Motor muhafazası içindeki nem yalıtım direncini düürecektir.
Nemden üphe edilirse motoru kurutun ve ölçümü tekrarlayın.
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
86 TR – Hızlı montaj kılavuzu
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
Yerel dillerdeki uyarı etiketlerini yapıştırın
Güç kablolarını bağlayın
Bkz. ekil C, D, E ve G. Motor kablosu için simetrik blendajlı kablo kullanın.
5. Ön kapaın yanlarındaki montaj vidalarını sökün.
6. Öne doru kaydırarak kapaı çıkarın.
7. Lokal dildeki kaçak gerilim uyarı etiketini kontrol paneli montaj kitine yapıtırın.
8. Kabloların balanması için lastik rondelaları geçi plakasından çıkarın.
9. IP21 kasaları
: Kablo konektörlerini (bir plastik torbanın içinde teslimata dahildir)
kablo geçi plakası deliklerine sabitleyin.
10. Giri gücü ve motor kablolarının uçlarını ekilde gösterildii gibi hazırlayın.
11. Kablo blendajlarını kablo konektörlerinde (IP21 üniteler) ya da kelepçelerin (IP55
üniteler) altında 360 derece topraklayın.
12. Giri kablosunun bükümlü blendajını PE terminaline balayın.
13. Giri kablosunun PE iletkenini ek PE terminaline balayın.
14. Motor kablosu ve direnç kablosunun (eer varsa) bükümlü blendajını topraklama
terminaline balayın.
15. Giri, motor ve direnç kablolarının faz iletkenlerini balayın. Vidaları sıkın.
16. Kontrol kablosu topraklama rafını kablo giri kutusuna takın.
17. Sürücünün dıında yer alan kabloları mekanik olarak sabitleyin.
18. Motor kablo blendaj
ını motor tarafında topraklayın. Mümkün olan en az parazit
için, kablo geçiinde 360 derece topraklama yapın veya saç örgüsünü kısa tutun.
Kontrol kablolarını bağlayın
Bkz. ekil H.
1. Lastik rondelaların içine yeterince delik açın ve rondelaları kabloların üstüne
kaydırın. Kabloları, alt plaka deliklerinin içine kaydırın ve rondelaları deliklere
takın.
2. Kablo uçlarını soyun ve uygun uzunlukta kesin (topraklama iletkenlerinin ilave
uzunluuna dikkat edin).
3. Tüm kontrol kablolarının dı blendajlarını kablo giri kutusundaki bir topraklama
kelepçesine 360 derece topraklayın.
TR – Hızlı montaj kılavuzu 87
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
4. Çift kablo koruyucularını topraklama kelepçesine topraklayın. Blendajların dier
ucunu bota bırakın veya birkaç nanofarad yüksek frekanslı kondansatör
üzerinden dolaylı olarak topraklayın; ör. 3,3 nF / 630 V.
5. letkenleri kontrol panelinin ilgili terminallerine balayın (bkz. sayfa 88).
6. Teslimata dahil olmaları halinde opsiyonel modüllerin kablolarını balayın.
7. Ön kapaı tekrar takın.
Haberleşme kabloları için not: Bkz. ekil I.
1. lave topraklama rafını takın.
2. Dı kabloların blendajlarını bir topraklama kelepçesinde 360 derece topraklayın.
3. Takılacak kablolar için kablo giri kutusu kapaında delikler açın. Kablo giri
kutusu kapaını takı
n.
4. Konektörü haberleme modülüne takın.
Varsayılan I/O bağlantıları
ACS880 birincil kontrol programı Fabrika makrosunun varsayılan G/Ç balantıları
aaıda gösterilmitir.
88 TR – Hızlı montaj kılavuzu
TR
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
TR
XPOW Harici güç girii
1 +24VI
24 VDC, 2 A
2 GND
XAI Referans gerilimi ve analog giriler
1 +VREF 10 VDC, R
L
1…10 kohm
2 -VREF -10 VDC, R
L
1…10 kohm
3 AGND Topraklama
4 AI1+ Hız referansı 0(2)…10 V, R
in
>
200 kohm
5 AI1-
6 AI2+
Varsayılan olarak kullanımda deildir.
0(4)…20 mA, R
in
> 100 ohm
7 AI2-
J1 J1 AI1 akım/gerilim seçim jumper'ı
J2 J2 AI2 akım/gerilim seçim jumper'ı
XAO Analog çıkılar
1 AO1 Motor hızı rpm 0…20 mA, R
L
<
500 ohm
2 AGND
3 AO2
Motor akımı 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D Sürücü - sürücü balantısı
1 B
Sürücü - sürücü balantısı
2 A
3 BGND
J3 J3
Sürücü - sürücü balantısı sonlandırma anahtarı
XRO1, XRO2, XRO3 Röle çıkıları
11 NC
Hazır
250 VAC/30 VDC
2 A
12 COM
13 NO
21 NC
Çalışıyor
250 VAC/30 VDC
2 A
22 COM
23 NO
31 NC
Hatalı(-1)
250 VAC/30 VDC
2 A
32 COM
33 NO
XD24 Dijital kilit
1 DIIL Çalıma izni
2 +24 VD +24 VDC 200 mA
1)
3 DICOM Dijital giri toprak hattı
4 +24 VD +24 VDC 200 mA
1)
5 DIOGND Dijital giriıkı toprak hattı
J6 Toprak seçim anahtarı
XDIO Dijital giriıkılar
1 DIO1 Çıkı: Hazır
2 DIO2 Çıkı: Çalııyor
XDI Dijital giriler
1 DI1 Stop (0) / Start (1)
2 DI2 leri (0) / Geri (1)
3 DI3 Reset
4 DI4 Hızlanma ve yavalama seçimi
5 DI5 Sabit hız 1 (1 = ık)
6 DI6 Varsayılan olarak kullanımda deildir.
XSTO Güvenli moment kapatma
1 OUT1
Güvenli moment kapatma. Sürücünün
balaması için her iki devre
kapatılmalıdır.
2 SGND
3 IN1
4 IN2
X12 Güvenlik fonksiyonları modülü balantısı
X13 Kontrol paneli balantısı
X205 Hafıza kartı balantısı
Kablo boyutları:
0,5 … 2,5 mm
2
(24…12 AWG)
Sıkma torkları:
Hem telli hem
som kablo için
0,5 N·m
(5lbf·in).
1)
Bu çıkıların
toplam yük
kapasitesi 4,8 W
(200 mA / 24 V)
eksi DIO1 ve DIO2
tarafından alınan
güçtür.
Hata
中文
快速安装指南
89
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
CN
ZH
中文快速安装指南
本指南简要介绍如何安装变频器。更多详细说明、工程指导、技术数据和完整安全说
明,请参阅硬件手册(www.abb.com/drives:选择
文件库
并搜索文件编号
3AUA0000078093 [英文])。
遵循安全指导
变频器下方的地板材料应阻燃。
检查电容是否需要重整
如果变频器超过一年或以上未通电(储存或闲置),则电容需要重整。
您可以从序列号来确定生产日期,序列号可以在变频器所贴的型号标签上找到。序列
号的格式为 MYYWWRXXXXYY WW 以如下方式说明生产年份和周次:
YY 171819分别代表 2017 年、2018 年、2019 年、
WW: 010203分别代表第 1 周、第 2 周、第 3 周、
有关电容重整的信息,请参阅互联网上的
直流链路电容重整说明中的带直流电解电
容的变频器模块)
(3BFE64059629 [英语]),网址:
www.abb.com/drives/documents
选择电缆
应根据当地规范选择能承载变频器型号标签上标称电流的电缆规格。
请查阅第 100 页上的表 J:典型的电力电缆尺寸,请参阅硬件手册。
警告!请遵循这些指导。如果忽略这些指导,可能会导致受伤、死亡或设备
损坏:
仅允许由具备资质的专业电工对变频器进行安装和维护。
当接上主电源时,切勿对变频器、电机电缆或电机进行操作。如果变频器已经
连接到了输入电源,请在断开输入电源等待 5 分钟后,再对变频器、电机电缆
或电机进行操作。
当变频器或外部控制电路连接了电源时,切勿触碰控制电缆。
请务必将变频器、电机和相邻设备接到电源的保护接地网 (PE) 上。
在安装时,确保不让钻孔和研磨产生的碎屑进入变频器。
切勿将变频器连接到带有高于型号标签上所标电压数值的电源。
3AUA0000085966 修订版 H
90
中文
快速安装指南
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
ZH
确保冷却
请参阅第 97 页上的表 B 了解传动损耗和冷却空气流量。在不降低定额值的情况下,
传动的允许工作温度范围为 -15 +40 °C
保护变频器和输入电缆
请参阅第 97 页表 B。检查熔断器的运作时间是否在 0.5 秒以下。
在墙上安装变频器
请参阅第 97 页的图 A
检查与 IT(不接地)系统、角接地三角形系统、中点接地三角
形系统和 TT 系统的兼容性。
带有相线对地压敏电阻的标准变频器可被安装至对称接地的 TN-S 系统。对于其他系
统,请参阅硬件手册和 ACS880
外型尺寸
R1 -R11 EMC
滤波器
和压敏电阻断开说明
3AUA0000125152 [英语])。
中文
快速安装指南
91
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
CN
ZH
A = TN-S 系统,B1 = 角接地系统,B2 = 中点接地系统C = IT 系统
警告!勿将带有 EMC 滤波器选件(+E200 +E202)的变频器连接至滤波器不
兼容的系统中。这可能会导致危险或损坏变频器。
警告!勿将带有压敏电阻的变频器连接至压敏电阻不兼容的系统中。如果您这
么做,压敏电阻电路将会损坏。请参阅变频器硬件手册。
注:使用 +E201 选件,拆除 TN-S 以外系统中的 EMC ACEMC DC VAR 螺丝,如果出
厂时没有拆除。更多信息请联系 ABB
检查输入和电机电缆以及电机本身的绝缘
将输入电缆连接到传动前,请按当地法规检查其绝缘情况。
电机电缆从传动上断开时,检查电机和电机电缆绝缘情况,请参见第 98 页的图 F。使
1000V DC测量电压测量各相导线之间的绝缘电阻,然后测量每相导线与保护接地导
线之间的绝缘电阻。ABB 电机的绝缘电阻必须超过 100 Mohm(参照值为 25°C
77°F 时测得)。对于其他电机的绝缘电阻,请参阅其制造商的说明注:电机外壳
内部的湿气会降低绝缘电阻。如果湿气长期存在,请干燥电机后再次测量。
PE
N
L3
L2
L1
PE
L3
L2
L1
L3
L2
L1
PE
L3
L2
L1
B1 CA
B2
92
中文
快速安装指南
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
ZH
贴上以当地语言写成的警告贴纸
连接电力电缆
请参阅图 CDE G。请使用对称屏蔽电缆进行电机电缆敷设。
5. 拆卸前盖两侧的安装螺丝。
6. 将盖子向前滑动,从而将其取下。
7. 将本地语言的剩余电压警告贴纸贴在控制盘安装的醒目位置。
8. 将橡胶绝缘圈从电缆接入板上取下,以便连接电缆
9. IP21
变频器: 将电缆连接器(发货时放在塑料袋中)固定在电缆接入板孔上。
10. 如图所示准备好输入动力电缆和电机电缆的两端。
11. 将电缆连接器(IP21)中或电缆夹(IP55)下的电缆护套 360 度接地。
12. 将输入电缆的双绞线屏蔽层连接到 PE 端子。
13. 将输入电缆的PE导线连接到附 PE 端子。
14. 将电机电缆和制动电阻电缆的双绞线屏蔽层(如存在)连接到接地端子。
15. 连接输入电缆、电机电缆和制动电阻电缆,拧紧螺钉。
16. 将控制电缆接地架安装在变频器底部的电缆接线盒。
17. 在驱动器外用机械方法固定好电缆。
18. 在电机端将电机电缆屏蔽层接地。要使干扰降至最低水平,在线缆接入处提供 360
度接地或尽可能地缩短屏蔽层接地的裸露部分。
连接控制电缆
请参阅图片 H
1. 在橡胶绝缘圈上切出足够大的孔,然后将绝缘圈套到电缆上。将电缆从底板的孔
中穿过并将绝缘圈固定到接线盒的底板孔上。
2. 剥开电缆末端并截取到合适的长度(要注意接地导线的额外长度)。
3. 在电缆接线盒的接地夹处,将所有控制电缆的外屏蔽层做 360 度接地。
4. 将双绞电缆屏蔽层固定到接地夹子下,另一端的屏蔽层悬空或使用 3.3 nF/630 V
高频电容间接接地。
5. 将导线连接到控制板的适当端子上。参见(第94页).
6. 如果交付的货物中包括选装模块,则为其连接电缆
7. 装回前盖。
现场总线布线注意事项请参阅图片 I
中文
快速安装指南
93
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
CN
ZH
1. 安装附加接地架。
2. 将电缆的外屏蔽层在接地夹处 360 度接地。
3. 在电缆接线盒盖上对应安装电缆的位置开孔,引入通讯电缆。
4. 将通讯电缆接头连接现场总线模块。
默认 I/O 连接
ACS880 工厂宏控制程序的默认 I/O 连接如下所示。
94
中文
快速安装指南
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
ZH
XPOW
外部电源输入
1 +24VI
24 V DC2 A
2 GND
XAI
参考电压和模拟输入
1 +VREF
10 V DCR
L
1…10 kohm
2 -VREF
-10 V DCR
L
1…10 kohm
3 AGND
4 AI1+
速度参考 0(2)…10 V, R
in
> 200 kohm
5 AI1-
6 AI2+
默认不使用。0(4)…20 mA
R
in
= 100 ohm
7 AI2-
J1 J1
AI1 电流/电压选择跳线
J2 J2
AI2 电流/电压选择跳线
XAO
模拟输出
1 AO1
电机速度 rpm 0…20 mA, R
L
< 500 ohm
2 AGND
3 AO2
电机电流 0…20 mA, R
L
< 500 ohm
4 AGND
XD2D
变频器到变频器链路
1 B
变频器到变频器链路
2 A
3 BGND
J3 J3
变频器到变频器链路终端开关。
XRO1XRO2XRO3 继电器输出
11 NC
就绪
250 VAC / 30 VDC
2 A
12 COM
13 NO
21 NC
正在运行
250 VAC / 30 VDC
2 A
22 COM
23 NO
31 NC
故障 (-1)
250 VAC / 30 VDC
2 A
32 COM
33 NO
XD24
数字联锁
1 DIIL
运行使能
2 +24VD +24 V DC 200 mA
1)
3 DICOM
数字输入接地
4 +24VD +24 V DC 200 mA
1)
5 DIOGND
数字输入/输出接地
J6
接地选择开关
XDIO
数字输入/输出
1 DIO1
输出:就绪
2 DIO2
输出:正在运行
XDI
数字输入
1 DI1
停止(0) / 启动(1)
2 DI2
正向(0) / 反向(1)
3 DI3
复位
4 DI4
斜坡时间选择
5 DI5
恒定转速 11 = 开启
6 DI6
默认不使用。
XSTO
安全转矩取消
1 OUT1
安全转矩取消。两个电路都必须闭合后
方可启动电机。
2 SGND
3 IN1
4 IN2
X12
安全功能模块连接
X13
控制盘连接
X205
记忆单元连接
电缆规格:
0.5 … 2.5 mm
2
(24…12 AWG)
拧紧扭矩:
0.5 N·m
(5 lbf·in)
用于多芯和实心
导线。
1)
这些输出的总负
载能力为 4.8 W
(200 mA / 24 V)
DIO1 DIO2
功耗。
故障
Declaration of conformity 95
Declaration of conformity
96 Declaration of conformity
97
Figures
A
B
ACS880-
01-
Air flow
(m
3
/h)
Losses
(W)
ACS880-01- Air flow
(m
3
/h)
Losses
(W)
04A6-2 44 73 OFAF000H6 02A4-3/02A1-5 44 30 OFAF000H4
06A6-2 44 94 OFAF000H10 03A3-303A0-5 44 40 OFAF000H6
07A5-2 44 122 OFAF000H16 04A0-303A4-5 44 52 OFAF000H6
10A6-2 44 172 OFAF000H16 05A6-3/04A8-5 44 73 OFAF000H10
16A8-2 88 232 OFAF000H25 07A2-3/05A2-5 44 94 OFAF000H10
24A3-2 88 337 OFAF000H40 09A4-3/07A6-5 44 122 OFAF000H16
031A-2 134 457 OFAF000H50 12A6-3/11A0-5 44 172 OFAF000H16
07A4-7 134 114 OFAA000GG16 017A-3/014A-5 88 232 OFAF000H25
09A9-7 134 143 OFAA000GG20 025A-3/021A-5 88 337 OFAF000H32
14A3-7 134 207 OFAA000GG25 032A-3/027A-5 134 457 OFAF000H40
019A-7 134 274 OFAA000GG35 038A-3/034A-5 134 562 OFAF000H50
023A-7 134 329 OFAA000GG50
027A-7 134 405 OFAA000GG50
× 4
× 4
× 4
× 4
1 2 3
5
4
< 40 °C
b
a
200 mm
300 mm
a
(mm)
b
(mm)
IP21
R1
R2
358 98
R3 451 125
IP55
R1
R2
434 98
R3 509 125
R1 6 kg
R2 8 kg
R3 10 kg
6
11
C
D
L1 L2 L3 T1/U T2/V T3/W
UDC+
R+
UDC-
R-
ACS880-01
PE
U1
V1
W1
3 ~ M
L1 L2 L3PE
1
2
5
1
3
4
IP55
IP21
1
M4×16 Torx T20
2 N·m
M4x16 Torx T20
2 N·m
IP21
98
E
T3/W
T2/V
T1/U
UDC-
R+
R-
L3
L2
L1
L1, L2, L3, T1/
U, T2/V, T3/W,
R-, R+/UDC+,
UDC
(N·m) (N·m)
R1 0.6 1.8
R2 0.6 1.8
R3 1.7 1.8
PE
PE
PE
PE
10
10
9
8
7
11
11
10
9
8
12
6
6 6
M4×8 Torx T20
1.5 N·m
1.5 N·m
Phillips PT2
R1, R2: 1.5 N·m
R3: 2 N·m
R1, R2: 1.5 N·m
R3: 2 N·m
F
G
H
ohm
M
3~
U1
V1
W1
PE
14
14
T3/W
T2/V
T1/U
UDC-
R+
R-
L3
L2
L1
1.5 N·m
0.5 N·m
3
4
5
5
1
1
M4×20 Torx T20
99
I
1
3
M4×8 Torx T20
2 N·m
M4×20 Torx T20
1.5 N·m
2
4
Available from 2014-09
100
J
Drive type Frame
size
IEC US
Cu cable type Cu cable type
mm
2
AWG/kcmil
U
N
= 230 V
ACS880-01-04A6-2 R1 3×1.5 14
ACS880-01-06A6-2 R1 3×1.5 14
ACS880-01-07A5-2 R1 3×1.5 14
ACS880-01-10A6-2 R1 3×1.5 14
ACS880-01-16A8-2 R2 3×6 10
ACS880-01-24A3-2 R2 3×6 10
ACS880-01-031A-2 R3 3×10 8
U
N
= 400 V
ACS880-01-02A4-3 R1 3×1.5 14
ACS880-01-03A3-3 R1 3×1.5 14
ACS880-01-04A0-3 R1 3×1.5 14
ACS880-01-05A6-3 R1 3×1.5 14
ACS880-01-07A2-3 R1 3×1.5 14
ACS880-01-09A4-3 R1 3×1.5 14
ACS880-01-12A6-3 R1 3×1.5 14
ACS880-01-017A-3 R2 3×6 10
ACS880-01-025A-3 R2 3×6 10
ACS880-01-032A-3 R3 3×10 8
ACS880-01-038A-3 R3 3×10 8
U
N
= 500 V
ACS880-01-02A1-5 R1 3×1.5 14
ACS880-01-03A0-5 R1 3×1.5 14
ACS880-01-03A4-5 R1 3×1.5 14
ACS880-01-04A8-5 R1 3×1.5 14
ACS880-01-05A2-5 R1 3×1.5 14
ACS880-01-07A6-5 R1 3×1.5 14
ACS880-01-11A0-5 R1 3×1.5 14
ACS880-01-014A-5 R2 3×6 10
ACS880-01-021A-5 R2 3×6 10
ACS880-01-027A-5 R3 3×10 8
ACS880-01-034A-5 R3 3×10 8
U
N
= 690 V
ACS880-01-07A4-7 R3 3×1.5 14
ACS880-01-09A9-7 R3 3×1.5 14
ACS880-01-14A3-7 R3 3×2.5 14
ACS880-01-019A-7 R3 3×4 12
ACS880-01-023A-7 R3 3×6 10
ACS880-01-027A-7 R3 3×10 8
101
Figures – US
A
A
B
ACS880-01- Air flow
(ft
3
/min)
Losses
(W)
ACS880-01- Air flow
(ft
3
/min)
Losses
(W)
04A6-2 26 73 JJS-15 02A1-5 26 30 JJS-3
06A6-2 26 94 JJS-15 03A0-5 26 40 JJS-6
07A5-2 26 122 JJS-15 03A4-5 26 52 JJS-6
10A6-2 26 172 JJS-20 04A8-5 26 73 JJS-10
16A8-2 52 232 JJS-25 05A2-5 26 94 JJS-10
24A3-2 52 337 JJS-40 07A6-5 26 122 JJS-15
031A-2 79 457 JJS-50 11A0-5 26 172 JJS-20
07A4-7 79 114 JJS-15 014A-5 52 232 JJS-25
09A9-7 79 143 JJS-20 021A-5 52 337 JJS-35
14A3-7 79 207 JJS-30 027A-5 79 457 JJS-40
019A-7 79 274 JJS-40 034A-5 79 562 JJS-50
023A-7 79 329 JJS-50
027A-7 79 405 JJS-50
× 4
× 4
× 4
× 4
1
2 3
5
4
< 104 °F
M5
b
a
7.87”
11.81”
a
(in.)
b
(in.)
UL Type 1
R1
R2
15.16 3.86
R3 17.76 4.92
UL Type 12
R1
R2
17.09 3.86
R3 20.04 4.92
.23
.45
R1 13 lb
R2 18 lb
R3 22 lb
C
D
L1 L2 L3 T1/U T2/V T3/W
UDC+
R+
UDC-
R-
L1 L2 L3PE
ACS880-01
PE
U1
V1
W1
3 ~ M
1
2
3
4
1
Ul Type 12§
UL Type 1
M4×16 Torx T20
2 N·m M6x12 Torx T25
M4x16 Torx T20
2 N·m
USA
102
E
T3/W
T2/V
T1/U
UDC-
R+
R-
L3
L2
L1
L1, L2, L3, T1/U,
T2/V, T3/W, R-, R+/
UDC+, UDC
(lbf·ft)(lbf·ft)
R1
0.4 1.3
R2
0.4 1.3
R3
1.3 1.3
6 AWG
5
6
6
6
77 8
9
M4×8 Torx T20
18 lbf·in
F
G
ohm
M
3~
U1
V1
W1
PE
T3/W
T2/V
T1/U
UDC-
R+
R-
L3
L2
L1
3
4
13 lbf·in
5 lbf·in
5
5
M4×20 Torx T20
3AUA0000085966 Rev H
Cable conduit installation
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative,
quoting the type designation and serial number of the unit in question. A
listing of ABB sales, support and service contacts can be found by navigating to
abb.com/searchchannels.
Product training
For information on ABB product training, navigate to
new.abb.com/service/training.
Providing feedback on ABB Drives manuals
Your comments on our manuals are welcome. Navigate to
new.abb.com/drives/manuals-feedback-form.
Document library on the Internet
You can find manuals and other product documents in PDF format on the
Internet at abb.com/drives/documents.
abb.com/drives
© Copyright 2019 ABB. All rights reserved.
Specifications subject to change without notice.
