ABB ACS880 Series Quick Start Up Manual

Type
Quick Start Up Manual
English . . . . . . . .3
Dansk . . . . . . . .13
Deutsch. . . . . . .23
Español. . . . . . .35
Suomi . . . . . . . .47
Français . . . . . .57
Italiano . . . . . . .69
Nederlands . . . .81
Polski . . . . . . . .91
Português . . . .103
Русский . . . . .113
Svenska . . . . .125
rkçe. . . . . . . 135
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ABB industrial drives
Quick start-up guide
ACS880 drives with primary control program
List of related manuals in English
Dr
ive hardware manuals Code (English)
ACS880-01 drives hardware manual 3AUA0000078093
ACS880-01 quick installation guide for frames R1 to R3 3AUA0000085966
ACS880-01 quick installation guide for frames R4 and R5 3AUA0000099663
ACS880-01 quick installation guide for frames R6 to R9 3AUA0000099689
ACS880-07 drives hardware manual 3AUA0000105718
ACS880-104 inverter modules hardware manual 3AUA0000104271
ACS880-107 inverter units hardware manual 3AUA0000102519
Drive firmware manuals and guides
ACS880 primary control program firmware manual 3AUA0000085967
ACS880 drives with primary control program, quick start-
up guide
3AUA0000098062
Option manuals and guides
ACS-AP-x assistant control panels user’s manual 3AUA0000085685
Drive composer Start-up and maintenance PC tool User’s
manual
3AUA0000094606
Manuals and quick guides for I/O extension modules,
fieldbus adapters, encoder interfaces, etc.
3AUA0000098062 Rev D
MUL
EFFECTIVE: 2012-10-22
2012 ABB Oy. All Rights Reserved.
Quick start-up guide for ACS880 drives with primary control program 3
EN
DE
ES
FI
FR
IT
NL
RU
SV
Quick start-up guide for
ACS880 drives with primary
control program
About this guide
This guide describes the basic start-up sequence of an ACS880 drive equipped with
the primary control program. Complete documentation of the drive firmware can be
found in Firmware manual (see list of manuals on the inside of the front cover).
In this guide, the drive is set up using the ACS-AP-I control panel. The start-up
sequence can also be carried out using the Drive composer PC tool.
Before you start
Ensure that the drive has been mechanically and electrically installed as described in
the appropriate Quick installation guide and/or Hardware manual.
Safety
WARNING! All electrical installation and maintenance work on the drive should
be carried out by qualified electricians only.
Never work on the drive, the braking chopper circuit, the motor cable or the motor
when power is applied to the drive. Always ensure by measuring that no voltage is
actually present.
4 Quick start-up guide for ACS880 drives with primary control program
EN
DE
ES
FI
FR
IT
NL
RU
SV
Start-up
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the safety
instructions on the first pages of the appropriate Hardware manual.
Check the installation. See the installation checklist in the appropriate Hardware manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
there is a risk of damage in case of an incorrect direction of rotation, or
•a Normal ID run is required during the drive start-up, when the load torque is higher
than 20% or the machinery is not able to withstand the nominal torque transient during
the ID run.
1 – Power-up, date and time settings
Power up the drive.
Note: It is normal that warning messages
appear at various points along the start-up
process. To hide a message and to resume
the start-up process, press .
Hide any warnings now to enter the Home
view (shown on the right).
The two commands at the bottom of the
display (in this case, Options and Menu),
show the functions of the two softkeys
and located below the display. The
commands assigned to the softkeys vary
depending on the context.
In the Home view, press (Menu).
The main Menu (right) appears.
Remote 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:34
Menu
Remote 0.0 rpm
Menu
Parameters
Assistants
Energy efficiency
Event log
Exit
12:34
Select
Quick start-up guide for ACS880 drives with primary control program 5
EN
DE
ES
FI
FR
IT
NL
RU
SV
Highlight Settings on the menu using
and and press (Select).
In the Settings menu, highlight Date & time
(if not already highlighted) and press
(Select).
In the Date & time menu, highlight Date (if
not already highlighted) and press
(Select).
Remote 0.0 rpm
Settings
Language
Date & time
Back
12:34
Select
Edit texts
Display settings
Next daylight saving start 28.03.
Remote 0.0 rpm
Date & time
Date
Back
12:35
Edit
Time
Show date as
01.01.1980
12:34:56
day.month.year
Show time as 24-hour
Daylight saving EU
Remote 0.0 rpm
Date
Cancel
12:35
Save
Day Month Year
Tuesday
.01.198001
6 Quick start-up guide for ACS880 drives with primary control program
EN
DE
ES
FI
FR
IT
NL
RU
SV
Set the correct date:
Use and to move the cursor left
and right.
Use and to change the value.
•Press (Save) to accept the new
setting.
Check/adjust all the remaining settings in the
Date & time menu.
The Show clock setting determines whether
the time is shown at all times in the bottom
pane of the display.
After you have made the settings, press
(Back or Exit) repeatedly until the
Home view (right) reappears.
2 – Supply voltage and motor data settings
Switch to local control to ensure that external
control is disabled by pressing the
key. Local control is indicated by the text
“Local” in the top pane.
Open the main Menu by pressing
(Menu).
Remote 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:35
Menu
Loc/Rem
Local 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:36
Menu
Local 0.0 rpm
Menu
Parameters
Assistants
Energy efficiency
Event log
Exit
12:36
Select
Quick start-up guide for ACS880 drives with primary control program 7
EN
DE
ES
FI
FR
IT
NL
RU
SV
Highlight Parameters and press
(Select).
Highlight Complete list using and
and press (Select).
A listing of parameter groups is displayed.
Highlight parameter group 95 HW
configuration and press (Select).
Note that the list wraps around in either
direction between groups 99 and 01. In this
case, it is quicker to use to locate group
95 on the list.
After selecting a group, a listing of
parameters within the group is displayed.
Highlight parameter 95.01 Supply voltage
(if not already highlighted) and press
(Edit).
The available parameter settings are listed.
Local 0.0 rpm
Parameters
Favorites
By function
Back
12:36
Select
Complete list
Modified
Local 0.0 rpm
Complete list
01 Actual values
03 Input references
04 Warnings and faults
05 Diagnostics
06 Control and status words
07 System info
Back
12:36
Select
Local 0.0 rpm
95 HW configuration
95.01 Supply voltage
Back
12:36
Edit
95.02 Adaptive voltage limits
95.04 Control board supply
Not given
Disable
Internal 24V
Local 0.0 rpm
95.01 Supply voltage
[0] Not given
[1] 208…240 V
Cancel
12:36
Save
[2] 380…415 V
[3] 440…480 V
[4] 500 V
8 Quick start-up guide for ACS880 drives with primary control program
EN
DE
ES
FI
FR
IT
NL
RU
SV
Highlight the correct setting on the list and
press (Save).
Press (Back) to display the list of parameter groups again. Select parameter group
99 Motor data, and set parameter 99.03 Motor type.
Set parameter 99.04 Motor ctrl mode.
DTC = Direct torque control; Scalar
DTC is suitable for most cases. Scalar mode is recommended if
the nominal current of the motor is less than 1/6 of the nominal current of the drive,
the drive is used for test purposes with no motor connected, or
the drive controls multiple motors and the number of motors connected is variable.
Refer to the motor nameplate for the following parameter settings. Whenever possible, enter
the values exactly
as shown on the motor nameplate.
Example of a nameplate of an induction
(asynchronous) motor:
Example of a nameplate of a permanent
magnet motor:
99.06 Motor nominal current
The allowable range is
in DTC mode: 1/6 × I
Hd
… 2 × I
Hd
of the drive
in Scalar mode: 0 … 2 × I
Hd
Note: With numerical parameter values:
Use and to change the value of a digit.
Use and to move the cursor left and right.
•Press (Save) to enter the value.
Local 0.0 rpm
95 HW configuration
95.01 Supply voltage
Back
12:36
Edit
95.02 Adaptive voltage limits
95.04 Control board supply
380…415 V
Disable
Internal 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Quick start-up guide for ACS880 drives with primary control program 9
EN
DE
ES
FI
FR
IT
NL
RU
SV
Make the following parameter settings in the same manner.
99.07 Motor nominal voltage
The allowable range is 1/6 × U
N
… 2 × U
N
of the drive.
With permanent magnet motors, the nominal voltage is the BackEMF voltage at nominal
speed. If the voltage is given in volt/rpm (eg. 60 V per 1000 rpm), the voltage at a nominal
speed of 3000 rpm is 3 × 60 V = 180 V. Note that nominal voltage is not the same as
equivalent DC motor voltage (EDCM) given by some manufacturers. The nominal voltage
can be calculated by dividing the EDCM voltage by 1.7 (or square root of 3).
99.08 Motor nominal frequency
With permanent magnet motors, if the nominal frequency is not shown on the nameplate,
it can be calculated using the following formula:
f = n × p / 60
where n = nominal motor speed, p = number of pole pairs.
99.09 Motor nominal speed
99.10 Motor nominal power
99.11 Motor nominal cosfii
99.12 Motor nominal torque
These values are not required, but can be entered to improve control accuracy. If not
known, leave at 0.
99.13 Identification run request
This parameter selects the mode of the identification run (DTC motor control mode only).
WARNING! The identification run modes marked thus * will run the motor in the
forward direction (see below for details). Make sure it is safe to run the motor
before choosing any of these modes.
*Normal mode should be selected whenever possible. The driven machinery must be de-
coupled from the motor if
the load torque is higher than 20%, or
the machinery is not able to withstand the nominal torque transient during the
identification run.
*Reduced mode should be selected if the mechanical losses are higher than 20%, ie. the
load cannot be de-coupled, or full flux is required to keep the motor brake open (eg. with
conical motors).
The Standstill mode should be selected if neither the *Normal or *Reduced mode can
be used. Notes:
This mode cannot be used with a permanent magnet motor if the load torque is higher
than 20% of nominal.
Mechanical brake is not opened by the logic for the identification run.
Ensure that the Safe torque off and emergency stop circuits (if present) are closed.
Start the identification run by pressing the
(Start) button.
A warning will indicate that the
identification run is in progress.
10 Quick start-up guide for ACS880 drives with primary control program
EN
DE
ES
FI
FR
IT
NL
RU
SV
Check that the motor runs in the correct direction (forward direction shown below).
The identification run has completed when the drive stops and the value of parameter
99.13 reverts to “No”.
If the motor ran in the wrong direction, correct the motor cabling or adjust parameter
99.16 Phase order.
3 – Control signal settings
Check the positions of jumpers J1 and J2 on the control unit of the drive. These jumpers
determine whether analog inputs AI1 and AI2 are current or voltage.
Check/adjust the following parameters.
20.01 Ext1 commands
By default, the drive starts/stops according to the status of digital input DI1 (0 = Stop,
1 = Start). DI2 determines the direction of rotation (0 = Forward, 1 = Reverse).
If other sources are required, change the value accordingly. The sources In1In3 are
defined by parameters 20.0320.05.
12.15 AI1 unit selection
Set this to either mA or V corresponding to the setting of jumper J1.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scaled at AI1 min
12.20 AI1 scaled at AI1 max
The default input for speed reference is analog input AI1. (This is controlled by the
parameters in group 22.)
Parameters 12.17 and 12.18 set the low and high limits of the analog input signal. Scaling
parameters 12.19 and 12.20 define the internal signal levels that correspond to these
limits as follows:
The corresponding parameters for analog input AI2 are 12.2712.30.
AI (scaled)
AI (mA/V)
12.20
12.18
12.17
12.19
Quick start-up guide for ACS880 drives with primary control program 11
EN
DE
ES
FI
FR
IT
NL
RU
SV
13.12 AO1 source
13.17 AO1 source min
13.18 AO1 source max
13.19 AO1 out at AI1 src min
13.20 AO1 out at AI1 src max
Parameter 13.12 selects the source for analog output AO1 (by default, motor speed in
rpm).
Parameters 13.17 and 13.18 set low and high source signal values that correspond to the
actual analog output values defined by parameters 13.19 and 13.20.
46.10 Speed scaling
23.11 Ramp set selection
23.12 Acceleration time 1
23.13 Deceleration time 1
23.14 Acceleration time 2
23.15 Deceleration time 2
You can define two different sets of acceleration/deceleration ramps. The source that
switches between the two sets is selected by parameter 23.11.
Each acceleration/deceleration time set in parameters 23.1223.15 refers to the time it
takes for the drive to accelerate or decelerate between 0 and scaling speed (parameter
46.10).
Source signal
AO (mA)
13.18
13.20
13.19
13.17
Time
Speed
46.10
23.12
23.14
23.13
23.15
Acc. Dec.
0
12 Quick start-up guide for ACS880 drives with primary control program
EN
DE
ES
FI
FR
IT
NL
RU
SV
30.11 Minimum speed
30.12 Maximum speed
30.17 Maximum current
30.19 Minimum torque
30.20 Maximum torque
Check, and set if necessary, the limits for motor speed, current and torque.
Start the drive with a positive (forward) speed reference:
From control panel (Local control): In the Home view,press (Options), select
Reference, adjust the reference using the , ,
, and keys, press Save, and
press the Start button.
From I/O: In Remote control, adjust analog input AI1 (reference), switch digital input
DI2 to 0 (forward), and switch digital input DI1 to 1 (start).
Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 13
DA
DA
ES
FI
FR
IT
NL
RU
SV
Quick Start-up Guide for
ACS880-frekvensomformere
med standardstyreprogram
Om denne vejledning
Denne guide beskriver den grundlæggende opstartssekvens for en ACS880-
frekvensomformer med standardstyreprogram. Den komplette dokumentation til
frekvensomformerens firmware findes i firmwaremanualen. Se listen over manualer
på indersiden af forsiden.
I denne guide er frekvensomformeren indstillet til at bruge ACS-AP-I-kontrolpanelet.
Opstartssekvensen kan også udføres ved hjælp af pc-værktøjet Drive composer.
Inden du starter
Du skal sikre dig, at frekvensomformeren er blevet mekanisk og elektrisk installeret
som beskrevet i den tilhørende Hurtig installationsvejledning og/eller
hardwaremanualen.
Sikkerhed
ADVARSEL! Al elektrisk installation og alt vedligeholdelsesarbejde på
frekvensomformeren må kun udføres af en autoriseret installatør.
Arbejd aldrig på frekvensomformeren, bremsechopperkredsen, motorkablet eller
motoren, når netspændingen er tilsluttet frekvensomformeren. Sørg altid for at sikre
dette ved at måle, at der ikke er nogen spænding til stede.
14 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram
DA
DA
ES
FI
FR
IT
NL
RU
SV
Opstart
Sikkerhed
Opstartsproceduren må kun gennemføres af en kvalificeret elektriker.
Sikkerhedsinstruktionerne skal følges under opstartsproceduren. Se
sikkerhedsinstruktionerne på de første sider af den tilhørende hardwaremanual.
Kontroller installationen. Se installationstjeklisten i den tilhørende hardwaremanual.
Kontroller, at start af motoren ikke medfører fare.
Belastningsmaskinen frakobles, hvis:
Der er risiko for ødelæggelse i tilfælde af forkert omløbsretning, eller
•en normal identifikationstest kræves under opstarten af frekvensomformeren, hvis
belastningsmomentet er højere end 20 %, eller hvis maskinen ikke kan tåle det
nominelle transiente moment under identifikationstesten.
1 – Opstart, angivelse af dato og klokkest
Start frekvensomformeren op.
Berk! Det er normalt, at der der vises
advarsler på forskellige tidspunkter i
opstartsprocessen. Tryk på , hvis du vil
skjule en meddelelse og fortsætte
opstartsprocessen.
Skjul alle advarsler nu for at få vist
skærmbilledet Home (vist til højre).
De to kommandoer nederst i displayet (i
dette tilfælde Indstillinger og Menu), viser
funktionerne for de to taster og
nederst i displayet. Tasternes tilknyttede
kommandoer varierer alt efter
sammenhængen.
Tryk i Startsiden på (Menu).
Hovedmenuen (højre) vises.
Fjern 0,0 o/min
0.00
0.00
Motormoment %
%
0.0
Motorstrøm
A
Benyttet motorhastighed
o/min
Indstillinger
12:34
Menu
Fjern 0,0 o/min
Menu
Parametre
Assistenter
Energieffektivitet
ndelseslog
Afslut
12:34
lg
Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 15
DA
DA
ES
FI
FR
IT
NL
RU
SV
Marker Indstillinger i menuen ved at bruge
og , og tryk på (Vælg).
I menuen Indstillinger kan du markere Dato
og klokkeslæt (hvis valget ikke allerede er
markeret). Tryk herefter på (Vælg).
I menuen Dato og klokkeslæt kan du
markere Dato (hvis valget ikke allerede er
markeret). Tryk herefter på (Vælg).
Fjern 0,0 o/min
Indstillinger
Sprog
Dato og klokkeslæt
Tilbage
12:34
lg
Rediger tekst
Vis indstillinger
Næste sommertid starter 28.03.
Fjern 0,0 o/min
Dato og klokkeslæt
Dato
Tilbage
12:35
Rediger
Klokkeslæt
Vis dato som
01.01.1980
12:34:56
dag.måned.år
Vis klokkeslæt som 24-timer
Sommertid EU
Fjern 0,0 o/min
Dato
Annuller
12:35
Gem
Dag Måned År
Tirsdag
.01.198001
16 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram
DA
DA
ES
FI
FR
IT
NL
RU
SV
Indstil den korrekte dato:
Brug og til at flytte markøren til
venstre eller højre.
Brug og til at ændre værdien.
Tryk på (Gem) for at acceptere den
nye indstilling.
Kontrollér/juster de andre indstillinger i
menuen Dato og klokkeslæt
Indstillingen Vis ur angiver, om klokkeslæt
altid skal vises nederst i displaypanelet.
Når du har udført indstillingerne, skal du
trykke (Tilbage eller Afslut)
gentagne gange, indtil Startsiden (højre)
vises igen.
2 – Indstillinger for forsyningsspænding og motordata
Skift til lokal styring for at sikre, at ekstern
styring er deaktiveret, ved at trykke på tasten
. Lokalstyring er angivet med teksten
"Lokal" øverst i panelet.
Aktiver hovedmenuen ved at trykke på
(Menu).
Fjern 0,0 o/min
0.00
0.00
Motormoment %
%
0.0
Motorstrøm
A
Benyttet motorhastighed
o/min
Indstillinger
12:35
Menu
Loc/Rem
Lokal 0,0 o/min
0.00
0.00
Motormoment %
%
0.0
Motorstrøm
A
Benyttet motorhastighed
o/min
Indstillinger
12:36
Menu
Lokal 0,0 o/min
Menu
Parametre
Assistenter
Energieffektivitet
ndelseslog
Afslut
12:36
lg
Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 17
DA
DA
ES
FI
FR
IT
NL
RU
SV
Marker Parametre, og tryk på (Vælg).
Marker Komplet liste i menuen ved at bruge
og , og tryk på (Vælg).
Der vises en liste med parametergrupper.
Marker parametergruppe 95 HW-
konfiguration, og tryk på (Vælg).
Bemærk, at listen vil fortsætte i retning mod
gruppe 99 eller 01. I dette tilfælde er det
hurtigere at bruge til at finde gruppe 95
på listen.
Når du har valgt en gruppe, vises en liste
med parametre for gruppen.
Marker parameteren Forsyningsspænding
(hvis den ikke allerede er markeret), og tryk
(Rediger).
De tilgængelige parameterindstillinger vises.
Lokal 0,0 o/min
Parametre
Favoritter
Efter funktion
Tilbage
12:36
lg
Komplet liste
Ændret
Lokal 0,0 o/min
Komplet liste
01 Aktuel værdi
03 Inputreferencer
04 Advarsler og fejl
05 Diagnostik
06 Kontrol- og statusord
07 Systemoplysninger
Tilbage
12:36
lg
Lokal 0,0 o/min
95 HW konfiguration
95.01 Forsyningsspæn.
Tilbage
12:36
Rediger
95.02 Adaptive spænd.grænse
95.04 Styrekort forsyning
Ikke angivet
Inaktiv
Intern 24V
Lokal 0,0 o/min
95.01 Forsyningssnding
[0] Ikke angivet
[1] 208…240 V
Annuller
12:36
Gem
[2] 380…415 V
[3] 440…480 V
[4] 500 V
18 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram
DA
DA
ES
FI
FR
IT
NL
RU
SV
Marker den korrekte indstilling på listen og
tryk på (Gem).