3AUA0000085966 Rev H (MUL) 2019-05-08
ACS880-01 manuals

Documenttranscriptie

— ABB INDUSTRIAL DRIVES ACS880-01 drives Frames R1 to R3 Quick installation guide English . . . . . . . . . 3 EN English – USA . . . 9 USA Dansk . . . . . . . . .17 DA Deutsch . . . . . . .23 DE Español . . . . . . .29 ES Suomi . . . . . . . . .35 FI Français . . . . . . .41 FR Italiano. . . . . . . .47 IT Nederlands . . . .53 NL Polski . . . . . . . . .59 PL Português . . . . .65 PT Русский . . . . . . .71 RU Svenska . . . . . . .77 SV Türkçe . . . . . . . .83 TR 中文 . . . . . . . . . . .89 ZH 3AUA0000085966 Rev H MUL EFFECTIVE: 2019-05-08 — List of related manuals Drive hardware manuals and guides Code (English) ACS880-01 hardware manual 3AUA0000078093 ACS880-01 quick installation guide for frames R1 to R3 ACS880-01 quick installation guide for frames R4 and R5 ACS880-01 quick installation guide for frames R6 to R9 ACS880-01 +P940 drives for cabinet installation supplement ACS880-01 assembly drawings for cable entry boxes of IP21 frames R5 to R9 ACS-AP-x assistant control panels user’s manual Vibration dampers for ACS880-01 drives (frames R4 and R5, option +C131) installation guide Vibration dampers for ACS880-01 drives (frames R6 to R9, option +C131) installation guide ACS880-01 +C132 marine type-approved drives supplement ACS880-01 +N7502 drives for SynRM motors (0.8 to 200 kW) supplement 3AUA0000085966 3AUA0000099663 3AUA0000099689 3AUA0000145446 3AUA0000119627 3AUA0000085685 3AXD50000010497 3AXD50000013389 3AXD50000010521 3AXD50000029482 Drive firmware manuals and guides ACS880 primary control program firmware manual Quick start-up guide for ACS880 drives with primary control program 3AUA0000085967 3AUA0000098062 Option manuals and guides Manuals and quick guides for I/O extension modules, fieldbus adapter, etc. You can find manuals and other product documents in PDF format on the Internet. See section Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative. The code below opens an online listing of the manuals applicable to the product: ACS880-01 manuals EN – Quick installation guide 3 EN – Quick installation guide This guide instructs briefly how to install the drive. For more detailed instructions, engineering guide lines, technical data and complete safety instructions, see the hardware manual (www.abb.com/drives: Select Document Library and search for document number 3AUA0000078093 [English]). Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: • Only qualified electrical professionals are allowed to install and maintain the drive. • Never work on the drive, motor cable or motor when main power is applied. If the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power. • Never work on the control cables when power is applied to the drive or to the external control circuits. • Always ground the drive, the motor and adjoining equipment to the protective earth (PE) bus of the power supply. • Make sure that debris from borings and grindings does not enter the drive when installing. • Do not connect the drive to a voltage higher than what is marked on the type designation label. EN DA DE ES FI FR IT NL PT The floor material below the drive must be non-flammable. RU Check if capacitors need to be reformed SV Reform the capacitors if the drive has not been powered (either in storage or unused) for a year or more. TR You can determine the manufacturing date from the serial number, which you find on the type designation label attached to the drive. The serial number is of format MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows: YY: WW: 17, 18, 19, … for 2017, 2018, 2019, … 01, 02, 03, … for week 1, week 2, week 3, … For information on reforming the capacitors, see Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions 3AUA0000085966 Rev H CN 4 EN – Quick installation guide (3BFE64059629 [English]), available on the Internet at www.abb.com/drives/documents. Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive. Typical power cable sizes are listed in table J on page 100. For the conditions of the sizing, see the hardware manual. EN Ensure the cooling See table B on page 97 for the losses and the cooling air flow through the drive. The DA allowed operating temperature range of the drive without derating is -15 to +40 °C. DE Protect the drive and input power cable ES See table B on page 97. Check that the operating time of the fuse is below 0.5 seconds. FI FR IT NL Install the drive on the wall See figure A on page 97. Check the compatibility with IT (ungrounded), cornergrounded delta, midpoint-grounded delta and TT systems The standard drive with ground-to-phase varistors connected can be installed to a PT symmetrically grounded TN-S system. For other systems, see the hardware manual and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor RU disconnecting instructions (3AUA0000125152 [English]). SV TR CN EN – Quick installation guide 5 . A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = TN-S system, B1 = Corner-grounded system, B2 = Midpoint-grounded system, C = IT system WARNING! Do not install the drive with EMC filter options +E200 and +E202 connected to a system that the filter is not suitable for. This can cause danger, or damage the drive. WARNING! Do not install the drive with the ground-to-phase varistor connected to a system that the varistor is not suitable for. If you do, the varistor circuit can be damaged. See the drive hardware manual. Note: With option +E201, remove EMC AC, EMC DC and VAR screws in for systems other than TN-S if not removed at the factory. For more information, contact ABB. Check the insulation of the input and motor cables and the motor Check the insulation of the input cable according to local regulations before you connect it to the drive. Check the insulation of the motor cable and motor when the cable is disconnected from the drive, see figure F on page 98. Measure the insulation resistance between each phase conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, FR IT NL PT RU SV TR CN 6 EN – Quick installation guide please consult the manufacturer’s instructions. Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement. Attach the warning stickers in local languages Connect the power cables See figures C, D, E and G. Use symmetrical shielded cable for motor cabling. 1. Undo the mounting screws at the sides of the front cover. EN 2. Remove the cover by sliding it forward. DA 3. Attach the residual voltage warning sticker in the local language to the control panel mounting platform. DE 4. Remove the rubber grommets from the lead-through plate for the cables to be connected. ES 5. IP21 units: Fasten the cable connectors (included in the delivery in a plastic bag) to the cable lead-through plate holes. FI 6. Prepare the ends of the input power and motor cables as illustrated in the figure. FR 7. Ground the cable shields 360 degrees in the cable connectors (IP21 units) or under the clamps (IP55 units). IT 8. Connect the twisted shield of the input cable to the PE terminal. NL 9. Connect the PE conductor of the input cable to the additional PE terminal. PT 10. Connect the twisted shield of the motor cable and resistor cable (if present) to the grounding terminal. RU 11. Connect the phase conductors of the input, motor and resistor cables. Tighten the SV screws. 12. Install the control cable grounding shelf in the cable entry box. TR 13. Secure the cables mechanically outside the drive. CN 14. Ground the motor cable shield at the motor end. For minimal interference, make a 360-degree grounding at the cable lead-through, or keep the pig tail short. Connect the control cables See figure H. EN – Quick installation guide 7 1. Cut adequate holes into the rubber grommets and slide the grommets onto the cables. Slide the cables through the holes of the bottom plate and attach the grommets to the holes. 2. Strip the cable ends and cut to suitable length (note the extra length of the grounding conductors). 3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in the cable entry box. 4. Ground the pair-cable shields to the grounding clamp. Leave the other end of the shields unconnected or ground them indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V. 5. Connect the conductors to the appropriate terminals of the control board (see page 8). 6. Wire the optional modules if included in the delivery. 7. Reinstall the front cover. EN DA DE Note for fieldbus cabling. See figure I. ES 1. Install the additional grounding shelf. FI 2. Ground the outer shields of the cables 360 degrees at a grounding clamp. 3. Knock out holes in the cable entry box cover for the cables to be installed. Install the cable entry box cover. 4. Plug the connector to the fieldbus module. Default I/O connections The default I/O connections of the Factory macro of the ACS880 primary control program are shown below. FR IT NL PT RU SV TR CN 8 EN – Quick installation guide Wire sizes: 0.5 … 2.5 mm2 (24…12 AWG) Tightening torques: 0.5 N·m (5 lbf·in) for both stranded and solid wiring. EN DA DE ES FI FR IT NL PT RU SV TR CN 1) Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus the power taken by DIO1 and DIO2. Fault XPOW External power input 1 +24VI 24 V DC, 2 A 2 GND XAI Reference voltage and analog inputs 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF -10 V DC, RL 1…10 kohm 3 AGND Ground 4 AI1+ Speed reference 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ By default not in use. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 current/voltage selection jumper J2 J2 AI2 current/voltage selection jumper XAO Analog outputs 1 AO1 Motor speed rpm 0…20 mA, RL < 2 AGND 500 ohm 3 AO2 Motor current 0…20 mA, RL < 500 ohm 4 AGND XD2D Drive-to-drive link 1 B Drive-to-drive link 2 A 3 BGND J3 J3 Drive-to-drive link termination switch XRO1, XRO2, XRO3 Relay outputs 11 NC Ready 250 V AC / 30 V DC 12 COM 2A 13 NO 21 NC Running 250 V AC / 30 V DC 22 COM 2A 23 NO 31 NC Faulted(-1) 250 V AC / 30 V DC 32 COM 2A 33 NO XD24 Digital interlock 1 DIIL Run enable 2 +24VD +24 V DC 200 mA 1) 3 DICOM Digital input ground 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Digital input/output ground J6 Ground selection switch XDIO Digital input/outputs 1 DIO1 Output: Ready 2 DIO2 Output: Running XDI Digital inputs 1 DI1 Stop (0) / Start (1) 2 DI2 Forward (0) / Reverse (1) 3 DI3 Reset 4 DI4 Acceleration & deceleration select 5 DI5 Constant speed 1 (1 = On) 6 DI6 By default not in use. XSTO Safe torque off 1 OUT1 2 SGND Safe torque off. Both circuits must be closed for the drive to start. 3 IN1 4 IN2 X12 Safety functions module connection X13 Control panel connection X205 Memory unit connection EN – USA quick installation guide 9 EN – USA quick installation guide This guide instructs briefly how to install the drive. For more detailed instructions, engineering guide lines, technical data and complete safety instructions, see the hardware manual (www.abb.com/drives: Select Document Library and search for document number 3AUA0000078093 [English]). Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: • • Only qualified electrical professionals are allowed to install and maintain the drive. Never work on the drive, motor cable or motor when main power is applied. If the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power. • Never work on the control cables when power is applied to the drive or to the external control circuits. • Always ground the drive, the motor and adjoining equipment to the protective earth (PE) bus of the power supply. • Make sure that debris from borings and grindings does not enter the drive when installing. • Do not connect the drive to a voltage higher than what is marked on the type designation label. DA USA DA DE ES FI FR IT NL The floor material below the drive must be non-flammable. PT Check if capacitors need to be reformed RU Reform the capacitors if the drive has not been powered (either in storage or unused) for a year or more. SV You can determine the manufacturing date from the serial number, which you find on the type designation label attached to the drive. The serial number is of format MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows: YY: WW: 17, 18, 19, … for 2017, 2018, 2019, … 01, 02, 03, … for week 1, week 2, week 3, … For information on reforming the capacitors, see Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions TR CN 10 EN – USA quick installation guide (3BFE64059629 [English]), available on the Internet at www.abb.com/drives/documents. Select the power cables Select the power cables according to local regulations to carry the nominal current given on the type designation label of your drive. Typical power cable sizes are listed in table J on page 100. For the conditions of the sizing, see the hardware manual. DA Ensure the cooling See table B on page 101 for the losses and the cooling air flow through the drive. The USA allowed operating temperature range of the drive without derating is -5 to +104 °F. DA Protect the drive and input power cable DE See table B on page 101. Check that the operating time of the fuse is below 0.5 seconds. ES FI FR IT Install the drive on the wall See figure A on page 101. Check the compatibility with IT (ungrounded), cornergrounded delta, midpoint-grounded delta and TT systems The standard drive with ground-to-phase varistors connected can be installed to a NL symmetrically grounded TN-S system. For other systems, see the hardware manual and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor PT disconnecting instructions (3AUA0000125152 [English]). RU SV TR CN EN – USA quick installation guide 11 B1 A C L1 L1 L1 L2 L3 L2 L2 L3 PE L3 N PE DA B2 L1 USA L2 L3 PE DA DE ES A = TN-S system, B1 = Corner-grounded system, B2 = Midpoint-grounded system, C = IT system FI WARNING! Do not install the drive with EMC filter options +E200 and +E202 connected to a system that the filter is not suitable for. This can cause danger, or damage the drive. FR IT WARNING! Do not install the drive with the ground-to-phase varistor connected to a system that the varistor is not suitable for. If you do, the varistor circuit can be damaged. See the drive hardware manual. Note: With option +E201, remove EMC AC, EMC DC and VAR screws in for systems other than TN-S if not removed at the factory. For more information, contact ABB. Check the insulation of the input and motor cables and the motor Check the insulation of the input cable according to local regulations before you connect it to the drive. Check the insulation of the motor cable and motor when the cable is disconnected from the drive, see figure F on page 102. Measure the insulation resistance between each phase conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, NL PT RU SV TR CN 12 EN – USA quick installation guide please consult the manufacturer’s instructions. Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement. Connect the power cables See figures C, D and E on page 101 and 102. 1. Undo the two mounting screws at the sides of the front cover. 2. Remove the cover by sliding it forward. DA 3. Attach the residual voltage warning sticker in the local language to the control panel mounting platform. USA 4. Remove the rubber grommets from the lead-through plate for the cables to be connected. DA 5. Fasten the cable conduits to the cable lead-through plate holes. Strip the cable ends. Slide the cables through the connectors. DE 6. Connect the grounding conductors to the grounding terminals. ES 7. Connect the phase conductors of the input and motor cables. Tighten the screws. FI 8. Units with option +D150: Connect the brake resistor cable conductors to the R+ and R- terminals. FR 9. Install the control cable grounding shelf in the cable entry box. IT 10. Connect the motor cable at the motor end. NL Connect the control cables PT See figure G on page 102. RU 1. Fasten the cable conduits to the cable lead-through plate holes. Slide the cables through the connectors. SV 2. Strip the cable ends and cut to suitable length (note the extra length of the grounding conductors). TR 3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in the cable entry box. CN EN – USA quick installation guide 13 4. Ground the pair-cable shields to the grounding clamp. Leave the other end of the shields unconnected or ground them indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V. 5. Connect the conductors to the appropriate terminals of the control board (see page 14). 6. Wire the optional modules if included in the delivery. For fieldbus cabling, see page 99. 7. Reinstall the front cover. Default I/O connections The default I/O connections of the Factory macro of the ACS880 primary control program are shown below. DA USA DA DE ES FI FR IT NL PT RU SV TR CN 14 EN – USA quick installation guide Wire sizes: 0.5 … 2.5 mm2 (24…12 AWG) Tightening torques: 0.5 N·m (5 lbf·in) for both stranded and solid wiring. DA USA DA DE ES FI FR IT NL PT RU SV TR CN 1) Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus the power taken by DIO1 and DIO2. Fault XPOW External power input 1 +24VI 24 V DC, 2 A 2 GND XAI Reference voltage and analog inputs 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF -10 V DC, RL 1…10 kohm 3 AGND Ground 4 AI1+ Speed reference 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ By default not in use. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 current/voltage selection jumper J2 J2 AI2 current/voltage selection jumper XAO Analog outputs 1 AO1 Motor speed rpm 0…20 mA, RL < 2 AGND 500 ohm 3 AO2 Motor current 0…20 mA, RL < 500 ohm 4 AGND XD2D Drive-to-drive link 1 B Drive-to-drive link 2 A 3 BGND J3 J3 Drive-to-drive link termination switch XRO1, XRO2, XRO3 Relay outputs 11 NC Ready 250 V AC / 30 V DC 12 COM 2A 13 NO 21 NC Running 250 V AC / 30 V DC 22 COM 2A 23 NO 31 NC Faulted(-1) 250 V AC / 30 V DC 32 COM 2A 33 NO XD24 Digital interlock 1 DIIL Run enable 2 +24VD +24 V DC 200 mA 1) 3 DICOM Digital input ground 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Digital input/output ground J6 Ground selection switch XDIO Digital input/outputs 1 DIO1 Output: Ready 2 DIO2 Output: Running XDI Digital inputs 1 DI1 Stop (0) / Start (1) 2 DI2 Forward (0) / Reverse (1) 3 DI3 Reset 4 DI4 Acceleration & deceleration select 5 DI5 Constant speed 1 (1 = On) 6 DI6 By default not in use. XSTO Safe torque off 1 OUT1 2 SGND Safe torque off. Both circuits must be closed for the drive to start. 