Tryk på (Tilbage) for igen at få vist listen med parametergrupper. Marker
parametergruppe 99 Motordata, og indstil parameter 99.03 Motortype.
Indstil parameter 99.04 Motorstyringstilstand.
DTC = Direkte momentstyring, Skalar
DTC er egnet i de fleste tilfælde. Skalarmode anbefales, hvis
motorens nominelle strøm er mindre end 1/6 af frekvensomformerens nominelle strøm
frekvensomformeren anvendes til test, hvor der ikke er tilsluttet en motor til den, eller
frekvensomformeren styrer flere motorer, og antallet af tilsluttede motorer er variabelt.
Se motorens mærkeplade for oplysninger om de følgende parameterindstillinger. Indtast, hvis
det er muligt, værdierne nøjagtigt
som de er angivet på motormærkepladen.
Eksempel på en mærkeplade fra en
(asynkron) induktionsmotor:
Eksempel på en mærkeplade fra en
permamagnetmotor:
99.06 Nominel motorstrøm
Det tilladte interval er
i DTC-tilstand: 1/6 × I
Hd
… 2 × I
Hd
for frekvensomformeren
i skalartilstand: 0 … 2 × I
Hd
Berk! Med numeriske parameterværdier:
Brug og til at ændre værdien for et ciffer.
Brug og til at flytte markøren til venstre eller højre.
Tryk på (Gem) for at indsætte værdien.
Lokal 0,0 o/min
95 HW konfiguration
95.01 Forsyningsspæn.
Tilbage
12:36
Rediger
95.02 Adaptive spæn.grænser
95.04 Styrekort forsyning
380…415 V
Inaktiv
Intern 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 19
DA
DA
ES
FI
FR
IT
NL
RU
SV
Foretag indstillinger for de følgende parametre på samme måde.
99.07 Nominel motorspænding
Det tilladte interval er 1/6 × U
N
… 2 × U
N
for frekvensomformeren.
Med permanmagnetmotorer er den nominelle spænding BackEMF-spændingen ved
nominel hastighed. Hvis spændingen angives i volt / o/min (f.eks. 60 V pr. 1000 o/min), er
spændingen ved en nominel hastighed på 3000 o/min 3 × 60 V = 180 V. Bemærk, at
nominel spænding ikke svarer til den tilsvarende DC-motorspændingsværdi (EDCM), der
angives af nogle producenter. Den nominelle spænding kan beregnes ved at dividere
EDCM-spændingen med 1,7 (= kvadratroden af 3).
99.08 Nominel motorfrekvens
For permanmagnetmotorer vises den nominelle frekvens ikke på mærkepladen. Den kan
beregnes ved hjælp af følgende formel:
f = n × p / 60
hvor n = nominel motorhastighed, p = antal polpar.
99.09 Nominel motorhastighed
99.10 Motorens nominelle effekt
99.11 Nominel motor-cosfii
99.12 Nominel motormoment
Disse værdier kræves ikke, men de kan indtastes for at forbedre styrenøjagtigheden.
Hvis værdien ikke kendes, kan du lade den forblive 0.
99.13 Identifikationskørsel anmodn.
Denne parameter vælger tilstanden for identifikationskørslen (kun i DTC-
motorstyringstilstand).
ADVARSEL! De med * markerede tilstande for identifikationskørsel vil køre
motoren i forlæns omløbsretning (se oplysningerne herunder). Du skal kontrollere,
at det er sikkert at køre motoren, inden du vælger en af disse tilstande.
*Normal tilstand bør altid vælges, når det er muligt. Den drevne maskine skal være
frakoblet motoren, hvis
belastningsmomentet er højere end 20 %, eller
hvis maskinanlægget ikke kan tåle det nominelle transiente moment under
identifikationskørslen.
*Reduceret tilstand bør vælges, hvis de mekaniske tab er højere end 20%, dvs. hvis
belastningen ikke kan frakobles, eller der kræves fuld flux for at holde motorbremsen
åben (konisk motor).
Tilstanden Stilstand bør vælges, hvis du hverken kan benytte *Normal eller *Reduceret
tilstand. Bemærk!
Denne tilstand kan ikke benyttes med en permamagnetmotor, hvis
belastningsmomentet er højere end 20 % af det nominelle.
Mekanisk bremsning åbnes ikke af logikken for identifikationskørslen
Sørg for, at Safe toque of- og nødstopskredsløbene (hvis sådanne findes) er lukkede.
Start identifikationskørslen ved at trykke
knappen (Start).
En advarsel vil angive, at
idetifikationskørslen er i gang.
20 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram
DA
DA
ES
FI
FR
IT
NL
RU
SV
Kontroller at motorer kører i den rigtige omløbsretning (forlæns omløbsretning er vist
herunder).
Identifikationskørslen er afsluttet, når frekvensomformeren stopper og værdien for
parameter 99.13 skifter tilbage til "Nej".
Hvis motoren kørte i den forkerte retning, skal du kontrollere motorkablingen eller indstille
parameteren 99.16 Faserækkefølge.
3 – Indstillinger for styresignaler
Kontrollér positionen af jumperne J1 og J2 på frekvensomformerens styreenhed. Disse
jumpere bestemmer, om analogindgange AI1 og AI2 angiver strøm eller spænding.
Kontrollér/juster følgende parametre.
20.01 Ext1-kommandoer
Som standard starter/stopper frekvensomformeren i overensstemmelse med status for
digitalindgang DI1 (0 = Stop, 1 = Start). DI2 Bestemmer rotationsretningen (0 = Forlæns,
1 = Baglæns).
Hvis der skal bruges andre kilder, skal du ændre værdien tilsvarende. Kilderne In1In3
defineres med parametrene 20.0320.05.
12.15 AI1-enhedsvalg
Indstil denne til enten mA eller V i overensstemmelse med indstillingerne for jumper J1.
Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 21
DA
DA
ES
FI
FR
IT
NL
RU
SV
12.17 AI1-min
12.18 AI1-maks.
12.19 AI1-skala ved AI1-min
12.20 AI1-skala ved AI1-maks.
Standardindgang for hastighedsreference er analogindgang AI1. (Denne styres af
parametrene i gruppe 22).
Parametrene 12.17 og 12.18 indstiller grænserne for laveste og højeste analoge
indgangssignal. Skalaparametrene 12.19 og 12.20 definerer de interne signalniveauer,
som svarer til følgende grænser:
De tilsvarende parametre for analogindgang AI2 er 12.2712.30.
13.12 AO1-kilde
13.17 AO1-kilde min
13.18 AO1-kilde maks.
13.19 AO1 ud ved AI1-kilde min
13.19 AO1 ud ved AI1-kilde maks.
Parameter 13.12 vælger kilde for analogudgang AO1 (standard er motorhastighed
angivet i o/min).
Parametrene 13.17 og 13.18 indstiller lav og høj signalværdi, som svarer til
analogudgangsværdierne defineret med parametrene 13.19 og 13.20.
AI (skaleret)
AI (mA/V)
12.20
12.18
12.17
12.19
Kildesignal
AO (mA)
13.18
13.20
13.19
13.17
22 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram
DA
DA
ES
FI
FR
IT
NL
RU
SV
46.10 Hastighedsskaler
23.11 Valg af rampesæt
23.12 Accelerationstid 1
23.13 Decelerationstid 1
23.14 Accelerationstid 2
23.15 Decelerationstid 2
Du kan definere to forskellige rampesæt for acceleration/deceleration. Skift mellem de to
sæt foretages ved at vælge indstilling med parameter 23.11.
Valgene for accelerations-/decelerationstid indstillet med parametrene 23.1223.15
henviser til den tid, det tager frekvensomformeren at accelerere eller decelerere mellem 0
og hastighedsskalering (parameter 46.10).
30.11 Minimum hastighed
30.12 Maksimum hastighed
30.17 Maksimum strøm
30.19 Minimum moment
30.20 Maksimum moment
Kontroller og indstil (hvis det er nødvendigt) grænserne for motorens hastighed, strøm og
moment.
Start frekvensomformeren med en positiv (forlæns) hastighedsreference:
På betjeningspanelet (Lokal styring): Tryk i startbilledet på (Indstillinger), vælg
Reference, tilpas referencen ved hjælp af tasterne , ,
, og , tryk på Gem,
og tryk på knappen Start.
Fra I/O: I fjernkontrol skal du justere analogindgangen AI1 (reference), skifte
digitalindgang DI2 til 0 (forlæns) og skifte digitalindgang DI1 til 1 (start).
Tid
Hastighed
46.10
23.12
23.14
23.13
23.15
Acc. Dec.
0
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 23
EN
DE
DE
FI
FR
IT
NL
RU
SV
Kurzanleitung für den Start
des ACS880 mit Haupt-Rege-
lungsprogramm
Informationen über diese Anleitung
In dieser Anleitung wird die Basis-Inbetriebnahme des ACS880 mit dem Haupt-Rege-
lungsprogramm beschrieben. Die vollständige Dokumentation der Frequenzumrich-
ter-Firmware ist im Firmware-Handbuch (siehe Liste der Handbücher auf der
vorderen Einband-Innenseite) enthalten.
In dieser Anleitung erfolgt die Inbetriebnahme des Frequenzumrichters mithilfe des
Bedienpanels ACS-AP-I. Die Inbetriebnahme kann auch mit dem PC-Tool Drive
Composer erfolgen.
Bevor Sie beginnen
Stellen Sie sicher, dass der Frequenzumrichter mechanisch und elektrisch entspre-
chend den Anweisungen in der jeweiligen Kurzanleitung und/oder im Hardware-
Handbuch installiert wurde.
Sicherheit
WARNUNG! Alle elektrischen Installations- und Wartungsarbeiten an dem
Antrieb dürfen nur von qualifiziertem Fachpersonal durchgehrt werden.
Arbeiten Sie niemals bei eingeschalteter Spannungsversorgung an dem Frequenz-
umrichter, dem Brems-Chopper, dem Motorkabel oder dem Motor. Stellen Sie immer
durch eine Messung sicher, dass keine Spannung anliegt.
24 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
Inbetriebnahme
Sicherheit
Die Inbetriebnahme darf nur durch qualifiziertes Fachpersonal vorgenommen
werden.
Die Sicherheitsvorschriften müssen bei der Inbetriebnahme befolgt werden. Siehe die
Sicherheitsvorschriften auf den ersten Seiten des jeweiligen Hardware-Handbuchs.
Prüfung der Installation. Siehe Installations-Checkliste im jeweiligen Hardware-
Handbuch.
Prüfen Sie, dass durch den Start des Motors keine Gefährdungen entstehen.
Die angetriebene Maschine abkoppeln, wenn:
durch eine falsche Drehrichtung des Motors eine Gefährdung entstehen kann, oder
bei der Inbetriebnahme des Antriebs ein normaler ID-Lauf erforderlich ist, wenn das
Lastmoment höher als 20% ist oder die angetriebene Maschine den Lastwechseln mit
Nennmoment während des ID-Laufs nicht standhält.
1 – Einschalten, Datum- und Zeiteinstellung
Den Frequenzumrichter einschalten.
Hinweis: Es ist normal, dass zu verschiede-
nen Punkten während des Startprozesses
Warnmeldungen erscheinen. Zum Ausblen-
den einer Meldung und zum Fortsetzen des
Startprozesses Taste drücken.
Jetzt alle Warnmeldungen ausblenden, um
in die Startansicht (rechts dargestellt) zu
gelangen.
Die zwei Befehlsanzeigen am unteren Rand
des Displays (in diesem Fall Optionen und
Menü) zeigen die Funktionen der zwei Funk-
tionstasten und an, die unter
dem Display sind. Die den Funktionstasten
zugeordneten Befehlsanzeigen sind vom
Betriebszustand abhängig.
In der Startansicht die Taste (Menü)
drücken.
Das Hauptmenü (rechts) wird angezeigt.
Fernsteuerung 0.0 U/min
0.00
0.00
Motordrehmoment %
%
0.0
Motorstrom
A
Motordrehzahl benutzt
U/min
Optionen
12:34
Me
0.0 U/min
Me
Parameter
Assistenten
Energieeffizienz
Ereignisprotokoll
Beenden
12:34
Auswählen
Fernsteuerung
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 25
EN
DE
DE
FI
FR
IT
NL
RU
SV
Im Menü Einstellungen mit den Tasten
und auswählen und Taste
(Auswählen) drücken.
Im Menü Einstellungen - Datum & Zeit
auswählen (wenn nicht bereits ausgewählt)
und Taste (Auswählen) drücken.
Im Menü Datum & Zeit - Datum auswählen
(wenn noch nicht markiert) und dann Taste
(Auswählen) drücken.
0.0 U/min
Einstellungen
Sprache
Datum & Zeit
Zurück
12:34
Auswählen
Texte bearbeiten
Display-Einstellungen
Fernsteuerung
Start nächste Sommerzeit 28.03.
0.0 U/min
Datum & Zeit
Datum
Zurück
12:35
Bearbeiten
Zeit
Datum anzeigen als
01.01.1980
12:34:56
Tag.Monat.Jahr
Zeitanzeige als 24 STD
Sommerzeit EU
Fernsteuerung
0.0 U/min
Datum
Abbruch
12:35
Speichern
Tag Monat Jahr
Dienstag
.01.198001
Fernsteuerung
26 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
Das korrekte Datum einstellen.
Mit den Tasten und den Cursor
nach links und rechts bewegen.
Mit den Tasten und den
Einstellwert ändern.
Mit der Funktionstaste (Speichern)
die neue Einstellung übernehmen.
Alle Einstellungen im Menü Datum & Zeit
vornehmen bzw. prüfen.
Durch die Einstellung Uhr zeigen wird
festgelegt, ob die Zeit immer am unteren
Rand des Displays angezeigt wird.
Wenn die Einstellungen korrekt sind, Taste
(Zurück oder Beenden) mehrmals
drücken, bis die Startansicht (rechts)
erscheint.
2 – Einspeisespannung und Motordaten einstellen
Sicherstellen, dass die Fernsteuerung
(externe Steuerung) deaktiviert ist und mit
Taste auf Lokalsteuerung
umschalten. Die Lokalsteuerung wird durch
“Lokal” oben im Display angezeigt.
Das Hauptmenü mit Taste (Menü)
öffnen.
0.0 U/min
0.00
0.00
Motordrehmoment %
%
0.0
Motorstrom
A
Motordrehzahl benutzt
U/min
Optionen
12:35
Me
Fernsteuerung
Loc/Rem
Lokal 0.0 U/min
0.00
0.00
Motordrehmoment %
%
0.0
Motorstrom
A
Motordrehzahl benutzt
U/min
Optionen
12:36
Me
Lokal 0.0 U/min
Me
Parameter
Assistenten
Energieeffizienz
Ereignisprotokoll
Beenden
12:36
Auswählen
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 27
EN
DE
DE
FI
FR
IT
NL
RU
SV
Parameter auswählen und Taste
(Auswählen) drücken.
Komplette Liste mit den Tasten und
auswählen und Taste (Auswählen)
drücken.
Eine Liste mit Parametergruppen wird
angezeigt.
Parametergruppe 95 Hardware-
Konfiguration auswählen und Taste
(Auswählen) drücken.
Beachten Sie, dass die Liste in beiden
Richtungen nach den Gruppen 99 und 01
durchblättert werden kann. In diesem Fall ist
es schneller, die Taste zu betätigen, um
zur Gruppe 95 in der Liste zu gelangen.
Nach der Auswahl einer Gruppe wird eine
Parameterliste mit den Parametern der
Parametergruppe angezeigt.
Parameter 95.01 Einspeisespannung
auswählen (wenn nicht bereits ausgewählt)
und Taste (Bearbeiten) drücken.
Die verfügbaren Parametereinstellungen
werden aufgelistet.
Lokal 0.0 U/min
Parameter
Favoriten
Nach Funktion
Zurück
12:36
Auswählen
Komplette Liste
Geändert
Lokal 0.0 U/min
Komplette Liste
01 Istwerte
03 Eingangssollwerte
04 Warnungen und Störungen
05 Diagnosen
06 Steuer- und Statusworte
07 System-Info
Zurück
12:36
Auswählen
Lokal 0.0 U/min
95 Hardware-Konfiguration
95.01 Einspeisespannung
Zurück
12:36
Bearbeiten
95.02 Adaptive Spannu...
95.04 Spann.Vers.Regel...
Nicht gegeben
Deaktivieren
Interne 24V
Lokal 0.0 U/min
95.01 Einspeisespannung
[0] Nicht gegeben
[1] 208…240 V
Abbruch
12:36
Speichern
[2] 380…415 V
[3] 440…480 V
[4] 500 V
28 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
Die richtige Einstellung aus der Liste
auswählen und Taste (Speichern)
drücken.
Die Taste (Zurück) drücken, um wieder die Liste der Parametergruppen
anzuzeigen. Die Parametergruppe 99 Motordaten wählen und den Parameter 99.03
Motorart einstellen.
Parameter 99.04 Motor-Regelmodus einstellen.
DTC = Direkte Drehmomentregelung; Skalar
DTC ist für die meisten Anwendungen geeignet. Skalarregelung wird empfohlen, wenn
der Nennstrom des Motors weniger als 1/6 des Nennausgangsstroms des
Frequenzumrichters beträgt.
der Frequenzumrichter ohne angeschlossenen Motor betrieben wird (z.B. für
Prüfzwecke) oder
der Frequenzumrichter mehrere Motoren regelt und die Anzahl der angeschlossenen
Motoren variabel ist.
Für die folgenden Parametereinstellungen die Daten vom Motor-Typenschild verwenden.
Wenn möglich, die auf dem Motor-Typenschild angegeben Werte genau
eingeben.
Beispiel für ein Typenschild eines
Asynchronmotors:
Beispiel für ein Typenschild eines
Permanentmagnetmotors:
Lokal 0.0 U/min
95 Hardware-Konfiguration
95.01 Einspeisespannung
Zurück
12:36
Bearbeiten
95.02 Adaptive Spannu...
95.04 Spann.Vers.Regelu...
380…415 V
Deaktivieren
Interne 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 29
EN
DE
DE
FI
FR
IT
NL
RU
SV
99.06 Motor-Nennstrom
Der zulässige Bereich ist
im DTC-Modus: 1/6 × I
Hd
… 2 × I
Hd
des Frequenzumrichters
im Skalarmodus: 0 … 2 × I
Hd
Hinweis: Bei numerischen Parameterwerten:
Mit den Tasten und den Wert einer Ziffer ändern.
Mit den Tasten und den Cursor nach links und rechts bewegen.
•Die Taste (Speichern) zum Sichern des Werts drücken.
Nehmen Sie folgenden Parametereinstellungen wie gerade beschrieben vor.
99.07 Motor-Nennspannung
Der zulässige Bereich ist 1/6 × U
N
… 2 × U
N
des Frequenzumrichters.
Bei Permanentmagnetmotoren ist die Nennspannung die Gegen-EMK-Spannung bei
Nenndrehzahl. Wenn die Spannung als Spannung pro U/min angegeben ist, z.B. 60 V
pro 1000 U/min, dann beträgt die Spannung für eine Nenndrehzahl von 3000 U/min = 3×
60 V = 180 V. Beachten Sie, dass die Spannung nicht der äquivalenten DC-Motorspan-
nung (EDCM) entspricht, die von einigen Motorenherstellern angegeben wird. Die Nenn-
spannung kann berechnet werden, indem die EDCM-Spannung durch 1,7 (oder
Quadratwurzel von 3) dividiert wird.
99.08 Motor-Nennfrequenz
Wenn bei Permanentmagnetmotoren die Nennfrequenz nicht auf dem Typenschild
angegeben ist, kann sie mit der folgenden Formel berechnet werden:
f = n × p / 60
wobei n = Motornenndrehzahl, p = Anzahl der Polpaare ist.
99.09 Motor-Nenndrehzahl
99.10 Motor-Nennleistung
99.11 Motor-Cosphi
99.12 Motor-Nenndrehmoment
Die Werte sind nicht erforderlich, können aber zur Erhöhung der Regelgenauigkeit
eingegeben werden. Wenn die Werte nicht bekannt sind, die Einstellung auf 0 lassen.
30 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
99.13 Ausw. Mot.-ID-Laufmodus
Mit diesem Parameter wird der Modus des Identifikationslaufs ausgewählt (nur DTC-
Motorregelungsart).