3 IN1 4 IN2 X12 Safety functions module connection X13 Control panel connection X205 Memory unit connection EN – USA quick installation guide 15 UL checklist • The drive must be installed in clean air according to enclosure classification. Cooling air must be clean, free from corrosive materials and electrically conductive dust. (IP55)- UL Type 12 enclosure. This enclosure provides protection from airborne dust and light sprays or splashing water from all directions. • The maximum ambient air temperature is 40 °C (104 °F) at rated current. The current is derated for 40 to 55 °C (104 to 131 °F). • The drive is suitable for use in a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 500 V maximum. The ampere rating is based on tests done according to UL 508C. DA • The cables located within the motor circuit must be rated for at least 75 °C (167 °F) in UL-compliant installations. USA • The input cable must be protected with fuses. Circuit breakers must not be used without fuses in the USA. Suitable IEC (class aR) fuses and UL (class T) fuses are listed in the hardware manual. For suitable circuit breakers, contact your local ABB representative. • For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical Code (NEC) and any applicable local codes. To fulfill this requirement, use the UL classified fuses. • For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and any applicable provincial codes. To fulfill this requirement, use the UL classified fuses. • The drive provides overload protection in accordance with the National Electrical Code (NEC). DA DE ES FI FR IT NL PT RU SV TR CN 16 EN – USA quick installation guide DA USA DA DE ES FI FR IT NL PT RU SV TR CN DA – Hurtig installationsvejledning 17 DA – Hurtig installationsvejledning Denne guide er en kortfattet vejledning i, hvordan du installerer frekvensomformeren. Hvis du vil have mere detaljerede instruktioner, tekniske retningslinjer, tekniske data og komplette sikkerhedsinstruktioner, kan du se hardwaremanualen (www.abb.com/drives: Vælg Document Library, og søg efter dokumentnummer 3AUA0000078093 (på engelsk). Overhold sikkerhedsinstruktionerne ADVARSEL! Følg disse instruktioner. Hvis de ignoreres, kan det resultere i personskader, dødsfald eller skade på udstyret: • Kun autoriserede elinstallatører må udføre installation og vedligeholdelse af frekvensomformeren. • Undlad at arbejde med frekvensomformeren, motorkablet eller motoren, når tilslutning til nettet er foretaget. Hvis frekvensomformeren allerede er tilsluttet netforsyningen, skal du vente 5 minutter efter frakobling af netspændingen. • Du må aldrig arbejde med signalkablerne, når netspændingen er tilsluttet frekvensomformeren eller de eksterne styrekredse. • Frekvensomformeren, motoren og tilstødende udstyr skal altid jordes med strømforsyningens beskyttelsesjordbus (PE). EN DA DA ES FI FR IT • Undgå, at der trænger smuds fra boringer og sliberester ind i frekvensomformeren under installation. NL • Frekvensomformeren må ikke tilsluttes til en spænding, der er højere end den, der er angivet på mærkatet med typebetegnelse. PT Gulvmaterialet under frekvensomformeren skal være ikke-brandbart. Kontrollér, om det er nødvendigt at reformere kondensatorerne Reformér kondensatorerne, hvis frekvensomformeren ikke har været tilsluttet strøm i over et år (opbevaret eller ikke anvendt). Du kan bestemme produktionsdatoen ud fra serienummeret, som du finder på mærkatet med typebetegnelse på frekvensomformeren. Serienummeret har formatet MYYWWRXXXX. YY og WW angiver produktionsåret og ugen på følgende måde: YY: WW: 17, 18, 19, … for 2017, 2018, 2019, … 01, 02, 03, … for uge 1, uge 2, uge 3, … 3AUA0000085966 Rev H RU SV TR CN 18 DA – Hurtig installationsvejledning Oplysninger om reformering af kondensatorer findes i Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 (på engelsk)), som findes på internettet på www.abb.com/drives/documents. Vælg effektkabler Vælg en størrelse til kablerne i henhold til lokale forskrifter til at bære den nominelle strøm, der er anført på mærkatet med typebetegnelsen på din frekvensomformer. EN DA Typiske størrelser på effektkabler er vist i tabellen J på side 100. Se hardwaremanualen for oplysninger om betingelserne for størrelse. Sørg for kølingen Se tabel B på side 97 for tabene og frekvensomformerens gennemstrømning af DA kølende luft. Frekvensomformerens tilladte driftstemperaturområde uden reduktion er -15 til +40 °C. ES FI Beskyt frekvensomformeren og forsyningskabel Se tabellen B på side 97. Ud fra sikringens smeltekurve kontrolleres, at smeltetiden FR er under 0,5 sekunder. IT NL PT RU Installer frekvensomformeren på væggen Se figur A på side 97. Kontrollér kompatibiliteten med IT-net (ujordede), hjørnejordede delta-, midtpunktsjordet delta- og TT-systemer Standardfrekvensomformeren med tilsluttet jord-til-fase-varistorer kan installeres SV sammen med et symmetrisk jordet TN-S-system. Oplysninger om andre systemer finder du i hardwaremanualen samt i ACS880 frames R1 to R11 EMC filter and TR ground-to-phase varistor disconnecting instructions (3AUA0000125152 (på engelsk)). CN DA – Hurtig installationsvejledning 19 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DA ES FI A = TN-S-system, B1 = Hjørnejordet system, B2 = Midtpunktsjordet system, C = IT-system ADVARSEL! Installer ikke en frekvensomformer med tilsluttet EMC-filter ekstraudstyr +E200 og +E202 til et system, hvortil filtret ikke er egnet. Dette kan medføre fare eller ødelægge frekvensomformeren. ADVARSEL! Installer ikke frekvensomformeren med tilsluttet jord-til-fasevaristor til et system, hvortil varistoren ikke er egnet. Hvis du gør det, kan varistorkredsløbet tage skade. Se frekvensomformerens hardwaremanual. Bemærk! Hvis du anvender ekstraudstyr +E201, skal du fjerne EMC AC-, EMC DCog VAR-skruerne i andre systemer end TN-S, hvis de ikke allerede er fjernet på fabrikken. Kontakt ABB for at få yderligere oplysninger. Kontroller isoleringen på forsynings- og motorkabel samt motoren Kontrollér, at isoleringen af forsyningskablet er i overensstemmelse med de nationale forskrifter, inden du tilslutter det til frekvensomformeren. Kontrollér isoleringen af motorkabel og motor, når kablet er koblet fra frekvensomformeren. Se figur F på side 98. Mål isolationsmodstanden mellem hver faseleder og beskyttelsesjordens leder med en målespænding på 1000 V DC. Isolationsmodstanden på en ABB-motor skal være større end 100 Mohm FR IT NL PT RU SV TR CN 20 DA – Hurtig installationsvejledning (referenceværdi ved 25 °C eller 77 °F). Se producentens instruktioner for at få oplysninger om isolationsmodstanden på andre motorer. Bemærk! Fugt inden i motorhuset reducerer isolationsmodstanden. Hvis der er mistanke om fugt, skal motoren tørres, og målingen gentages. Fastgør advarselsmærkaterne på de lokale sprog Tilslut effektkablerne. Se figurerne C, D, E og G. Anvend et skærmet symmetrisk kabel til motoren. EN 8. Løsn monteringsskruerne i siderne af frontdækslet. 9. Fjern dækslet ved at skubbe det fremad. DA DA 10. Fastgør advarselsmærkatet om restspænding på det lokale sprog på betjeningspanelets monteringsplatform. 11. Fjern gummimufferne fra gennemføringspladen, så kablerne kan tilsluttes. ES FI 12. IP21-enheder: Fastspænd kabelstikkene (inkluderet i leveringen i en plastikpose) via hullerne i kablets gennemføringsplade. 13. Forbered enderne på forsynings- og motorkablet som vist på figuren. FR IT 14. Jord kabelskærmene 360 grader i kabelstikkene (IP21-enheder) eller under bøjlerne (IP55-enheder). 15. Forbind den snoede del af forsyningskablets skærm med PE-terminalen. NL 16. Forbind forsyningskablets PE-leder med den ekstra PE-terminal. PT 17. Forbind den snoede skærm i motorkablet og i modstandskablet (hvis det findes) til jordterminalen. RU 18. Forbind faselederne på forsynings-, motor- og modstandskablerne. Stram SV skruerne. 19. Installér medfølgende jordingsterminal for styrekabler i kabelsektionen. TR 20. Fastgør kablerne mekanisk uden for frekvensomformeren. CN 21. Tilslut motorkablets skærm i motoren. Opnå minimal interferens ved at lave en 360 graders jording ved kabelgennemføringen eller holde den snoede kobberskærm kort. DA – Hurtig installationsvejledning 21 Tilslut styrekablerne Se figur H. 1. Klip passende huller i gummimufferne, og skub mufferne på kablerne. Før kablerne gennem hullerne på bundpladen, og sæt mufferne fast i hullerne. 2. Afisoler kabelenderne, og skær dem af i en passende længde (bemærk jordledernes ekstra længde). 3. Jord de ydre skærme på alle kabler 360 grader ved en jordingsklemme i kabelsektionen. 4. Jord skærmene på de parsnoede kabler til jordingsklemmen. Lad den anden ende af skærmene være frakoblet, eller slut dem indirekte til jord med en højfrekvenskondensator på nogle få nanofarad (f.eks. 3,3 nF / 630 V). EN DA 5. Forbind kablets ledere til de korrekte klemmer på styrekortet (se side 22). 6. Forbind de valgfrie moduler, hvis de indgår i leverancen. 7. Genmonter frontdækslet. Bemærkning til kabelføring for fieldbuskommunikation. Se figur I. DA ES FI 1. Montér den ekstra jordingsterminal. 2. Jord de udvendige skærme på kabler 360 grader ved en jordingsklemme. 3. Lav huller i kabelindgangskassens dæksel til de kabler, der skal installeres. Monter kabelindgangskassens dæksel. 4. Tilslut stikket til fieldbusmodulet. I/O-standardtilslutninger I/O-standardtilslutninger til fabriksmakroen for det primære styreprogram for ACS880 er vist herunder. FR IT NL PT RU SV TR CN 22 DA – Hurtig installationsvejledning Ledningsstørrelse: 0,5 … 2,5 mm2 (24…12 AWG) Fastspændingsmomenter: 0,5 N·m (5 lbf·in) til både trådledere og stive ledere. EN DA DA ES FI FR IT NL PT RU SV TR CN 1) Den totale belastningskapacitet for disse udgange er 4,8 W (200 mA / 24 V) minus den strøm, der benyttes af DIO1 og DIO2. Fejl XPOW Ekstern strømforsyning 1 +24VI 24 V DC, 2 A 2 GND XAI Referencespænding og analoge indgange 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF -10 V DC, RL 1…10 kohm 3 AGND Jord 4 AI1+ Hastighedsreference 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Som standardindstilling ubenyttet. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1-jumper til valg af strøm/spænding J2 J2 AI2-jumper til valg af strøm/spænding XAO Analoge udgange 1 AO1 Motorhastighed o/min 0…20 mA, 2 AGND RL < 500 ohm 3 AO2 Motorstrøm 0…20 mA, RL < 500 ohm 4 AGND XD2D Drev-til-drev-forbindelse 1 B Drev-til-drev-forbindelse 2 A 3 BGND J3 J3 Afbryder til drev-til-drev-forbindelse XRO1, XRO2, XRO3 Relæudgange 11 NC Startklar 250 V AC / 30 V DC 12 COM 2A 13 NEJ 21 NC Kører 250 V AC / 30 V DC 22 COM 2A 23 NEJ 31 NC Fejl(-1) 250 V AC / 30 V DC 32 COM 2A 33 NEJ XD24 Digital interlock 1 DIIL Start frigiv 2 +24VD +24 V DC 200 mA 1) 3 DICOM Jording af digital indgang 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Jording af digital indgang/udgang J6 Afbryder til valg af jord XDIO Digitale indgange/udgange 1 DIO1 Udgang: Startklar 2 DIO2 Udgang: Kører XDI Digital indgang 1 DI1 Stop (0) / Start (1) 2 DI2 Forlæns (0) / Baglæns (1) 3 DI3 Nulstil 4 DI4 Acceleration og deceleration vælg 5 DI5 Konstant hastighed 1 (1 = Til) 6 DI6 Som standardindstilling ubenyttet. XSTO Safe torque off 1 OUT1 Safe torque off. Begge kredse skal være 2 SGND lukkede, for at frekvensomformeren kan 3 IN1 starte. 4 IN2 X12 Modulforbindelse med sikkerhedsfunktioner X13 Tilslutning til betjeningspanel X205 Tilslutning til hukommelsesenhed DE – Kurzanleitung für die Installation 23 DE – Kurzanleitung für die Installation Diese Kurzanleitung beschreibt die Installation des Frequenzumrichters. Weitere Informationen, Planungsrichtlinien, technische Daten und die vollständigen Sicherheitsvorschriften finden Sie im Hardware-Handbuch. (www.abb.com/drives: Wählen Sie Document Library und suchen Sie die Dokumentennummer 3AUA0000078093 [Englisch]). Befolgen Sie die Sicherheitsvorschriften WARNUNG! Befolgen Sie diese Anweisungen. Wenn diese nicht befolgt werden, können Verletzungen, tödliche Unfälle oder Schäden an den Geräten auftreten: • • Installation und Wartung des Frequenzumrichters dürfen nur von qualifiziertem Fachpersonal ausgeführt werden. EN DA DE Am Frequenzumrichter, dem Motorkabel oder dem Motor dürfen keinerlei Arbeiten ausgeführt werden, solange die Netzspannung anliegt. Wenn der Frequenzumrichter bereits an die Spannungsversorgung angeschlossen ist/war, warten Sie 5 Minuten nach der Trennung von der Eingangsspannung. DE • Führen Sie keine Arbeiten an den Steuerkabeln durch, wenn Spannung am Frequenzumrichter oder den externen Steuerkreisen anliegt. FR • Erden Sie immer den Frequenzumrichter, den Motor und die benachbarten Geräte über die PE-Sammelschiene der Spannungsversorgung. • Stellen Sie sicher, dass bei der Installation keine Bohrspäne und Staub in den Frequenzumrichter eindringen. • Am Frequenzumrichter keine Spannung anlegen, die höher ist, als auf dem Typenschild angegeben. FI IT NL PT RU SV Der Boden unterhalb des Geräts muss aus nicht entflammbarem Material bestehen. TR Prüfen Sie, ob Kondensatoren nachformiert werden müssen Die Kondensatoren müssen neu formiert werden, wenn der Frequenzumrichter für mehr als ein Jahr nicht eingeschaltet wurde (entweder gelagert oder nicht benutzt wurde). Das Herstellungsdatum kann anhand der Seriennummer bestimmt werden, welche auf dem am Frequenzumrichter angebrachten Typenschild angegeben ist. Die Seriennummer hat das Format MJJWWRXXXX. JJ und WW geben das Herstellungsjahr und die -woche an: 3AUA0000085966 Rev H CN 24 DE – Kurzanleitung für die Installation JJ: WW: 17, 18, 19, … für 2017, 2018, 2019, … 01, 02, 03, … für Woche 1, Woche 2, Woche 3, … Informationen zum Formieren der Kondensatoren enthält die Anleitung Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [Englisch], 3AUA0000044714 [Deutsch]), verfügbar im Internet unter www.abb.com/drives/documents. Auswahl der Leistungskabel Die Leistungskabel müssen nach den örtlichen Vorschriften für den auf dem Typenschild des Frequenzumrichters angegebenen Nennstrom ausreichend EN bemessen sein. DA DE Typische Kabelgrößen sind in Tabelle J auf Seite 100 aufgelistet. Bedingungen der Dimensionierung siehe Hardware-Handbuch). Ausreichende Kühlung sicherstellen DE Verluste und Kühlluftstrom durch den Frequenzumrichter siehe Tabelle B auf Seite 97. Der zulässige Betriebstemperaturbereich für den Frequenzumrichter ohne FI Leistungsminderung beträgt -15 bis +40 °C. FR Schutz des Frequenzumrichters und der Einspeisekabel IT Siehe Tabelle B auf Seite 97. Prüfen Sie, ob die Ansprechzeit der Sicherungen weniger als 0,5 Sekunden beträgt. NL PT RU SV TR Wandmontage des Frequenzumrichters Siehe Abbildung A auf Seite 97. Prüfung der Kompatibilität mit (ungeerdeten) IT-, asymmetrisch geerdeten, mittelpunktgeerdeten und TT-Netzen Der Standard-Frequenzumrichter mit angeschlossenem Erde-Phase-Varistor kann an CN ein symmetrisch geerdetes TN-S-Netz angeschlossen werden. Andere Netze siehe Hardware-Handbuch und ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [Englisch]). DE – Kurzanleitung für die Installation 25 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE DE FI A = TN-S-Netz, B1 = asymmetrisch geerdetes Netz, B2 = mittelpunktgeerdetes Netz, C = IT-Netz WARNUNG! Installieren Sie den Frequenzumrichter mit angeschlossenem EMV-Filteroptionen +E200 und +E202 nicht an einem Netz, für das der Filter nicht geeignet ist. Dadurch können Gefahren entstehen oder der Frequenzumrichter kann beschädigt werden. FR IT NL PT WARNUNG! Installieren Sie den Frequenzumrichter mit angeschlossenem Erde-Phase-Varistor nicht an einem Netz, für das der Varistor nicht geeignet ist. Dann kann die Varistorschaltung beschädigt werden. Siehe das entsprechende Hardware-Handbuch des Frequenzumrichters. Hinweise: Entfernen Sie mit Option +E201 die EMV AC-, EMV DC- und VARSchrauben für andere Netze als TN-S, falls dies nicht bereits ab Werk geschehen ist. Für weitere Informationen setzen Sie sich mit ABB in Verbindung. Prüfen Sie die Isolierung der Einspeise- und Motorkabel und des Motors. Prüfen Sie, ob die Isolation des Netzanschlusskabels den örtlichen Vorschriften entspricht, bevor es an den Frequenzumrichter angeschlossen wird. Prüfen Sie die Isolation des Motorkabels und des Motors, wenn das Motorkabel vom Frequenzumrichter getrennt wird, siehe Abbildung F auf Seite 98. Messen Sie die RU SV TR CN 26 DE – Kurzanleitung für die Installation Isolationswiderstände zwischen jeder Phase und der Schutzerde mit einer Messspannung von 1000 V DC. Der Isolationswiderstand eines ABB-Motors muss 100 MOhm überschreiten (Referenzwert bei 25 °C bzw. 77 °F). Die Isolationswiderstände anderer Motoren entnehmen Sie bitte der Anleitung des Herstellers. Hinweis: Feuchtigkeit innerhalb des Motorgehäuses reduziert den Isolationswiderstand. Bei Verdacht auf Feuchtigkeit muss der Motor getrocknet und die Messung wiederholt werden. Bringen Sie die Warnaufkleber in der Landessprache an EN Anschluss der Leistungskabel Siehe Abbildungen C, D, E und G. Ein symmetrisch geschirmtes Motorkabel DA verwenden. DE 5. Die Befestigungsschrauben auf den Seiten der Frontabdeckung lösen. 6. Die Abdeckung durch Vorschieben abnehmen. DE 7. Den Restspannungs-Warnaufkleber in der erforderlichen lokalen Sprache auf der Bedienpanel-Halterung anbringen. FI 8. Die Gummi-Kabeldurchführungen für die anzuschließenden Kabel vom Durchführungsblech abnehmen. FR IT 9. IP21 Einheiten: Die Kabelschellen (mitgeliefert, in einem Plastikbeutel) an den Bohrungen des Durchführungsblechs befestigen. NL 10. Die Enden der Einspeise- und Motorkabel wie in der Abbildung gezeigt vorbereiten. PT 11. Die Kabelschirme 360 Grad an den Kabelanschlüssen (IP21 Einheiten) oder unter den Schellen (IP55 Einheiten) erden. RU 12. Den verdrillten Schirm des Einspeisekabels an die Erdungsklemme anschließen. SV 13. Den Erdungsleiter (PE) des Einspeisekabels an die zusätzliche Erdungsklemme anschließen. TR 14. Die verdrillten Schirme des Motor- und Widerstandskabels (falls vorhanden) an die Erdungsklemme anschließen. CN 15. Die Phasenleiter des Einspeise-, Motor- und Widerstandskabels anschließen. Ziehen Sie die Schrauben fest. 16. Die Steuerkabel-Erdungsschellenschiene im Kabelanschlusskasten installieren. 17. Die Kabel außerhalb des Frequenzumrichters mechanisch sichern. 18. Die Motorkabelschirme motorseitig an Erde/PE anschließen. Um eine geringe Interferenz sicherzustellen, eine 360-Grad-Erdung an der Kabeldurchführung vornehmen oder den verdrillten Schirm kurz halten. DE – Kurzanleitung für die Installation 27 Die Steuerkabel anschließen Siehe Abbildung H. 1. Eine passende Öffnung in die Gummi-Kabeldurchführungen schneiden und die Kabeldurchführungen auf die Kabel schieben. Die Kabel durch die Öffnungen des unteren Abschlussblechs stecken und die Kabeldurchführungen in die Öffnungen drücken. 2. Die Kabelenden abisolieren und auf die passende Länge abschneiden (beachten Sie die zusätzliche bei den Erdleitern benötigte Länge). 3. Für die äußeren Schirme aller Steuerkabel im Kabelanschlusskasten eine 360-Grad-Erdung an einer Erdungsschelle herstellen. 4. Den Kabelschirm an der Erdungsklemme erden. Das andere Ende der Schirme nicht anschließen oder indirekt über einen Hochfrequenz-Kondensator mit wenigen Nanofarad (z.B. 3,3 nF / 630 V) erden. 5. Schließen Sie die Leiter an die entsprechenden Anschlüsse der Regelungseinheit an (siehe Seite 28). 6. Die Optionsmodule, falls im Lieferumfang enthalten, verdrahten. EN DA DE DE FI 7. Die Frontabdeckung wieder anbringen: Hinweis zur Feldbusverkabelung. Siehe Abbildung I. 1. Installieren Sie die zusätzliche Erdungsschellenschiene. 2. Die äußeren Schirme der Kabel 360 Grad unter der Erdungsschelle erden. FR IT NL 3. Für die zu installierenden Kabel die Abdeckungen aus den Öffnungen im Kabelanschlusskasten brechen. Die Abdeckung des Kabelanschlusskastens installieren. PT 4. Den Stecker an das Feldbus Modul anschließen. RU Standard E/A-Anschlüsse SV Die Standard-E/A-Anschlüsse des Makros Werkseinstellung des ACS880 Hauptregelungsprogramms sind nachfolgend dargestellt. TR CN 28 DE – Kurzanleitung für die Installation Leitergrößen: 0,5 … 2,5 mm2 (24…12 AWG) Anzugsmomente: 0,5 Nm (5 lbf·in) für Litzen und einadrige Leiter. EN DA DE DE FI FR IT NL PT RU SV TR CN 1) Die Gesamtbelastbarkeit dieser Ausgänge beträgt 4,8 W (200 mA / 24 V) minus der Energie, die von DIO1 und DIO2 verbraucht wird. Störung XPOW Eingang für externe Spannungsversorgung 1 +24VI 24 V DC, 2 A GND/Masse 2 XAI Referenzspannungsausgänge und Analogeingänge 1 +VREF 10 V DC, RL 1…10 kOhm 2 -VREF -10 V DC, RL 1…10 kOhm 3 AGND Masse 4 AI1+ Drehzahl-Sollwert 0(2)…10 V, Rin > 200 kOhm 5 AI16 AI2+ Standardmäßig nicht benutzt. 0(4)...20 mA, Rin = 100 Ohm 7 AI2AI1 Steckbrücke für Auswahl Strom/Spannung I/U J1 J1 AI2 Steckbrücke für Auswahl Strom/Spannung I/U J2 J2 XAO Analogausgänge 1 AO1 Motordrehzahl U/min 0…20 mA, 2 AGND RL < 500 Ohm 3 AO2 Motorstrom 0…20 mA, 4 AGND RL < 500 Ohm XD2D Umrichter-Umrichter-Verbindung (D2D) 1 B Umrichter-Umrichter-Verbindung (D2D) 2 A 3 BGND Schalter für Abschluss der D2D-Verbindung J3 J3 XRO1, XRO2, XRO3 Relaisausgänge 11 NC Bereit 250 V AC / 30 V DC 12 COM 2A 13 NO 21 NC Läuft 250 V AC / 30 V DC 22 COM 2A 23 NO 31 NC Störung (-1) 250 V AC / 30 V DC 32 COM 2A 33 NO XD24 Digital-Startsperre 1 DIIL Reglerfreigabe 2 +24 VD +24 V DC 200 mA 1) 3 DICOM Digitaleingang Masse 4 +24 VD +24 V DC 200 mA 1) 5 DIOGND Digitaleingang/-ausgang Masse J6 Schalter Masse-Auswahl XDIO Digitaleingänge/-ausgänge 1 DIO1 Ausgang: Startbereit 2 DIO2 Ausgang: In Betrieb XDI Digitaleingänge 1 DI1 Stop (0) / Start (1) 2 DI2 Vorwärts (0) /Rückwärts (1) 3 DI3 Störungsquittierung 4 DI4 Auswahl Beschl./Verzög.-Rampen 5 DI5 Konstantdrehzahl 1 (1 = Ein) 6 DI6 Standardmäßig nicht benutzt. XSTO Sicher abgeschaltetes Drehmoment 1 OUT1 Sicher abgeschaltetes Drehmoment 2 SGND (STO). Beide Kreise müssen für den 3 IN1 Start des Antriebs geschlossen sein. 4 IN2 X12 Sicherheitsfunktionsmodul-Anschluss X13 Bedienpanel-Anschluss X205 Anschluss für Memory Unit ES – Guía rápida de instalación 29 ES – Guía rápida de instalación Esta guía ofrece unas breves instrucciones para la instalación del convertidor de frecuencia. Para obtener instrucciones más detalladas, directrices de ingeniería, datos técnicos y unas instrucciones de seguridad completas, véase el Manual de hardware (www.abb.com/drives: seleccione Biblioteca de documentos y busque el número de documento 3AUA0000078093). Siga estrictamente las instrucciones de seguridad ADVERTENCIA: Siga estrictamente estas instrucciones. Si no lo hace, se pueden producir daños en el equipo o en las personas, e incluso causar la muerte: • Sólo podrán efectuar la instalación y el mantenimiento del convertidor electricistas cualificados. • No intente trabajar con el convertidor, el cable de motor o el motor con la alimentación principal conectada. Si el convertidor está conectado a la potencia de entrada, espere 5 minutos tras desconectarlo. ES DA DE ES ES • Nunca manipule los cables de control mientras el convertidor o los circuitos de control externo reciban alimentación. • Conecte siempre el convertidor, el motor y los equipos auxiliares al embarrado de conexión a tierra (PE) de la fuente de alimentación. • Asegúrese de que los restos de polvo y virutas resultantes de practicar orificios y rectificaciones no entren en el convertidor de frecuencia durante la instalación. NL • No conecte el convertidor a una tensión superior a la indicada en la etiqueta de designación de tipo. PT FR IT El material del suelo situado bajo el convertidor debe ser de un material ignífugo. RU Compruebe si es necesario reacondicionar los condensadores SV Reacondicione los condensadores si el convertidor no ha sido alimentado (por estar almacenado o sin usar) durante un año o más. Puede determinar la fecha de fabricación a partir del número de serie, que encontrará en la etiqueta de designación de tipo adherida al convertidor. El número de serie tiene el formato MAASSRXXXX. AA y SS indican el año y la semana de fabricación, de la forma siguiente: AA: SS: 17, 18, 19… para 2017, 2018, 2019… 01, 02, 03… para semana 1, semana 2, semana 3… 3AUA0000085966 Rev H TR CN 30 ES – Guía rápida de instalación Para más información sobre el reacondicionamiento de los condensadores, consulte el documento Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [Inglés]), disponible en Internet en www.abb.com/drives/documents. Seleccione los cables de potencia Dimensione los cables de potencia de conformidad con los reglamentos locales para el transporte de la intensidad nominal indicada en la etiqueta de designación de tipo de su convertidor de frecuencia. Puede ver los tamaños de cables de potencia más habituales en la tabla J de la ES página 100. Consulte en el Manual de hardware las condiciones de los tamaños de los cables. DA DE Garantice la refrigeración Véase la tabla B de la página 97 para conocer las pérdidas y el caudal de aire de ES refrigeración a través del convertidor de frecuencia. El rango de temperatura de funcionamiento permitido para el convertidor de frecuencia sin pérdidas de potencia ES es de -15 a +40 °C. FR IT Protección del convertidor y el cable de potencia de entrada Véase la tabla B en la página 97. Compruebe que el tiempo de fusión del fusible sea NL inferior a 0,5 segundos. PT RU SV TR Monte el convertidor de frecuencia en la pared Véase la figura A de la página 97. Compruebe la compatibilidad con redes IT (sin conexión a tierra), redes en triángulo conectadas a tierra en un vértice o en el punto medio y redes TT Los convertidores estándar con varistores tierra-fase conectados se pueden instalar CN en una red TN-S conectada a tierra simétricamente. Para otros sistemas, véase el Manual de hardware y ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [Inglés]). ES – Guía rápida de instalación 31 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE ES B2 L1 DA L2 L3 PE DE ES ES A = Red TN-S, B1 = Red conectada a tierra en un vértice, B2 = Red conectada a tierra en el punto medio, C = Red IT ADVERTENCIA: No instale el convertidor de frecuencia con los opcionales de filtro EMC +E200 y +E202 conectados a un sistema para el cual el filtro no es adecuado. Esto puede entrañar peligro o provocar daños en el convertidor. FR IT NL PT ADVERTENCIA: No instale el convertidor de frecuencia con un varistor tierrafase conectado en un sistema para el cual no sea adecuado el varistor. Si lo hace, el circuito del varistor podría resultar dañado. Consulte el manual de hardware del convertidor. Nota: Con el opcional +E201, si no se han quitado en la fábrica, retire los tornillos EMC AC, EMC DC y VAR para todas las redes excepto TN-S. Para más información, póngase en contacto con ABB. RU SV TR CN 32 ES – Guía rápida de instalación Compruebe el aislamiento de los cables de entrada y motor y del propio motor Compruebe el aislamiento del cable de entrada conforme a las normativas locales antes de conectar el convertidor a la red. Compruebe el aislamiento del cable de motor y del motor mientras el cable está desconectado del convertidor, véase la figura F en la página 98. Mida la resistencia de aislamiento entre cada conductor de fase y el conductor de protección a tierra con una tensión de medición de 1000 V CC. La resistencia de aislamiento de un motor ABB debe ser superior a los 100 Mohmios (valor de referencia a 25 °C o 77 °F). En cuanto a la resistencia de aislamiento de otros motores, véanse las instrucciones ES del fabricante. Nota: La humedad en el interior de la carcasa del motor reduce la resistencia de aislamiento. Si sospecha de la presencia de humedad, seque el motor DA y repita la medición. DE ES Fije las etiquetas de advertencia disponibles en los idiomas locales ES Conecte los cables de potencia FR Véanse las figuras C, D, E y G. Use cable apantallado simétrico para el cableado al motor. IT 5. Afloje los tornillos de montaje situados a los lados de la cubierta frontal. NL PT RU 6. Retire la cubierta deslizándola hacia delante. 7. Pegue el adhesivo de advertencia de tensión residual en el idioma local a la plataforma de montaje del panel de control. 8. Retire las arandelas de goma de la placa pasacables para los cables que desee conectar. SV 9. Unidades IP21: Sujete los conectores de cables (incluidos en el suministro dentro de una bolsa de plástico) a los orificios de la placa pasacables. TR 10. Prepare los extremos de los cables de potencia de entrada y de motor de la forma mostrada en la figura. CN 11. Conecte a tierra los apantallamientos de los cables a 360 grados a los conectores de cable (unidades IP21) o debajo de las abrazaderas (unidades IP55). 12. Conecte el apantallamiento trenzado del cable de entrada al terminal PE. 13. Conecte el conductor de conexión a tierra del cable de potencia de entrada al terminal PE. 14. Conecte la pantalla trenzada del cable de motor y del cable de resistencia (si lo hubiese) al terminal de conexión a tierra. ES – Guía rápida de instalación 33 15. Conecte los conductores de fase de los cables de entrada, motor y resistencia. Apriete los tornillos. 16. Instale la pletina de conexión a tierra para cables de control en la caja de entrada de cables. 17. Sujete los cables mecánicamente al exterior del convertidor. 18. Conecte a tierra la pantalla del cable de motor en el extremo del motor. Para unas mínimas interferencias, realice una conexión a tierra a 360 grados en el pasacables o mantenga el mallado corto. Conexión de los cables de control ES Véase la figura H. 1. Practique orificios adecuados en las arandelas de goma y haga pasar los cables a través de ellas. Deslice los cables a través de los orificios del panel inferior y fije las arandelas a los orificios. DA DE 2. Pele los extremos de los cables y corte a una longitud adecuada (recuerde la longitud adicional de los conductores de conexión a tierra). ES 3. Conecte a tierra los apantallamientos exteriores de todos los cables de control a 360 grados a la abrazadera de conexión a tierra de la caja de entrada de cables. ES 4. Conecte a tierra el apantallamiento del par de cables en la abrazadera de tierra. Deje el otro extremo de las pantallas sin conectar o conéctelas a tierra de forma indirecta a través de un condensador de alta frecuencia de unos pocos nanofaradios, por ejemplo, 3,3 nF / 630 V. 5. Conecte los conductores a los terminales adecuados de la tarjeta de control (véase la página 34). 6. Cablee los módulos opcionales si están incluidos en el suministro. 7. Vuelva a colocar la cubierta frontal. Nota para el cableado de bus de campo. Véase la figura I. 1. Instale la pletina adicional de conexión a tierra. 2. Conecte a tierra las pantallas exteriores de los cables a 360 grados en una abrazadera de conexión a tierra. 3. Practique orificios en la cubierta de la caja de entrada de cables para los cables que se van a instalar. Instale la cubierta de la caja de entrada de cables. 4. Enchufe el conector al módulo de bus de campo. Conexiones de E/S por defecto A continuación se muestran las conexiones de E/S por defecto de la macro de fábrica del programa de control primario ACS880. FR IT NL PT RU SV TR CN 34 ES – Guía rápida de instalación Tamaños de hilos: 0,5 … 2,5 mm2 (24…12 AWG) Pares de apriete: 0,5 N·m (5 lbf·in) tanto para los cables flexibles como para los sólidos. ES DA DE ES ES FR IT NL PT RU SV TR CN 1) La capacidad de carga total de estas salidas es de 4,8 W (200 mA / 24 V) menos la potencia consumida por DIO1 y DIO2. Fallo XPOW Entrada de alimentación externa 1 +24 VI 24 V CC, 2 A 2 GND XAI Tensión de referencia y entradas analógicas 1 +VREF 10 V CC, RL 1…10 kohmios 2 -VREF -10 V CC, RL 1…10 kohmios 3 AGND Tierra 4 AI1+ Ref. de velocidad 0(2)…10 V, Rin > 200 kohmios 5 AI16 AI2+ Por defecto no se usa. 0(4)…20 mA, Rin = 100 ohmios 7 AI2Puente de selección de Tensión/Corriente AI1 J1 J1 Puente de selección de Tensión/Corriente AI2 J2 J2 XAO Salidas analógicas 1 AO1 Régimen de motor rpm 0…20 mA, 2 AGND RL < 500 ohmios 3 AO2 Intensidad de motor 0…20 mA, 4 AGND RL < 500 ohmios XD2D Enlace de convertidor a convertidor 1 B Enlace de convertidor a convertidor 2 A 3 BGND Terminador de enlace de convertidor a convertidor J3 J3 XRO1, XRO2, XRO3 Salidas de relé 11 NC Listo 250 V CA / 30 V CC 12 COM 2A 13 NO 21 NC En marcha 250 V CA / 30 V CC 22 COM 2A 23 NO 31 NC Fallo(-1) 250 V CA / 30 V CC 32 COM 2A 33 NO XD24 Bloqueo de marcha 1 DIIL Permiso de marcha 2 +24 VD +24 V CC 200 mA 1) 3 DICOM Tierra de entrada digital 4 +24 VD +24 V CC 200 mA 1) 5 DIOGND Tierra de entrada/salida digital J6 Interruptor de selección de tierra XDIO Entradas/salidas digitales 1 DIO1 Salida: Listo 2 DIO2 Salida: En marcha XDI Entradas digitales 1 DI1 Paro (0) / Marcha (1) 2 DI2 Avance (0) / Retroceso (1) 3 DI3 Restaurar 4 DI4 Selección de aceleración y deceleración 5 DI5 Velocidad constante 1 (1 = activado) 6 DI6 Por defecto no se usa. XSTO Safe Torque Off 1 OUT1 Safe Torque Off. Ambos circuitos deben 2 SGND estar cerrados para que el convertidor 3 IN1 pueda ponerse en marcha. 4 IN2 X12 Conexión de módulo de funciones de seguridad X13 Conexión del panel de control X205 Conexión de la unidad de memoria FI – Asennuksen pikaopas 35 FI – Asennuksen pikaopas Tässä oppaassa on taajuusmuuttajan lyhyet asennusohjeet. Yksityiskohtaisemmat ohjeet, suunnitteluohjeet, tekniset tiedot ja täydelliset turvaohjeet löytyvät laiteoppaasta (www.abb.com/drives: valitse Document Library ja kirjoita hakukenttään dokumentin numero 3AUA0000078093 [englanninkielinen]). Noudata turvaohjeita VAROITUS! Noudata näitä ohjeita. Ohjeiden laiminlyönti voi aiheuttaa fyysisen vamman tai hengenvaaran tai vahingoittaa laitteistoa. • Taajuusmuuttajan asennus- ja huoltotyöt saa suorittaa vain valtuutettu sähköalan ammattilainen. • Tee kaikki taajuusmuuttajan, moottorikaapelin ja moottorin asennus- ja huoltotyöt jännitteen ollessa katkaistuna. Jos taajuusmuuttaja on jo kytketty syöttöverkkoon, kytke se irti verkosta ja odota 5 minuuttia. • Älä käsittele ohjauskaapeleita, kun taajuusmuuttajaan tai ulkoisiin ohjauspiireihin on kytketty jännite. • Maadoita taajuusmuuttaja, moottori ja niihin liittyvät laitteet aina syötön suojamaakiskoon (PE). • Varmista, ettei poraus- tai hiomajäte pääse laitteen sisään asennuksen yhteydessä. • Älä kytke taajuusmuuttajaa tyyppikilpeen merkittyä jännitettä suurempaan jännitteeseen. EN DA DE ES FI FI IT NL PT Taajuusmuuttajan alla olevan lattiamateriaalin tulee olla palamatonta. RU Tarkista, täytyykö kondensaattorit elvyttää SV Elvytä kondensaattorit, jos taajuusmuuttajaan ei ole kytketty virtaa vähintään vuoteen (laite on ollut varastoituna tai käyttämättä). TR Voit selvittää valmistusajankohdan sarjanumeron perusteella. Sarjanumero on taajuusmuuttajaan kiinnitetyssä tyyppikilvessä. Sarjanumero on muotoa MYYWWRXXXX. YY ja WW ilmaisevat valmistusvuoden ja -viikon seuraavasti: YY: WW: 17, 18, 19,…, mikä tarkoittaa vuotta 2017, 2018, 2019,… 01, 02, 03,…, mikä tarkoittaa viikkoa 1, 2, 3,… Lisätietoja kondensaattorien elvyttämisestä on Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions -oppaassa 3AUA0000085966 Rev. H CN 36 FI – Asennuksen pikaopas (3BFE64059629, englanninkielinen), joka on saatavana osoitteesta www.abb.com/drives/documents. Valitse tehokaapelit Mitoita tehokaapelit taajuusmuuttajan tyyppikilvessä ilmoitetun nimellisvirran mukaan. Noudata paikallisia määräyksiä. Tyypilliset tehokaapelien koot on esitetty taulukossa J sivulla 100. Mitoitukseen liittyvät ehdot on kerrottu laiteoppaassa. EN Varmista jäähdytys Katso tiedot lämpöhäviöistä ja taajuusmuuttajan läpi virtaavasta jäähdytysilmasta DA sivulla 97 olevasta taulukosta B. Taajuusmuuttajan sallittu käyttölämpötila-alue ilman kuormitettavuuden alennusta on –15...+40 °C. DE ES Suojaa taajuusmuuttaja ja syöttökaapeli FI Katso taulukko B sivulla 97. Varmista, että sulakkeen toiminta-aika on alle 0,5 sekuntia. FI Asenna taajuusmuuttaja seinälle IT NL PT Katso kuva A sivulla 97. Tarkista yhteensopivuus maadoittamattomien IT-verkkojen, epäsymmetrisesti ja keskipisteestä maadoitettujen kolmioverkkojen sekä TT-verkkojen kanssa Vakiomallinen taajuusmuuttaja, johon on liitetty maajohtimen ja vaihejohtimen väliset RU varistorit, voidaan asentaa symmetrisesti maadoitettuun TN-S-verkkoon. Katso muiden verkkojen osalta laiteopas sekä opas ACS880 frames R1 to R11 EMC filter SV and ground-to-phase varistor disconnecting instructions (3AUA0000125152, englanninkielinen). TR CN FI – Asennuksen pikaopas 37 . A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = TN-S-verkko, B1 = epäsymmetrisesti maadoitettu verkko, B2 = keskipisteestä maadoitettu verkko, C = IT-verkko VAROITUS! Älä asenna taajuusmuuttajaa, johon on liitetty EMC-suodin (lisävarusteet +E200 ja +E202), verkkoon, johon suodin ei sovellu. Tämä voi aiheuttaa vaaratilanteen tai vahingoittaa taajuusmuuttajaa. FI IT NL PT VAROITUS! Älä asenna taajuusmuuttajaa, johon on liitetty maajohtimen ja vaihejohtimen välinen varistori, verkkoon, johon varistori ei sovellu. Muussa tapauksessa varistoripiiri voi vahingoittua. Lisätietoja on taajuusmuuttajan laiteoppaassa. Huomaa: Jos järjestelmässä on lisävaruste +E201, poista EMC AC-, EMC DC- ja VAR-ruuvit muita kuin TN-S-verkkoja varten, jos niitä ei ole poistettu tehtaalla. Lisätietoja on saatavana ABB:ltä. Tarkista syöttö- ja moottorikaapelien sekä moottorin eristys Tarkista syöttökaapelin eristys paikallisten määräysten mukaisesti ennen kaapelin kytkemistä taajuusmuuttajaan. Tarkista moottorikaapelin ja moottorin eristys, kun kaapeli on irti taajuusmuuttajasta. Katso kuva F sivulla 98. Mittaa jokaisen vaihejohtimen ja suojamaajohtimen (PE) RU SV TR CN 38 FI – Asennuksen pikaopas välinen eristysvastus 1 000 V DC:n mittausjännitteellä. ABB:n moottoreiden eristysvastuksen tulee olla yli 100 megaohmia (ohjearvo lämpötilassa 25 °C). Lisätietoja muiden moottorien eristysvastuksista on valmistajan ohjeissa. Huomautus: Moottorin kotelon sisällä oleva kosteus pienentää eristysvastusta. Jos epäilet, että kotelon sisällä on kosteutta, kuivata moottori ja toista mittaus. Kiinnitä tarrat, joissa varoitukset on annettu paikallisilla kielillä Kytke tehokaapelit EN Katso kuvat C, D, E ja G. Käytä suojattua symmetristä moottorikaapelia. DA 5. Avaa etukannen sivuilla olevat kiinnitysruuvit. 6. Irrota kansi vetämällä sitä eteenpäin. DE 7. Kiinnitä oikeankielinen jäännösjännitteen varoitustarra ohjauspaneelin kiinnitysalustaan. ES FI FI IT NL 8. Irrota kumitiivisteet läpivientilevystä kytkettäviä kaapeleita varten. 9. IP21-yksiköt: Kiinnitä kaapeliliittimet (ovat toimitukseen kuuluvassa muovipakkauksessa) kaapelien läpivientilevyn reikiin. 10. Valmistele syöttö- ja moottorikaapelien päät kuvassa esitetyllä tavalla. 11. Maadoita kaapelin suojavaipat 360 astetta kaapeliliittimissä (IP21-yksiköt) tai kiinnikkeiden alla (IP55-yksiköt). 12. Kytke syöttökaapelin kierretty suojavaippa PE-liittimeen. PT 13. Kytke syöttökaapelin PE-johdin PE-lisäliittimeen. RU 14. Kytke moottorikaapelin ja mahdollisen vastuskaapelin kierretty suojavaippa maadoitusliittimeen. SV 15. Kytke syöttö-, moottori- ja vastuskaapelien vaihejohtimet. Kiristä ruuvit. TR 16. Asenna ohjauskaapelin maadoitushylly kaapelin läpivientikoteloon. CN 17. Kiinnitä taajuusmuuttajan ulkopuolella olevat kaapelin osat mekaanisesti. 18. Maadoita moottorikaapelin suojavaippa moottorin päästä. Jotta häiriöt voitaisiin minimoida, tee kaapelin läpiviennissä 360 asteen maadoitus tai pidä kierretty johdin lyhyenä. FI – Asennuksen pikaopas 39 Kytke ohjauskaapelit Katso kuva H. 1. Leikkaa kumitiivisteisiin sopivan kokoiset aukot ja vedä kumitiivisteet kaapeleihin. Vie kaapelit pohjalevyssä olevien reikien läpi ja kiinnitä kumitiivisteet reikiin. 2. Kuori kaapelien päät ja leikkaa ne sopivaan pituuteen (huomaa maadoitusjohtimien ylimääräinen pituus). 3. Maadoita kaikkien ohjauskaapelien ulkovaipat 360 astetta kaapelien läpivientikotelossa olevan maadoituskiinnikkeen kohdalla. 4. Maadoita parikaapelien vaipat maadoituskiinnikkeeseen. Jätä suojavaippojen toiset päät maadoittamatta tai maadoita ne epäsuorasti muutaman nanofaradin suurtaajuuskondensaattorilla, esim. 3,3 nF / 630 V. EN DA 5. Liitä johtimet oikeisiin ohjauskortin liittimiin (katso sivu 40). 6. Kytke myös lisävarustemoduulit, mikäli niitä sisältyy toimitukseen. 7. Asenna etukansi takaisin paikalleen. Kenttäväyläkaapeleita koskeva huomautus: Katso kuva I. DE ES FI 1. Asenna lisämaadoitushylly. 2. Maadoita kaapelien ulommat suojavaipat 360 astetta maadoitusliittimen kohdalla. 3. Avaa kaapelien läpivientikotelon kanteen aukot asennettaville kaapeleille. Asenna kaapelien läpivientikotelon kansi. 4. Kiinnitä liitin kenttäväylämoduuliin. Oletusarvoiset I/O-ohjauskytkennät ACS880-perusohjausohjelman tehdasmakron oletusarvoiset I/O-ohjauskytkennät on esitetty seuraavassa kaaviossa. FI IT NL PT RU SV TR CN 40 FI – Asennuksen pikaopas Johdinkoot: 0,5 … 2,5 mm2 (24…12 AWG) Kiristysmomentit: 0,5 Nm yksilankaisille ja kerratuille johtimille. EN DA DE ES FI FI IT NL PT RU SV TR CN 1) Näiden lähtöjen kokonaiskapasiteetti on 4,8 W (200 mA / 24 V), josta vähennetään DIO1- ja DIO2liitäntöjen kuluttama teho. Vika XPOW Ulkoinen syöttö 1 +24VI 24 V DC, 2 A 2 GND XAI Ohjejännite ja analogiatulot 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF –10 V DC, RL 1…10 kohm 3 AGND Maa 4 AI1+ Nopeusohje 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Oletusasetuksena ei käytössä. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 (virran/jännitteen valinnan siirtoliitin) J2 J2 AI2 (virran/jännitteen valinnan siirtoliitin) XAO Analogialähdöt 1 AO1 Moottorin nopeus (rpm) 0…20 mA, RL 2 AGND < 500 ohm 3 AO2 Moottorin virta 0…20 mA, RL < 4 AGND 500 ohm XD2D Taajuusmuuttajien välinen liitäntä 1 B Taajuusmuuttajien välinen liitäntä 2 A 3 BGND J3 J3 Liitännän päätevastuksen valintakytkin XRO1, XRO2, XRO3 Relelähdöt 11 NC Valmis 250 V AC / 30 V DC 12 COM 2A 13 NO 21 NC Käy 250 V AC / 30 V DC 22 COM 2A 23 NO 31 NC Vika(-1) 250 V AC / 30 V DC 32 COM 2A 33 NO XD24 Digitaalinen lukitus 1 DIIL Käyntilupa 2 +24VD +24 V DC 200 mA 1) 3 DICOM Digitaalitulon maa 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Digitaalitulon/-lähdön maa J6 Maadoituksen valintakytkin XDIO Digitaalitulot/-lähdöt 1 DIO1 Lähtö: Valmis 2 DIO2 Lähtö: Käy XDI Digitaalitulot 1 DI1 Seis (0) / Käy (1) 2 DI2 Eteen (0) / Taakse (1) 3 DI3 Kuittaus 4 DI4 Kiihdytyksen ja hidastuksen valinta 5 DI5 Vakionopeus 1 (1 = Käytössä) 6 DI6 Oletusasetuksena ei käytössä. XSTO Safe torque off -toiminto 1 OUT1 Safe torque off -toiminto. Molempien 2 SGND piirien on oltava suljettuina, jotta 3 IN1 taajuusmuuttaja käynnistyy. 4 IN2 X12 Turvatoimintomoduulin liitäntä X13 Ohjauspaneelin liitäntä X205 Muistiyksikön liitäntä FR – Guide d'installation 41 FR – Guide d'installation Ce guide vous explique brièvement comment installer le variateur. Pour des consignes détaillées, des directives d'ingénierie, les caractéristiques techniques ou les consignes de sécurité complètes, reportez-vous au manuel d'installation (www.abb.com/drives : Sélectionnez Document Library (vous devrez peut-être afficher la page en anglais pour voir cette rubrique) et recherchez le document anglais de référence 3AUA0000078093. Consignes de sécurité EN ATTENTION ! Vous devez suivre les consignes de sécurité à la lettre. Leur non-respect est susceptible de provoquer des blessures graves, voire mortelles, ou des dégâts matériels. DA • Seuls des électriciens qualifiés sont autorisés à procéder à l’installation et la maintenance du variateur. DE • N'intervenez jamais sur le variateur, le moteur ou son câblage sous tension. S’il est déjà raccordé au réseau, vous devez attendre 5 minutes après sectionnement de l’alimentation avant d’intervenir. • Vous ne devez jamais intervenir sur les câbles de commande lorsque le variateur ou les circuits de commande externes sont sous tension. • Le variateur ainsi que le moteur et les équipements annexes doivent être mis à la terre en permanence via le bus PE de l'alimentation. • En cas de perçage ou de rectification d’un élément, évitez toute pénétration de débris dans le variateur. • Vous ne devez pas alimenter le variateur avec une tension supérieure à la valeur figurant sur sa plaque signalétique. ES FI FR FR NL PT RU SV La surface (sol) sous l'appareil doit être en matériau ininflammable. TR Vérification des condensateurs Si le variateur est resté plus d'un an sans être mis sous tension (en stockage ou non utilisé), vous devez réactiver les condensateurs. Pour connaître la date de fabrication, consultez le numéro de série, qui se trouve sur la plaque signalétique de l'appareil. Le numéro de série est au format MAASSRXXXX, avec AA et SS indiquant respectivement l’année et la semaine de fabrication : AA : SS : 17, 18, 19, … = 2017, 2018, 2019, etc. 01, 02, 03, … = semaine 1, semaine 2, semaine 3, ... 