WARNUNG! Bei * gekennzeichneten Modi des Identifikationslaufs wird der Motor
in Drehrichtung vorwärts gedreht (genauere Angaben, siehe unten). Sicherstellen,
dass der Motor ohne Gefährdungen gedreht werden kann, bevor einer dieser Modi
gewählt wird.
Der Modus *Normal sollte immer, wenn möglich, gewählt werden. Die angetriebene
Maschine muss vom Motor abgekoppelt werden, wenn
das Lastmoment höher als 20% ist oder
die angetriebene Maschine beim ID-Lauf den Lastwechseln mit Nennmoment nicht
standhält.
*Der Modus *Reduziert sollte ausgewählt werden, wenn die mechanischen Verluste
höher als 20% sind, d.h., wenn die Last nicht abgekoppelt werden kann oder ein voller
Fluss erforderlich ist, um die Motorbremse geöffnet zu halten (z. B. mit
Verschiebeankermotoren).
Der Modus Stillstand sollte ausgewählt werden, wenn weder der Modus *Normal noch
der Modus *Reduziert verwendet werden kann.
Hinweise:
Dieser Modus kann bei einem Permanentmagnetmotor nicht verwendet werden, wenn
das Lastmoment um 20% höher als das Motor-Nennmoment ist.
Eine mechanische Bremse wird durch die Schaltlogik im Umrichter beim ID-Lauf nicht
geöffnet.
Sicherstellen, dass die Schaltkreise für das sicher abgeschaltete Drehmoment (STO) und
für Notstopp (falls vorhanden) geschlossen sind.
Start des Motor-Identifikationslaufs mit der
Taste (Start).
Mit einer Warnmeldung wird angezeigt,
dass der Identifikationslauf gerade
durchgeführt wird.
Prüfen, dass der Motor in die richtige Richtung dreht (vorwärts, siehe wie folgt).
Der Identifikationslauf wurde erfolgreich durchgeführt, wenn der Wert des Parameters
99.13 auf “Nein” wechselt.
Wenn der Motor die falsche Drehrichtung hatte, den Motorkabelanschluss korrigieren
oder Parametereinstellung von 99.16 Phasenfolge ändern.
3 – Einstellung der Steuersignale
Die Position der Jumper J1 und J2 der Regelungseinheit des Frequenzumrichters prüfen.
Durch diese Jumper wird festgelegt, ob die Analogeingänge AI1 und AI2 als Strom- oder
Spannungseingänge verwendet werden.
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 31
EN
DE
DE
FI
FR
IT
NL
RU
SV
Die folgenden Parameter prüfen/anpassen.
20.01 Ext1 Befehlsquellen
Standardmäßig startet/stoppt der Frequenzumrichter entsprechend dem Status von
Digitaleingang DI1 (0 = Stopp, 1 = Start). DI2 legt die Drehrichtung fest (0 = Vorwärts,
1 = Rückwärts).
Wenn andere Quellen erforderlich sind, den Wert entsprechend ändern. Die Quellen
In1In3 werden mit den Parametern 20.0320.05 festgelegt.
12.15 AI1 Wahl Einheit
Auf mA oder V je nach Einstellung von Jumper J1 einstellen.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 skaliert min
12.20 AI1 skaliert max
Der Standardeingang für den Drehzahl-Sollwert ist Analogeingang AI1. (Dieses wird
durch die Parameter in Gruppe 22 gesteuert.)
Parameter 12.17 und 12.18 bestimmen die Unter- und Obergrenze des Analogeingangs-
signals. Die Skalierungsparameter 12.19 und 12.20 bestimmen die internen Signalpegel,
die diesen Grenzen wie folgt entsprechen:
Die entsprechenden Parameter für Analogeingang AI2 sind 12.2712.30.
AI (skaliert)
AI (mA / V)
12.20
12.18
12.17
12.19
32 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
13.12 AO1 Quelle
13.17 AO1 Quelle min
13.18 AO1 Quelle max
13.19 AO1 min
13.20 AO1 max
Parameter 13.12 bestimmt die Quelle für Analogausgang AO1 (standardmäßig
Motordrehzahl in U/min).
Parameter 13.17 und 13.18 setzen niedrige und hohe Quellensignalwerte, die den mit
den Parametern 13.19 und 13.20 festgelegten Istwerten der Analogausgänge
entsprechen.
46.10 Drehzahl-Skalierung
23.11 Auswahl Rampeneinstell.
23.12 Beschleunigungszeit 1
23.13 Verzögerungszeit 1
23.14 Beschleunigungszeit 2
23.15 Verzögerungszeit 2
Der Benutzer kann zwei unterschiedliche Sätze von Beschleunigungs-/Verzögerungs-
rampen festlegen. Die Quelle, die zwischen den beiden Sätzen umschaltet, wird mit
Parameter 23.11 festgelegt.
Jede in den Parametern 23.1223.15 eingestellte Beschleunigungs-/Verzögerungszeit
entspricht der Zeit, die der Frequenzumrichter zur Beschleunigung oder Verzögerung
zwischen 0 und der skalierten Drehzahl benötigt (Parameter 46.10).
Quellsignal
AO (mA)
13.18
13.20
13.19
13.17
Zeit
Drehzahl
46.10
23.12
23.14
23.13
23.15
Beschleunigung Verzögerung
0
Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 33
EN
DE
DE
FI
FR
IT
NL
RU
SV
30.11 Minimal-Drehzahl
30.12 Maximal-Drehzahl
30.17 Maximal Strom
30.19 Minimal-Moment
30.20 Maximal-Moment
Die Grenzen für Motordrehzahl, Strom und Drehmoment prüfen und gegebenenfalls
einstellen.
Den Frequenzumrichter mit einem positiven Drehzahl-Sollwert (vorwärts) starten:
Mit dem Bedienpanel (Lokalsteuerung): In der Startansicht die Taste (Optionen)
drücken, den Sollwert wählen und den Sollert mit den Tasten , ,
, und
einstellen, dann Taste Speichern drücken und mit der Start-Taste den Antrieb starten.
Mit E/A-Steuerung: Bei Fernsteuerung den Analogeingang AI1 (Sollwert) einstellen,
Digitaleingang DI2 auf 0 (vorwärts) und Digitaleingang DI1 auf 1 (Start) setzen.
34 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm
EN
DE
DE
FI
FR
IT
NL
RU
SV
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 35
EN
DE
ES
ES
FR
IT
NL
RU
SV
Guía rápida de puesta en
marcha para los
convertidores ACS880 con
programa de control primario
Acerca de esta guía
En esta guía se describe la secuencia de puesta en marcha básica de un convertidor
ACS880 equipado con el programa de control primario. Encontrará toda la
documentación del firmware del convertidor en el Manual de firmware (véase la lista
de manuales del interior de la portada).
A los efectos de esta guía, el convertidor se configura con el panel de control
ACS-AP-I. La secuencia de puesta en marcha también puede realizarse con la
herramienta para PC Drive Composer.
Antes de empezar
Asegúrese de que el convertidor esté instalado mecánica y eléctricamente de la
forma descrita en su correspondiente Guía rápida de instalación y/o Manual de
hardware.
Seguridad
¡ADVERTENCIA! Todos los trabajos de instalación eléctrica y mantenimiento
realizados en el convertidor deben ser ejecutados únicamente por electricistas
cualificados.
Nunca trabaje en el convertidor, el circuito del chopper de frenado, el cable de motor
ni el motor con la alimentación del convertidor conectada. Realice siempre una
medición para verificar que no exista tensión.
36 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
Puesta en marcha
Seguridad
La puesta en marcha sólo puede ser efectuada por un electricista cualificado.
Deben seguirse las instrucciones de seguridad durante todo el procedimiento de
puesta en marcha. Lea las instrucciones de seguridad incluidas en las primeras
páginas del Manual de hardware correspondiente.
Compruebe la instalación. Lea la lista de comprobación de la instalación en el Manual de
Hardware correspondiente.
Compruebe que la puesta en marcha del motor no suponga ningún peligro.
Desacople la maquinaria accionada si:
existe riesgo de daños en caso de una dirección de giro incorrecta, o
se necesita una marcha de ID Normal durante la puesta en marcha del convertidor,
cuando el par de carga es superior al 20% o la maquinaria no es capaz de soportar el
par nominal momentáneo durante la marcha de ID.
1 – Puesta en marcha, ajustes de fecha y hora
Ponga en marcha el convertidor.
Nota: Es normal que aparezcan mensajes
de advertencia en distintos momentos del
proceso de puesta en marcha. Para ocultar
un mensaje y reanudar el proceso de puesta
en marcha, pulse .
Oculte cualquier advertencia ahora para
entrar en la vista Inicio (que se muestra a la
derecha).
Los dos comandos de la parte inferior de la
pantalla (en este caso, Opciones y Menú),
muestran las funciones de las dos teclas
programables y situadas debajo
de la pantalla. Los comandos asignados a
las teclas programables varían en función
del contexto.
En la vista Inicio, pulse (Menú).
Aparece el Me principal (que se muestra a
la derecha).
Remote 0.0 rpm
0.00
0.00
Par motor %
%
0.0
Intensidad Motor
A
Velocidad Motor Usada
rpm
Opciones
12:34
Me
Remoto 0.0 rpm
Me
Parámetros
Asistentes
Energy Efficiency
Registro de eventos
Salir
12:34
Seleccionar
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 37
EN
DE
ES
ES
FR
IT
NL
RU
SV
Resalte Ajustes en el menú usando y
y pulse (Seleccionar).
En el menú Ajustes, resalte Fecha y hora
(si no está resaltado) y pulse
(Seleccionar).
En el menú Fecha y hora, resalte Fecha (si
no está resaltado) y pulse
(Seleccionar).
Remoto 0.0 rpm
Ajustes
Idioma
Fecha y hora
Atrás
12:34
Seleccionar
Editar textos
Ajustes de pantalla
Próximo inicio de ahorro diurno 28.03.
Remoto 0.0 rpm
Fecha y hora
Fecha
Hora
Mostrar fecha como
01.01.1980
12:34:56
día.mes.año
Mostrar hora como 24 horas
Ahorro diurno UE
Remoto 0.0 rpm
Fecha
Cancelar
12:35
Guardar
Día Mes Año
Martes
.01.198001
Ats
12:35
Editar
38 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
Ajuste la fecha correcta:
Use y para mover el cursor hacia
la izquierda y la derecha.
Use y para cambiar el valor.
•Pulse (Guardar) para aceptar el
nuevo ajuste.
Compruebe y ajuste todos los demás ajustes
del menú Fecha y hora.
El ajuste Mostrar reloj determina si debe
mostrarse la hora en todo momento en el
panel inferior de la pantalla.
Una vez hechos los ajustes, pulse
(Atrás o Salir) repetidamente hasta que
reaparezca la vista Inicio (que se muestra a
la derecha).
2 – Ajustes de tensión de alimentación y datos de motor
Cambie a control local para asegurarse de
que se ha inhabilitado el control externo.
Para ello pulse la tecla . El control
local se indica a través del texto “Local” en el
panel superior.
Vaya al Menú principal pulsando
(Menú).
Remoto 0.0 rpm
0.00
0.00
Par motor %
%
0.0
Intensidad Motor
A
Velocidad Motor Usada
rpm
Opciones
12:35
Me
Loc/Rem
Local 0.0 rpm
0.00
0.00
Par motor %
%
0.0
Intensidad Motor
A
Velocidad Motor Usada
rpm
Opciones
12:36
Me
Local 0.0 rpm
Me
Parámetros
Asistentes
Energy Efficiency
Registro de eventos
Salir
12:36
Seleccionar
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 39
EN
DE
ES
ES
FR
IT
NL
RU
SV
Resalte Parámetros y pulse
(Seleccionar).
Resalte Lista completa usando y y
pulse (Seleccionar).
Aparece una lista de grupos de parámetros.
Resalte el grupo de parámetros 95
Configuración Hardware y pulse
(Seleccionar).
Recuerde que la lista se muestra de forma
continua en ambas direcciones entre los
grupos 99 y 01. En este caso, resulta más
rápido usar para llegar al grupo 95 de la
lista.
Tras seleccionar un grupo, aparece una lista
con los parámetros del grupo.
Resalte el parámetro 95.01 Tension
Alimentacion (si no está resaltado) y pulse
(Editar).
Se enumeran los ajustes de los parámetros
disponibles.
Local 0.0 rpm
Pametros
Favoritos
Por función
Atrás
12:36
Seleccionar
Lista completa
Modificado
Local 0.0 rpm
Lista completa
01 Valores actuales
03 Entradas de Referencia
04 Alarmas y Fallos
05 Diagnósticos
06 Palabras de Control y Estado
07 Info Sistema
Atrás
12:36
Seleccionar
Local 0.0 rpm
95 Configuracion Hardware
95.01
Tension Alimentacion
Atrás
12:36
Editar
95.02 Limites Tension Adaptativos
95.04 Aliment Tarjeta Control
No se indica
Deshabilitar
24 V interna
Local 0.0 rpm
95.01 Tension Alimentacion
[0] No se indica
[1] 208…240 V
Cancelar
12:36
Guardar
[2] 380…415 V
[3] 440…480 V
[4] 500 V
40 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
Resalte el ajuste correcto en la lista y pulse
(Guardar).
Pulse (Atrás) para mostrar nuevamente la lista de grupos de parámetros.
Seleccione el grupo de parámetros 99 Datos Motor y ajuste el parámetro 99.03 Tipo de
Motor.
Ajuste el parámetro 99.04 Modo Ctrl Motor.
DTC = Control directo del par; Escalar
El DTC es adecuado en la mayoría de los casos. Se recomienda el modo escalar si:
la intensidad nominal del motor es inferior a 1/6 de la intensidad nominal del
convertidor,
el convertidor se usa con fines de prueba sin un motor conectado, o
el convertidor controla diferentes motores y el número de motores conectados varía.
Consulte la placa de características del motor para conocer los siguientes ajustes de
parámetros. Siempre que sea posible, introduzca los valores exactamente
de la forma
mostrada en la placa de características del motor.
Ejemplo de placa de características de un
motor de inducción (asíncrono):
Ejemplo de placa de características de un
motor de imanes permanentes:
Local 0.0 rpm
95 Configuracion Hardware
95.01
Tension Alimentacion
Atrás
12:36
Editar
95.02 Limites Tension Adaptativos
95.04 Aliment Tarjeta Control
380…415 V
Deshabilitar
24 V interna
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 41
EN
DE
ES
ES
FR
IT
NL
RU
SV
99.06 Intensidad Nominal Motor
El rango permisible es
en el modo DTC: 1/6 × I
Hd
… 2 × I
Hd
del convertidor
en el modo escalar: 0 … 2 × I
Hd
Nota: Con valores de parámetro numéricos:
Use y para cambiar el valor de un dígito.
Use y para mover el cursor hacia la izquierda y la derecha.
•Pulse (Guardar) para introducir el valor.
Realice los siguientes ajustes de parámetros, siguiendo el mismo método.
99.07 Tension Nominal Motor
El rango permitido es 1/6 × U
N
… 2 × U
N
del convertidor.
En el caso de los motores de imanes permanentes, la tensión nominal es la tensión
BackEMF a la velocidad nominal. Si la tensión se expresa en voltios/rpm (p. ej. 60 V por
cada 1.000 rpm), la tensión a la velocidad nominal de 3.000 rpm es de 3 × 60 V = 180 V.
Recuerde que la tensión nominal no es la misma que la tensión de CC equivalente del
motor (EDCM) indicada por algunos fabricantes. Es posible calcular la tensión nominal si
se divide la tensión EDCM por 1,7 (o la raíz cuadrada de 3).
99.08 Frecuencia Nominal Motor
En el caso de los motores de imanes permanentes, si la frecuencia nominal no aparece
en la placa de características, debe calcularse con ayuda de la siguiente formula:
f = n × p / 60
donde n = velocidad nominal del motor, p = número de pares de polos.
99.09 Velocidad Nominal Motor
99.10 Potencia Nominal Motor
99.11 Cosfi Nominal Motor
99.12 Par Nominal Motor
Estos valores no son obligatorios, pero pueden introducirse para aumentar la exactitud
del control. Si los desconoce, deje el valor 0.
42 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
99.13 Peticion Marcha Ident
Este parámetro selecciona el modo de la marcha de identificación (sólo en el modo DTC
de control de motor).
¡ADVERTENCIA! Los modos de marcha de identificación marcados con * hacen
que el motor se mueva en el sentido de avance (para más detalles, véase la
información que aparece a continuación). Asegúrese de que resulte seguro poner en
marcha el motor antes de seleccionar cualquiera de estos modos.
*Siempre que sea posible, debe seleccionarse el modo Normal. La maquinaria
accionada debe desacoplarse del motor si
el par de carga es superior al 20%, o
la maquinaria no puede resistir la oscilación del par nominal durante la marcha de
identificación.
*El modo Reducido debe seleccionarse si las pérdidas mecánicas son superiores al
20%, es decir, si no es posible desacoplar la carga o si se requiere un flujo completo para
mantener abierto el freno del motor (por ejemplo en el caso de los motores cónicos).
El modo En reposo debe seleccionarse si no es posible utilizar los modos *Normal ni
*Reducido. Notas:
Este modo no puede usarse en el caso de los motores de imanes permanentes si el
par de carga es superior al 20% del valor nominal.
El freno mecánico no es abierto por la lógica para la marcha de identificación.
Asegúrese de que los circuitos de la función Safe Torque Off y de paro de emergencia
estén cerrados (si los hubiere).
Inicie la marcha de identificación pulsando el
botón (Marcha).
Aparecerá una advertencia para indicar
que la marcha de identificación está en
curso.
Compruebe que el motor funcione en el sentido correcto
(el sentido de avance mostrado abajo).
La marcha de identificación se ha completado cuando el convertidor se detiene y el valor
del parámetro 99.13 vuelve a ser “No”.
Si el motor funcionó en el sentido incorrecto, corrija el cableado del motor o ajuste el
parámetro 99.16 Orden Fases.
3 – Ajustes de señal de control
Compruebe las posiciones de los puentes J1 y J2 en la unidad de control del convertidor.
Estos puentes determinan si las entradas analógicas AI1 y AI2 son de intensidad o de
tensión.
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 43
EN
DE
ES
ES
FR
IT
NL
RU
SV
Compruebe/ajuste los siguientes parámetros.
20.01 Ext1 Marcha/Paro/Dir
Por defecto, el convertidor se pone en marcha o se detiene en función del estado de la
entrada digital DI1 (0 = Paro, 1 = Marcha). DI2 determina el sentido de giro (0 = Avance,
1 = Retroceso).
Si se requieren otras fuentes, cambie el valor según corresponda. Las fuentes In1In3
se definen con los parámetros 20.0320.05.
12.15 AI1 Seleccion Unidad
Cambie este ajuste a mA o V en función del ajuste del puente J1.
12.17 AI1 Min
12.18 AI1 Max
12.19 AI1 Escala en AI1 Min
12.20 AI1 Escala en AI1 Max
La entrada por defecto para la referencia de velocidad es la entrada analógica AI1.
(Se controla con los parámetros del grupo 22.)
Los parámetros 12.17 y 12.18 establecen los límites bajo y alto de la señal de entrada
analógica. Los parámetros de escala 12.19 y 12.20 definen de la siguiente forma los
niveles de señal internos que corresponden a estos límites:
Los parámetros correspondientes para la entrada analógica AI2 son 12.2712.30.
AI (escalada)
AI (mA/V)
12.20
12.18
12.17
12.19
44 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
13.12 AO1 Fuente
13.17 AO1 Fuente Min
13.18 AO1 Fuente Max
13.19 AO1 mA en Fuente Min
13.20 AO1 mA en Fuente Max
El parámetro 13.12 selecciona el origen de la salida analógica AO1 (por defecto, la
velocidad del motor en rpm).
Los parámetros 13.17 y 13.18 definen los valores bajo y alto de señal de origen que se
corresponden con los valores de salida analógica actuales definidos por los parámetros
13.19 y 13.20.
46.10 Escalado Velocidad
23.11 Seleccion Rampa 1/2
23.12 Tiempo Aceleracion 1
23.13 Tiempo Deceleracion 1
23.14 Tiempo Aceleracion 2
23.15 Tiempo Deceleracion 2
Usted puede definir dos conjuntos diferentes de rampas de aceleración/deceleración. La
fuente que conmuta entre los dos conjuntos se selecciona con el parámetro 23.11.
Los distintos conjuntos de tiempos de aceleración/deceleración de los parámetros
23.1223.15 se refieren al tiempo que el convertidor necesita para acelerar o decelerar
entre 0 y la velocidad de escalado (parámetro 46.10).
Señal fuente
AO (mA)
13.18
13.20
13.19
13.17
Tiempo
Velocidad
46.10
23.12
23.14
23.13
23.15
Acel. Decel.
0
Guía rápida de puesta en marcha para los convertidores ACS880 con programa de
control primario 45
EN
DE
ES
ES
FR
IT
NL
RU
SV
30.11 Velocidad Minima
30.12 Velocidad Maxima
30.17 Intensidad Maxima
30.19 Par Minimo
30.20 Par Maximo
Compruebe y ajuste en caso necesario los límites de velocidad del motor, intensidad y
par.
Ponga en marcha el convertidor con una referencia de velocidad positiva (avance):
Desde el panel de control (control local): En la vista Inicio, pulse (Opciones),
seleccione Referencia, ajuste la referencia con las teclas , ,
, y , pulse
Guardar y pulse el botón Inicio.
Desde E/S: En el control remoto, ajuste la entrada analógica AI1 (referencia), cambie
la entrada digital DI2 a 0 (avance) y cambie la entrada digital DI1 a 1 (marcha).
46 Guía rápida de puesta en marcha para los convertidores ACS880 con programa
de control primario
EN
DE
ES
ES
FR
IT
NL
RU
SV
Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 47
EN
DE
ES
FI
FI
IT
NL
RU
SV
Pika-aloitusopas perusohja-
usohjelmalla varustetuille
ACS880-taajuusmuuttajille
Johdanto
Tässä oppaassa kuvataan perusohjausohjelmalla varustetun ACS880-
taajuusmuuttajan käyttöönoton perustoimenpiteet. Kattavat tiedot taajuusmuuttajan
ohjelmistosta on ohjelmointioppaassa (käyttöoppaat on lueteltu etukannen
sipuolella).
Tässä oppaassa taajuusmuuttajan asetukset määritetään ACS-AP-I-ohjauspaneelin
avulla. Käyttöönoton toimenpiteet voidaan suorittaa myös Drive composer -PC-
työkalun avulla.
Ennen käynnistystä
Varmista, että taajuusmuuttajan mekaaninen asennus ja sähasennus on suoritettu
asianmukaisessa pika-asennusoppaassa ja/tai laiteoppaassa kuvatulla tavalla.
Turvallisuus
VAROITUS! Taajuusmuuttajan sähköliitännät ja huoltotyöt saa suorittaa vain
pätevä sähköalan ammattilainen.
Mitään taajuusmuuttajan, jarrukatkojan, moottorikaapelin tai moottorin asennustöitä
ei saa tehdä, kun taajuusmuuttajaan on kytketty jännite. Taajuusmuuttajan
jännitteettömyys tulee aina varmistaa mittaamalla.
48 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille
EN
DE
ES
FI
FI
IT
NL
RU
SV
Käyttöönotto
Turvallisuus
Käyttöönoton saa suorittaa vain pätevä sähköalan ammattilainen.
Käyttöönoton aikana on noudatettava turvaohjeita. Turvaohjeet ovat vastaavan
laiteoppaan alussa.
Tarkista asennus. Laiteoppaassa on asennuksen tarkistuslista.
Varmista, ettei moottorin käynnistäminen aiheuta vaaraa.
Kytke käytettävä laite irti,
jos väärä pyörimissuunta voi aiheuttaa vahinkoa tai
jos taajuusmuuttajan käyttöönoton yhteydessä on suoritettava normaali tunnistusajo,
kuormamomentti on suurempi kuin 20 prosenttia tai laitteisto ei kestä tunnistusajon
aikana esiintyvää nimellistä momenttia.
1 – Virran kytkeminen, , päivämäärän ja ajan asetukset
Kytke taajuusmuuttajan virta.
Huomautus: On normaalia, että
käyttöönoton aikana näyttöön tulee
varoitusviestejä useassa eri vaiheessa. Voit
piilottaa viestin ja jatkaa käyttöönottoa
painamalla -painiketta.
Piilota nyt kaikki varoitukset, jotta pääset
kotinäyttöön (näkyy oikealla).
Näytön alareunan kaksi komentoa (tässä
tapauksessa Valinnat ja Valikko), osoittavat
näytön alla olevien kahden valintapainikkeen
ja toiminnot. Valintapainikkeilla
annettavat komennot vaihtelevat tilanteen
mukaan.
Paina kotinäytössä -painiketta
(Valikko).
Näyttöön tulee Valikko (oikealla).
Kauko 0.0 kierr./min
0.00
0.00
Moottorin momentti %
%
0.0
Moottorin virta
A
Moottorin nopeus ytetty
kierr./min
Valinnat
12:34
Valikko
Kauko 0.0 kierr./min
Valikko
Parametrit
Assistantit
Energiatehokkuus
Tapahtumaloki
Lopeta
12:34
Valitse
Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 49
EN
DE
ES
FI
FI
IT
NL
RU
SV
Korosta Asetukset valikosta - tai -
painikkeella ja paina -painiketta
(Valitse).
Korosta Asetukset-valikossa Päiväys ja
kellonaika (jos se ei näy korostettuna) ja
paina -painiketta (Valitse).
Korosta Päiväys-valikossa Päiväys ja
kellonaika (jos se ei näy korostettuna) ja
paina -painiketta (Valitse).
Kauko 0.0 kierr./min
Asetukset
Kieli
Päiväys ja kellonaika
Takaisin
12:34
Valitse
Muokkaa tekstejä
Näytön asetukset
Seuraavan kesäajan alku 28.03.
Kauko 0.0 kierr./min
Päiväys ja kellonaika
iväys
Takaisin
12:35
Muokkaa
Aika
Päivämäärän näyttötapa
01.01.1980
12:34:56
pp.kk.vv
Ajan näyttötapa 24-tuntinen
Daylight saving EU
Kauko 0.0 kierr./min
Päiväys
Peruuta
12:35
Tallenna
Päivä Kuuk. Vuosi
Tiistai
.01.198001
50 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille
EN
DE
ES
FI
FI
IT
NL
RU
SV
Aseta oikea päivämäärä:
Siirrä kohdistinta vasemmalle ja oikealle
- ja -painikkeilla.
Muuta arvoa - ja -painikkeilla.
Hyväksy uusi asetus painamalla -
painiketta (Tallenna).
Tarkista loput iväys ja kellonaika -valikon
asetukset.
Näytä kello -asetus määrittää, näytetäänkö
aika aina näytön alareunassa.
Kun olet määrittänyt asetukset, paina -
painiketta (Takaisin tai Lopeta) toistuvasti,
kunnes kotinäyttö (oikealla) tulee
uudestaan näyttöön.
2 – Syöttöjännitteen ja moottoritietojen asetukset
Varmista, että ulkoinen ohjaus on poistettu
käytöstä: vaihda paikallisohjaukseen
painamalla ohjauspaneelin -painiketta.
Paikallisohjaus on ilmaistu näytön
yläreunassa näkyvällä Paikallinen-tekstillä.
Avaa Valikko painamalla -painiketta
(Valikko).
Kauko 0.0 kierr./min
0.00
0.00
Moottorin momentti %
%
0.0
Moottorin virta
A
Moottorin nopeus ytetty
kierr./min
Valinnat
12:35
Valikko
Loc/Rem
Paikallinen 0.0 kierr./min
0.00
0.00
Moottorin momentti %
%
0.0
Moottorin virta
A
Moottorin nopeus ytetty
kierr./min
Valinnat
12:36
Valikko
Paikallinen 0.0 kierr./min
Valikko
Parametrit
Assistantit
Energiatehokkuus
Tapahtumaloki
Lopeta
12:36
Valitse
Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 51
EN
DE
ES
FI
FI
IT
NL
RU
SV
Korosta vaihtoehto Parametrit ja paina
-painiketta (Valitse).
Korosta Täydellinen luettelo - tai -
painikkeella ja paina -painiketta
(Valitse).
Näyttöön tulee parametriryhmien luettelo.
Korosta parametriryhmä 95 Laitteiston
konfigurointi ja paina -painiketta
(Valitse).
Huomaa, että lista pyörii ympäri ryhmien 99
ja 01 välillä. Ryhmän 95 voi siis hakea
nopeasti -painikkeella.
Kun ryhmä on valittu, näyttöön tulee luettelo
ryhmän sisäisistä parametreista.
Korosta parametri 95.01 Syöttöjännite (jos
sitä ei ole jo korostettu) ja paina -
painiketta (Muokkaa).
Käytettävissä olevat parametriasetukset on
lueteltu.
Paikallinen 0.0 kierr./min
Parametrit
Suosikit
Toiminnon mukaan
Takaisin
12:36
Valitse
Täydellinen luettelo
Muokattu
Paikallinen 0.0 kierr./min
Täydellinen luettelo
01 Oloarvot
03 Tulon ohjearvot
04 Varoitukset ja viat
05 Vianhaku
06 Ohjaus- ja tilasanat
07 Järjestelmän tiedot
Takaisin
12:36
Valitse
Paikallinen 0.0 kierr./min
95 Laitteiston konfigurointi
95.01 Syöttöjännite
Takaisin
12:36
Muokkaa
95.02 Adapt. jänniterajat
95.04 Ohj.kortin syöttö
Ei annettu
Poista käyt.
Sisäinen 24 V
Paikallinen 0.0 kierr./min
95.01 Syöttöjännite
[0] Ei annettu
[1] 208…240 V
Peruuta
12:36
Tallenna
[2] 380…415 V
[3] 440…480 V
[4] 500 V
52 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille
EN
DE
ES
FI
FI
IT
NL
RU
SV
Korosta oikea asetus luettelosta ja paina
-painiketta (Tallenna).
Palaa parametriryhmien luetteloon painamalla -painiketta (Takaisin). Valitse
parametriryhmä 99 Moottorin tiedot ja aseta parametri 99.03 Moottorin tyyppi.
Aseta parametri 99.04 Moottorisäätötila.
DTC = suora momentinsäätö; Skalaari
DTC on sopiva useimmissa tapauksissa. Skalaarisäätöä suositellaan, jos
moottorin nimellisvirta on alle 1/6 taajuusmuuttajan nimellisvirrasta
taajuusmuuttajaa käytetään testitarkoituksiin ilman moottoria tai
taajuusmuuttaja ohjaa useita moottoreita ja kytkettyjen moottorien määrä vaihtelee.
Tarkista seuraavat parametriasetukset moottorin arvokilvestä. Syötä arvot tarkalleen
moottorin
arvokilvessä kuvatulla tavalla, mikäli mahdollista.
Esimerkki epätahtimoottorin arvokilvestä: Esimerkki kestomagneettimoottorin
arvokilvestä:
99.06 Moottorin nimellisvirta
Sallittu alue on
DTC-tilassa: 1/6 × I
Hd
… 2 × I
Hd
taajuusmuuttajasta
Skalaaritilassa: 0 … 2 × I
Hd
Huomautus: Kun parametriarvo on numero:
Muuta arvoa - ja -painikkeilla.
Siirrä kohdistinta vasemmalle ja oikealle - ja -painikkeilla.
Syötä arvo painamalla -painiketta (Tallenna).
Paikallinen 0.0 kierr./min
95 Laitteiston konfigurointi
95.01 Syöttöjännite
Takaisin
12:36
Muokkaa
95.02 Adapt. jänniterajat
95.04 Ohj.kortin syöttö
380…415 V
Poista käyt.
Sisäinen 24 V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 53
EN
DE
ES
FI
FI
IT
NL
RU
SV
Tee seuraavat parametriasetukset samalla tavalla.
99.07 Moottorin nimellisjännite
Sallittu alue on 1/6 × U
N
… 2 × U
N
taajuusmuuttajan jännitteeseen verrattuna.
Kestomagneettimoottoreissa nimellisjännite on BackEMF-jännite moottorin
nimellisnopeudella. Jos jännite annetaan voltteina kierroslukua kohden (esim. 60 V / 1000
rpm), jännite 3 000 rpm:n nimellisnopeudella on 3 × 60 V = 180 V. Huomaa, että
nimellisjännite ei ole sama kuin joidenkin valmistajien ilmoittama moottorin DC-jännite
(EDCM). Nimellisjännite voidaan laskea jakamalla EDCM-jännite 1,7:llä (kolmen
neliöjuurella).
99.08 Moottorin nimellistaajuus
Jos kestomagneettimoottorin nimellistaajuutta ei ole merkitty arvokilpeen, se voidaan
laskea seuraavalla kaavalla:
f = n × p / 60
jossa n = moottorin nimellisnopeus, p = napaparien määrä.
99.09 Moottorin nimellisnopeus
99.10 Moottorin nimellisteho
99.11 Moottorin nimellinen cosfii
99.12 Moottorin nimellismomentti
Nämä arvot eivät ole pakollisia, mutta voidaan syöttää ohjaustarkkuuden parantamiseksi.
Jos arvot eivät ole tiedossa, jätä arvoksi 0.
99.13 Tunnistusajopyyntö
Tällä parametrilla valitaan tunnistusajon tila (vain DTC-moottoriohjaustilassa).
VAROITUS! Tunnistusajon tilat, joissa on merkintä *, pyörittävät moottoria
eteenpäin (lisätietoja alla). Varmista ennen näiden tilojen valitsemista, että
moottorin pyörittäminen on turvallista.
*Normaali tila kannattaa valita aina, kun se on mahdollista. Moottori on kytkettävä irti
käytetystä laitteesta, jos
kuormamomentti on suurempi kuin 20 prosenttia tai
laitteisto ei kestä tunnistusajon aikana esiintyvää nimellistä momenttia.
*Supistettu tila tulee valita, jos mekaaniset häviöt ylittävät 20 prosenttia eli kuormaa ei
voi kytkeä irti, tai moottorin jarrun auki pitämiseen tarvitaan täysi vuo (esimerkiksi
kartiojarrumoottoreilla).
Paikallaanajotila tulee valita, jos *normaalia tai *supistettua tilaa ei voi käyttää.
Huomautukset:
Tätä tilaa ei voi käyttää kestomagneettimoottoreilla, jos kuorman momentti on yli 20
prosenttia nimellisarvosta.
Logiikka ei avaa mekaanista jarrua tunnistusajoa varten.
Varmista, että Safe torque off- ja hätäpysäytyspiirit (jos käytössä) ovat suljettuina.
Käynnistä moottori painamalla
(Käynnistys) -painiketta.
Varoitus ilmoittaa, että tunnistusajo on
käynnissä.
54 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille
EN
DE
ES
FI
FI
IT
NL
RU
SV
Tarkista, että moottori pyörii oikeaan suuntaan (eteen alla olevassa kuvassa esitetyllä
tavalla).
Tunnsitusajo on suoritettu, kun taajuusmuuttaja pysähtyy ja parametrin 99.13 arvoksi
palaa Ei.
Jos moottori pyörii väärään suuntaan, korjaa moottorin kaapelointi tai säädä parametria
99.16 Vaihejärjestys.
3 – Ohjaussignaalin asetukset
Tarkista taajuusmuuttajan ohjausyksikön siirtoliittimien J1 ja J2 asennot. Nämä
siirtoliittimet määrittävät, ovatko analogiatulot AI1 ja AI2 virta- vai jännitetuloja.
Tarkista/säädä seuraavat parametrit.
20.01 Ulk1 komennot
Oletusarvoisesti taajuusmuuttaja käynnistyy/pysähtyy digitaalitulon DI1 tilan mukaisesti
(0 = pysäytys, 1 = käynnistys). DI2 määrittää pyörimissuunnan (0 = eteen, 1 = taakse).
Jos muita lähteitä tarvitaan, muuta arvoa sen mukaisesti. Lähteet In1In3äritetään
parametreilla 20.0320.05.
12.15 AI1 yksikön valinta
Määritä asetukseksi mA tai V siirtoliittimen J1 asetuksen mukaisesti.
12.17 AI1 min.
12.18 AI1 maks.
12.19 AI1 skaalattu AI1-minimiin
12.20 AI1 skaalattu AI1-maksimiin
Nopeusohjeen oletustulo on analogiatulo AI1. (Tämä valitaan ryhmän 22 parametreilla.)
Parametrit 12.17 ja 12.18 määrittävät analogiatulon signaalin ala- ja ylärajat.
Skaalausparametrit 12.19 ja 12.20 määrittävät sisäiset signaalitasot, jotka vastaavat
rajoja seuraavasti:
Vastaavat parametrit analogiatulolle AI2 ovat 12.2712.30.
AI (skaalattu)
AI (mA/V)
12.20
12.18
12.17
12.19
Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 55
EN
DE
ES
FI
FI
IT
NL
RU
SV
13.12 AO1 lähde
13.17 AO1 lähteen minimi
13.18 AO1 lähteen maksimi
13.19 AO1 out at AI1 src min
13.20 AO1 out at AI1 src max
Parametrilla 13.12 valitaan lähde analogiatulolle AO1 (oletusarvo on moottorin nopeus
kierroksina minuutissa).
Parametreilla 13.17 ja 13.18 asetetaan lähdesignaalin ala- ja ylärajan arvot, jotka
vastaavat parametreilla 13.19 ja 13.20äritettyjä analogiatulon oloarvoja.
46.10 Nopeuden skaalaus
23.11 Ramppiasetuksen valinta
23.12 Kiihdytysaika 1
23.13 Hidastusaika 1
23.14 Kiihdytysaika 2
23.15 Hidastusaika 2
Voit määrittää kaksi eri kiihdytys-/hidastusaikaa. Kahden eri ajan välillä vaihteleva lähde
valitaan parametrilla 23.11.
Jokainen parametreilla 23.1223.15 määritetty kiihdytys-/hidastusaika viittaa aikaan,
jonka kuluessa taajuusmuuttaja kiihdyttää nollasta skaalattavaan nopeuteen tai hidastaa
skaalatusta nopeudesta nollaan (parametri 46.10).
Lähdesignaali
AO (mA)
13.18
13.20
13.19
13.17
Aika
Nopeus
46.10
23.12
23.14
23.13
23.15
Kiihd. Hid.
0
56 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille
EN
DE
ES
FI
FI
IT
NL
RU
SV
30.11 Miniminopeus
30.12 Maksiminopeus
30.17 Maksimivirta
30.19 Minimimomentti
30.20 Maksimimomentti
Tarkista ja tarvittaessa aseta moottorin nopeuden, virran ja momentin rajat.
Käynnistä taajuusmuuttaja positiivisella nopeusohjeella (eteen):
Ohjauspaneelista (paikallisohjaus): Paina kotinäkymäs -painiketta (Valinnat),
valitse Ohje, säädä ohjetta -, -,
- ja -painikkeilla, valitse Tallenna ja paina
käynnistyspainiketta.
I/O-ohjauksesta: Säädä kauko-ohjauksessa analogiatuloa AI1 (ohje), aseta
digitaalitulon DI2 arvoksi 0 (eteen) ja digitaalitulon DI1 arvoksi 1 (käynnistys).
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 57
EN
DE
ES
FI
FR
FR
NL
RU
SV
Guide de mise en route pour
l'ACS880 avec programme de
contrôle standard
Introduction
Ce guide présente sommairement la séquence de mise en route d'un variateur
ACS880 équipé du programme de contrôle standard. Vous trouverez une
documentation complète dans le manuel d'exploitation (Firmware Manual) (cf. liste
des manuels au dos de la page de couverture).
Dans ce guide, nous décrivons la configuration du variateur avec la micro-console
ACS-AP-I. La séquence de mise en route peut aussi être effectuée à l'aide de l'outil
logiciel PC Drive composer.
Avant de commencer
Vérifiez que le montage et les raccordements du variateur sont conformes aux
consignes du Guide d'installation et/ou du Manuel d'installation approprié.
Sécurité
ATTENTION ! Seuls des électriciens qualifiés sont autorisés à procéder à
l'installation et à la maintenance du variateur.
N'intervenez jamais sur le variateur, le circuit du hacheur de freinage, le câble moteur
ou le moteur lorsque le variateur est sous tension. Vous devez toujours vérifier
l'absence effective de tension par une mesure.
58 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
Mise en route
Sécurité
La mise en route doit uniquement être réalisée par un électricien qualifié.