3AUA0000085966 Rév H CN 42 FR – Guide d'installation Pour la procédure de réactivation, cf. document anglais Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629), disponible sur Internet (www.abb.com/drives/documents). Sélection des câbles de puissance Les câbles de puissance doivent être dimensionnés en fonction de la réglementation locale pour supporter le courant nominal indiqué sur la plaque signalétique du variateur. EN DA Le tableau J page 100 indique les sections typiques des câbles de puissance. Reportez-vous au manuel d'installation pour le calcul du dimensionnement. Refroidissement Cf. tableau B page 97 pour les pertes et le débit d'air de refroidissement dans le DE variateur. Sans déclassement, la plage de température de fonctionnement admissible va de -15 à +40 °C. ES FI Protection du variateur et du câble réseau Cf. tableau B page 97. Vérifiez que le temps de manœuvre du fusible est inférieur à FR 0,5 seconde. FR NL PT RU SV Montage mural du variateur Cf. figure A page 97. Vérification de la compatibilité avec les réseaux en régime IT (neutre isolé ou impédant), TT, et en couplage triangle avec mise à la terre asymétrique ou centrale (« high leg delta ») En standard (varistance phase-terre branchée), le variateur peut être raccordé sur un réseau en régime TN-S (mise à la terre symétrique). Autres exécutions : reportezTR vous au manuel d'installation ainsi qu’au document anglais ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions CN (3AUA0000125152). FR – Guide d'installation 43 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = réseau en régime TN-S, B1 = mise à la terre asymétrique, B2 = mise à la terre centrale, C = réseau en régime IT ATTENTION ! Il est interdit de raccorder un variateur équipé du filtre RFI (options +E200 et +E202) sur un réseau non prévu pour cet usage, ce qui peut s’avérer dangereux ou endommager l’appareil. FR FR NL PT ATTENTION ! Il est interdit de raccorder un variateur équipé de la varistance phase-terre sur un réseau non prévu pour cet usage, car cela risque d’endommager le circuit des varistances. Cf. manuel d’installation du variateur. RU SV Nota : Avec l’option +E201, lorsque le variateur est raccordé à un réseau autre que TN-S, retirez les vis EMC AC, EMC DC et VAR si cela n’a pas déjà été effectué en usine. Pour en savoir plus, contactez ABB. Mesurez la résistance d'isolement du câble réseau, du moteur et de son câblage Mesurez la résistance d’isolement du câble réseau avant de le brancher sur le variateur conformément à la réglementation en vigueur. Mesurez la résistance d'isolement du moteur et de son câblage lorsqu'il est sectionné du variateur : cf. figure F page 98. Mesurez la résistance d’isolement du câble moteur entre chaque phase et la terre de protection (PE) avec une tension de mesure de TR CN 44 FR – Guide d'installation 1000 Vc.c. Les valeurs mesurées sur un moteur ABB doivent être supérieures à 100 Mohm (valeur de référence à 25 °C ou 77 °F). Pour la résistance d'isolement des autres moteurs, prière de consulter les consignes du fabricant. Nota : La présence d’humidité à l’intérieur de l’enveloppe du moteur réduit sa résistance d’isolement. Si vous soupçonnez la présence d’humidité, séchez le moteur et recommencez la mesure. Fixation des étiquettes de mise en garde dans votre langue Raccordement des câbles de puissance EN Cf. figures C, D, E et G. Utilisez un câble moteur symétrique blindé. DA 5. Retirez les vis de fixation sur les côtés du capot avant. 6. Démontez le capot en le faisant glisser vers l'avant. DE ES 7. Vous devez fixer une étiquette de mise en garde contre les tensions résiduelles dans votre langue sur le logement de la micro-console. FI 8. Sur la plaque passe-câbles, retirez les passe-câbles en caoutchouc des câbles à raccorder. FR 9. Appareils IP21 : Fixez les connecteurs de câbles (joints à la livraison dans un sachet en plastique) à la plaque passe-câbles. FR 10. Préparez les extrémités des câbles d'alimentation et moteur comme l'illustre la figure. NL 11. Effectuez une reprise de masse sur 360 degrés au niveau des connecteurs (appareils IP21) ou sous les colliers (appareils IP55). PT 12. Raccordez le blindage torsadé du câble réseau à la borne PE. RU 13. Raccordez le conducteur PE du câble réseau à la borne PE supplémentaire. SV 14. Raccordez les blindages torsadés des câbles moteur et de la résistance (si présent) à la borne de terre. TR 15. Raccordez les conducteurs de phase des câbles réseau, moteur et de la résistance. Serrez les vis. CN 16. Montez la platine de mise à la terre des câbles de commande dans le boîtier d'entrée des câbles. 17. Fixez les câbles mécaniquement à l’extérieur du variateur. 18. Mettez à la terre le blindage du câble moteur du côté moteur. Pour minimiser les interférences, effectuez une reprise de masse sur 360 degrés au niveau du passe-câbles ou faites une queue de cochon aussi courte que possible. FR – Guide d'installation 45 Raccordement des câbles de commande Cf. figure H 1. Découpez des trous de diamètre adéquat dans les passe-câbles en caoutchouc pour les glisser sur les câbles. Insérez les câbles dans les trous de la plaque inférieure et fixez-y les passe-câbles. 2. Dénudez les extrémités de câbles et coupez à la longueur adéquate (vous remarquerez que les conducteurs de terre sont plus longs). 3. Effectuez une reprise de masse sur 360° des blindages extérieurs de tous les câbles de commande au niveau du collier de mise à la terre du boîtier d'entrée de câbles. 4. Mettez à la masse des blindages de câbles au niveau du collier de mise à la terre. L'autre extrémité des blindages doit être laissée non connectée ou être reliée à la terre indirectement par le biais d’un condensateur haute fréquence de quelques nanofarads (ex., 3,3 nF/630 V). 5. Raccordez les conducteurs aux bornes correspondantes de la carte de commande. (cf. page 46). 6. Raccordez les modules optionnels, si inclus à la livraison. 7. Remontez le capot avant. Nota : Pour les câbles du bus de terrain, cf. figure I. EN DA DE ES FI FR FR 1. Montez la platine de mise à la terre supplémentaire. 2. Effectuez une reprise de masse sur 360° des blindages externes sous le collier de terre. 3. Percez les ouvertures dans le capot du boîtier d'entrée des câbles pour le passage des câbles. Montez le capot du boîtier d'entrée des câbles. 4. Raccordez le connecteur au module coupleur réseau. Raccordement des signaux d’E/S (préréglages) Le schéma suivant présente les préréglages usine des signaux d’E/S du macroprogramme Usine du programme de commande standard de l'ACS880 NL PT RU SV TR CN 46 FR – Guide d'installation Section des fils : 0,5 … 2,5 mm2 (24…12 AWG) Couples de serrage : 0,5 N·m (5 lbf·in) pour câbles à brins multiples toronnés et monobrin. EN DA DE ES FI FR FR NL PT RU SV TR CN 1) La capacité de charge totale des sorties est de 4,8 W (200 mA / 24 V) moins la puissance consommée par DIO1 et DIO2. Défaut XPOW Entrée alimentation externe 1 +24VI 24 Vc.c., 2 A 2 GND XAI Tension de référence et entrées analogiques 1 +VREF 10 Vc.c., RL 1…10 kohm 2 -VREF -10 Vc.c., RL 1…10 kohm 3 AGND Terre 4 AI1+ Référence vitesse 0(2)…10 V, Ren > 200 kohm 5 AI16 AI2+ Non utilisée par défaut. 0(4)…20 mA, Ren = 100 ohm 7 AI2Sélection courant/tension AI1 par cavalier J1 J1 Sélection courant/tension AI2 par cavalier J2 J2 XAO Sorties analogiques 1 AO1 Vitesse moteur tr/min 0…20mA, RL < 2 AGND 500 ohm 3 AO2 Courant moteur 0…20 mA, RL < 4 AGND 500 ohm XD2D Liaison multivariateurs (D2D) 1 B Liaison multivariateurs 2 A 3 BGND Commutateur de terminaison de la liaison D2D J3 J3 XRO1, XRO2, XRO3 Sorties relais 11 NC Prêt 250 Vc.a. / 30 Vc.c. 12 COM 2A 13 NO 21 NC En marche 250 Vc.a. / 30 Vc.c. 22 COM 2A 23 NO 31 NC Défaut(-1) 250 Vc.a. / 30 Vc.c. 32 COM 2A 33 NO XD24 Verrouillage logique 1 DIIL Validation Marche 2 +24VD +24 Vc.c. 200 mA 1) 3 DICOM Masse entrées logiques 4 +24VD +24 Vc.c. 200 mA 1) 5 DIOGND Masse entrées/sorties logiques J6 Commutateur de sélection de masse XDIO Entrées/sorties logiques 1 DIO1 Sortie : Prêt 2 DIO2 Sortie : En marche XDI Entrées logiques 1 DI1 Arrêt (0) / Démarrage (1) 2 DI2 Avant (0) / Arrière (1) 3 DI3 Réarmement 4 DI4 Sélection accélération & décélération 5 DI5 Vitesse constante 1 (1 = On) 6 DI6 Non utilisée par défaut XSTO Interruption sécurisée du couple STO 1 OUT1 Interruption sécurisée du couple STO. 2 SGND Les deux circuits doivent être fermés pour autoriser le démarrage du 3 IN1 variateur. 4 IN2 X12 Raccordement module de fonctions de sécurité X13 Raccordement micro-console X205 Raccordement unité mémoire IT – Guida rapida all'installazione 47 IT – Guida rapida all'installazione Questa guida illustra brevemente la procedura di installazione del convertitore di frequenza. Per istruzioni più dettagliate, linee guida ingegneristiche, dati tecnici e norme di sicurezza complete, si rimanda al Manuale hardware (www.abb.com/drives: selezionare Document Library e cercare il numero del documento 3AUA0000078093 [inglese]). Rispettare le norme di sicurezza AVVERTENZA! Rispettare le seguenti norme di sicurezza. La mancata osservanza di queste norme può mettere in pericolo l'incolumità delle persone, con rischio di morte, e danneggiare le apparecchiature: • L'installazione e la manutenzione del convertitore di frequenza devono essere eseguite solo da elettricisti qualificati. • Non operare mai sul convertitore, sul cavo motore o sul motore quando è inserita l'alimentazione. Se il convertitore è già collegato all'alimentazione, disinserirla e attendere 5 minuti. IT DA DE ES FI • Non lavorare mai sui cavi di controllo quando il convertitore o i circuiti di controllo esterni sono alimentati. • Mettere sempre a terra il convertitore, il motore e le apparecchiature adiacenti collegandoli al bus di terra (PE) dell'alimentazione. • Assicurarsi che i detriti generati da forature e smerigliature non si infiltrino nell'unità durante l'installazione. IT • Non collegare il convertitore a una tensione superiore al valore indicato sull'etichetta di identificazione dell'unità. PT Il pavimento sottostante all'unità deve essere di materiale non infiammabile. RU Ricondizionamento dei condensatori SV I condensatori devono essere ricondizionati se il convertitore è fermo da oltre un anno (perché è rimasto inutilizzato oppure in magazzino). TR La data di fabbricazione si legge dal numero di serie riportato sull'etichetta identificativa del convertitore. Il formato del numero di serie è MYYWWRXXXX. YY e WW indicano rispettivamente l'anno e la settimana di produzione, nel modo seguente: YY: WW: 17, 18, 19, … per 2017, 2018, 2019, … 01, 02, 03, … per settimana 1, settimana 2, settimana 3, … Per informazioni sul ricondizionamento dei condensatori, vedere Converter Modules with Electrolytic DC Capacitors in the DC Link Capacitor Reforming 3AUA0000085966 Rev H FR IT CN 48 IT – Guida rapida all'installazione Instructions (3BFE64059629 [inglese]), disponibile in Internet al sito www.abb.com/drives/documents. Selezione dei cavi di potenza Dimensionare i cavi di potenza in base alle normative locali. I cavi devono essere adatti a condurre la corrente nominale indicata sull'etichetta identificativa del convertitore. Le dimensioni tipiche dei cavi di potenza sono riportate nella tabella J a pag. 100. Per le regole di dimensionamento, vedere il Manuale hardware. IT Raffreddamento DA Vedere la tabella B a pag. 97 per i dati relativi alle perdite e al flusso d'aria attraverso il convertitore di frequenza. Il range di temperatura operativa del convertitore, senza DE declassamento, è -15 ... +40 °C. ES FI Protezione del convertitore e del cavo di alimentazione di ingresso Vedere la tabella B a pag. 97. Verificare che il tempo di intervento del fusibile sia FR inferiore a 0.5 secondi. IT Montaggio del convertitore di frequenza a parete IT Vedere la figura A a pag. 97. PT RU Verifica della compatibilità con sistemi IT (senza messa a terra), sistemi a triangolo con una fase a terra, a triangolo con messa a terra nel punto mediano e sistemi TT Il convertitore standard, con i varistori fase-terra collegati, può essere installato in un sistema TN-S con messa a terra simmetrica. Per gli altri sistemi, vedere il Manuale hardware e ACS880 Frames R1 to R11 EMC Filter and Ground-to-Phase Varistor TR Disconnecting Instructions (3AUA0000125152 [inglese]). SV CN IT – Guida rapida all'installazione 49 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE IT B2 L1 DA L2 L3 PE DE ES FI A = sistema TN-S, B1 = sistema con una fase a terra, B2 = sistema con messa a terra nel punto mediano, C = sistema IT AVVERTENZA! Non installare il convertitore con il filtro EMC collegato (opzioni +E200 e +E202) in un sistema che non consente l'uso del filtro. Questo può determinare una situazione di pericolo o danneggiare l'unità. FR IT IT PT AVVERTENZA! Non installare il convertitore con il varistore fase-terra collegato in un sistema che non consente l'uso del varistore, poiché così facendo si può danneggiare il circuito del varistore. Vedere il Manuale hardware del convertitore. Nota: con l'opzione +E201, rimuovere le viti EMC AC, EMC DC e VAR per i sistemi di tipo diverso da TN-S, se le viti non sono state rimosse in fabbrica. Per ulteriori informazioni, contattare ABB. Controllo dell'isolamento di cavo di ingresso, motore e cavo motore Verificare che l'isolamento del cavo di ingresso sia conforme alle normative locali prima di collegarlo al convertitore di frequenza. Controllare l'isolamento del cavo motore e del motore quando il cavo è scollegato dal convertitore; vedere la figura F a pag. 98. Misurare la resistenza di isolamento tra RU SV TR CN 50 IT – Guida rapida all'installazione ogni conduttore di fase e il conduttore di protezione di terra (PE) con una tensione di misura di 1000 Vcc. La resistenza di isolamento dei motori ABB deve essere superiore a 100 Mohm (valore di riferimento a 25 °C o 77 °F). Per la resistenza di isolamento di altri motori, consultare le istruzioni del produttore. Nota: la presenza di umidità all'interno dell'alloggiamento del motore riduce la resistenza di isolamento. In caso di umidità, asciugare il motore e ripetere la misurazione. Applicazione degli adesivi di avvertenza nelle lingue locali Collegamento dei cavi di potenza IT Vedere le figure C, D, E e G. Utilizzare un cavo schermato di tipo simmetrico per il motore. DA 5. Svitare le viti di montaggio ai lati del coperchio anteriore. DE 6. Rimuovere il coperchio facendolo scorrere in avanti. 7. Applicare l'adesivo con il messaggio di avvertenza per tensione residua (nella ES lingua locale) sulla piastra di fissaggio del pannello di controllo. FI 8. Rimuovere i gommini dalla piastra passacavi per il passaggio dei cavi che si intendono collegare. FR 9. Unità IP21: applicare i connettori dei cavi (inclusi nella fornitura, all'interno di un sacchetto di plastica) sui fori della piastra passacavi. IT 10. Preparare le estremità del cavo di alimentazione e del cavo motore come illustrato nella figura. IT 11. Mettere a terra a 360° le schermature dei cavi in corrispondenza dei connettori dei cavi (unità IP21) o sotto i morsetti (unità IP55). PT RU 12. Collegare la schermatura intrecciata del cavo di ingresso al morsetto PE. 13. Collegare il conduttore PE del cavo di ingresso al morsetto PE supplementare. SV TR CN 14. Collegare le schermature intrecciate del cavo del motore e del cavo della resistenza (se presente) al morsetto di terra. 15. Collegare i conduttori di fase del cavo di ingresso, del cavo del motore e del cavo della resistenza. Serrare le viti. 16. Installare la piastra di messa a terra dei cavi di controllo nella cassetta di ingresso dei cavi. 17. Fissare i cavi meccanicamente all'esterno del convertitore di frequenza. 18. Mettere a terra la schermatura del cavo del motore sul lato motore. Per ridurre al minimo le interferenze, eseguire una messa a terra a 360° in corrispondenza della piastra passacavi, o ridurre al minimo la lunghezza del fascio intrecciato. IT – Guida rapida all'installazione 51 Collegamento dei cavi di controllo Vedere la figura H. 1. Praticare fori di dimensioni idonee nei gommini e fare scivolare i gommini sui cavi. Inserire i cavi nei fori della piastra inferiore e fissare i gommini ai fori. 2. Spellare le estremità dei cavi e tagliarle a una lunghezza adeguata (tenendo conto della lunghezza extra dei conduttori di terra). 3. Mettere a terra le schermature esterne di tutti i cavi di controllo a 360° sotto un morsetto di terra nella cassetta di ingresso dei cavi. 4. Mettere a terra le schermature dei doppini sotto il morsetto di terra. Lasciare scollegata l'altra estremità delle schermature o metterla a terra indirettamente utilizzando un condensatore ad alta frequenza di pochi nanofarad (es. 3.3 nF / 630 V). 5. Collegare i conduttori ai morsetti corrispondenti della scheda di controllo (vedere pag. 52). 6. Collegare i moduli opzionali, se inclusi nella fornitura. 7. Reinstallare il coperchio anteriore. Nota per il cablaggio del bus di campo. Vedere la figura I. IT DA DE ES FI FR 1. Installare la piastra supplementare di messa a terra. 2. Mettere a terra le schermature esterne dei cavi a 360° in corrispondenza del morsetto di terra. 3. Aprire dei fori nel coperchio della cassetta di ingresso cavi, in corrispondenza dei cavi da installare. Installare il coperchio della cassetta di ingresso cavi. 4. Inserire il connettore nel modulo bus di campo. IT IT PT RU Collegamenti di I/O di default SV Di seguito sono illustrati i collegamenti degli I/O di default della macro Fabbrica del programma di controllo primario dell'ACS880. TR CN 52 IT – Guida rapida all'installazione Dimensioni fili: 0.5 … 2.5 mm2 (24…12 AWG) Coppie di serraggio: 0.5 N·m (5 lbf·in) per cavi intrecciati e pieni. IT DA DE ES FI FR IT 1) La capacità di carico totale di queste uscite PT è 4.8 W (200 mA / RU 24 V) meno la potenza assorbita da SV DIO1 e DIO2. IT TR CN Guasto XPOW Ingresso alimentazione esterna 1 +24VI 24 Vcc, 2 A 2 GND XAI Ingressi analogici e tensione di riferimento 1 +VREF 10 Vcc, RL 1…10 kohm 2 -VREF -10 Vcc, RL 1…10 kohm 3 AGND Terra 4 AI1+ Riferimento velocità 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Di default non utilizzati. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 Ponticello di selezione corrente/tensione AI1 J2 J2 Ponticello di selezione corrente/tensione AI2 XAO Uscite analogiche 1 AO1 Velocità motore rpm 0…20 mA, RL < 500 ohm 2 AGND 3 AO2 Corrente motore 0…20 mA, RL < 500 ohm 4 AGND XD2D Collegamento drive-to-drive 1 B Collegamento drive-to-drive 2 A 3 BGND Interruttore terminazione collegamento drive-to-drive J3 J3 XRO1, XRO2, XRO3 Uscite relè 11 NC Pronto 250 Vca / 30 Vcc 12 COM 2A 13 NO 21 NC In marcia 250 Vca / 30 Vcc 22 COM 2A 23 NO 31 NC Guasto(-1) 250 Vca / 30 Vcc 32 COM 2A 33 NO XD24 Interblocco digitale 1 DIIL Abilitazione marcia 2 +24VD +24 Vcc 200 mA 1) 3 DICOM Terra ingressi digitali 4 +24VD +24 Vcc 200 mA 1) 5 DIOGND Terra ingressi/uscite digitali J6 Interruttore di selezione terra XDIO Ingressi/uscite digitali 1 DIO1 Uscita: pronto 2 DIO2 Uscita: in marcia XDI Ingressi digitali 1 DI1 Arresto (0) / Avviamento (1) 2 DI2 Avanti (0) / Indietro (1) 3 DI3 Reset 4 DI4 Selezione accelerazione e decelerazione 5 DI5 Velocità costante 1 (1 = On) 6 DI6 Di default non utilizzato. XSTO Safe Torque Off 1 OUT1 2 SGND Safe Torque Off. Per avviare il convertitore entrambi i circuiti devono essere chiusi. 3 IN1 4 IN2 X12 Collegamento modulo funzioni di sicurezza X13 Collegamento pannello di controllo X205 Collegamento unità di memoria NL – Beknopte installatiegids 53 NL – Beknopte installatiegids Deze gids geeft een beknopte beschrijving van het installeren van de omvormer. Zie, voor nadere instructies, technische richtlijnen, technische gegevens en complete veiligheidsinstructies, de hardwarehandleiding (www.abb.com/drives: Kies Document Library en zoek document nummer 3AUA0000078093 [Engels]). Volg de veiligheidsvoorschriften WAARSCHUWING! Volg deze instructies. Indien u deze negeert, kan dit lichamelijk letsel of de dood tot gevolg hebben, of er kan schade aan de apparatuur ontstaan: • De installatie en het onderhoud van de omvormer mag uitsluitend worden uitgevoerd door gekwalificeerde elektrotechnische vakmensen. • Voer nooit werkzaamheden uit aan de frequentie-omvormer, de motorkabel of de motor als ze onder spanning staan. Als de omvormer al is aangesloten op het voedingsnet, ontkoppelt u de omvormer en wacht u 5 minuten. • Voer nooit werkzaamheden uit aan de besturingskabels als de omvormer of externe besturingscircuits onder spanning staan. • Aard de omvormer, de motor en bijbehorende apparatuur altijd aan de veiligheidsaarde (PE) -bus van de voeding. EN DA DE ES FI FR IT • Zorg bij de installatie dat er geen boor- of slijpafval in de omvormer binnendringt. NL • Sluit de omvormer niet op een spanning aan die hoger is dan die vermeld is op het typeplaatje. NL Het materiaal van de vloer onder de omvormer dient onbrandbaar te zijn. Controleer of condensatoren opnieuw geformeerd moeten worden Formeer de condensatoren opnieuw als de omvormer een jaar of langer niet aan geweest is (in de opslag of niet gebruikt). U kunt de fabricagedatum bepalen uit het serienummer, dat op het typeplaatje, bevestigd aan de omvormer, te vinden is. Het serienummer heeft het formaat MYYWWRXXXX. YY en WW bepalen als volgt het jaar en de week van fabricage: YY: WW: 17, 18, 19, … voor 2017, 2018, 2019, … 01, 02, 03, … voor week 1, week 2, week 3, … 3AUA0000085966 Rev H RU SV TR CN 54 NL – Beknopte installatiegids Zie, voor informatie over het opnieuw formeren van de condensatoren, Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [Engels]), dat op internet te vinden is op www.abb.com/drives/documents. Kies de vermogenskabels Dimensioneer de vermogenskabels volgens de plaatselijke regelgeving om de nominale stroom te voeren die gegeven is op het typeplaatje van uw omvormer. EN DA Typische vermogenskabel-afmetingen zijn te vinden in tabel J op pagina 100. Zie, voor de voorwaarden van de afmetingen, de hardwarehandleiding. Zorg voor de koeling Zie tabel B op pagina 97 voor de verliezen en de koelluchtstroom door de omvormer. DE Het toegestane bedrijfstemperatuurbereik van de omvormer zonder derating is -15 tot +40 °C. ES FI Beveilig de omvormer en de voedingskabel Zie tabel B op pagina 97. Controleer dat de aanspreektijd van de zekering korter is FR dan 0,5 seconde. IT NL NL Installeer de omvormer aan de wand Zie figuur A op pagina 97. Controleer de compatibiliteit met IT (ongeaarde), cornergrounded delta, midpoint-grounded delta, en TT systemen RU De standaard omvormer met aangesloten aarde-naar-fase varistors kan geïnstalleerd worden in een symmetrisch geaard TN-S systeem. Zie voor andere SV systemen de hardwarehandleiding en ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [Engels]). TR CN NL – Beknopte installatiegids 55 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = TN-S systeem, B1 = Corner-grounded systeem, B2 = Midpoint-grounded systeem, C = IT systeem WAARSCHUWING! Installeer de omvormer niet met aangesloten EMC-filter opties +E200 en +E202 in een systeem waarvoor het filter niet geschikt is. Dit kan gevaar opleveren of de omvormer beschadigen. WAARSCHUWING! Installeer de omvormer niet met aangesloten aarde-naarfase varistor in een systeem waarvoor de varistor niet geschikt is. Indien u dit wel doet, kan het varistor-circuit beschadigd worden. Zie de hardwarehandleiding van de omvormer. Opmerking: Verwijder bij optie +E201 de EMC AC, EMC DC en VAR schroeven voor andere systemen dan TN-S systemen indien ze nog niet in de fabriek verwijderd zijn. Neem voor meer informatie contact op met ABB. Controleer de isolatie van de ingangs- en motorkabels en van de motor Controleer de isolatie van de ingangskabel volgens plaatselijke regelgeving alvorens u deze aansluit op de omvormer. Controleer de isolatie van de motorkabel en motor wanneer de kabel losgekoppeld is van de omvormer, zie figuur F op pagina 98. Meet de isolatieweerstand tussen elke fasegeleider en de veiligheidsaardegeleider door een meetspanning van 1000 V DC FR IT NL NL RU SV TR CN 56 NL – Beknopte installatiegids te gebruiken. De isolatieweerstand van een ABB-motor moet hoger zijn dan 100 Mohm (referentiewaarde bij 25 °C of 77 °F). Voor de isolatieweerstand van andere motors moet u de instructies van de fabrikant raadplegen. Opmerking: Vocht in de motorbehuizing zal de isolatieweerstand verlagen. Als u vocht vermoedt, moet u de motor drogen en de meting herhalen. Bevestig de waarschuwingsstickers in plaatselijke talen Sluit de vermogenskabels aan Zie figuren C, D, E en G. Gebruik symmetrisch afgeschermde kabel voor de EN motorbekabeling. DA 5. Draai de montageschroeven aan de zijkanten van de frontkap los. 6. Verwijder de kap door deze naar voren te schuiven. DE ES 7. Bevestig de waarschuwingssticker tegen restspanning in de plaatselijke taal op het montageplatform voor het bedieningspaneel. FI 8. Verwijder de rubberen doorvoertules van de doorvoerplaat zodat de kabels aangesloten kunnen worden. FR 9. IP21 units: Bevestig de kabelconnectoren (meegeleverd in een plastic zak) in de gaten van de kabeldoorvoerplaat. IT 10. Maak de uiteinden van de voedings- en motorkabels gereed zoals in de figuur geïllustreerd. NL 11. Aard de kabelafschermingen over 360 graden in de kabelconnectoren (IP21 units) of onder de klemmen (IP55 units). NL 12. Sluit de getwiste afscherming van de ingangskabel aan op de PE-klem. RU 13. Sluit de PE-geleider van de ingangskabel aan op de extra PE-klem. SV 14. Sluit de getwiste afscherming van de motorkabel en weerstandskabel (indien aanwezig) aan op de aardingsklem. TR 15. Sluit de fasegeleiders van de ingangs-, motor- en weerstandskabels aan. Draai de schroeven vast. CN 16. Installeer de aardingsplaat voor de besturingskabels in het kabelingangsblok. 