Les consignes de sécurité doivent être respectées pendant toute la procédure. Ces
consignes figurent au début du Manuel d’installation correspondant.
Vérification de l'installation de l'appareil Cf. liste des points à vérifier dans le Manuel
d'installation correspondant.
Vérifiez que le moteur peut être démarré en toute sécurité.
Vous devez désaccoupler la machine entraînée dans les cas suivants :
si elle risque d'être endommagée en cas d'erreur de sens de rotation du moteur ou
si une identification normale du moteur est requise : si le couple de charge est
supérieur à 20 % ou si la mécanique n’est pas capable de supporter le couple nominal
sur une période transitoire lors de l’exécution de la fonction d’identification moteur.
1 - Mise sous tension, réglage de la de la date et de l'heure
Mettez le variateur sous tension.
N.B. : Il est normal que des messages
d'alarme s'affichent à divers moments de la
procédure de mise en route. Pour masquer
un message et continuer la procédure,
appuyez sur .
Masquez toutes les alarmes éventuelles
pour passer en vue Accueil (affichée à
droite).
Les deux commandes en bas de l'écran
(dans ce cas, Options et Menu)
représentent les fonctions des deux touches
et situées sous l'écran. Les
commandes des touches de fonction varient
selon le contexte.
Dans la vue Accueil, enfoncez la touche
(Menu).
Le menu principal apparaît (à droite).
Distant 0.0 tr/min
0.00
0.00
Couple moteur %
%
0.0
Courant moteur
A
Vitesse moteur utilisee
tr/min
Options
12:34
Menu
Distant 0.0 tr/min
Menu
Paramètres
Assistants
Efficacité énergétique
Pile Événements
Sortie
12:34
Sel
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 59
EN
DE
ES
FI
FR
FR
NL
RU
SV
Mettez Réglages en surbrillance en
naviguant à l'aide des touches et puis
enfoncez la touche (Sel)
Dans le menu Reglages, mettez Date &
Heure en surbrillance (si ce n'est pas encore
le cas) et enfoncez (Sel).
Dans le menu Date & Heure, mettez Date
en surbrillance (si ce n'est pas encore le cas)
et enfoncez (Sel).
Distant 0.0 tr/min
Réglages
Langue
Date & Heure
Retour
12:34
Sel
Edition textes
Réglages affichage
Prochain passage heure d'été 28.03.
Distant 0.0 tr/min
Date & Heure
Date
Retour
12:35
Edition
Heure
Format date
01.01.1980
12:34:56
jour.mois.année
Format heure 24 heures
Heure d'été UE
Distant 0.0 tr/min
Date
Annuler
12:35
Sauvegarder
Jour Mois Année
Mardi
.01.198001
60 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
Réglez la date :
placez le curseur vers la droite ou la
gauche avec les touches et .
Ajustez la valeur avec et .
Sauvegardez votre réglage avec
(Sauvegarder).
Vérifiez et ajustez au besoin tous les autres
réglage du menu Date & Heure.
Le réglage Visu horloge vous permet de
choisir si vous voulez afficher l'heure en bas
de l'écran en permanence.
Une fois le réglage effectué, enfoncez la
touche (Retour ou Sortie) jusqu'à
revenir à la vue Accueil (à droite).
2 - Réglage de la tension réseau et des données moteur
Sélectionnez le mode de commande Local
pour vous assurer que la commande à
distance est désactivée. Pour cela, enfoncez
la touche . Lorsque le variateur est en
commande locale, «Local» s'affiche en haut
de l'écran.
Ouvrez le menu principal en enfonçant la
touche (Menu).
Distant 0.0 tr/min
0.00
0.00
Couple moteur %
%
0.0
Courant moteur
A
Vitesse moteur utilisee
tr/min
Options
12:35
Menu
Loc/Rem
Local 0.0 tr/min
0.00
0.00
Couple moteur %
%
0.0
Courant moteur
A
Vitesse moteur utilisee
tr/min
Options
12:36
Menu
Local 0.0 tr/min
Menu
Paramètres
Assistants
Efficacité énergétique
Pile Événements
Sortie
12:36
Sel
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 61
EN
DE
ES
FI
FR
FR
NL
RU
SV
Mettez Paramètres en surbrillance et
enfoncez la touche (Sel).
Mettez Liste complète en surbrillance à
l'aide des touches et puis enfoncez la
touche (Sel)
La liste des groupes de paramètres s'affiche.
Mettez le groupe de paramètres 95
Configuration materiel en surbrillance et
enfoncez la touche (Sel).
La liste défile dans les deux sens entre les
groupes de paramètres 99 et 01. Dans ce
cas, il est donc plus rapide d'utiliser pour
atteindre le groupe 95.
Une fois le groupe sélectionné, la liste des
paramètres de ce groupe s'affiche.
Mettez le paramètre 95.01 Tension reseau
en surbrillance (s'il ne l'est pas déjà) et
enfoncez (Edition).
La liste des réglages disponibles s'affiche.
Local 0.0 tr/min
Paratres
Favoris
Par fonction
Retour
12:36
Sel
Liste complète
Modifie
Local 0.0 tr/min
Liste complète
01 Valeurs actives
03 References entree
04 Alarmes et defauts
05 Diagnostic
06 Mots de commande et etat
07 Info système
Retour
12:36
Sel
Local 0.0 tr/min
95 Configuration materiel
95.01 Tension reseau
Retour
12:36
Edition
95.02 Limite tension adaptative
95.04 Alim carte commande
Vide
Desactive
Interne 24V
Local 0.0 tr/min
95.01 Tension reseau
[0] Vide
[1] 208…240 V
Annuler
12:36
Sauvegarder
[2] 380…415 V
[3] 440…480 V
[4] 500 V
62 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
Mettez en surbrillance le réglage correct et
enfoncez la touche (Sauvegarder).
Enfoncez (Retour) pour afficher la liste des groupes de paramètres. Sélectionnez
le groupe de paramètre 99 Donnees moteur et réglez le paramètre 99.03 Type moteur.
Réglez le paramètre 99.04 Mode commande moteur.
DTC = Contrôle direct de couple ; Scalaire
Le mode DTC est parfaitement adapté à la plupart des applications. Le mode Scalaire est
préconisé si :
le courant nominal du moteur est inférieur à 1/6 du courant de sortie nominal du
variateur ;
le variateur est utilisé à des fins d’essais sans moteur raccordé ;
le variateur commande plusieurs moteurs et le nombre de moteurs raccordés est
variable.
Reportez-vous à la plaque signalétique du moteur pour régler les paramètres suivants. Vous
devez autant que possible entrer les valeurs exactes
de la plaque signalétique du moteur.
Exemple de plaque signalétique d'un moteur
asynchrone :
Exemple de plaque signalétique d'un
moteur à aimants permanents :
Local 0.0 tr/min
95 Configuration materiel
95.01 Tension reseau
Retour
12:36
Edition
95.02 Limite tension adaptative
95.04 Alim carte commande
380…415 V
Desactive
Interne 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 63
EN
DE
ES
FI
FR
FR
NL
RU
SV
99.06 Courant nominal moteur
Plage de réglage autorisée :
en mode DTC : 1/6 × I
int
… 2 × I
int
du variateur
en mode Scalaire : 0 … 2 × I
int
N.B. : Avec des valeurs numériques :
Incrémentez et décrémentez les valeurs avec les touches et .
Déplacez le curseur vers la droite ou la gauche avec les touches et .
Enfoncez (Sauvegarder) pour enregistrer la valeur.
Procédez de la même manière pour régler les autres paramètres.
99.07 Tension nominale moteur
La plage de réglage autorisée est 1/6 × U
N
… 2 × U
N
du variateur.
Moteurs à aimants permanents : la tension nominale est la tension inverse FEM
(BackEMF) à la vitesse nominale. Si la tension est spécifiée par tr/min (ex., 60 V pour
1000 tr/min), la tension pour une vitesse nominale de 3000 tr/min est 3 × 60 V = 180 V.
Vous noterez que la tension nominale n’est pas égale à la valeur de tension d’un moteur
c.c. équivalent donnée par certains constructeurs de moteur La tension nominale peut
être calculée en divisant la tension d’un moteur c.c. équivalent par 1,7 (= racine carrée de
3).
99.08 Fréquence nominale moteur
Moteurs à aimants permanents : si la fréquence nominale ne figure pas sur la plaque
signalétique du moteur, elle doit être calculée avec la formule suivante :
f = n × p / 60
avec n = vitesse nominale moteur et p = nombre de paires de pôles.
99.09 Vitesse nominale moteur
99.10 Puissance nominale moteur
99.11 Cosfii nominal moteur
99.12 Couple nominal moteur
Ces valeurs sont facultatives mais peuvent améliorer la précision de la commande. Si
vous ne les connaissez pas, n'indiquez rien.
64 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
99.13 Demande identif moteur
Ce paramètre sélectionne le type d'identification moteur (en mode DTC uniquement).
ATTENTION ! Lorsque le mode d'identification est précédé d'un astérisque (*), le
moteur tournera dans le sens avant (voir détails ci-dessous). Vous devez vous
assurer qu'il peut fonctionner en toute sécurité avant de choisir un de ces modes.
Le mode *Normal doit être sélectionné chaque fois que cela est possible. Le moteur doit
être désaccouplé de la machine entraînée
si le couple de charge est supérieur à 20 % ou
si la machine n’est pas capable de supporter le couple nominal sur une période
transitoire lors de l’exécution de la fonction.
*Le mode Reduced doit être sélectionné si les pertes mécaniques sont supérieures à
20 %, par exemple s'il est impossible de désaccoupler la charge ou si un flux complet est
exigé pour maintenir le frein moteur ouvert (moteur conique).
Le mode Standstill convient si vous ne pouvez utiliser ni le mode *Normal ni le mode
*Reduced. N.B. :
Vous ne devez pas utiliser ce mode avec un moteur à aimants permanents si le couple
de charge est supérieur à 20 % du couple nominal.
Le frein mécanique n'est pas ouvert par la logique de la fonction d'identification moteur.
Vérifiez que les éventuels circuits d’Interruption sécurisée du couple (STO) et d'arrêt
d'urgence sont fermés.
Lancez l'identification moteur en enfonçant
la touche (Start).
Une alarme vous indique que
l'identification est en cours.
Vérifiez que le moteur tourne dans le bon sens (sens avant illustré ci-dessous).
L'identification moteur est terminée lorsque le variateur s'arrêt et que la valeur du
paratre 99.13 revient sur «Non»
Si le moteur a tourné dans le mauvais sens, rectifiez sont câblage ou modifier le réglage
du paramètre 99.16 Ordre des phases.
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 65
EN
DE
ES
FI
FR
FR
NL
RU
SV
3 – Réglage des signaux de commande
Vérifiez l'emplacement des cavaliers J1 et J2 sur l'unité de commande du variateur. Leur
position détermine l'utilisation des entrées analogiques 1 et 2 (courant ou tension).
Réglez/ajustez les paramètres suivants.
20.01 Commandes Ext1
Le variateur est préréglé pour démarrer/s'arrêter selon le statut de l'entrée logique 1 (DI1)
(0 = arrêt ; 1 = démarrage). L'entrée logique 2 (DI2) règle le sens de rotation (0 = avant ;
1 = arrière).
Si vous souhaitez utiliser d'autres sources, réglez les valeurs en conséquence. Les
sources Src1 à Src3 sont réglées aux paramètres 20.03 à 20.05.
12.15 Selection unite AI1
Choisissez mA ou V selon le réglage du cavalier J1.
12.17 Mini AI1
12.18 Maxi AI1
12.19 Mini echelle AI1
12.20 Maxi echelle AI1
La référence de vitesse est préréglée sur l'entrée analogique 1 (AI1). (réglage commandé
par les paramètres du groupe 22)
Les paramètres 12.17 et 12.18finissent les limites haute et basse du signal d'entrée
analogique. Les paramètres de mise à l'échelle 12.19 et 12.20 règlent le niveau de signal
interne correspondant à ces limites comme suit :
Les paramètres correspondants pour l'entrée analogique 2 (AI2) sont 12.2712.30.
AI (mise à l'échelle)
AI (mA / V)
12.20
12.18
12.17
12.19
66 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
13.12 Source AO1
13.17 Mini source AO1
13.18 Maxi source AO1
13.19 Valeur mini sortie AO1
13.20 Valeur maxi sortie AO1
Le paramètre 13.12lectionne la source pour l'entrée analogique 1 (AO1). Le
préréglage usine est la vitesse moteur en tr/min.
Les paramètres 13.17 et 13.18 règlent les valeurs haute et basse des signaux sources
correspondant aux valeurs actives des sorties analogiques définies aux paramètres
13.19 et 13.20.
46.10 Echelle vitesse
23.11 Selection jeu rampe
23.12 Temps acceleration 1
23.13 Temps deceleration 1
23.14 Temps acceleration 2
23.15 Temps deceleration 2
Vous pouvez définir deux jeux de rampe d'accélération/décélération. Indiquez la source
pour la permutation entre les deux jeux au paramètre 23.11.
Chaque jeu de temps d'accélération/décélération des paramètres 23.12 à 23.15 indique
le temps nécessaire au variateur pour passer de la vitesse nulle à la vitesse mise à
l'échelle (paramètre 46.10).
Signal source
AO (mA)
13.18
13.20
13.19
13.17
Temps
Vitesse
46.10
23.12
23.14
23.13
23.15
Acc. Déc.
0
Guide de mise en route pour l'ACS880 avec programme de contrôle standard 67
EN
DE
ES
FI
FR
FR
NL
RU
SV
30.11 Vitesse minimum
30.12 Vitesse maximum
30.17 Courant maximum
30.19 Couple minimum
30.20 Couple maximum
Vérifiez et réglez si nécessaire les limites de vitesse, courant et couple moteur.
Démarrez le variateur avec une référence de vitesse positive (rotation en sens avant).
Avec la micro-console (commande locale) : Dans la vue Accueil, enfoncez la touche
(Options), sélectionnez Référence et réglez la référence à l'aide des touches
, ,
et . Enfoncez la touche Sauvegarder puis la touche Start.
Avec les E/S : En commande distante, réglez l'entrée analogique 1 (AI1, référence),
mettez l'entrée logique 2 (DI2) sur 0 (avant) et l'entrée logique 1 (DI1) sur 1
(démarrage).
68 Guide de mise en route pour l'ACS880 avec programme de contrôle standard
EN
DE
ES
FI
FR
FR
NL
RU
SV
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 69
EN
DE
ES
FI
FR
IT
IT
RU
SV
Guida rapida all'avviamento
dei convertitori ACS880 con
Programma di controllo
primario
Informazioni sulla guida
Questa guida descrive la sequenza di avviamento base dei convertitori di frequenza
ACS880 dotati di Programma di controllo primario. La documentazione completa sul
firmware dei convertitori è contenuta nel Manuale firmware (vedere l'elenco delle
pubblicazioni nella seconda di copertina).
In questa guida, il convertitore viene impostato utilizzando il pannello di controllo
ACS-AP-I. La sequenza di avviamento può essere eseguita anche utilizzando il tool
PC Drive Composer.
Prima di iniziare
Verificare che l'installazione meccanica ed elettrica del convertitore di frequenza sia
stata eseguita correttamente, secondo le istruzioni contenute nella rispettiva Guida
rapida all'installazione e/o nel Manuale hardware.
Sicurezza
AVVERTENZA! L'installazione elettrica e gli interventi di manutenzione sul
convertitore di frequenza devono essere eseguiti solo da elettricisti qualificati.
Non intervenire mai sul convertitore, sul circuito del chopper di frenatura, sul cavo
motore o sul motore quando il convertitore è sotto tensione. Verificare sempre che
non sia presente tensione.
70 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
Avviamento
Sicurezza
L'avviamento deve essere eseguito solo da elettricisti qualificati.
Rispettare scrupolosamente le norme di sicurezza durante la procedura di
avviamento. Leggere le norme di sicurezza riportate nelle prime pagine del Manuale
hardware del convertitore.
Controllare l'installazione. Vedere la checklist di installazione nel Manuale hardware.
Controllare che l'avviamento del motore non determini situazioni di pericolo.
Disaccoppiare la macchina comandata se
vi è il rischio di danni in caso di direzione di rotazione non corretta, o
è necessario eseguire una routine di identificazione (ID run) Normale all'avviamento
del convertitore, quando la coppia di carico è superiore al 20% o la macchina non è in
grado di sostenere il transitorio della coppia nominale durante l'ID run.
1 – Accensione e impostazione di data e ora
Accendere il convertitore.
Nota: è normale che durante la procedura di
avviamento vengano visualizzati dei
messaggi di allarme. Per cancellare i
messaggi e riprendere l'avviamento,
premere .
Cancellare i messaggi eventualmente
presenti per accedere alla vista Home
(figura a destra).
I due comandi in basso sullo schermo (in
questo caso, Opzioni e Menu)
corrispondono alle funzioni dei due tasti
software e posizionati sotto il
display. I comandi assegnati ai tasti software
variano in base al contesto.
Nella vista Home, premere (Menu).
Viene visualizzato il Menu principale (a
destra).
Remoto 0.0 rpm
0.00
0.00
Coppia motore %
%
0.0
Corrente motore
A
Vel motore utilizzata
rpm
Opzioni
12:34
Menu
Remoto 0.0 rpm
Menu
Parametri
Assistenti
Efficienza energetica
Log eventi
Esci
12:34
Seleziona
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 71
EN
DE
ES
FI
FR
IT
IT
RU
SV
Evidenziare Impostazioni sul menu
utilizzando e e premere
(Seleziona).
Nel menu Impostazioni, evidenziare Data e
ora (se non è già evidenziato) e premere
(Seleziona).
Nel menu Data e ora, evidenziare Data (se
non è già evidenziato) e premere
(Seleziona).
Remoto 0.0 rpm
Imposta
Lingua
Data e ora
Indietro
12:34
Seleziona
Modifica testi
Impostazioni display
Inizio prossima ora legale 28.03.
Remoto 0.0 rpm
Data e ora
Data
Indietro
12:35
Modifica
Ora
Formato data
01.01.1980
12:34:56
giorno.mese.anno
Formato ora 24 ore
Ora legale EU
Remoto 0.0 rpm
Data
Annulla
12:35
Salva
Giorno Mese Anno
Martedì
.01.198001
72 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
Impostare la data:
Per spostare il cursore a destra e a
sinistra, premere e .
Per modificare il valore, premere e .
Premere (Salva) per confermare
l'impostazione visualizzata.
Verificare/regolare tutte le altre impostazioni
del menu Data e ora.
La voce Mostra orologio attiva o nasconde
la visualizzazione dell'orologio in basso sul
display.
Una volta completate le impostazioni,
premere ripetutamente (Indietro o
Esci) fino a tornare alla vista Home (a
destra).
2 – Impostazione della tensione di alimentazione e dei dati del motore
Passare al controllo locale per assicurarsi
che il controllo esterno sia disabilitato
premendo il tasto . Quando è attivo il
controllo locale, in alto sul display compare
la scritta "Locale".
Aprire il Menu principale premendo
(Menu).
Remoto 0.0 rpm
0.00
0.00
Coppia motore %
%
0.0
Corrente motore
A
Vel motore utilizzata
rpm
Opzioni
12:35
Menu
Loc/Rem
Locale 0.0 rpm
0.00
0.00
Coppia motore %
%
0.0
Corrente motore
A
Vel motore utilizzata
rpm
Opzioni
12:36
Menu
Locale 0.0 rpm
Menu
Parametri
Assistenti
Efficienza energetica
Log eventi
Esci
12:36
Seleziona
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 73
EN
DE
ES
FI
FR
IT
IT
RU
SV
Evidenziare Parametri e premere
(Seleziona).
Evidenziare Elenco completo utilizzando
e e premere (Seleziona).
Viene visualizzato un elenco di gruppi di
parametri.
Evidenziare il gruppo di parametri 95
Configurazione HW e premere
(Seleziona).
L'elenco dei gruppi è continuo, da 99 a 01, e
consultabile in entrambe le direzioni. In
questo caso, è più rapido utilizzare per
trovare il gruppo 95 in elenco.
Quando si seleziona un gruppo, vengono
visualizzati tutti i parametri di quel gruppo.
Evidenziare il parametro 95.01 Tensione
alimentaz (se non è già evidenziato) e
premere (Modifica).
Vengono mostrate le impostazioni disponibili
per il parametro.
Locale 0.0 rpm
Parametri
Preferiti
Per funzione
Indietro
12:36
Seleziona
Elenco completo
Modificati
Locale 0.0 rpm
Elenco completo
01 Valori effettivi
03 Riferimenti ingressi
04 Allarmi e guasti
05 Diagnostica
06 Word controllo e stato
07 Info sistema
Indietro
12:36
Seleziona
Locale 0.0 rpm
95 Configurazione HW
95.01 Tensione alimentaz
Indietro
12:36
Modifica
95.02 Limiti tensione adattiva
95.04 Alimentaz scheda ctrl
Non dato
Disabilita
24V interna
Locale 0.0 rpm
95.01 Tensione alimentaz
[0] Non dato
[1] 208…240 V
Annulla
12:36
Salva
[2] 380…415 V
[3] 440…480 V
[4] 500 V
74 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
Evidenziare l'impostazione corretta
nell'elenco e premere (Salva).
Premere (Indietro) per tornare all'elenco dei gruppi di parametri. Selezionare il
gruppo 99 Dati motore e impostare il parametro 99.03 Tipo motore.
Impostare il parametro 99.04 Modo controllo motore.
DTC = Direct Torque Control (controllo diretto di coppia); Scalare
Il modo DTC è adatto nella maggior parte dei casi. Il modo scalare è raccomandato se
la corrente nominale del motore è inferiore a 1/6 della corrente nominale del
convertitore di frequenza,
il convertitore viene utilizzato a scopo di collaudo senza un motore collegato, o
il convertitore controlla più motori e il numero di motori collegati è variabile.
Per le seguenti impostazioni parametriche, fare riferimento ai dati riportati sulla targa del
motore. Quando possibile, i valori devono essere inseriti esattamente
come compaiono sulla
targa del motore.
Esempio di targa di un motore a induzione
(asincrono):
Esempio di targa di un motore a magneti
permanenti:
Locale 0.0 rpm
95 Configurazione HW
95.01 Tensione alimentaz
Indietro
12:36
Modifica
95.02 Limiti tensione adattiva
95.04 Alimentaz scheda ctrl
380…415 V
Disabilita
24V interna
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 75
EN
DE
ES
FI
FR
IT
IT
RU
SV
99.06 Corrente nomin motore
Il range consentito è
modo DTC: 1/6 × I
Hd
… 2 × I
Hd
del convertitore
modo scalare: 0 … 2 × I
Hd
Nota: per i valori dei parametri in forma numerica:
Per modificare il valore di una unità, premere e .
Per spostare il cursore a destra e a sinistra, premere e .
Premere (Salva) per confermare il valore.
Impostare nello stesso modo i seguenti parametri.
99.07 Tensione nomin motore
Il range consentito è 1/6 × U
N
… 2 × U
N
del convertitore.
Con i motori a magneti permanenti, la tensione nominale è la tensione
controelettromotrice alla velocità nominale del motore. Se la tensione è espressa in
volt/rpm (es. 60 V a 1000 rpm), la tensione alla velocità nominale di 3000 rpm è 3 × 60 V
= 180 V. Si noti che la tensione nominale non è uguale alla tensione equivalente del
motore in c.c. (EDCM) fornita da alcuni costruttori di motori. La tensione nominale può
essere calcolata dividendo la tensione EDCM per 1.7 (o radice quadrata di 3).
99.08 Frequenza nomin motore
Nel caso dei motori a magneti permanenti, se la frequenza nominale non è indicata sulla
targa, si può calcolare con la formula seguente:
f = n × p / 60
dove n = velocità nominale del motore, p = numero di coppie di poli.
99.09 Velocità nomin motore
99.10 Potenza nomin motore
99.11 cosfii nomin motore
99.12 Coppia nomin motore
Questi valori non sono obbligatori, ma si possono ugualmente inserire per migliorare la
precisione del controllo. Se non sono noti, lasciare l'impostazione su 0.
76 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
99.13 Richiesta ID-run
Questo parametro seleziona la modalità per la routine di identificazione (solo con il
controllo motore DTC).
AVVERTENZA! Nelle modalità di ID run contrassegnate dall'asterisco (*), il motore
ruota in direzione "avanti" (vedere oltre per i dettagli). Assicurarsi che il
funzionamento del motore non comporti alcun rischio quando si selezionano queste
modalità.
*Normale: se possibile, selezionare sempre questa modalità. Il motore deve essere
disaccoppiato dalla macchina comandata se
la coppia di carico è superiore al 20%, o
la macchina non è in grado di sostenere il transitorio della coppia nominale durante l'ID
run.
*Ridotta: selezionare questa modalità se le perdite meccaniche sono superiori al 20%,
cioè se il carico non può essere disaccoppiato, oppure se è richiesto il flusso completo
per tenere aperto il freno motore (es. con motori conici).
Statica: selezionare questa modalità quando non è possibile utilizzare le modalità
*Normale e *Ridotta. Note:
Questa modalità non può essere utilizzata con motori a magneti permanenti se la
coppia di carico è superiore al 20% del valore nominale.
Il freno meccanico non viene aperto dalla logica per l'ID run.
Verificare che il circuito della funzione Safe Torque Off e il circuito di arresto di
emergenza (se presenti) siano chiusi.
Avviare l'ID run premendo il pulsante
(Start).
Un allarme indica che la routine di
identificazione è in corso.
Verificare che il motore ruoti nella direzione corretta (direzione "avanti", come illustrato
sotto).
La routine termina quando il convertitore si arresta e il valore del parametro 99.13 torna a
"No".
Se il motore ha ruotato nella direzione sbagliata, correggere il cablaggio del motore o
regolare il parametro 99.16 Ordine fasi.
3 – Impostazioni dei segnali di controllo
Verificare le posizioni dei ponticelli J1 e J2 sull'unità di controllo del convertitore. Questi
ponticelli determinano la funzione degli ingressi analogici AI1 e AI2 come ingressi di
corrente o tensione.
Verificare/regolare i seguenti parametri.
20.01 Comandi Est1
Di default, il convertitore si avvia e si arresta in base allo stato dell'ingresso digitale DI1
(0 = arresto, 1 = marcia). DI2 determina la direzione di rotazione (0 = avanti, 1 = indietro).
Se è necessario avere altre sorgenti, modificare opportunamente i valori. Le sorgenti
In1In3 sono definite dai parametri 20.0320.05.
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 77
EN
DE
ES
FI
FR
IT
IT
RU
SV
12.15 Selezione unità AI1
Impostare su mA o V in base all'impostazione del ponticello J1.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scalato a AI1 min
12.20 AI1 scalato a AI1 max
L'ingresso di default per il riferimento di velocità è l'ingresso analogico AI1. (Si controlla
con i parametri del gruppo 22.)
I parametri 12.17 e 12.18 impostano i limiti inferiore e superiore del segnale di ingresso
analogico. I parametri di adattamento con fattore di scala 12.19 e 12.20 definiscono i
livelli dei segnali interni che corrispondono a questi limiti, nel modo seguente:
I parametri corrispondenti per l'ingresso analogico AI2 sono 12.2712.30.
AI (scalato)
AI (mA/V)
12.20
12.18
12.17
12.19
78 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
13.12 Sorgente AO1
13.17 Min sorgente AO1
13.18 Max sorgente AO1
13.19 Usc AO1 a min sorg AI1
13.20 Usc AO1 a max sorg AI1
Il parametro 13.12 seleziona la sorgente per l'uscita analogica AO1 (di default, la velocità
del motore in rpm).
I parametri 13.17 e 13.18 impostano i valori minimo e massimo del segnale sorgente che
corrispondono ai valori effettivi dell'uscita analogica definiti dai parametri 13.19 e 13.20.
46.10 Adattam velocità
23.11 Selezione set rampe
23.12 Tempo accelerazione 1
23.13 Tempo decelerazione 1
23.14 Tempo accelerazione 2
23.15 Tempo decelerazione 2
L'utente può definire due diversi set di rampe di accelerazione/decelerazione. La
sorgente che determina il passaggio dall'uno all'altro set si seleziona con il parametro
23.11.
Ogni set di tempi di accelerazione/decelerazione nei parametri 23.1223.15 esprime il
tempo richiesto dal convertitore per accelerare o decelerare tra la velocità 0 e la velocità
scalata (parametro 46.10).
Segnale sorgente
AO (mA)
13.18
13.20
13.19
13.17
Tempo
Velocità
46.10
23.12
23.14
23.13
23.15
Acc. Dec.
0
Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario 79
EN
DE
ES
FI
FR
IT
IT
RU
SV
30.11 Velocità minima
30.12 Velocità massima
30.17 Corrente massima
30.19 Coppia minima
30.20 Coppia massima
Verificare e, se necessario, impostare i limiti di velocità motore, corrente e coppia.
Avviare il convertitore con un riferimento di velocità positivo (avanti):
Dal pannello di controllo (controllo locale): nella vista Home, premere (Opzioni),
selezionare Riferimento, regolare il riferimento utilizzando i tasti , , e ,
premere Salva e premere il pulsante Start.
Tramite I/O: in modalità di controllo remoto, regolare l'ingresso analogico AI1
(riferimento), commutare l'ingresso digitale DI2 su 0 (avanti) e commutare l'ingresso
digitale DI1 su 1 (marcia).
80 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo
primario
EN
DE
ES
FI
FR
IT
IT
RU
SV
Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 81
EN
DE
ES
FI
FR
IT
NL
NL
SV
Beknopte opstartgids voor
ACS880 omvormers met
primair
besturingsprogramma
Inleiding
Deze gids beschrijft de basis opstartcyclus van een ACS880 omvormer voorzien van
het primaire besturingsprogramma. Complete documentatie van de firmware van de
omvormer is te vinden in de Firmwarehandleiding (zie de lijst met handleidingen aan
de binnenkant van het voorblad).
In deze gids wordt de omvormer ingesteld via het ACS-AP-I bedieningspaneel. De
opstartcyclus kan ook uitgevoerd worden met de Drive composer PC tool.
Vóór het starten
Zorg er voor dat de omvormer mechanisch en elektrisch geïnstalleerd is zoals
beschreven in de betreffende Beknopte installatiegids en/of Hardwarehandleiding.
Veiligheid
WAARSCHUWING! Alle werkzaamheden wat betreft elektrische installatie en
onderhoud van de omvormer mogen alleen door gekwalificeerde elektriciens
uitgevoerd worden.
Voer nooit werkzaamheden uit aan de omvormer, het remchoppercircuit, de
motorkabel of de motor wanneer de omvormer onder spanning staat. Verzeker u er
altijd van dat er geen spanning aanwezig is door meting.
82 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma
EN
DE
ES
FI
FR
IT
NL
NL
SV
Opstarten
Veiligheid
Het opstarten mag uitsluitend worden uitgevoerd door een gekwalificeerd elektricien.
Gedurende het opstarten moeten de veiligheidsinstructies worden opgevolgd. Zie de
veiligheidsinstructies op de eerste pagina's van de betreffende Hardware-
handleiding.
Controleer de installatie. Zie de installatiechecklist in de betreffende Hardware-
handleiding.
Controleer of het starten van de motor geen gevaar oplevert.
Ontkoppel de aangedreven machine als
er een risico van schade bestaat bij een eventueel verkeerde draairichting of
een normale ID-run vereist is tijdens het opstarten van de omvormer, wanneer het
lastkoppel hoger is dan 20% of de machine niet bestand is tegen de nominale koppel-
piek tijdens de ID-run.
1 – Inschakelen, instelling van datum en tijd
Schakel de voeding van de omvormer in.
Opmerking: Het is normaal dat er
waarschuwingsberichten verschijnen op
diverse punten in het opstartproces. Om een
bericht te verbergen en het opstartproces te
hervatten, drukt u op .
Verberg nu eventuele waarschuwingen om
naar het Home-scherm te gaan (hiernaast
getoond).
De twee commando's onder aan het display
(in dit geval, Opties en Menu), tonen de
functies van de twee softkeys en
die zich onder het display bevinden. De
commando's die aan de softkeys
toegewezen zijn variëren afhankelijk van de
context.
In het Home-scherm, drukt u op
(Menu).
Het hoofdmenu (rechts) verschijnt.
Afstand 0.0 rpm
0.00
0.00
Motor koppel %
%
0.0
Motorstroom
A
Gebruikte motortoerental
rpm
Opties
12:34
Menu
Afstand 0.0 rpm
Menu
Parameters
Assistenten
Energie rendement
Logboek
Afsluiten
12:34
Selecteren
Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 83
EN
DE
ES
FI
FR
IT
NL
NL
SV
Markeer Instellingen in het menu via en
en druk op (Selecteren).
In het menu Instellingen markeert u Datum
& tijd (als dit nog niet gemarkeerd is) en
drukt u op (Selecteren).
In het menu Datum & tijd markeert u Datum
(als dit nog niet gemarkeerd is) en drukt u op
(Selecteren).
Afstand 0.0 rpm
Instellingen
Taal
Datum & tijd
Terug
12:34
Selecteren
Teksten bewerken
Display-instellingen
Volgende omzetting naar zomertijd28.03.
Afstand 0.0 rpm
Datum & tijd
Datum
Terug
12:35
Bewerken
Tijd
Toon datum als
01.01.1980
12:34:56
dag.maand.jaar
Toon tijd als 24-uur
Zomer-/wintertijd EU
Afstand 0.0 rpm
Datum
Annuleren
12:35
Opslaan
Dag Maand Jaar
Dinsdag
.01.198001
84 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma
EN
DE
ES
FI
FR
IT
NL
NL
SV
Stel de juiste datum in:
Gebruik en om de cursor naar links
en rechts te verplaatsen.
Gebruik en om de waarde te
wijzigen.
Druk op (Opslaan) om de nieuwe
instelling te accepteren.
Controleer/ pas alle overige instellingen aan
in het menu Datum & tijd.
De instelling van Toon klok bepaalt of de tijd
continu op de onderste regel van het display
getoond wordt.
Nadat u de instellingen aangepast hebt,
drukt u herhaaldelijk op (Terug of
Afsluiten) totdat het Home-scherm (rechts)
verschijnt.
2 – Instelling van voedingsspanning en motorgegevens
Schakel over op lokale besturing om er
zeker van te zijn dat externe besturing
geblokkeerd is door op de toets te
drukken. Lokale besturing wordt
aangegeven met de tekst “Lokaal” op de
bovenste regel.
Open het hoofdmenu door op (Menu)
te drukken.
Afstand 0.0 rpm
0.00
0.00
Motor koppel %
%
0.0
Motorstroom
A
Gebruikte motortoerental
rpm
Opties
12:35
Menu
Loc/Rem
Lokaal 0.0 rpm
0.00
0.00
Motor koppel %
%
0.0
Motorstroom
A
Gebruikte motortoerental
rpm
Opties
12:36
Menu
Lokaal 0.0 rpm
Menu
Parameters
Assistenten
Energie rendement
Logboek
Afsluiten
12:36
Selecteren
Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 85
EN
DE
ES
FI
FR
IT
NL
NL
SV
Markeer Parameters en druk op
(Selecteren).
Markeer Complete lijst via en en
druk op (Selecteren).
Er wordt een lijst met parametergroepen
getoond.
Markeer parametergroep 95 HW
configuratie en druk op (Selecteren).
Merk op dat de lijst in beide richtingen
doorloopt, tussen de groepen 99 en 01. In dit
geval is het sneller om te gebruiken om
groep 95 in de lijst te lokaliseren.
Nadat een groep gekozen is, wordt een lijst
met parameters binnen de groep getoond.
Markeer parameter 95.01
Voedingsspanning (indien nog niet
gemarkeerd) en druk op (Bewerken).
De beschikbare parameterinstellingen
worden weergegeven.
Lokaal 0.0 rpm
Parameters
Favorieten
Naar functie
Terug
12:36
Selecteren
Complete lijst
Gewijzigd
Lokaal 0.0 rpm
Complete lijst
01 Actuele waarden
03 Ingang referenties
04 Waarschuwingen en fouten
05 Diagnostiek
06 Control- en status woorden
07 Systeem info
Terug
12:36
Selecteren
Lokaal 0.0 rpm
95 HW configuratie
95.01 Voedingsspanning
Terug
12:36
Bewerken
95.02
Adaptieve spanningslimieten
95.04 Stuurkaart voeding
Niet gegeven
Blokkeren
Interne 24V
Lokaal 0.0 rpm
95.01 Voedingsspanning
[0] Niet gegeven
[1] 208…240 V
Annuleren
12:36
Opslaan
[2] 380…415 V
[3] 440…480 V
[4] 500 V
86 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma
EN
DE
ES
FI
FR
IT
NL
NL
SV
Markeer de juiste instelling uit de lijst en druk
op (Opslaan).
Druk op (Terug) om de lijst met parametergroepen weer te tonen. Selecteer
parametergroep 99 Motorgegevens, en stel parameter 99.03 Motor type in.
Stel parameter 99.04 Motor besturing modus in.
DTC = Direct torque control; Scalar
DTC voldoet in de meeste gevallen. Scalarmodus wordt aanbevolen indien
de nominale motorstroom minder is dan 1/6 van de nominale stroom van de omvormer,
de omvormer voor testdoeleinden zonder aangesloten motor wordt gebruikt, of
de omvormer meerdere motoren bestuurt en het aantal aangesloten motoren variabel
is.
Raadpleeg het motortypeplaatje voor de volgende parameterinstellingen. Voer de waarden,
indien mogelijk exact
hetzelfde in als op het motortypeplaatje.
Voorbeeld van een typeplaatje van een
(asynchrone) inductiemotor:
Voorbeeld van een typeplaatje van een
permanentmagneetmotor:
99.06 Nominale motorstroom
Het toegestane bereik is
in DTC modus: 1/6 × I
Hd
… 2 × I
Hd
van de omvormer
in Scalar modus: 0 … 2 × I
Hd
Opmerking: Bij numerieke parameterwaarden:
Gebruik en om de waarde van een cijfer te veranderen.
Gebruik en om de cursor naar links en rechts te verplaatsen.
Druk op (Opslaan) om de waarde te bevestigen.
Lokaal 0.0 rpm
95 HW configuratie
95.01 Voedingsspanning
Terug
12:36
Bewerken
95.02
Adaptieve spanningslimieten
95.04 Stuurkaart voeding
380…415 V
Blokkeren
Interne 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 87
EN
DE
ES
FI
FR
IT
NL
NL
SV
Voer de volgende parameterinstellingen op dezelfde manier uit.
99.07 Nominale motorspanning
Het toegestane bereik is 1/6 × U
N
… 2 × U
N
van de omvormer.
Bij permanentmagneetmotoren is de nominale spanning de BackEMF spanning bij
nominaal toerental. Als de spanning gegeven is in volt/rpm (bijv. 60 V per 1000 rpm), dan
is de spanning bij een nominaal toerental van 3000 rpm, 3 × 60 V = 180 V. Merk op dat
nominale spanning niet hetzelfde is als equivalente DC motorspanning (EDCM) die door
sommige fabrikanten opgegeven wordt. De nominale spanning kan berekend worden
door de EDCM spanning te delen door 1,7 (of vierkantswortel uit 3).
99.08 Nominale motorfrequentie
Bij permanentmagneetmotoren kan de nominale frequentie, indien deze niet op het
typeplaatje gegeven is, berekend worden via de volgende formule:
f = n × p / 60
waarbij n = nominaal motortoerental, p = aantal poolparen.
99.09 Nominaal motortoerental
99.10 Nominaal motorvermogen
99.11 Nominale motor cosfii
99.12 Nominaal motorkoppel
Deze waarden zijn niet vereist, maar ze kunnen ingevoerd worden om de
regelnauwkeurigheid te verbeteren. Indien onbekend, laat dan op 0 staan.
99.13 Identificatierun verzoek
Deze parameter kiest de modus van de identificatierun (alleen in DTC-
motorbesturingsmodus).
WAARSCHUWING! De identificatierun-modi gemarkeerd met * zullen de motor in
voorwaartse richting doen draaien (zie hieronder voor details). Zorg er voor dat de
het veilig is om de motor te laten draaien voordat u een van deze modi kiest.
*Normale modus dient gekozen te worden wanneer mogelijk. De aangedreven
apparatuur moet ontkoppeld zijn van de motor indien
het lastkoppel hoger is dan 20%, of
de machines niet bestand zijn tegen de nominale koppelpiek tijdens de identificatierun.