17. Zet de kabels buiten de omvormer mechanisch vast. 18. Aard de motorkabelafscherming aan de motorzijde. Maak, om interferentie te minimaliseren, een aarding van 360 graden bij de kabeldoorvoer, of houd de pigtail kort. NL – Beknopte installatiegids 57 Sluit de besturingskabels aan Zie figuur H. 1. Snij voldoende grote gaten in de rubberen doorvoertules en schuif de doorvoertules op de kabels. Schuif de kabels door de gaten van de bodemplaat en maak de doorvoertules in de gaten vast. 2. Strip de kabeluiteinden en snijd deze tot een geschikte lengte (houd rekening met de extra lengte van de aardgeleiders). 3. Aard de buitenste afschermingen van alle besturingskabels over 360 graden aan een aardingsklem in het kabelinvoerblok. 4. Aard de kabelpaar-afschermingen aan de aardklem. Sluit het andere uiteinde van de afschermingen niet aan of aard deze indirect via een hoogfrequente condensator van enkele nanofarad, bijvoorbeeld 3,3 nF / 630 V). 5. Sluit de geleiders op de juiste klemmen van de besturingskaart aan (zie pagina 58). 6. Bedraad de optionele modules indien deze bij de levering bijgevoegd zijn. EN DA DE ES 7. Zet de frontkap terug? Opmerking voor?veldbus-bekabeling. Zie figuur I. 1. Installeer de extra aardingsplaat. 2. Aard de buitenste afscherminen van de kabels over 360 graden bij de aardklem. 3. Druk gaten in het deksel van het kabelingangsblok uit zodat de kabels geïnstalleerd kunnen worden. Installeer het deksel van het kabelingangsblok. 4. Plug de connector in de veldbusmodule. FI FR IT NL NL Standaard I/O aansluitingen RU De standaard I/O-aansluitingen voor de Fabrieksmacro van het ACS880 primair besturingsprogramma worden hieronder getoond. SV TR CN 58 NL – Beknopte installatiegids EN Aderafmetingen: 0,5 … 2,5 mm2 (24…12 AWG) Aanhaalmoment en: 0,5 N·m (5 lbf·in) voor zowel gevlochten als massieve bedrading. DA DE ES FI FR IT NL NL RU SV TR CN 1) Totale belastingscapaciteit van deze uitgangen is 4,8 W (200 mA / 24 V) minus het vermogen opgenomen door DIO1 en DIO2. Fout XPOW Externe hulpspanningsingang 1 +24VI 24 V DC, 2 A 2 GND XAI Referentiespanning en analoge ingangen 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF -10 V DC, RL 1…10 kohm 3 AGND Aarde 4 AI1+ Toerentalreferentie 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Standaard niet in gebruik. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 stroom/spanning selectiejumper J2 J2 AI2 stroom/spanning selectiejumper XAO Analoge uitgangen 1 AO1 Motortoerental rpm 0…20 mA, RL < 2 AGND 500 ohm 3 AO2 Motorstroom 0…20 mA, RL < 500 ohm 4 AGND XD2D Drive-to-drive link 1 B Drive-to-drive link 2 A 3 BGND J3 J3 Afsluitingsjumper drive-to-drive link XRO1, XRO2, XRO3 Relaisuitgangen 11 NC Gereed 250 V AC/30 V DC 12 COM 2A 13 NO 21 NC In bedrijf 250 V AC/30 V DC 22 COM 2A 23 NO 31 NC Fout(-1) 250 V AC/30 V DC 32 COM 2A 33 NO XD24 Digitale blokkering 1 DIIL Runvrijgave 2 +24VD +24 V DC 200 mA 1) 3 DICOM Aarde digitale ingang 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Aarde digitale ingang/uitgang J6 Aarde selectiejumper XDIO Digitale ingang/uitgangen 1 DIO1 Uitgang: Gereed 2 DIO2 Uitgang: In bedrijf XDI Digitale ingangen 1 DI1 Stop (0) / Start (1) 2 DI2 Voorwaarts (0) / Achterwaarts (1) 3 DI3 Reset 4 DI4 Acceleratie & deceleratie keuze 5 DI5 Constant toerental 1 (1 = Aan) 6 DI6 Standaard niet in gebruik. XSTO Safe torque off 1 OUT1 Safe torque off. Beide circuits moeten 2 SGND gesloten zijn voordat de omvormer kan 3 IN1 starten. 4 IN2 X12 Aansluiting veiligheidsfuncties-module X13 Aansluiting bedieningspaneel X205 Aansluiting geheugenunit PL — Skrócona instrukcja montażu 59 PL — Skrócona instrukcja montażu Ten dokument zawiera skróconą instrukcję montażu przemiennika częstotliwości. Bardziej szczegółowe wskazówki, wytyczne i dane techniczne oraz pełne instrukcje bezpieczeństwa zawiera podręcznik użytkownika (www.abb.com/drives: należy wybrać opcję Document Library [Biblioteka dokumentów] oraz wyszukać dokument w języku angielskim o numerze 3AUA0000078093). Należy przestrzegać instrukcji bezpieczeństwa OSTRZEŻENIE! Należy przestrzegać tych instrukcji. Nieprzestrzeganie instrukcji może skutkować obrażeniami, śmiercią lub uszkodzeniem urządzenia: • Do montażu i konserwacji przemiennika częstotliwości uprawnieni są wyłącznie wykwalifikowani elektrycy. • Nie można wykonywać żadnych prac przy przemienniku częstotliwości, kablu silnika ani silniku, jeśli podłączone jest źródło zasilania. Jeśli przemiennik częstotliwości jest już podłączony do zasilania, należy odczekać 5 minut po jego odłączeniu. • Nie wolno nigdy wykonywać żadnych prac przy kablach sterowania, jeśli do przemiennika częstotliwości lub zewnętrznych obwodów sterowania doprowadzone jest zasilanie. • Zawsze uziemić przemiennik częstotliwości, silnik oraz pobliskie urządzenia. do szyny uziemiającej (PE) zasilania. • Podczas montażu należy uważać, aby opiłki powstające w trakcie wiercenia i szlifowania nie przedostały się do wnętrza przemiennika częstotliwości. • Nie można podłączać przemiennika częstotliwości do napięcia wyższego niż podane na tabliczce znamionowej. EN DA DE ES FI FR IT NL PT PL SV Materiał znajdujący się na podłodze pod przemiennikiem częstotliwości musi być niepalny. TR Sprawdzenie, czy kondensatory wymagają formowania CN Jeśli przemiennik częstotliwości nie był włączany od ponad roku (był w magazynie lub nie był używany), należy wykonać formowanie kondensatorów. Datę produkcji można określić na podstawie numeru seryjnego, który jest widoczny na tabliczce znamionowej przymocowanej do przemiennika częstotliwości. Numer seryjny ma format MRRTTRXXXX. RR i TT określają rok i tydzień produkcji w następujący sposób: RR: TT: 17, 18, 19, … oznacza 2017, 2018, 2019, … 01, 02, 03, … to 1. tydzień, 2. tydzień, 3. tydzień, … 3AUA0000085966 wersja H 60 PL — Skrócona instrukcja montażu Więcej informacji na temat formowania kondensatorów zawiera dokument Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [j.ang.]), który jest dostępny na stronie internetowej www.abb.com/drives/documents. Dobór kabli zasilania Kable zasilania należy zwymiarować zgodnie z obowiązującymi przepisami lokalnymi, tak aby zapewnić przepływ prądu znamionowego, którego wartość jest podana na tabliczce znamionowej przemiennika częstotliwości. Typowe rozmiary kabli zasilania wymieniono w tabeli J na stronie 100. Warunki EN dotyczące dobierania rozmiarów można znaleźć w podręczniku oprogramowania przemiennika częstotliwości. DA DE Zapewnianie chłodzenia W tabeli B na stronie 97 zawarto informacje o stratach oraz przepływie powietrza ES chłodzącego przez przemiennik częstotliwości. Dozwolony zakres temperatury pracy przemiennika częstotliwości bez obniżenia jego wartości znamionowych wynosi od FI 15 do +40°C. FR IT Ochrona przemiennika częstotliwości i kabla zasilania wejściowego Odpowiednie informacje zawiera tabela B na stronie 97. Należy upewnić się, że czas NL zadziałania bezpiecznika wynosi mniej niż 0,5 s. PT PL SV Montaż przemiennika częstotliwości na ścianie Patrz rysunek A na stronie 97. Sprawdzanie zgodności z sieciami IT (bez uziemienia), typu trójkąt z uziemieniem wierzchołkowym i centralnym oraz TT TR Standardowy przemiennik częstotliwości z podłączonymi warystorami uziemieniefaza można połączyć z uziemioną symetrycznie siecią TN-S. W przypadku innych CN sieci informacji należy szukać w podręczniku użytkownika i dokumencie ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [j. ang.]). PL — Skrócona instrukcja montażu 61 . A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = sieć TN-S, B1 = sieć uziemiona wierzchołkowo, B2 = sieć uziemiona centralnie, C = sieć IT OSTRZEŻENIE! Nie należy instalować przemiennika częstotliwości z podłączonymi opcjami +E200 i +E202 filtra EMC w sieci, dla której ten filtr jest nieodpowiedni. Może to spowodować zagrożenie lub uszkodzić przemiennik częstotliwości. OSTRZEŻENIE! Nie należy instalować przemiennika częstotliwości z podłączonym warystorem uziemienie-faza w sieci, dla której ten warystor jest nieodpowiedni. Może to uszkodzić obwód warystora. Więcej informacji znajduje się w podręczniku użytkownika przemiennika częstotliwości. Uwaga: W przypadku opcji +E201 należy wykręcić wkręty EMC AC, EMC DC i VAR dla sieci innych niż TN-S (o ile nie zostały wykręcone w fabryce). Więcej informacji na ten temat można uzyskać od firmy ABB. Sprawdzenie izolacji wejściowego kabla zasilania i kabla silnika oraz samego silnika Przed podłączeniem wejściowego kabla zasilania do przemiennika częstotliwości należy sprawdzić, czy jego izolacja jest zgodna z lokalnymi przepisami. Izolację silnika oraz kabla silnika i silnika należy sprawdzić, gdy kabel jest odłączony od przemiennika częstotliwości; patrz rysunek F na stronie 98. Zmierzyć rezystancję izolacji pomiędzy poszczególnymi przewodami fazowymi a przewodem uziomowym FR IT NL PT PL SV TR CN 62 PL — Skrócona instrukcja montażu przy użyciu napięcia pomiarowego 1000 V DC. Rezystancja izolacji silnika ABB musi przekraczać 100 MΩ (wartość zadana przy temperaturze 25 °C lub 77 °F). Wymagania dotyczące rezystancji izolacji innych silników zostały podane w instrukcjach dostarczonych przez producenta. Uwaga: Wilgoć wewnątrz obudowy silnika zmniejsza rezystancję izolacji. Jeśli istnieje prawdopodobieństwo obecności wilgoci, należy wysuszyć silnik i powtórzyć pomiar. Mocowanie nalepek ostrzegawczych w językach lokalnych Podłączanie kabli zasilania EN Patrz rysunki C, D, E i G. W okablowaniu silnika należy używać symetrycznego kabla ekranowanego. DA 5. Odkręcić wkręty montażowe po bokach osłony przedniej. DE 6. Usunąć osłonę, przesuwając ją do przodu. ES 7. Przykleić naklejkę z ostrzeżeniem o napięciu szczątkowym w odpowiednim języku do platformy montażowej panelu sterowania. FI 8. Wyjąć gumowe dławiki z płyty przepustowej w miejscach, w których mają zostać wprowadzone kable. FR 9. Jednostki IP21: Zamocować łączniki kablowe (znajdujące się w torebce foliowej w opakowaniu) w otworach na kable w płycie. IT 10. Przygotować końcówki kabli zasilania oraz silnika w sposób przedstawiony na rysunku. NL PT 11. Uziemić ekrany kabli na całym obwodzie w łącznikach kablowych (jednostki IP21) lub pod zaciskami (jednostki IP55). PL 12. Podłączyć skręcany ekran kabla wejściowego do zacisku ochronnego. SV 13. Podłączyć przewód ochronny kabla wejściowego do dodatkowego zacisku ochronnego. TR 14. Podłączyć skręcony ekran kabla silnika i kabla rezystora (jeśli jest używany) do zacisku uziemienia. CN 15. Podłączyć przewody fazowe kabla wejściowego, kabla silnika i kabla rezystora. Dokręcić wkręty. 16. Zamontować listwę uziomową kabla sterowania w skrzynce kablowej. 17. Zabezpieczyć kable mechanicznie na zewnątrz przemiennika częstotliwości. 18. Uziemić ekran kabla silnika po stronie silnika. W celu ograniczenia zakłóceń należy uziemić ekran na całym obwodzie kabla na przepuście kabla lub postarać się, aby jego końcówka była jak najkrótsza. PL — Skrócona instrukcja montażu 63 Podłączanie kabli sterowania Patrz rysunek H. 1. Wyciąć odpowiednie otwory w gumowych dławikach i nasunąć je na kable. Przeciągnąć kable przez otwory w płycie dolnej i zamocować dławiki w tych otworach. 2. Ściągnąć izolację z końcówek kabli i przyciąć je do odpowiedniej długości (pamiętając o większej długości przewodów uziomowych). 3. Wykonać uziemienia zewnętrznych ekranów wszystkich kabli sterowania na całym obwodzie przy użyciu zacisku uziomowego w skrzynce kablowej. 4. Uziemić ekrany kabli dwużyłowych przy użyciu zacisku uziomowego. Drugi koniec ekranu powinien pozostać niepodłączony lub uziemiony pośrednio przez kondensator wysokoczęstotliwościowy o pojemności kilku nanofaradów, np. 3,3 nF/630 V. 5. Podłączyć przewody do odpowiednich zacisków tablicy rozdzielczej (patrz strona 64). 6. Podłączyć moduły opcjonalne, jeśli są częścią dostawy. EN DA DE ES FI 7. Założyć osłonę przednią. Uwaga dotycząca okablowania magistrali komunikacyjnej. Patrz rysunek I. 1. Zamontować dodatkową listwę uziemiającą. 2. Uziemić obwodowo zewnętrzne ekrany kabli pod zaciskiem uziemiającym. 3. Przygotować w osłonie skrzynki kablowej otwory dla kabli, które będą podłączane. Zainstalować pokrywę skrzynki kablowej. 4. Podłączyć złącze do modułu magistrali komunikacyjnej. FR IT NL PT PL Domyślne połączenia we/wy SV Poniżej przedstawiono domyślne połączenia we/wy makra fabrycznego dla standardowego oprogramowania przemiennika częstotliwości ACS880. TR CN 64 PL — Skrócona instrukcja montażu Rozmiary przewodów: 0.5 … 2,5 mm2 (24…12 AWG) Momenty dokręcania: 0,5 N m dla kabli jedno- i wielożyłowych. EN DA DE ES FI FR IT NL PT PL SV TR CN 1) Całkowita obciążalność tych wyjść wynosi 4,8 W (200 mA / 24 V) minus moc pobierana przez złącza DIO1 i DIO2. Błąd XPOW Wejście zasilania zewnętrznego 1 +24VI 24 V DC, 2 A 2 GND XAI Napięcie odniesienia i wejścia analogowe 1 +VREF 10 V DC, RL 1…10 kΩ 2 -VREF -10 V DC, RL 1…10 kΩ 3 AGND Uziemienie 4 AI1+ Wartość zadana prędkości 0(2)…10 V, Rin > 200 kΩ 5 AI16 AI2+ Domyślnie nieużywane. 0(4)…20 mA, Rin = 100 Ω 7 AI2Zworka wyboru trybu pracy wejścia AI1 (prądowe/napięciowe) J1 J1 Zworka wyboru trybu pracy wejścia AI2 (prądowe/napięciowe) J2 J2 XAO Wyjścia analogowe 1 AO1 Prędkość silnika w obrotach na 2 AGND minutę 0…20mA, RL < 500Ω 3 AO2 Prąd silnika 0…20mA, RL < 500Ω 4 AGND XD2D Łącze drive-to-drive 1 B Łącze drive-to-drive 2 A 3 BGND Przełącznik terminacji łącza drive-to-drive J3 J3 XRO1, XRO2, XRO3 Wyjścia przekaźnikowe 11 NC Stan gotowości 250 V AC / 30 V DC 12 COM 2A 13 NO 21 NC Bieg 250 V AC / 30 V DC 22 COM 2A 23 NO 31 NC Błąd (-1) 250 V AC / 30 V DC 32 COM 2A 33 NO XD24 Blokada cyfrowa 1 DIIL Zezwolenie na bieg 2 +24VD +24 V DC 200 mA1) 3 DICOM Masa wejścia cyfrowego 4 +24VD +24 V DC 200 mA1) 5 DIOGND Masa wejścia/wyjścia cyfrowego J6 Przełącznik wyboru masy XDIO Wejścia/wyjścia cyfrowe 1 DIO1 Wyjście: Stan gotowości 2 DIO2 Wyjście: Bieg XDI Wejścia cyfrowe 1 DI1 Stop (0)/Start (1) 2 DI2 Do przodu (0)/Do tyłu (1) 3 DI3 Reset Wybór czasów przyspieszenia i zwolnienia 4 DI4 5 DI5 Stała prędkość 1 (1 = Wł.) 6 DI6 Domyślnie nieużywane. XSTO Bezpieczne wyłączanie momentu 1 OUT1 Bezpieczne wyłączanie momentu (STO). 2 SGND Oba obwody muszą być zamknięte, aby było możliwe uruchomienie 3 IN1 przemiennika częstotliwości. 4 IN2 X12 Złącze modułu funkcji bezpieczeństwa X13 Złącze panelu sterowania X205 Złącze modułu pamięci PT - Guia rápido de instalação 65 PT - Guia rápido de instalação Este guia contém instruções sobre como instalar o acionamento. Para instruções mais detalhadas, indicações de engenharia, dados técnicos e instruções de segurança completas, consulte o manual de hardware em (www.abb.com/drives: Selecione Document Library e aceda ao documento número 3AUA0000078093 [Inglês]). Cumpra as instruções de segurança AVISO! Cumprir estas instruções. Se ignorar as mesmas, podem ocorrer ferimentos ou morte, ou danos no equipamento: • Apenas profissionais eletricistas qualificados estão autorizados a instalar e a reparar o acionamento. • Nunca trabalhe no acionamento, no cabo do motor ou no motor com a alimentação aplicada. Se o acionamento já estiver ligado à entrada de alimentação, aguarde 5 minutos depois de desligar a alimentação de entrada. • Nunca manipule os cabos de controlo quando a alimentação está aplicada ao acionamento ou aos circuitos de controlo externos. • Ligue sempre o acionamento, o motor e o equipamento circundante ao barramento da terra de proteção (PE) da alimentação de potência. EN DA DE ES FI FR IT • Certifique-se que as poeiras das perfurações não entram no acionamento durante a instalação. NL • Não ligue o acionamento a uma tensão superior à assinalada na etiqueta de designação de tipo. PT O material do piso por baixo do acionamento deve ser não inflamável. Verificar se é necessário reformar os condensadores Deve beneficiar os condensadores se o acionamento não tiver sido ligado (estiver armazenado ou não tiver sido usado) durante um ou mais anos. É possível determinar a data de fabrico a partir do número de série, que se encontra na etiqueta de designação de tipo colada no acionamento. O número de série é do formato MYYWWRXXXX. YY e WW indicam o ano e a semana de fabrico como se segue: YY: WW: 17, 18, 19, … para 2017, 2018, 2019, … 01, 02, 03, … para semana 1, semana 2, semana 3, … 3AUA0000085966 Rev H RU PT TR CN 66 PT - Guia rápido de instalação Para informações sobre a beneficiação de condensadores, consulte Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [Inglês]), disponível na Internet em www.abb.com/drives/documents. Selecionar os cabos de potência Dimensione os cabos de potência de acordo com os regulamentos locais para cumprimento da corrente nominal apresentada na etiqueta de designação tipo do seu acionamento. Os tamanhos típicos do cabo de potência estão listados na tabela J na página 100. EN Sobre as condições de dimensionamento, consulte o manual de hardware. DA Assegurar a refrigeração DE Consulte a tabela B na página 97 sobre as perdas e o fluxo de ar de refrigeração através do acionamento A gama de temperatura de operação permitida para o ES acionamento sem desclassificação é -15 para +40 °C. FI Proteger o acionamento e o cabo de entrada de potência FR Veja a tabela B na página 97. Verifique se o tempo de operação do fusível é inferior a 0.5 segundos. IT Instalar o acionamento na parede NL Veja a figura A na página 97. PT RU Verificar a compatibilidade com sistemas IT (sem ligação à terra), sistemas de redes flutuantes e delta de ponto médio e sistemas TT PT Um acionamento com varístores terra-para-fase ligados pode ser instalado num sistema TN ligado à terra simetricamente. Sobre outros sistemas, consulte o manual TR de hardware e ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [Inglês]). CN PT - Guia rápido de instalação 67 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = Sistemas TN-S, B1 = Sistemas de redes flutuantes, B2 = delta de ponto médio, C = Sistema IT AVISO! Não instale o acionamento com filtro EMC opções +E200 e +E202 ligado a um sistema cujo filtro não seja o adequado. Isto pode ser perigoso ou danificar o acionamento. AVISO! Não instale o acionamento com o varístor terra-para-fase ligado a um sistema cujo varístor não seja o adequado. Se o fizer, o circuito de varístores pode ser danificado. Consulte o manual de hardware do acionamento. Nota: Com a opção +E201, remova os parafusos EMC AC, EMC DC e VAR para sistemas diferentes de TN-S, se não tiverem sido removidos na fábrica. Para mais informações, contacte a ABB. Verificar o isolamento do cabo de entrada e dos cabos do motor Verifique o isolamento do cabo de entrada de acordo com os regulamentos locais antes de o ligar ao acionamento. Verifique o isolamento do cabo do motor e do motor quando o cabo estiver desligado do acionamento, veja a figura F na página 98. Meça a resistência de isolamento entre cada condutor de fase e o condutor de Proteção à Terra usando a tensão de medida de 1000 V CC. A resistência de isolamento de um motor da ABB deve FR IT NL PT RU PT TR CN 68 PT - Guia rápido de instalação exceder 100 Mohm (valor de referência a 25 °C ou 77 °F). Para a resistência do isolamento de outros motores, consulte as instruções do fabricante. Nota: A presença de humidade no interior da caixa do motor reduz a resistência do isolamento. Se suspeitar da presença de humidade, seque o motor e volte a efetuar a medição. Colocar os autocolante de aviso nos idiomas locais Ligar os cabos de alimentação Veja as figuras C, D, E e G. Usar cabo de motor blindado simétrico para a cablagem EN do motor. DA 5. Desaperte os parafusos de montagem nos lados da tampa frontal. 6. Remova a tampa fazendo a mesma deslizar para a frente. DE ES 7. Cole o autocolante de aviso de tensão residual no idioma local à plataforma de contagem da consola de programação. 8. Remova os bucins de borracha da placa guia para os cabos serem ligados. FI FR 9. Unidades IP21: Aperte os conectores de cabo (incluídos na entrega num saco plástico) aos orifícios da placa guia de cabos. IT 10. Prepare as extremidades dos cabos de entrada de potência e do motor como ilustrado na figura. NL 11. Ligue à terra as blindagens de cabo a 360-graus nos conectores de cabo (unidades IP21) ou por baixo dos grampos (unidades IP55). PT 12. Ligue a blindagem entrançada do cabo ao terminal PE. RU 13. Ligue o condutor PE do cabo de entrada ao terminal PE adicional. 14. Ligue as blindagens entrançadas do cabo de entrada e o cabo da resistência (se presente) ao terminal de ligação à terra. PT TR 15. Ligue os condutores de fase dos cabos de entrada, motor e resistência. Aperte os parafusos. CN 16. Instale a prateleira de ligação à terra do cabo de controlo na caixa de entrada de cabos. 17. Fixe mecanicamente os cabos no exterior do acionamento. 18. Ligue à terra a blindagem do cabo do motor no lado do motor. Para interferência mínima, efetue uma ligação à terra a 360 graus na placa guia de cabos, ou mantenha a espiral curta. PT - Guia rápido de instalação 69 Ligar os cabos de controlo Ver a figura H. 1. Faça os furos adequados nos bucins de borracha e faça os mesmos deslizar sobre os cabos. Passe os cabos através dos orifícios da placa inferior e fixe os bucins aos orifícios. 2. Descarne as extremidades do cabo e corte ao comprimento pretendido (considerar o comprimento extra dos condutores de ligação à terra). 3. Ligue à terra as blindagens exteriores de todos os cabos de controlo a 360 graus no grampo de ligação à terra na caixa da entrada de cabo. 4. Ligue à terra as blindagens do par de cabo ao grampo de ligação à terra. Deixe a outra extremidade das blindagens desligadas ou ligue-as à terra indiretamente através de um condensador de alta frequência com alguns nano farads, ex.: 3.3 nF / 630 V. 5. Ligue os condutores aos terminais apropriados da placa de controlo (consulte a página 70). 6. Ligue os módulos opcionais, se incluídos na entrega. EN DA DE ES FI 7. Reinstale a tampa frontal. Nota para cabos de fieldbus: Veja a figura I. FR 1. Instale a prateleira de ligação à terra adicional. IT 2. Ligue à terra as blindagens exteriores dos cabos 360 graus ao grampo de ligação à terra. NL 3. Faça os furos na tampa da caixa de entrada de cabos para os cabos a instalar. Instale a tampa da caixa de entrada de cabos. PT 4. Ligue o conector ao módulo de fieldbus. RU Ligações E/S de fábrica PT As ligações de E/S por defeito da macro Factory do programa de controlo primário do ACS800, são apresentadas abaixo. TR CN 70 PT - Guia rápido de instalação Tamanho cabos: 0.5 … 2.5 mm2 (24…12 AWG) Binários de aperto: 0.5 N·m (5 lbf·in) para cablagem entrançada e rígida. EN DA DE ES FI FR IT NL PT RU PT TR CN 1) A capacidade de carga total destas saídas é 4.8 W (200 mA / 24 V) menos a potência tomada por EDS1 e EDS2. Falha XPOW Entrada de potência externa 1 +24VI 24 V CC, 2 A 2 GND XAI Tensão de referência e entradas analógicas 1 +VREF 10 V CC, RL 1…10 kohm 2 -VREF -10 V CC, RL 1…10 kohm 3 AGND Terra 4 EA1+ Referência de velocidade 0(2)…10 V, Rin > 200 kohm 5 EA16 EA2+ Por defeito não usada. 0(4)…20 mA, Rin = 100 ohm 7 EA2Jumper de seleção de corrente/tensão EA1 J1 J1 Jumper de seleção de corrente/tensão EA2 J2 J2 XAO Saídas analógicas 1 SA1 Rpm velocidade do motor 0…20 mA, 2 AGND RL < 500 ohm 3 SA2 Corrente motor 0…20 mA, RL < 4 AGND 500 ohm XD2D Ligação acionamento-para-acionamento 1 B Ligação acionamento-para-acionamento 2 A 3 BGND Interruptor de ligação de terminação acionamento-para-acionamento J3 J3 XRO1, XRO2, XRO3 Saídas a relé 11 NF Pronto 250 V CA / 30 V CC 12 COM 2A 13 NA 21 NF Operação 250 V CA / 30 V CC 22 COM 2A 23 NA 31 NF Falha (-1) 250 V CA / 30 V CC 32 COM 2A 33 NA XD24 Interlock digital 1 DIIL Permissão func 2 +24VD +24 V CC 200 mA 1) 3 DICOM Terra entrada digital 4 +24VD +24 V CC 200 mA 1) 5 DIOGND Terra entrada/saída digital J6 Interruptor de seleção de terra XDIO Entradas/saídas digitais 1 ESD1 Saída: Pronto 2 ESD2 Saída: Operação XDI Entradas digitais 1 ED1 Parar (0) / Arrancar (1) 2 ED2 Direto (0) / Inverso (1) 3 ED3 Rearme 4 ED4 Seleção aceleração & desaceleração 5 ED5 Velocidade constante 1 (1 = On) 6 ED6 Por defeito não usada. XSTO Binário seguro off 1 OUT1 Binário de segurança off. Ambos os 2 SGND circuitos devem estar fechados para o 3 IN1 acionamento arrancar. 4 IN2 X12 Ligação do módulo de funções de segurança X13 Ligação da consola de programação X205 Ligação da unidade de memória RU — Краткое руководство по монтажу 71 RU — Краткое руководство по монтажу Настоящее руководство содержит краткие инструкции по монтажу привода. Более подробную информацию, технические указания, технические данные и полные инструкции по технике безопасности см. в руководстве по монтажу и вводу в эксплуатацию (www.abb.com/drives: Выберите Document Library и найдите номер документа 3AUA0000078093 (на англ. языке). Следуйте указаниям по технике безопасности ПРЕДУПРЕЖДЕНИЕ! Неукоснительно следуйте данным указаниям. Несоблюдение этих указаний может привести к травмам людей вплоть до летального исхода и стать причиной повреждения оборудования. • • К монтажу и техническому обслуживанию привода допускаются только квалифицированные электрики. EN DA DE Запрещается выполнять какие-либо работы по обслуживанию привода, двигателя или кабеля двигателя при включенном питании. Если на привод подано напряжение питания, подождите по крайней мере 5 минут после отключения напряжения. ES • Запрещается выполнять какие-либо работы с кабелями управления при включенном питании привода или внешних цепей управления. FR • Обязательно выполните заземление привода, электродвигателя и сопряженного оборудования на шину защитного заземления (PE) источника питания. • • Перед тем как приступить к монтажу, следует исключить возможность попадания стружки, мусора и иных посторонних материалов внутрь привода. Запрещается подавать на привод напряжение выше указанного на паспортной табличке. FI IT NL PT RU SV RU Материал пола, на котором устанавливается привод, должен быть негорючим. CN Проверьте, не требуется ли формовка конденсаторов Если на привод не подавалось питание (он находился на хранении или не использовался) в течение одного года или дольше, выполните формовку конденсаторов. Дату изготовления можно определить по серийному номеру, который указан на прикрепленной к приводу паспортной табличке. Серийный номер имеет формат MYYWWRXXXX. YY и WW указывают год и неделю изготовления, а именно: 3AUA0000085966 ред. H 72 RU — Краткое руководство по монтажу YY: WW: 17, 18, 19, … для 2017, 2018, 2019, … 01, 02, 03, … для 1-й недели, 2-й недели, 3-й недели, … Сведения о формовке конденсаторов см. в инструкции Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (код английской версии 3BFE64059629), которую можно загрузить в Интернете на странице www.abb.com/drives/documents. Выберите силовые кабели EN Сечение силовых кабелей следует выбирать в соответствии с местными нормами и величиной номинального тока привода, указанной на его паспортной табличке. Типовые сечения силовых кабелей перечислены в таблице J на стр. 100. DA Конкретные значения сечений приводятся в руководстве по монтажу и вводу в эксплуатацию. DE Обеспечьте надлежащее охлаждение ES Величину потерь и расхода охлаждающего воздуха см. в таблице B на стр. 97. Допустимый диапазон рабочих температур привода, в котором не наблюдается FI снижение рабочих характеристик, составляет от –15 до +40 °C. FR IT Защитите привод и входной силовой кабель от повреждений См. таблицу B на стр. 97. Убедитесь, что время срабатывания предохранителя NL составляет меньше 0,5 секунды. PT Закрепите привод на стене RU См. рис. A на стр. 97. SV RU CN Проверьте совместимость с системами IT (незаземленные сети), системами с заземленной вершиной треугольника, системами с заземленной средней точкой треугольника и системами TT Стандартный привод с подключенными варисторами «земля-фаза» может быть установлен в симметрично заземленной системе TN-S. Сведения о других системах см. в руководстве по монтажу и вводу в эксплуатацию и документе ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (код английской версии 3AUA0000125152). RU — Краткое руководство по монтажу 73 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = система TN-S, B1 = система с заземленной вершиной треугольника, B2 = система с заземленной средней точкой треугольника, C = система IT ПРЕДУПРЕЖДЕНИЕ! Запрещается устанавливать привод с подключенным фильтром ЭМС (дополнительные компоненты +E200 и +E202) в системе, для которой фильтр не предназначен. Такая ситуация представляет угрозу безопасности и может привести к повреждению привода. FR IT NL PT ПРЕДУПРЕЖДЕНИЕ! Запрещается устанавливать привод с подключенным варистором «земля-фаза» в системе, для которой варистор не предназначен. В противном случае возможно повреждение цепи варистора. См. руководство по монтажу и вводу в эксплуатацию привода. RU SV RU Примечание. При использовании дополнительного компонента +E201 удалите винты EMC AC, EMC DC и VAR во всех системах, кроме TN-S, если эти винты не были удалены на заводе. За дополнительными сведениями обращайтесь в корпорацию ABB. CN 74 RU — Краткое руководство по монтажу Проверьте изоляцию питающего кабеля, кабеля двигателя и самого двигателя Перед подключением входного кабеля к приводу проверьте его изоляцию в соответствии с местными правилами. Проверьте изоляцию двигателя и кабеля двигателя, когда кабель отсоединен от привода, см. рис. F на стр. 98. Измерьте сопротивление изоляции между проводниками каждой фазы и проводником защитного заземления, используя контрольное напряжение 1000 В=. Сопротивление изоляции двигателя ABB должно превышать 100 МОм (справочное значение при 25 °C). Сведения о сопротивлении изоляции других двигателей см. в инструкциях изготовителей. EN Примечание. Наличие влаги внутри корпуса двигателя приводит к снижению сопротивления изоляции. Если имеется подозрение о наличии влаги, просушите DA двигатель и повторите измерение. DE ES Прикрепите предупреждающие наклейки на местных языках FI Подключите силовые кабели FR См. рис. C, D, E и G. Для подключения двигателя используйте симметричный экранированный кабель. IT 5. Отверните крепежные винты на боковых сторонах передней крышки. NL PT 6. Удалите крышку, сдвигая ее вперед. 7. Прикрепите наклейку с предупреждением об остаточных напряжениях (на местном языке) на монтажную плату панели управления. 8. Удалите резиновые втулки из проходной пластины для ввода подключаемых кабелей. RU 9. Блоки IP21. Прикрепите кабельные разъемы (входят в комплект поставки, SV находятся в пластиковом пакете) к отверстиям для кабелей в проходной пластине. RU 10. Подготовьте концы входного кабеля и кабеля двигателя как показано на CN рисунке. 11. Выполните круговое заземление экранов кабелей в кабельных разъемах (блоки IP21) или под зажимами (блоки IP55). 12. Подключите скрученный экран кабеля питания к клемме защитного заземления. 13. Подключите провод защитного заземления кабеля питания к дополнительной клемме защитного заземления. 14. Подключите скрученный экран кабеля двигателя и кабеля тормозного резистора (если имеется) к клемме заземления. RU — Краткое руководство по монтажу 75 15. Присоедините фазные проводники кабелей питания, двигателя и тормозного резистора. Затяните винты. 16. Вставьте полку заземления кабелей управления в коробку ввода кабелей. 17. Обеспечьте механическое крепление кабелей вне привода. 18. Заземлите экран кабеля двигателя со стороны двигателя. С целью сведения к минимуму помех выполните заземление по всей окружности на вводе кабеля или оставьте короткий отрезок экрана. Подключите кабели управления См. рис. H. 1. Прорежьте отверстия требуемого размера в резиновых втулках и наденьте втулки на кабели. Пропустите кабели сквозь отверстия в нижней плате и закрепите втулки в отверстиях. 2. Снимите изоляцию с концов жил кабеля и обрежьте жилы до надлежащей длины (обратите внимание на то, что заземляющие провода должны быть длиннее) 3. Заземлите экраны всех кабелей управления по всей окружности при помощи заземляющего зажима во вводной коробке. 4. Присоедините экраны пар кабелей к заземляющему зажиму. Другие концы экранов следует оставить незаземленными или соединить их с землей напрямую через высокочастотный конденсатор емкостью несколько нанофарад, например: 3,3 нФ/630 В. 5. Подсоедините проводники к соответствующим выводам платы управления (см. стр. 76). 6. Подключите дополнительные модули, если они включены в комплект поставки. 7. Установите на место переднюю крышку. EN DA DE ES FI FR IT NL PT RU Обратите внимание на проводку Fieldbus. См. рис. I. SV 1. Установите дополнительную полку заземления. RU 2. Заземлите внешние экраны кабелей по всей окружности (360 градусов) зажимом заземления. CN 3. Вырубите отверстия в крышке коробки ввода для устанавливаемых кабелей. Установите крышку коробки ввода кабелей. 4. Вставьте разъем в модуль Fieldbus. Стандартные подключения входов/выходов На приведенном ниже рисунке показаны стандартные цепи входов/выходов заводских макросов основной программы управления ACS880. 76 RU — Краткое руководство по монтажу XPOW 1 2 XAI 1 2 3 4 5 6 7 J1 J2 XAO 1 2 3 4 XD2D 1 2 3 Сечение проводов: 0,5 … 2,5 мм2 Моменты затяжки: 0,5 Н·м как для многожильного, так и для сплошного провода. EN DA DE ES FI FR IT NL PT RU SV RU CN 1) Общая нагрузочная способность этих выходов составляет 4,8 Вт минус мощность, потребляемая цифровыми входами/ выходами DIO1 и DIO2. Отказ Вход внешнего питания +24VI 24 В=, 2 А GND Опорное напряжение и аналоговые входы +VREF 10 В=, RL 1…10 кОм -VREF -10 В=, RL 1…10 кОм AGND Земля AI1+ Задание скорости 0(2)…10 В, Rin > 200 кОм AI1AI2+ По умолчанию не используется. 0(4)…20 мА, Rin = 100 Ом AI2J1 Перемычка выбора тока/напряжения AI1 J2 Перемычка выбора тока/напряжения AI2 Аналоговые выходы AO1 Скорость двигателя, об/мин AGND 0…20 мА, RL < 500 Ом AO2 Ток двигателя 0…20 мА, RL < 500 Ом AGND Линия связи привод-привод B Линия связи привод-привод A BGND Выключатель оконечной нагрузки J3 J3 линии связи привод-привод XRO1, XRO2, XRO3 Релейные выходы 11 NC Готов 250 В~ / 30 В= 12 COM 2А 13 NO 21 NC В работе 250 В~ / 30 В= 22 COM 2А 23 NO 31 NC Отказ (-1) 250 В~ / 30 В= 32 COM 2А 33 NO XD24 Цифровая взаимная блокировка 1 DIIL Разрешение работы 2 +24VD +24 В=, 200 мА 1) 3 DICOM Земля цифровых входов 4 +24VD +24 В=, 200 мА 1) 5 DIOGND Земля цифровых входов/выходов J6 Переключатель выбора заземления XDIO Цифровые входы/выходы 1 DIO1 Выход: Готов 2 DIO2 Выход: В работе XDI Цифровые входы 1 DI1 Останов (0) / Пуск (1) 2 DI2 Вперед (0) / Назад (1) 3 DI3 Сброс 4 DI4 Выбор разгона и замедления 5 DI5 Фиксированная скорость 1 (1 = вкл) 6 DI6 По умолчанию не используется. XSTO Безопасное отключение крутящего момента 1 OUT1 Функция безопасного отключения 2 SGND крутящего момента. Для пуска привода необходимо замкнуть обе 3 IN1 цепи. 4 IN2 X12 Подключение модуля функций защиты X13 Подключение панели управления X205 Подключение блока памяти SV – Snabbguide för installation 77 SV – Snabbguide för installation Denna guide beskriver i korthet hur frekvensomriktaren installeras. För mera detaljerade instruktioner, konstruktionsriktlinjer, tekniska data och fullständiga säkerhetsinstruktioner, se hårdvaruhandledning (www.abb.com/drives: Välj Dokumentbibliotek och sök efter dokumentnummer 3AUA0000078093 [engelska]). Följ säkerhetsinstruktionerna VARNING! Följ dessa instruktioner. Om instruktionerna inte följs kan det orsaka personskador eller dödsfall eller skador på utrustningen: • Endast kvalificerad elektriker får installera och underhålla frekvensomriktaren. • Arbeta aldrig med frekvensomriktaren, motorkabeln eller motorn när nätspänning är ansluten. Om frekvensomriktaren är ansluten till matningsspänning, vänta 5 minuter efter att den har frånskilts. • Arbeta aldrig med styrkablarna om frekvensomriktaren eller dess externa styrkretsar är spänningssatta. • Jorda alltid frekvensomriktaren, motorn och ansluten utrustning till strömförsörjningens skyddsjordledare (PE). EN DA DE ES FI FR • Var noga med att inga borr- eller slipspån kommer in i frekvensomriktaren i samband med installationen. IT • Anslut inte frekvensomriktaren till en spänning som är högre än angivelsen på märkskylten. NL Golvet/ytan under frekvensomriktaren måste vara av icke brännbart material. Kontrollera om kondensatorerna måste reformeras PT RU SV Reformera kondensatorerna om frekvensomriktaren har förvarats i mer än ett år. Tillverkningsdatumet kan fastställas med serienumren som finns på märkskylten på frekvensomriktaren. Serienumret är i formatet MÅÅVVRXXXX. ÅÅ och VV visar tillverkningsår och -vecka enligt följande: ÅÅ: VV: 17, 18, 19, … för 2017, 2018, 2019, … 01, 02, 03, … för vecka 1, vecka 2, vecka 3, … För information om reformering av kondensatorer, se Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [engelska]), på Internet på www.abb.com/drives/documents. 3AUA0000085966 Rev H TR SV 78 SV – Snabbguide för installation Val av kraftkablar Dimensionera kraftkablarna enligt lokala föreskrifter och den märkström som anges på frekvensomriktarens märkskylt. Typiska kraftkabeldimensioner anges i tabellen J på sidan 100. För förhållanden för dimensionering, se hårdvaruhandledningen. Kontrollera att kylningen är tillfredsställande EN DA Se tabell B på sidan 97 för information om förlusteffekt och kylluftflöde genom frekvensomriktaren. Tillåtet driftstemperaturområde för frekvensomriktaren utan nedstämpling är -15 till +40°C. Skydd för frekvensomriktaren och matningskabeln Se tabell B på sid 97. Kontrollera att säkringens utlösningstid understiger 0,5 sekunDE der. ES Installera frekvensomriktaren på vägg FI Se figur A på sidan 97. FR IT Kontrollera kompatibilitet med IT-system (ickedirektjordade system), hörnjordade deltasystem, mittpunktjordade deltasystem och TT-system NL Standardfrekvensomriktare med jord till fas-varistorer anslutnga kan installeras i ett symmetriskt jordat TN-S-system. För övriga system, se hårdvaruhandledningen och PT ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [engelska]). RU SV TR SV SV – Snabbguide för installation 79 . A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = TN-S-system, B1 = hörnjordade system, B2 = mittpunktsjordade system, C = IT-system VARNING! Installera inte frekvensomriktaren med EMC-filtret tillval +E200 och +E202 anslutet till ett system som filtret inte passar till. Detta kan orsaka fara eller skada frekvensomriktaren. VARNING! Installera inte frekvensomriktaren med jord till fas-varistorn ansluten till ett system som varistorn inte passar till. I så fall kan varistorkretsen skadas. Se frekvensomriktarens hårdvaruhandledning. Obs! Med tillval +E201, ta bort EMC AC-, EMC DC- och VAR-skruvarna för andra system än TN-S om de inte borttagna från fabrik. För ytterligare information, kontakta ABB. Kontrollera isolationen hos nätkabel, motor och motorkabel Kontrollera ingångskabelns isolation enligt lokala föreskrifter innan du ansluter den till frekvensomriktaren. Kontrollera isolationen hos motorkabel och motor när kabeln är frånkopplad frånfrekvensomriktaren, se figur F på sidan 98. Mät isolationsresistansen mellan varje fas och skyddsjordledare med en mätspänning på 1000 V DC. Isolationsresistansen hos en ABB-motor måste överskrida 100 Mohm (referensvärde vid 25 °C). För isolations- FR IT NL PT RU SV TR SV 80 SV – Snabbguide för installation resistans hos andra motorer, se respektive tillverkares instruktioner. Obs! Fukt inuti motorkapslingen minskar isolationsresistansen. Om fukt misstänks, torka motorn och upprepa mätningen. Sätt fast varningsetiketten på det lokala språket Anslut matningskablarna Se figurerna C, D, E och G. Använd symmetrisk skärmad kabel för motoranslutning. 5. Lossa fästskruvarna på sidorna av frontkåpan. EN 6. Ta av kåpan genom att dra den framåt. 7. Sätt en varningsetikett på lokalt språk på manöverpanelens monteringsplatta. DA 8. Ta bort gummikragarna från genomföringsplåten för kablar som ska anslutas. DE 9. IP21-enheter: Montera kabelförskruvningarna (medföljer leveransen i en plastpåse) vidi kabelingångslådans hål. ES 10. Förbered de inkommande ändarna av matnings- och motorkablarna så som illustreras i figuren. FI 11. Jorda ledarskärmarna 360° runtom i genomföringarna (IP21-enheterna) eller runtom under jordningsöverfallet (IP55-enheter). FR IT 12. Anslut den tvinnade skärmen för ingångskabeln till jordplinten. NL 13. Anslut ledaren för skyddsjord för den inkommande kabeln till den extra jordplinten. PT 14. Anslut den tvinnade skärmen för motorkabeln och motståndskabeln (i förkommande fall) till jordplinten. RU 15. Anslut fasledarna för ingångs-, motor- och motståndskablarna. Dra åt skruvarna. SV 16. Montera styrkablarnas jordningsskena i kabelingångslådan. 