*Gereduceerde modus dient gekozen te worden als de mechanische verliezen hoger zijn
dan 20%, d.w.z. de last kan niet worden ontkoppeld, of volledige flux is vereist om de
motorrem open te houden bijv. bij conische motoren).
De Stilstand modus dient gekozen te worden als noch de *Normale, noch
*Gereduceerde modus gebruikt kan worden. Opmerkingen:
Deze modus kan niet gebruikt worden bij een permanentmagneetmotor als het
lastkoppel hoger is dan 20% van het nominale koppel.
De mechanische rem wordt niet geopend door de logica voor de identificatierun.
Zorg er voor dat de Safe Torque Off- en noodstopcircuits (indien aanwezig) gesloten zijn.
Start de identificatierun door op de knop
(Start) te drukken.
Een waarschuwing zal aangeven dat de
identificatierun bezig is.
88 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma
EN
DE
ES
FI
FR
IT
NL
NL
SV
Controleer dat de motor in de juiste richting draait (hieronder wordt voorwaartse richting
getoond).
De identificatierun is voltooid wanneer de omvormer stopt en de waarde van parameter
99.13 terugkeert naar “Nee”.
Als de motor in de verkeerde richting draaide, corrigeer dan de motorbekabeling of pas
parameter 99.16 Fasevolgorde aan.
3 – Instellen van de stuursignalen
Controleer de posities van de jumpers J1 en J2 op de besturingsunit van de omvormer.
Deze jumpers bepalen of de analoge ingangen AI1 en AI2 stroom- of spanningsingangen
zijn.
Controleer /pas de volgende parameters aan.
20.01 Ext1 opdrachten
Standaard start/stopt de omvormer volgens de status van digitale ingang DI1 (0 = Stop,
1 = Start). DI2 bepaalt de draairichting (0 = Voorwaarts, 1 = Achterwaarts).
Als andere bronnen vereist zijn, verander dan de waarde dienovereenkomstig. De
bronnen In1In3 worden bepaald door parameters 20.0320.05.
12.15 AI1 eenheid selectie
Stel dit in op mA of V in overeenstemming met de instelling van jumper J1.
Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 89
EN
DE
ES
FI
FR
IT
NL
NL
SV
12.17 AI1 min
12.18 AI1 max
12.19 AI1 geschaald bij AI1 min
12.20 AI1 geschaald bij AI1 max
De standaard ingang voor toerentalreferentie is analoge ingang AI1. (Dit wordt bestuurd
door de parameters in groep 22.)
Parameters 12.17 en 12.18 stellen de onder- en bovenlimieten van het analoge
ingangssignaal in. Schalingsparameters 12.19 en 12.20 bepalen als volgt de interne
signaalniveaus die overeenkomen met deze limieten:
De corresponderende parameters voor analoge ingang AI2 zijn 12.2712.30.
13.12 AO1 bron
13.17 AO1 bron min
13.18 AO1 bron max
13.19 AO1 uit bij AI1 bron min
13.20 AO1 uit bij AI1 bron max
Parameter 13.12 kiest de bron voor analoge uitgang AO1 (standaard, motortoerental in
rpm).
Parameters 13.17 en 13.18 stellen lage en hoge waarden van bronsignalen in die
corresponderen met de actuele analoge uitgangswaarden gedefinieerd door parameters
13.19 en 13.20.
AI (geschaald)
AI (mA/V)
12.20
12.18
12.17
12.19
Bronsignaal
AO (mA)
13.18
13.20
13.19
13.17
90 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma
EN
DE
ES
FI
FR
IT
NL
NL
SV
46.10 Toerentalschaling
23.11 Hellingset selectie
23.12 Acceleratietijd 1
23.13 Deceleratietijd 1
23.14 Acceleratietijd 2
23.15 Deceleratietijd 2
U kunt twee verschillende sets acceleratie-/deceleratiehellingen definiëren. De bron die
tussen de twee sets schakelt wordt gekozen door parameter 23.11.
Elke acceleratie-/deceleratietijd die in parameters 23.1223.15 ingesteld wordt, verwijst
naar de tijd die de omvormer nodig heeft om te accelereren of decelereren tussen 0 en
het geschaalde toerental (parameter 46.10).
30.11 Minimum toerental
30.12 Maximum toerental
30.17 Maximum stroom
30.19 Minimum koppel
30.20 Maximum koppel
Controleer de limieten voor motortoerental, -stroom en -koppel, en stel ze in, indien
nodig.
Start de omvormer met een positieve (voorwaartse) toerentalreferentie:
Vanaf het bedieningspaneel (Lokale besturing): Druk in het Home-scherm op
(Opties), selecteer Referentie, pas de referentie aan via de toetsen , ,
, en
, druk op Opslaan, en druk op de Start-knop.
Vanaf I/O: Pas, onder afstandsbediening, analoge ingang AI1 (referentie) aan, schakel
digitale ingang DI2 naar 0 (voorwaarts), en schakel digitale ingang DI1 naar 1 (start).
Tijd
Toerental
46.10
23.12
23.14
23.13
23.15
Acc. Dec.
0
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 91
PL
DE
ES
FI
FR
IT
NL
RU
PL
Skrócona instrukcja
uruchamiania przemienników
częstotliwości ACS880 ze
Standardowym
Oprogramowaniem
Aplikacyjnym
Informacje o tej instrukcji
W tej instrukcji opisano podstawową sekwencję uruchamiania przemiennika
częstotliwości ACS880 wyposażonego w Standardowe Oprogramowanie
Aplikacyjne. Pełna dokumentacja tego oprogramowania znajduje się w Podręczniku
Standardowego Oprogramowania Aplikacyjnego (patrz lista podręczników na
wewnętrznej stronie przedniej okładki).
W tym podręczniku opisano konfigurację przemiennika częstotliwości wykonywaną
za pomocą panelu sterowania ACS-AP-I. Proces uruchamiania można także
przeprowadzić za pomocą narzędzia komputerowego Drive Composer.
Przed rozpoczęciem
Należy upewnić się, że instalacja mechaniczna i elektryczna przemiennika
częstotliwości została przeprowadzona zgodnie z opisem zawartym w skróconej
instrukcji montażu i/lub podręczniku użytkownika.
Bezpieczeństwo
OSTRZEŻENIE! Wszelkie elektryczne prace instalacyjne i konserwacyjne
związane z przemiennikiem częstotliwości powinny być wykonywane tylko
przez wykwalifikowanych elektryków.
Nie należy wykonywać czynności serwisowych na przemienniku częstotliwości,
układzie czopera hamowania, kablu silnikowym i silniku, gdy przemiennik jest
podłączony do napięcia zasilania.
Zawsze należy sprawdzać, czy w danym momencie przemiennik nie jest pod
napięciem, wykonując odpowiedni pomiar.
92 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
Uruchamianie
Bezpieczeństwo
Uruchomienie może przeprowadzić tylko wykwalifikowany elektryk.
Podczas procedury uruchamiania należy przestrzegać instrukcji bezpieczeństwa.
Instrukcje bezpieczeństwa znajdują się na pierwszych stronach odpowiedniego
podręcznika użytkownika.
Sprawdzić instalację. Lista kontrolna instalacji znajduje się w odpowiednim podręczniku
użytkownika.
Sprawdzić, czy uruchomienie silnika nie spowoduje żadnego niebezpieczeństwa.
Należy odłączyć napędzane urządzenie, jeśli:
istnieje ryzyko uszkodzenia spowodowanego przez niewłaściwy kierunek obrotów
silnika lub
wymagane jest przeprowadzenie Normalnego Biegu Identyfikacyjnego silnika podczas
uruchomienia przemiennika częstotliwości, gdy moment obciążenia jest wyższy niż
20% lub gdy maszyna nie wytrzyma chwilowego znamionowego momentu obrotowego
podczas wykonywania Biegu Identyfikacyjnego.
1. Włączanie, daty i godziny
Włączyć przemiennik częstotliwości.
Uwaga: pojawianie się komunikatów
ostrzegawczych w różnych momentach
procesu uruchamiania jest normalne. Aby
ukryć komunikat i wznowić proces
uruchamiania, należy nacisnąć przycisk
.
Następnie należy ukryć wszystkie
ostrzeżenia, aby włączyć widok główny
Home (widoczny po prawej stronie).
Dwa wskaźniki znajdujące się w dolnej
części wyświetlacza (w tym przypadku
Options — Opcje i Menu) odpowiadają
funkcjom przycisków i . Te dwie
funkcje przypisane do przycisków mogą być
żne w zależności od kontekstu.
W widoku głównym Home nacisnąć przycisk
(Menu).
Pojawi się menu główne (widoczne po
prawej stronie).
Remote 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:34
Menu
Remote 0.0 rpm
Menu
Parameters
Assistants
Energy efficiency
Event log
Exit
12:34
Select
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 93
PL
DE
ES
FI
FR
IT
NL
RU
PL
Wybrać opcję Settings (Ustawienia) w
menu, naciskając przyciski i , a
następnie nacisnąć przycisk (Select
— Wybierz).
W menu Settings (Ustawienia) wybrać opcję
Date & time (Data i godzina), jeśli nie
została jeszcze wybrana, i nacisnąć przycisk
(Select — Wybierz).
W menu Date & time (Data i godzina)
wybrać opcję Date (Data), jeśli nie została
jeszcze wybrana, i nacisnąć przycisk
(Select — Wybierz).
Remote 0.0 rpm
Settings
Language
Date & time
Back
12:34
Select
Edit texts
Display settings
Next daylight saving start 28.03.
Remote 0.0 rpm
Date & time
Date
Back
12:35
Edit
Time
Show date as
01.01.1980
12:34:56
day.month.year
Show time as 24-hour
Daylight saving EU
Remote 0.0 rpm
Date
Cancel
12:35
Save
Day Month Year
Tuesday
.01.198001
94 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
Ustawić prawidłową datę:
Za pomocą przycisków i
przesunąć kursor w lewo lub prawo.
Za pomocą przycisków i zmienić
wartość.
•Nacisnąć przycisk (SaveZapisz),
aby zaakceptować nowe ustawienie.
Sprawdzić/dostosować wszystkie pozostałe
ustawienia w menu Date & time (Data i
godzina).
Ustawienie Show clock (Pokaż zegar)
określa, czy godzina ma być widoczna cały
czas w dolnej części wyświetlacza.
Po skonfigurowaniu tych ustawień nacisnąć
przycisk (Back lub Exit) (Wstecz lub
Wyjdź) wielokrotnie, aż do pojawienia się
widoku głównego Home (widocznego po
prawej stronie).
2. Ustawienia napięcia zasilania i danych silnika
Przełączyć się na sterowanie lokalne, aby
upewnić się, że sterowanie zewnętrzne jest
wyłączone, naciskając przycisk .
Sterowanie lokalne wskazuje tekst „Local” w
górnym lewym rogu wyświetlacza.
Otworzyć menu główne, naciskając przycisk
(Menu).
Remote 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:35
Menu
Loc/Rem
Local 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Options
12:36
Menu
Local 0.0 rpm
Menu
Parameters
Assistants
Energy efficiency
Event log
Exit
12:36
Select
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 95
PL
DE
ES
FI
FR
IT
NL
RU
PL
Wybrać opcję Parameters (Parametry) i
nacisnąć przycisk (Select — Wybierz).
Wybrać opcję Complete list (Cała lista),
naciskając przyciski i , a następnie
nacisnąć przycisk (Select — Wybierz).
Pojawi się lista grup parametrów.
Wybrać grupę parametrów 95 HW
configuration (95 Konfiguracja sprzętowa) i
nacisnąć przycisk (Select — Wybierz).
Należy pamiętać, że lista parametrów jest
zapętlona i możliwe jest przejście między
grupami 99 a 01 w obu kierunkach. W tym
przypadku pozycję 95 można znaleźć
szybciej, naciskając przycisk .
Po wybraniu danej grupy pojawi się lista
zawartych w niej parametrów.
Wybrać parametr 95.01 Supply voltage
(napięcie zasilania), jeśli jeszcze nie został
wybrany, i nacisnąć przycisk (Edit
Edycja).
Pojawi się
lista dostępnych ustawień
parametru.
Local 0.0 rpm
Parameters
Favorites
By function
Back
12:36
Select
Complete list
Modified
Local 0.0 rpm
Complete list
01 Actual values
03 Input references
04 Warnings and faults
05 Diagnostics
06 Control and status words
07 System info
Back
12:36
Select
Local 0.0 rpm
95 HW configuration
95.01 Supply voltage
Back
12:36
Edit
95.02 Adaptive voltage limits
95.04 Control board supply
Not given
Disable
Internal 24V
Local 0.0 rpm
95.01 Supply voltage
[0] Not given
[1] 208…240 V
Cancel
12:36
Save
[2] 380…415 V
[3] 440…480 V
[4] 500 V
96 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
Wybrać poprawne ustawienie z listy i
nacisnąć przycisk (Save — Zapisz).
Nacisnąć przycisk (Back — Wstecz), aby ponownie wyświetlić listę grup
parametrów. Wybrać grupę parametrów 99 Motor data (Dane silnika) i ustawić parametr
99.03 Motor type (Typ silnika).
Ustawić parametr 99.04 Motor ctrl mode (Tryb sterowania silnikiem).
DTC = Direct torque control (Bezpośrednie sterowanie momentem); Scalar (Skalarne)
Tryb DTC jest najczęściej odpowiedni. Tryb sterowania skalarnego jest zalecany, jeśli:
•prąd znamionowy silnika nie jest większy niż 1/6 prądu znamionowego przemiennika
częstotliwości,
przemiennik częstotliwości jest używany w celach testowych bez podłączonego silnika,
przemiennik częstotliwości steruje wieloma silnikami, a liczba podłączonych silników
jest zmienna.
Tabliczka znamionowa silnika przedstawia dane techniczne silnika, które należy wpisać do
odpowiednich parametrów. Należy wprowadzić wartości dokładnie
takie jakie przedstawia
tabliczka znamionowa silnika.
Przykładowa tabliczka znamionowa silnika
indukcyjnego (asynchronicznego):
Przykładowa tabliczka znamionowa silnika
synchronicznego z magnesami trwałymi:
Local 0.0 rpm
95 HW configuration
95.01 Supply voltage
Back
12:36
Edit
95.02 Adaptive voltage limits
95.04 Control board supply
380…415 V
Disable
Internal 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 97
PL
DE
ES
FI
FR
IT
NL
RU
PL
99.06 Motor nominal current (Prąd znamionowy silnika)
Dozwolony zakres wynosi:
w trybie DTC: 1/6 × I
Hd
… 2 × I
Hd
przemiennika częstotliwości
w trybie skalarnym: 0 … 2 × I
Hd
Uwaga: w przypadku numerycznych wartości znamionowych:
Za pomocą przycisków i zmienić wartość liczbową.
Za pomocą przycisków i przesunąć kursor w lewo lub prawo.
•Nacisnąć przycisk (Save — Zapisz), aby zapisać nowo wprowadzoną wartość.
Wprowadzić następujące ustawienia parametru w ten sam sposób.
99.07 Motor nominal voltage (Napięcie znamionowe silnika)
Dozwolony zakres wynosi 1/6 × U
N
… 2 × U
N
silnika.
W przypadku silnika synchronicznego z magnesami trwałymi napięcie znamionowe jest
napięciem BackEMF przy prędkości znamionowej.
Jeśli napięcie jest podane w jednostce V/obr./min (np. 60 V na 1000 obr./min), napięcie
przy prędkości znamionowej 3000 obr./min wynosi 3 × 60 V = 180 V. Należy pamiętać, że
napięcie znamionowe nie jest tym samym co równoważne napięcie silnika DC (EDCM)
podawane przez niektórych producentów. Napięcie znamionowe można obliczyć, dzieląc
napięcie EDCM przez 1,7 (pierwiastek kwadratowy z 3).
99.08 Motor nominal frequency (Znamionowa częstotliwość silnika)
W przypadku silnika synchronicznego z magnesami trwałymi, jeśli częstotliwość
znamionowa nie jest podana na tabliczce znamionowej, można ją obliczyć za pomocą
tego wzoru:
f = n × p / 60
gdzie n = znamionowa prędkość silnika, p = liczba par biegunów.
99.09 Motor nominal speed (Znamionowa prędkość silnika)
99.10 Motor nominal power (Znamionowa moc silnika)
99.11 Motor nominal cosfii (Znamionowa wartość cosinus fi silnika)
99.12 Motor nominal torque (Znamionowy moment obrotowy silnika)
Te wartości nie są wymagane, ale można je wprowadzić, aby zwiększyć dokładność
sterowania. Jeśli nie są znane, należy zostawić wartość 0.
98 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
99.13 Identification run request (Żądanie biegu identyfikacyjnego)
Ten parametr określa tryb biegu identyfikacyjnego (tylko w trybie DTC sterowania
silnikiem).
OSTRZEŻENIE! Tryby biegu identyfikacyjnych oznaczonych symbolem *
powodują uruchomienie silnika w kierunku do przodu (patrz szczegóły poniżej).
Przed wybraniem któregokolwiek z tych trybów, należy się upewnić, że uruchomienie
silnika jest bezpieczne.
Tryb *Normal (Normalny) należy wybierać zawsze, gdy jest to możliwe. Sterowane
urządzenie musi zostać odłączone od silnika, jeśli:
moment obciążenia jest wyższy niż 20% lub
•urządzenie nie wytrzyma chwilowego znamionowego momentu obrotowego podczas
wykonywania biegu identyfikacyjnego.
*Tryb-Reduced ( Zredukowany) należy wybrać, jeśli straty mechaniczne są wyższe niż
20%, tzn. nie można odłączyć obciążenia lub wymagany jest pełny strumień, aby
hamulec silnika pozostawał otwarty (np. w przypadku silników stożkowych).
Tryb Standstill (Nieruchomy) należy wybrać, jeśli nie można u
żyć trybu *Normal
(Normalny) ani *Reduced (Zredukowany). Uwagi:
Tego trybu nie można używać z silnikiem synchronicznym z magnesami trwałymi, jeśli
moment obciążenia jest wyższy niż 20% wartości znamionowej.
Hamulec mechaniczny nie jest otwierany przez układ sterujący na potrzeby biegu
identyfikacyjnego.
Upewnić się, że obwody bezpiecznego wyłączania momentu i zatrzymywania
awaryjnego (jeśli są obecne) są zamknięte.
Uruchomić bieg identyfikacyjny, naciskając
przycisk (Start).
Pojawi się ostrzeżenie, że bieg
identyfikacyjny trwa.
Sprawdzić, czy silnik obraca się we właściwym kierunku (do przodu, jak pokazano
poniżej).
Bieg identyfikacyjny zakończy się, gdy silnik się zatrzyma, a wartość parametru 99.13
zmieni się z powrotem na „No” (Nie).
Jeśli silnik obracał się
w niewłaściwą stronę, należy poprawić okablowanie silnika lub
ustawić parametr 99.16 Phase order (Kolejność faz).
3. Ustawienia sygnału sterowania
Sprawdzić pozycję zworek J1 i J2 na jednostce sterującej przemiennika częstotliwości.
Zworki te określają, czy wejścia analogowe AI1 i AI2 pracują w trybie prądowym, czy
napięciowym.
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 99
PL
DE
ES
FI
FR
IT
NL
RU
PL
Sprawdzić/dostosować następujące parametry.
20.01 Ext1 commands (Polecenia Zew1)
Domyślnie przemiennik częstotliwości włącza się lub wyłącza w zależności od stanu na
wejściu cyfrowym DI1 (0 = Stop, 1 = Start). Wejście DI2 określa kierunek obrotów (0 = do
przodu , 1 = do tyłu).
Jeśli są wymagane inne źdła sygnałów sterowania, należy odpowiednio skonfigurować
parametry od 20.03 do 20.05 (źródła od In1 do In3).
12.15 AI1 unit selection (Wybór jednostki AI1)
Wybrać wartość mA lub V odpowiadającą ustawieniu zworki J1.
12.17 AI1 min (wartość min. dla AI1)
12.18 AI1 max (wartość maks. dla AI1)
12.19 AI1 scaled at AI1 min (AI1 skalowane przy min. wartości AI1)
12.20 AI1 scaled at AI1 max (AI1 skalowane przy maks. wartości AI1)
Domyślnym wejściem do podłączenia wartości zadanej prę
dkości jest wejście analogowe
AI1. (Jest ono skonfigurowane w parametrach w grupie 22).