17. Fixera kablarna mekaniskt utanför enheten. TR 18. Jorda motorkabelskärmen vid motoränden. För att minimera störningarna, gör en 360° runtomgående jordning vid skåpgenomföringen, eller håll skärmstumpen SV kort. SV – Snabbguide för installation 81 Anslut styrkablarna Se figur H. 1. Skär lämpliga hål i gummikragarna i kabelingångslådans underdel och skjut upp kragarna på kablarna. För kablarna genom hålen i bottenplattan och fäst kragarna i hålen. 2. Skala ledarändarna och kapa ledarna till lämplig längd. Observera att jordledarna behöver vara något längre. 3. Jorda alla yttre skärmar på styrkablar 360° runtom vid en jordklämma i kabelingångslådan. 4. Anslut ledarparens skärmar till jordklämman. Lämna skärmarnas motsatta ändar oanslutna, eller jorda dem indirekt via en högfrekvenskondensator på några få nanofarad, t.ex. 3,3 nF/630 V). 5. Anslut ledarna till respektive plintar på styrkortet (se sid 82). 6. Anslut tillvalsmodulerna om de har medföljt leveransen. EN DA DE ES 7. Sätt tillbaka frontkåpan. Not för fältbusskablar: Se figur I. 1. Montera den extra jordningsplåten. 2. Jorda den yttre kabelskärmen 360 grader vid jordningsklämman. 3. Öppna de förberedda hålen i kabelingångslådan för kablarna som ska installeras. Installera kabelingångslådan. 4. Anslut kontaktdonet till fältbussmodulen. FI FR IT NL PT Förvalda I/O-anslutningar RU De förvalda I/O-anslutningarna för makrot FABRIK i ACS880 standardprogramvara visas nedan. SV TR SV 82 SV – Snabbguide för installation Ledardimensioner: 0,5 … 2,5 mm2 (24…12 AWG) åtdragningsmoment: 0,5 Nm för både mångtrådiga och enkelledare. EN DA DE ES FI FR IT NL PT RU SV TR SV 1) Total belastningskapacitet för dessa utgångar är 4,8 W (200 mA / 24 V) minus den effekt som krävs av DIO1 och DIO2. Fel XPOW Extern matning 1 +24VI 24 V DC, 2 A 2 GND XAI Referensspänning och analoga ingångar 1 +VREF 10 V DC, RL 1…10 kohm 2 -VREF -10 V DC, RL 1…10 kohm 3 AGND Jord 4 AI1+ Varvtalsreferens 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Används normalt ej. 0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 ström/spänning, valbygel J2 J2 AI2 ström/spänning, valbygel XAO Analoga utgångar 1 AO1 Motorvarvtal 0…20 mA, RL < 500 ohm 2 AGND 3 AO2 Motorström 0…20 mA, RL < 500 ohm 4 AGND XD2D Drift till drift-buss 1 B Drift till drift-buss 2 A 3 BGND J3 J3 Bygel för terminering av drift till drift-buss XRO1, XRO2, XRO3 Reläutgångar 11 NC Driftklar 250 V AC/30 V DC 12 COM 2A 13 NO 21 NC Drift 250 V AC/30 V DC 22 COM 2A 23 NO 31 NC Fel (-1) 250 V AC/30 V DC 32 COM 2A 33 NO XD24 Digital förregling 1 DIIL Driftfrigivning 2 +24VD +24 V DC 200 mA 1) 3 DICOM Jord för digitala ingångar 4 +24VD +24 V DC 200 mA 1) 5 DIOGND Jord för digitala in-/utgångar J6 Omkopplare för val av jord XDIO Digitala in-/utgångar 1 DIO1 Utgång: Driftklar 2 DIO2 Utgång: Drift XDI Digitala ingångar 1 DI1 Stopp (0)/Start (1) 2 DI2 Fram (0)/Back (1) 3 DI3 Felåterställning 4 DI4 Val av accelerations-/retardationsramp 5 DI5 Konstant varvtal 1 (1 = På) 6 DI6 Används normalt ej. XSTO Safe torque off 1 OUT1 Safe torque off. Båda kretsarna måste 2 SGND vara slutna för att frekvensomriktaren 3 IN1 skall starta. 4 IN2 X12 Anslutning för säkerhetsfunktionsmodul X13 Anslutning för manöverpanel X205 Anslutning för minnesenhet TR – Hızlı montaj kılavuzu 83 TR – Hızlı montaj kılavuzu Bu kılavuz sürücüyü nasıl kuracağınız hakkında kısa talimatlar verir. Daha ayrıntılı talimatlar, mühendislik kılavuzları, teknik veriler ve eksiksiz güvenlik talimatları için lütfen donanım kılavuzuna bakın (www.abb.com/drives: Document Library (Belge Kütüphanesi)'ni seçin ve 3AUA0000078093 [İngilizce] numaralı belgeyi arayın). Güvenlik talimatlarına uyun UYARI! Bu talimatlara uyun. Bunlara uymamanız halinde ölüm ya da yaralanma söz konusu olabilir veya ekipman zarar görebilir. • Sürücünün kurulumu ve bakımı sadece yetkili elektrik uzmanları tarafından yapılmalıdır. • Enerji verildiğinde sürücü, motor kablosu ve motor üzerinde hiçbir işlem yapmayın. Sürücü zaten giriş gücüne bağlıysa giriş gücü bağlantısını kestikten sonra 5 dakika bekleyin. • Sürücü veya harici kontrol devrelerine enerji verilirken kontrol kabloları üzerinde asla çalışma yapmayın. • Sürücüyü, motoru ve bitişik ekipmanları her zaman güç kaynağının koruyucu topraklama (PE) barasına topraklayın. • Delme ve taşlama kalıntılarının kurulum sırasında sürücü içine girmemesine dikkat edin. • Sürücüyü tip tanımlama etiketinde belirtilenden daha yüksek bir gerilime bağlamayın. Sürücünün altındaki zemin malzemesi yanmaz nitelikte olmalıdır. Kondansatörlerin yenilenmesinin gerekip gerekmediğini kontrol edin TR DA DE ES FI FR IT NL PT RU SV Sürücüye bir yıl veya daha uzun süre güç verilmemişse (sürücü depolanmışsa veya kullanılmıyorsa) kondansatörler yenilenmelidir. TR Üretim tarihini, sürücünün üzerindeki tip tanımlama etiketinde bulabileceğiniz seri numarasından belirleyebilirsiniz. Seri numarası MYYWWRXXXX biçimindedir. YY ile WW üretim yılını ve haftasını gösterir. CN YY: WW: 2017, 2018, 2019, … için 17, 18, 19, … hafta 1, hafta 2, hafta 3, … için 01, 02, 03, … Kondansatörlerin yenilenmesi ile ilgili bilgi için, bkz. Converter modules with electrolytic DC capacitors in the DC link capacitor reforming instructions (3BFE64059629 [İngilizce]), İnternet'te www.abb.com/drives/documents adresinde bulunmaktadır. 3AUA0000085966 Rev H TR 84 TR – Hızlı montaj kılavuzu Güç kablolarını seçin Sürücünüzün tip belirleme etiketinde verilen nominal akımı taşımak için güç kablolarını yerel yönetmeliklere uygun olarak boyutlandırın. Tipik güç kablosu boyutları sayfa 100‘da J tablosunda listelenmiştir. Boyutlandırma ilgili koşullar için lütfen donanım kılavuzuna bakın. Soğutmayı sağlayın Kayıplar ve sürücünün içinden geçen soğutma hava akışı için bkz. tablo B sayfa 97. Değer kaybı olmadan sürücünün izin verilen işletim sıcaklığı aralığı -15 ile +40°C TR arasındadır. DA Sürücüyü ve giriş güç kablosunu koruyun DE Bkz. tablo B, sayfa 97. Sigortaların çalışma süresinin 0,5 saniyenin altında olduğundan emin olun. ES FI FR IT Sürücüyü duvara monte edin Bkz. şekil A, sayfa 97. IT (topraklamasız), köşe topraklamalı delta, orta nokta topraklamalı delta ve TT sistemlerle uyumluluğu kontrol edin NL Toprak-faz varistörü bağlı olan standart sürücü, simetrik topraklamalı bir TN-S sistemine takılabilir. Diğer sistemler için bkz. donanım kılavuzu ve ACS880 frames R1 PT to R11 EMC filter and ground-to-phase varistor disconnecting instructions (3AUA0000125152 [İngilizce]) RU SV TR CN TR TR – Hızlı montaj kılavuzu 85 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE TR B2 L1 DA L2 L3 PE DE ES FI A = TN-S sistemi, B1 = Köşe topraklamalı sistem, B2 = Orta nokta topraklamalı sistem, C = IT sistemi UYARI! EMC filtresi opsiyonları +E200 ve +E202 bağlı olan bir sürücüyü filtrenin uygun olmadığı bir sisteme monte etmeyin. Bu, tehlikeye veya sürücüde hasara neden olabilir. FR IT NL UYARI! Toprak-faz varistörü bağlı olan bir sürücüyü varistörün uygun olmadığı bir sisteme monte etmeyin. Aksi halde, varistör devresi hasar görebilir. Sürücü donanım kılavuzuna bakın. PT Not: +E201 opsiyonunda, TN-S dışındaki sistemlerde bulunan EMC AC, EMC DC ve VAR vidalarını fabrikada sökülmemişlerse sökün. Daha fazla bilgi için, ABB ile irtibata geçin. SV Giriş ve motor kabloları ile motorun yalıtımını kontrol edin Sürücüye bağlamadan önce yerel yasalara uygun olarak giriş kablosunun yalıtımını kontrol edin. Motor kablosu sürücüden ayrılmış durumdayken, motor kablosu ve motorun yalıtımını kontrol edin, bkz. şekil F, sayfa 98. 1000 VDC ölçüm gerilimi kullanarak her bir faz iletkeni ile motor Koruyucu Topraklama iletkeni arasındaki yalıtım direncini ölçün. ABB motorunun yalıtım direnci 100 Mohm'u geçmelidir (referans değer, 25°C veya 77°F'de). Diğer motorların yalıtım direnci için, lütfen üreticinin talimatlarına başvurun. Not: Motor muhafazası içindeki nem yalıtım direncini düşürecektir. Nemden şüphe edilirse motoru kurutun ve ölçümü tekrarlayın. RU TR CN TR 86 TR – Hızlı montaj kılavuzu Yerel dillerdeki uyarı etiketlerini yapıştırın Güç kablolarını bağlayın Bkz. şekil C, D, E ve G. Motor kablosu için simetrik blendajlı kablo kullanın. 5. Ön kapağın yanlarındaki montaj vidalarını sökün. 6. Öne doğru kaydırarak kapağı çıkarın. 7. Lokal dildeki kaçak gerilim uyarı etiketini kontrol paneli montaj kitine yapıştırın. 8. Kabloların bağlanması için lastik rondelaları geçiş plakasından çıkarın. TR DA 9. IP21 kasaları: Kablo konektörlerini (bir plastik torbanın içinde teslimata dahildir) kablo geçiş plakası deliklerine sabitleyin. 10. Giriş gücü ve motor kablolarının uçlarını şekilde gösterildiği gibi hazırlayın. DE ES 11. Kablo blendajlarını kablo konektörlerinde (IP21 üniteler) ya da kelepçelerin (IP55 üniteler) altında 360 derece topraklayın. 12. Giriş kablosunun bükümlü blendajını PE terminaline bağlayın. FI 13. Giriş kablosunun PE iletkenini ek PE terminaline bağlayın. FR 14. Motor kablosu ve direnç kablosunun (eğer varsa) bükümlü blendajını topraklama terminaline bağlayın. IT 15. Giriş, motor ve direnç kablolarının faz iletkenlerini bağlayın. Vidaları sıkın. NL 16. Kontrol kablosu topraklama rafını kablo giriş kutusuna takın. PT 17. Sürücünün dışında yer alan kabloları mekanik olarak sabitleyin. RU 18. Motor kablo blendajını motor tarafında topraklayın. Mümkün olan en az parazit için, kablo geçişinde 360 derece topraklama yapın veya saç örgüsünü kısa tutun. SV Kontrol kablolarını bağlayın TR Bkz. şekil H. CN TR 1. Lastik rondelaların içine yeterince delik açın ve rondelaları kabloların üstüne kaydırın. Kabloları, alt plaka deliklerinin içine kaydırın ve rondelaları deliklere takın. 2. Kablo uçlarını soyun ve uygun uzunlukta kesin (topraklama iletkenlerinin ilave uzunluğuna dikkat edin). 3. Tüm kontrol kablolarının dış blendajlarını kablo giriş kutusundaki bir topraklama kelepçesine 360 derece topraklayın. TR – Hızlı montaj kılavuzu 87 4. Çift kablo koruyucularını topraklama kelepçesine topraklayın. Blendajların diğer ucunu boşta bırakın veya birkaç nanofarad yüksek frekanslı kondansatör üzerinden dolaylı olarak topraklayın; ör. 3,3 nF / 630 V. 5. İletkenleri kontrol panelinin ilgili terminallerine bağlayın (bkz. sayfa 88). 6. Teslimata dahil olmaları halinde opsiyonel modüllerin kablolarını bağlayın. 7. Ön kapağı tekrar takın. Haberleşme kabloları için not: Bkz. şekil I. 1. İlave topraklama rafını takın. 2. Dış kabloların blendajlarını bir topraklama kelepçesinde 360 derece topraklayın. TR 3. Takılacak kablolar için kablo giriş kutusu kapağında delikler açın. Kablo giriş kutusu kapağını takın. DA 4. Konektörü haberleşme modülüne takın. DE Varsayılan I/O bağlantıları ES ACS880 birincil kontrol programı Fabrika makrosunun varsayılan G/Ç bağlantıları aşağıda gösterilmiştir. FI FR IT NL PT RU SV TR CN TR 88 TR – Hızlı montaj kılavuzu Kablo boyutları: 0,5 … 2,5 mm2 (24…12 AWG) Sıkma torkları: Hem telli hem som kablo için 0,5 N·m (5lbf·in). TR DA DE ES FI FR IT NL PT RU SV TR CN TR 1) Bu çıkışların toplam yük kapasitesi 4,8 W (200 mA / 24 V) eksi DIO1 ve DIO2 tarafından alınan güçtür. Hata XPOW Harici güç girişi 1 +24VI 24 VDC, 2 A 2 GND XAI Referans gerilimi ve analog girişler 1 +VREF 10 VDC, RL 1…10 kohm 2 -VREF -10 VDC, RL 1…10 kohm 3 AGND Topraklama 4 AI1+ Hız referansı 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ Varsayılan olarak kullanımda değildir. 0(4)…20 mA, Rin > 100 ohm 7 AI2J1 J1 AI1 akım/gerilim seçim jumper'ı J2 J2 AI2 akım/gerilim seçim jumper'ı XAO Analog çıkışlar 1 AO1 Motor hızı rpm 0…20 mA, RL < 2 AGND 500 ohm 3 AO2 Motor akımı 0…20 mA, RL < 500 ohm 4 AGND XD2D Sürücü - sürücü bağlantısı 1 B Sürücü - sürücü bağlantısı 2 A 3 BGND Sürücü - sürücü bağlantısı sonlandırma anahtarı J3 J3 XRO1, XRO2, XRO3 Röle çıkışları 11 NC Hazır 250 VAC/30 VDC 12 COM 2A 13 NO 21 NC Çalışıyor 250 VAC/30 VDC 22 COM 2A 23 NO 31 NC Hatalı(-1) 250 VAC/30 VDC 32 COM 2A 33 NO XD24 Dijital kilit 1 DIIL Çalışma izni 2 +24 VD +24 VDC 200 mA 1) 3 DICOM Dijital giriş toprak hattı 4 +24 VD +24 VDC 200 mA 1) 5 DIOGND Dijital giriş/çıkış toprak hattı J6 Toprak seçim anahtarı XDIO Dijital giriş/çıkışlar 1 DIO1 Çıkış: Hazır 2 DIO2 Çıkış: Çalışıyor XDI Dijital girişler 1 DI1 Stop (0) / Start (1) 2 DI2 İleri (0) / Geri (1) 3 DI3 Reset 4 DI4 Hızlanma ve yavaşlama seçimi 5 DI5 Sabit hız 1 (1 = Açık) 6 DI6 Varsayılan olarak kullanımda değildir. XSTO Güvenli moment kapatma 1 OUT1 Güvenli moment kapatma. Sürücünün 2 SGND başlaması için her iki devre 3 IN1 kapatılmalıdır. 4 IN2 X12 Güvenlik fonksiyonları modülü bağlantısı X13 Kontrol paneli bağlantısı X205 Hafıza kartı bağlantısı 中文 – 快速安装指南 89 中文 – 快速安装指南 本指南简要介绍如何安装变频器。更多详细说明、工程指导、技术数据和完整安全说 明,请参阅硬件手册(www.abb.com/drives:选择文件库并搜索文件编号 3AUA0000078093 [英文])。 遵循安全指导 警告!请遵循这些指导。如果忽略这些指导,可能会导致受伤、死亡或设备 损坏: • 仅允许由具备资质的专业电工对变频器进行安装和维护。 EN • 当接上主电源时,切勿对变频器、电机电缆或电机进行操作。如果变频器已经 连接到了输入电源,请在断开输入电源等待 5 分钟后,再对变频器、电机电缆 或电机进行操作。 DA • 当变频器或外部控制电路连接了电源时,切勿触碰控制电缆。 • 请务必将变频器、电机和相邻设备接到电源的保护接地网 (PE) 上。 • 在安装时,确保不让钻孔和研磨产生的碎屑进入变频器。 • 切勿将变频器连接到带有高于型号标签上所标电压数值的电源。 DE ES FI FR IT 变频器下方的地板材料应阻燃。 NL 检查电容是否需要重整 如果变频器超过一年或以上未通电(储存或闲置),则电容需要重整。 PT 您可以从序列号来确定生产日期,序列号可以在变频器所贴的型号标签上找到。序列 号的格式为 MYYWWRXXXX。YY 和 WW 以如下方式说明生产年份和周次: RU YY: WW: SV 17、18、19、…分别代表 2017 年、2018 年、2019 年、… 01、02、03、…分别代表第 1 周、第 2 周、第 3 周、… 有关电容重整的信息,请参阅互联网上的 直流链路电容重整说明中的带直流电解电 容的变频器模块) (3BFE64059629 [英语]),网址: www.abb.com/drives/documents。 TR CN CN 选择电缆 应根据当地规范选择能承载变频器型号标签上标称电流的电缆规格。 请查阅第 100 页上的表 J:典型的电力电缆尺寸,请参阅硬件手册。 3AUA0000085966 修订版 H ZH 90 中文 – 快速安装指南 确保冷却 请参阅第 97 页上的表 B 了解传动损耗和冷却空气流量。在不降低定额值的情况下, 传动的允许工作温度范围为 -15 到 +40 °C。 保护变频器和输入电缆 请参阅第 97 页表 B。检查熔断器的运作时间是否在 0.5 秒以下。 在墙上安装变频器 EN DA 请参阅第 97 页的图 A 。 检查与 IT(不接地)系统、角接地三角形系统、中点接地三角 形系统和 TT 系统的兼容性。 DE 带有相线对地压敏电阻的标准变频器可被安装至对称接地的 TN-S 系统。对于其他系 统,请参阅硬件手册和 ACS880 外型尺寸 R1 -R11 EMC 滤波器和压敏电阻断开说明 ES (3AUA0000125152 [英语])。 FI FR IT NL PT RU SV TR CN CN ZH 中文 – 快速安装指南 91 A B1 L1 C L1 L2 L1 L2 L3 L3 N L2 L3 PE PE EN B2 L1 DA L2 L3 PE DE ES FI A = TN-S 系统,B1 = 角接地系统,B2 = 中点接地系统,C = IT 系统。 警告!勿将带有 EMC 滤波器选件(+E200 和 +E202)的变频器连接至滤波器不 兼容的系统中。这可能会导致危险或损坏变频器。 FR IT NL 警告!勿将带有压敏电阻的变频器连接至压敏电阻不兼容的系统中。如果您这 么做,压敏电阻电路将会损坏。请参阅变频器硬件手册。 注:使用+E201选件,拆除TN-S以外系统中的EMCAC、EMCDC和VAR螺丝,如果出 厂时没有拆除。更多信息请联系 ABB。 检查输入和电机电缆以及电机本身的绝缘 将输入电缆连接到传动前,请按当地法规检查其绝缘情况。 电机电缆从传动上断开时,检查电机和电机电缆绝缘情况,请参见第 98 页的图 F。使 用1000V DC测量电压测量各相导线之间的绝缘电阻,然后测量每相导线与保护接地导 线之间的绝缘电阻。ABB 电机的绝缘电阻必须超过 100 Mohm(参照值为 25°C 或 77°F 时测得)。对于其他电机的绝缘电阻,请参阅其制造商的说明。注:电机外壳 内部的湿气会降低绝缘电阻。如果湿气长期存在,请干燥电机后再次测量。 PT RU SV TR CN CN ZH 92 中文 – 快速安装指南 贴上以当地语言写成的警告贴纸 连接电力电缆 请参阅图 C、D、E 和 G。请使用对称屏蔽电缆进行电机电缆敷设。 5. 拆卸前盖两侧的安装螺丝。 6. 将盖子向前滑动,从而将其取下。 7. 将本地语言的剩余电压警告贴纸贴在控制盘安装的醒目位置。 8. 将橡胶绝缘圈从电缆接入板上取下,以便连接电缆。 EN 9. IP21 变频器: 将电缆连接器(发货时放在塑料袋中)固定在电缆接入板孔上。 DA 10. 如图所示准备好输入动力电缆和电机电缆的两端。 DE 11. 将电缆连接器(IP21)中或电缆夹(IP55)下的电缆护套 360 度接地。 12. 将输入电缆的双绞线屏蔽层连接到 PE 端子。 ES FI FR 13. 将输入电缆的PE导线连接到附加 PE 端子。 14. 将电机电缆和制动电阻电缆的双绞线屏蔽层(如存在)连接到接地端子。 15. 连接输入电缆、电机电缆和制动电阻电缆,拧紧螺钉。 16. 将控制电缆接地架安装在变频器底部的电缆接线盒。 IT 17. 在驱动器外用机械方法固定好电缆。 NL 18. 在电机端将电机电缆屏蔽层接地。要使干扰降至最低水平,在线缆接入处提供 360 度接地或尽可能地缩短屏蔽层接地的裸露部分。 PT RU 连接控制电缆 请参阅图片 H。 SV 1. 在橡胶绝缘圈上切出足够大的孔,然后将绝缘圈套到电缆上。将电缆从底板的孔 中穿过并将绝缘圈固定到接线盒的底板孔上。 TR 2. 剥开电缆末端并截取到合适的长度(要注意接地导线的额外长度)。 CN 3. 在电缆接线盒的接地夹处,将所有控制电缆的外屏蔽层做 360 度接地。 CN 4. 将双绞电缆屏蔽层固定到接地夹子下,另一端的屏蔽层悬空或使用 3.3 nF/630 V 高频电容间接接地。 ZH 5. 将导线连接到控制板的适当端子上。参见(第94页). 6. 如果交付的货物中包括选装模块,则为其连接电缆。 7. 装回前盖。 现场总线布线注意事项请参阅图片 I。 中文 – 快速安装指南 93 1. 安装附加接地架。 2. 将电缆的外屏蔽层在接地夹处 360 度接地。 3. 在电缆接线盒盖上对应安装电缆的位置开孔,引入通讯电缆。 4. 将通讯电缆接头连接现场总线模块。 默认 I/O 连接 ACS880 工厂宏控制程序的默认 I/O 连接如下所示。 EN DA DE ES FI FR IT NL PT RU SV TR CN CN ZH 94 中文 – 快速安装指南 电缆规格: 0.5 … 2.5 mm2 (24…12 AWG) 拧紧扭矩: 0.5 N·m (5 lbf·in) 适 用于多芯和实心 导线。 EN DA DE ES FI FR IT NL PT RU SV TR CN CN ZH 1) 这些输出的总负 载能力为 4.8 W (200 mA / 24 V) 减 去 DIO1 和 DIO2 的 功耗。 故障 XPOW 外部电源输入 1 +24VI 24 V DC,2 A 2 GND XAI 参考电压和模拟输入 1 +VREF 10 V DC,RL 1…10 kohm 2 -VREF -10 V DC,RL 1…10 kohm 3 AGND 地 4 AI1+ 速度参考 0(2)…10 V, Rin > 200 kohm 5 AI16 AI2+ 默认不使用。0(4)…20 mA, Rin = 100 ohm 7 AI2J1 J1 AI1 电流/电压选择跳线 J2 J2 AI2 电流/电压选择跳线 XAO 模拟输出 1 AO1 电机速度 rpm 0…20 mA, RL < 500 ohm 2 AGND 3 AO2 电机电流 0…20 mA, RL < 500 ohm 4 AGND XD2D 变频器到变频器链路 1 B 2 A 变频器到变频器链路 3 BGND J3 J3 变频器到变频器链路终端开关。 XRO1、XRO2、XRO3 继电器输出 11 NC 就绪 250 VAC / 30 VDC 12 COM 2A 13 NO 21 NC 正在运行 250 VAC / 30 VDC 22 COM 2A 23 NO 31 NC 故障 (-1) 250 VAC / 30 VDC 32 COM 2A 33 NO XD24 数字联锁 1 DIIL 运行使能 2 +24VD +24 V DC 200 mA 1) 3 DICOM 数字输入接地 4 +24VD +24 V DC 200 mA 1) 5 DIOGND 数字输入/输出接地 J6 接地选择开关 XDIO 数字输入/输出 1 DIO1 输出:就绪 2 DIO2 输出:正在运行 XDI 数字输入 1 DI1 停止(0) / 启动(1) 2 DI2 正向(0) / 反向(1) 3 DI3 复位 4 DI4 斜坡时间选择 5 DI5 恒定转速 1(1 = 开启) 6 DI6 默认不使用。 XSTO 安全转矩取消 1 OUT1 2 SGND 安全转矩取消。两个电路都必须闭合后 3 IN1 方可启动电机。 4 IN2 X12 安全功能模块连接 X13 控制盘连接 X205 记忆单元连接 Declaration of conformity 95 Declaration of conformity 96 Declaration of conformity A 97 C 1 2 b ×4 a b (mm) (mm) 3 ACS880-01 ×4 L1 PE L2 R- L3 UDC+ R+ UDC- T1/U T2/V T3/W IP21 R1 358 R2 98 R3 451 125 a ×4 IP55 R1 434 R2 98 R3 509 125 R1 6 kg R2 8 kg R3 10 kg V1 U1 6 PE L1 L2 L3 W1 3~M 11 200 mm 5 D ×4 IP55 IP21 M4x16 Torx T20 2 N·m 4 1 300 mm < 40 °C Figures 2 B ACS8800104A6-2 06A6-2 07A5-2 10A6-2 16A8-2 24A3-2 031A-2 07A4-7 09A9-7 14A3-7 019A-7 Air flow (m3/h) 44 44 44 44 88 88 134 134 134 134 134 Losses (W) 73 94 122 172 232 337 457 114 143 207 274 023A-7 134 329 027A-7 134 405 ACS880-01OFAF000H6 OFAF000H10 OFAF000H16 OFAF000H16 OFAF000H25 OFAF000H40 OFAF000H50 OFAA000GG16 OFAA000GG20 OFAA000GG25 OFAA000GG35 OFAA000GG50 OFAA000GG50 02A4-3/02A1-5 03A3-303A0-5 04A0-303A4-5 05A6-3/04A8-5 07A2-3/05A2-5 09A4-3/07A6-5 12A6-3/11A0-5 017A-3/014A-5 025A-3/021A-5 032A-3/027A-5 038A-3/034A-5 Air flow (m3/h) 44 44 44 44 44 44 44 88 88 134 134 Losses (W) 30 40 52 73 94 122 172 232 337 457 562 1 3 1 OFAF000H4 OFAF000H6 OFAF000H6 OFAF000H10 OFAF000H10 OFAF000H16 OFAF000H16 OFAF000H25 OFAF000H32 OFAF000H40 OFAF000H50 M4×16 Torx T20 2 N·m 5 4 IP21 98 F E PE PE 6 U1 6 V1 ohm W1 10 10 M 3~ PE G 14 14 H PE 6 8 L1, L2, L3, T1/ U, T2/V, T3/W, R-, R+/UDC+, UDC 10 T3/W T2/V T1/U 9 UDC- 8 R+ 9 R- L3 L2 L1 PE 11 11 5 (N·m) (N·m) R1 0.6 1.8 R2 0.6 1.8 R3 1.7 1.8 0.5 N·m 5 3 R1, R2: 1.5 N·m R3: 2 N·m T3/W T2/V T1/U UDC- R+ R- L3 L2 L1 1.5 N·m 1.5 N·m 4 R1, R2: 1.5 N·m R3: 2 N·m M4×20 Torx T20 7 1 12 Phillips PT2 M4×8 Torx T20 1.5 N·m 1 I 99 M4×20 Torx T20 1.5 N·m 1 2 M4×8 Torx T20 2 N·m Available from 2014-09 4 3 100J Drive type Frame size IEC US Cu cable type Cu cable type mm2 AWG/kcmil UN = 230 V ACS880-01-04A6-2 R1 3×1.5 14 ACS880-01-06A6-2 R1 3×1.5 14 ACS880-01-07A5-2 R1 3×1.5 14 ACS880-01-10A6-2 R1 3×1.5 14 ACS880-01-16A8-2 R2 3×6 10 ACS880-01-24A3-2 R2 3×6 10 ACS880-01-031A-2 R3 3×10 8 ACS880-01-02A4-3 R1 3×1.5 14 ACS880-01-03A3-3 R1 3×1.5 14 ACS880-01-04A0-3 R1 3×1.5 14 ACS880-01-05A6-3 R1 3×1.5 14 ACS880-01-07A2-3 R1 3×1.5 14 ACS880-01-09A4-3 R1 3×1.5 14 ACS880-01-12A6-3 R1 3×1.5 14 ACS880-01-017A-3 R2 3×6 10 UN = 400 V ACS880-01-025A-3 R2 3×6 10 ACS880-01-032A-3 R3 3×10 8 ACS880-01-038A-3 R3 3×10 8 ACS880-01-02A1-5 R1 3×1.5 14 ACS880-01-03A0-5 R1 3×1.5 14 ACS880-01-03A4-5 R1 3×1.5 14 ACS880-01-04A8-5 R1 3×1.5 14 ACS880-01-05A2-5 R1 3×1.5 14 ACS880-01-07A6-5 R1 3×1.5 14 ACS880-01-11A0-5 R1 3×1.5 14 ACS880-01-014A-5 R2 3×6 10 ACS880-01-021A-5 R2 3×6 10 ACS880-01-027A-5 R3 3×10 8 ACS880-01-034A-5 R3 3×10 8 ACS880-01-07A4-7 R3 3×1.5 14 ACS880-01-09A9-7 R3 3×1.5 14 ACS880-01-14A3-7 R3 3×2.5 14 ACS880-01-019A-7 R3 3×4 12 ACS880-01-023A-7 R3 3×6 10 ACS880-01-027A-7 R3 3×10 8 UN = 500 V UN = 690 V A 101 C 1 2 b ×4 a b (in.) (in.) 3 M5 ACS880-01 ×4 L1 PE UL Type 1 L2 R- L3 UDC+ R+ UDC- T1/U T2/V T3/W ×4 R1 15.16 3.86 R2 R3 17.76 4.92 a Figures – USA UL Type 12 R1 17.09 3.86 R2 R1 13 lb R2 18 lb R3 20.04 4.92 R3 22 lb .23 V1 .45 U1 PE 7.87” 5 L1 L2 L3 W1 3~M ×4 D Ul Type 12§ 4 M4x16 Torx T20 2 N·m UL Type 1 11.81” < 104 °F B ACS880-01- Air flow Losses (ft3/min) (W) 04A6-2 26 73 06A6-2 26 94 07A5-2 26 122 10A6-2 26 172 16A8-2 52 232 24A3-2 52 337 031A-2 79 457 07A4-7 79 114 09A9-7 79 143 14A3-7 79 207 019A-7 79 274 023A-7 79 329 027A-7 79 405 USA ACS880-01JJS-15 JJS-15 JJS-15 JJS-20 JJS-25 JJS-40 JJS-50 JJS-15 JJS-20 JJS-30 JJS-40 JJS-50 JJS-50 02A1-5 03A0-5 03A4-5 04A8-5 05A2-5 07A6-5 11A0-5 014A-5 021A-5 027A-5 034A-5 Air flow (ft3/min) 26 26 26 26 26 26 26 52 52 79 79 Losses (W) 30 40 52 73 94 122 172 232 337 457 562 3 JJS-3 JJS-6 JJS-6 JJS-10 JJS-10 JJS-15 JJS-20 JJS-25 JJS-35 JJS-40 JJS-50 2 1 1 M4×16 Torx T20 2 N·m M6x12 Torx T25 4 102E U1 V1 ohm W1 3AUA0000085966 Rev H F M 3~ PE G 5 7 6 8 7 5 lbf·in L1, L2, L3, T1/U, T2/V, T3/W, R-, R+/ UDC+, UDC 6 T3/W T2/V T1/U UDC- R+ R- L3 6 AWG L2 L1 5 (lbf·ft) (lbf·ft) R1 0.4 1.3 R2 0.4 1.3 R3 1.3 1.3 3 6 T3/W T2/V T1/U UDC- 9 M4×8 Torx T20 18 lbf·in R+ M4×20 Torx T20 R- 4 L3 13 lbf·in L2 L1 Cable conduit installation 5 — Further information Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to abb.com/searchchannels. Product training For information on ABB product training, navigate to new.abb.com/service/training. Providing feedback on ABB Drives manuals Your comments on our manuals are welcome. Navigate to new.abb.com/drives/manuals-feedback-form. Document library on the Internet You can find manuals and other product documents in PDF format on the Internet at abb.com/drives/documents. ACS880-01 manuals © Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice. 3AUA0000085966 Rev H (MUL) 2019-05-08 abb.com/drives
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104

ABB ACS880-01 Series Quick Installation Manual

Type
Quick Installation Manual