Parametry 12.17 i 12.18 określają górne i dolne wartości limitów wejściowych sygnałów
analogowych. Skalowanie parametrów 12.19 i 12.20 określa poziomy sygnałów
wewnętrznych odpowiadające tym limitom w następujący sposób:
Parametry od 12.27 do 12.30 odpowiadają analogicznie konfiguracji wejścia
analogowego AI2 .
AI (skalowane)
AI (mA/V)
12.20
12.18
12.17
12.19
100 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
13.12 AO1 source (Źródło AO1)
13.17 AO1 source min (Min. wartość AO1)
13.18 AO1 source max (Maks. wartość AO1)
13.19 AO1 out at AO1 src min (Wartość na wyjściu A01 przy minimalnej wartości
źródła A01)
13.20 AO1 out at AO1 src max (Wartość na wyjściu A01 przy maksymalnej wartości
źródła A01)
Parametr 13.12 określa źródło dla wyjścia analogowego AO1 (domyślnie: prędkość
silnika w obr./min).
Parametry 13.17 i 13.18 określają górne i dolne wartości sygnałów źródłowych
odpowiadające rzeczywistym wartościom wyjściowych sygnałów analogowych
określonym przez parametry 13.19 i 13.20.
46.10 Speed scaling (Skalowanie prędkości)
23.11 Ramp set selection (Wybór pary czasów przyspieszania i hamowania)
23.12 Acceleration time 1 (Czas przyspieszania 1)
23.13 Deceleration time 1 (Czas hamowania 1)
23.14 Acceleration time 2 (Czas przyspieszania 2)
23.15 Deceleration time 2 (Czas hamowania 2)
Można określić dwa różne zestawy ramp czasów przyspieszania/hamowania.
Źdło
przełączania między dwoma zestawami wybiera się za pomocą parametru 23.11.
Każdy czas przyspieszania/hamowania ustawiony w parametrach od 23.12 do 23.15
odnosi się do czasu, jaki potrzebuje przemiennik częstotliwości na przyspieszenie lub
wyhamowanie (między wartością 0 a prędkością skalowania, parametr 46.10).
Sygnał źródłowy
AO (mA)
13.18
13.20
13.19
13.17
Czas
Prędkość
46.10
23.12
23.14
23.13
23.15
Przysp. Ham..
0
Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym 101
PL
DE
ES
FI
FR
IT
NL
RU
PL
30.11 Minimum speed (Prędkość min.)
30.12 Maximum speed (Prędkość maks.)
30.17 Maximum current (Prąd maks.)
30.19 Minimum torque (Moment min.)
30.20 Maximum torque (Moment maks.)
Sprawdzić i w razie konieczności ustawić limity prędkości silnika, prądu i momentu
obrotowego.
Uruchomić przemiennik częstotliwości z dodatnią wartością odniesienia prędkości (do
przodu):
W panelu sterowania (Local control — Sterowanie lokalne): w widoku głównym Home
nacisnąć przycisk (Options — Opcje), wybrać opcję Reference (Zadawanie),
ustawić wartość zadaną za pomocą przycisków , , i , nacisnąć przycisk
Save (Zapisz), a następnie nacisnąć przycisk Start.
W sekcji I/O (We/Wy): w trybie Remote control (Sterowanie zdalne) ustawić wejście
analogowe AI1 (odniesienie), przełączyć wejście cyfrowe DI2 na wartość 0 (do przodu)
i przełączyć wejście cyfrowe DI1 na wartość 1 (start).
102 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze
Standardowym Oprogramowaniem Aplikacyjnym
PL
DE
ES
FI
FR
IT
NL
RU
PL
Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário 103
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Guia rápido de arranque para
acionamentos ACS880 com
programa de controlo primário
Sobre este guia
Este guia descreve a sequência básica de arranque de um acionamento ACS880
equipado com o programa de controlo primário. Está disponível documentação
completa do firmware do acionamento no Manual de firmware (consulte a lista de
manuais no interior da capa frontal).
Neste guia, o acionamento é configurado usando a consola de programação
ACS-AP-I. A sequência de arranque também pode ser efetuada usando a ferramenta
para PC, Drive composer.
Antes de arrancar
Certifique-se de que o acionamento foi mecânica e eletricamente instalado,
conforme descrito no Guia rápido de instalação e/ou no Manual de hardware
apropriado.
Segurança
AVISO!Todas as tarefas de instalação elétrica e de manutenção efetuadas no
acionamento devem ser realizadas por eletricistas qualificados.
Nunca trabalhe no acionamento, no circuito do chopper de travagem, no cabo do
motor ou no motor quando a alimentação está aplicada ao acionamento. Efetue
sempre uma medição para verificar que não existe tensão presente.
104 Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Arranque
Segurança
O arranque só pode ser executado por um eletricista qualificado.
As instruções de segurança devem ser seguidas durante o procedimento de
arranque. Veja as instruções de segurança nas primeiras páginas do Manual de
hardware apropriado.
Verificar a instalação. Consulte a lista de verificação da instalação no Manual de
hardware apropriado.
Verifique se o arranque do motor não provoca nenhum perigo.
Desacoplar a máquina acionada se:
existir risco de danos no caso de um sentido de rotação incorreto, ou
um ID run normal durante o arranque do acionamento, quando o binário de carga é
superior a 20% ou a maquinaria não suportar o binário nominal transitório durante o ID
run.
1 – Configurações de ligação, data e hora
Arranque do acionamento.
Nota: É normal que apareçam mensagens
de aviso em diversos pontos ao longo do
processo de arranque. Para ocultar uma
mensagem e para retomar o processo de
arranque, pressione .
Ocultar todos os avisos para aceder à vista
Início (apresentada no lado direito).
Os dois comandos na parte inferior do ecrã
(neste caso, Opções e Menu), apresentam
as funções das duas softkeys e
estão localizadas por baixo do ecrã. Os
comandos atribuídos às softkeys variam
dependendo do contexto.
Na vista Início , prima (Menu).
O Menu principal (direita) aparece.
Remoto 0.0 rpm
0.00
0.00
Binário motor %
%
0.0
Corrente motor
A
Velocidade motor usada
rpm
Opções
12:34
Menu
Remoto 0.0 rpm
Menu
Parâmetros
Assistentes
Eficncia energética
Registo de eventos
Sair
12:34
Selecionar
Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário 105
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Assinalar Ajustes no menu usando e
e premindo (Selecionar).
No menu Ajustes, assinale Data & hora (se
não estiver assinalado) e prima
(Selecionar).
No menu Data & hora, assinale Data (se
não estiver assinalada) e prima
(Selecionar).
Remoto 0.0 rpm
Ajustes
Idioma
Data & hora
Voltar
12:34
Selecionar
Editar textos
Ajustes ecrã
Próximo início poupança diurna 28.03.
Remoto 0.0 rpm
Data & hora
Data
Voltar
12:35
Editar
Tempo
Apresentar data como
01.01.1980
12:34:56
dia.mês.ano
Apresentar hora como 24-horas
Poupança diurna EU
Remoto 0.0 rpm
Data
Cancelar
12:35
Guardar
Dia Mês Ano
Terça
.01.198001
106 Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Definir a data correta:
Use e para mover o cursor para a
esquerda e direita.
Use e para ajustar o valor.
Pressione (Guardar) para aceitar
novo ajuste.
Verifique/ajuste todas as configurações no
menu Data & hora.
O ajuste Mostrar relógio determina se a
hora é sempre apresentada na parte inferior
do ecrã.
Após efetuar os ajustes, prima (Voltar
ou Sair) repetidamente até reaparecer a
vista Início (lado direito).
2 – Ajuste da tensão de alimentão e dados do motor
Mude para controlo local para assegurar que
o controlo externo é desativado
pressionando a tecla . O controlo
local é indicado pelo texto “Local” na parte
superior da consola.
Abra o Menu inicial premindo (Menu).
Assinale Parâmetros e pressione
(Selecionar).
Remoto 0.0 rpm
0.00
0.00
Binário motor %
%
0.0
Corrente do motor
A
Velocidade motor usada
rpm
Opções
12:35
Menu
Tecla Loc/Rem
Local 0.0 rpm
0.00
0.00
Binário motor %
%
0.0
Corrente do motor
A
Velocidade motor usada
rpm
Opções
12:36
Menu
Local 0.0 rpm
Menu
Parâmetros
Assistentes
Eficiência energética
Registo de eventos
Sair
12:36
Selecionar
Local 0.0 rpm
Pametros
Favoritos
Por função
Voltar
12:36
Selecionar
Lista completa
Modificados
Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário 107
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Assinale Lista completa usando e e
prima (Selecionar).
É apresentada uma lista completa de grupos
de parâmetros.
Assinale o grupo de parâmetros 95
Configuração HW e pressione
(Selecionar).
Note que a lista pode ser percorrida em
ambos os sentidos entre os grupos 99 e 01.
Neste caso, é mais rápido usar para
localizar o grupo 95 na lista.
Depois de selecionar um grupo, é
apresentada a lista de parâmetros dentro do
grupo.
Assinale o parâmetro 95.01 Tensão
alimentação (se não estiver assinalado) e
prima (Editar).
Os ajustes dos parâmetros disponíveis são
listados.
Assinale o ajuste correto na lista e prima
(Guardar).
Prima (Voltar) para apresentar novamente a lista dos grupos de parâmetros.
Selecione o grupo de parâmetros 99 Dados motor, e ajuste o parâmetro 99.03 Tipo
motor.
Local 0.0 rpm
Lista cpl
01 Valores atuais
03 Referências entrada
04 Avisos e falhas
05 Diagnósticos
06 Palavras de controlo e estado
07 Info Sistema
Voltar
12:36
Selecionar
Local 0.0 rpm
95 Configuração HW
95.01 Tensão alimentação
Voltar
12:36
Editar
95.02 Limites tensão adaptativa
95.04 Aliment. carta controlo
Não indicada
Desativar
24 V Interna
Local 0.0 rpm
95.01 Tensão alimentação
[0] Não indicada
[1] 208…240 V
Cancelar
12:36
Guardar
[2] 380…415 V
[3] 440…480 V
[4] 500 V
Local 0.0 rpm
95 Configuração HW
95.01 Tensão alimentação
Voltar
12:36
Editar
95.02 Lim tensão adaptativa
95.04 Alim. carta de controlo
380…415 V
Desativar
24 V Interna
108 Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
Ajuste o parâmetro 99.04 Modo ctrl motor.
DTC = Controlo direto de binário; Escalar
O DTC é apropriado para a maioria dos casos. O modo Escalar é recomendado se
a corrente nominal do motor for inferior a 1/6 da corrente nominal de saída do
acionamento,
o acionamento for usado para testes sem nenhum motor ligado, ou
o acionamento controlar múltiplos motores e o número de motores ligados for variável.
Consulte a chapa de características do motor para os ajustes de parâmetros seguintes.
Sempre que possível, introduza os valores exatamente
como apresentados na chapa de
características do motor.
Exemplo de uma chapa de características
de um motor de indução (assíncrono):
Exemplo de uma chapa de características
de um motor de ímanes permanentes:
99.06 Corrente nominal motor
A gama permitida é
em modo DTC: 1/6 × I
Hd
… 2 × I
Hd
do acionamento
em modo Escalar: 0 … 2 × I
Hd
Nota: Com valores de parâmetros numéricos:
Use e para alterar o valor de um dígito.
Use e para mover o cursor para a esquerda e direita.
•Prima (Guardar) para inserir o valor.
Ajuste os parâmetros seguintes da mesma forma.
99.07 Tensão nominal motor
A gama permitida é 1/6 × U
N
… 2 × U
N
do acionamento.
Com motores de ímanes permanentes, a tensão nominal é a tensão BackEMF à
velocidade nominal. Se a tensão é apresentada em volts/rpm (ex. 60 V por 1000 rpm), a
tensão à velocidade nominal de 3000 rpm é 3 × 60 V = 180 V. Note que a tensão nominal
não é o mesma que a tensão do motor CC equivalente (EDCM) apresentada por alguns
fabricantes. A tensão nominal pode ser calculada dividindo a tensão EDCM por 1.7 (ou
raiz quadrada de 3).
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
M
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário 109
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
99.08 Frequência nominal motor
Com motores de ímanes permanentes, se a frequência nominal não for apresentada na
chapa de características, pode ser calculada usando a seguinte fórmula:
f = n × p / 60
onde n = velocidade nominal do motor, p = número de pares de pólos.
99.09 Velocidade nominal motor
99.10 Potência nominal motor
99.11 Cosfii nominal motor
99.12 Binário nominal motor
Estes valores não são necessários, mas podem ser introduzidos para melhorar a
precisão do controlo. Se não forem conhecidos, deixe em 0.
99.13 Pedido volta de identificação (ID Run)
Este parâmetro seleciona o modo da volta de identificação (apenas modo DTC de
controlo do motor).
AVISO! Os modos da volta de identificação assinalados com * fazem o motor
funcionar no sentido direto (veja detalhes abaixo). Certifique-se de que é seguro
fazer funcionar o motor antes de selecionar qualquer um destes modos.
O modo *Normal deve ser selecionado sempre que possível. A máquina acionada deve
ser desacoplada do motor se
o binário de carga for superior a 20%, ou
a máquina não for capaz de suportar o binário nominal transitório durante o ID Run.
*O modo Reduzido deve ser selecionado se as perdas mecânicas forem superiores a
20%, ie. a carga não puder ser desacoplada, ou se for necessário fluxo total para manter
o travão do motor aberto (ex. com motores cónicos).
O modo Imobilizado deve ser selecionado se nenhum dos modos *Normal ou
*Reduzido puder ser usado. Notas:
Este modo não pode ser usado com um motor de ímanes permanentes se o binário de
carga for superior a 20% do nominal.
O travão mecânico não é aberto pela lógica para o ID Run.
Certifique-se que os circuitos da função de Binário seguro off e de paragem de
emergência (se presentes) estão fechados.
Arranque o motor pressionando o botão
(Arrancar).
Um aviso indica que a volta de
identificação está em progresso.
Verifique se o motor funciona no sentido correto (sentido direto apresentada abaixo).
A volta de identificação está completa quando o acionamento para e o valor do
parâmetro 99.13 reverte para “Não”.
Se o motor funcionar no sentido errado, corrija a cablagem do motor ou ajuste o
parâmetro 99.16 Ordem fases.
110 Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
3 – Ajustes do sinal de controlo
Verificar as posições dos jumpers J1 e J2 na unidade de controlo do acionamento. Estes
jumpers determinam se as entradas analógicas EA1 e EA2 são corrente ou tensão.
Verifique/ajuste os seguintes parâmetros.
20.01 Comandos Ext1
Por defeito, o acionamento arranca/para de acordo com o estado da entrada digital ED1
(0 = Parar, 1 = Arrancar). ED2 determina o sentido de rotação (0 = Direto, 1 = Inverso).
Se forem necessárias outras fontes, altere o valor de acordo. As fontes In1In3o
definidas pelos parâmetros 20.0320.05.
12.15 EA1 seleção unidade
Ajuste para mA ou V em correspondência com o ajuste do jumper J1.
12.17 EA1 Min
12.18 EA1 Max
12.19 EA1 escalada em EA1 Min
12.20 EA1 escalada em EA1 Max
A entrada por defeito para a referência de velocidade é a entrada analógica EA1. (Isto é
controlado pelos parâmetros no grupo 22.)
Os parâmetros 12.17 e 12.18 ajustam os limites inferior e superior para o sinal da
entrada analógica. A escala dos parâmetros 12.19 e 12.20 define os níveis do sinal
interno que corresponde a estes limites, como se segue:
Os parâmetros correspondentes para a entrada analógica EA2 são 12.2712.30.
EA (escalada)
EA (mA/V)
12.20
12.18
12.17
12.19
Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário 111
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
13.12 SA1 Fonte
13.17 SA1 Fonte min
13.18 SA1 Fonte max
13.19 SA1 em EA1 src min
13.20 SA1 em EA1 src max
O parâmetro 13.12 seleciona a fonte para a saída analógica SA1 (por defeito, velocidade
do motor em rpm).
Os parâmetros 13.17 e 13.18 ajustam os valores inferior e superior do sinal fonte
correspondentes aos valores atuais da saída analógica definidos pelos parâmetros 13.19
e 13.20.
46.10 Escala velocidade
23.11 Seleção rampa
23.12 Tempo aceleração 1
23.13 Tempo desaceleração 1
23.14 Tempo aceleração 2
23.15 Tempo desaceleração 2
É possível definir dois conjuntos diferentes de rampas de aceleração/desaceleração. A
fonte que comuta entre os dois conjuntos é selecionada pelo parâmetro 23.11.
Cada tempo de aceleração/desaceleração ajustado nos parâmetros 23.1223.15
refere-se ao tempo que o acionamento demora a acelerar ou desacelerar entre 0 e a
velocidade escalada (parâmetro 46.10).
Sinal fonte
SA (mA)
13.18
13.20
13.19
13.17
Tempo
Velocidade
46.10
23.12
23.14
23.13
23.15
Acel. Desacel.
0
112 Guia rápido de arranque para acionamentos ACS880 com programa de controlo
primário
PT
DE
ES
FI
FR
IT
NL
RU
SV
PT
30.11 Velocidade mínima
30.12 Velocidade máxima
30.17 Corrente máxima
30.19 Binário mínimo
30.20 Binário máximo
Verifique e ajuste se necessário, os limites para a velocidade, corrente e binário do
motor.
Arranque o acionamento com uma referência de velocidade positiva (direta):
Desde a consola de programação (controlo local): Na vista Início, prima
(Opções), selecione Referência, ajuste a referência usando as teclas , ,
, e
, prima Guardar, e prima o botão Arrancar.
Desde E/S: Em controlo Remoto, ajuste a entrada analógica EA1 (referência), comute
a entrada digital ED2 para 0 (direto) e a entrada digital ED1 para 1 (arrancar).
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 113
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Краткое руководство по
вводу в эксплуатацию
приводов ACS880 с
основной программой
управления
О настоящем руководстве
В этом руководстве приведено описание базовой процедуры ввода в эксплуа-
тацию привода ACS880, снабженного основной программой управления. Полная
документация по микропрограммному обеспечению привода содержится в
Руководстве по микропрограммному обеспечению (см перечень руководств
на внутренней стороне передней обложки).
В этом руководстве рассматривается настройка привода с панели управления
ACS-AP-I. Процедуру ввода в эксплуатацию можно выполнить также с помощью
компьютерного средства настройки приводов.
Подготовительные операции
Проверьте правильность механического и электрического монтажа привода по
соответствующему Краткому руководству по монтажу и/или Руководству по
монтажу и вводу в эксплуатацию.
Техника безопасности
ПРЕДУПРЕЖДЕНИЕ! Все работы по электрическому монтажу и
техническому обслуживанию привода должны проводиться только
квалифицированными электриками.
Запрещается выполнять работы на приводе, в цепи тормозного прерывателя,
на двигателе и его кабеле при включенном питании привода. Обязательно
убедитесь в фактическом отсутствии напряжения путем его измерения.
114 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Ввод в эксплуатацию
Техника безопасности
Ввод привода в эксплуатацию должен выполняться только квалифицированным
электриком.
При вводе привода в эксплуатацию необходимо соблюдать правила техники
безопасности. Указания по технике безопасности приведены в начале соответствующего
Руководства по монтажу и вводу в эксплуатацию.
Проверьте правильность монтажа. См. контрольный перечень операций проверки
монтажа в соответствующем Руководстве по монтажу и вводу в
эксплуатацию.
Убедитесь в том, что запуск двигателя не представляет опасности.
Отсоедините ведомый механизм в следующих случаях:
существует опасность повреждения в случае неправильного направления
вращения или
во время ввода привода в эксплуатацию требуется идентификационный прогон
врежиме Normal (Нормальный) в связи с тем, что крутящий момент нагрузки
превышает 20 % или машинное оборудование во
время идентификационного
прогона не может выдерживать номинальный переходный крутящий момент.
1 – Включение питания, установка даты и времени
Включите питание привода.
Примечание. Предупреждающие
сообщения, отображаемые на различных
этапах процесса ввода в эксплуатацию,
не свидетельствуют о нарушении
нормальной работы. Для скрытия
сообщения и возобновления процесса
ввода в эксплуатацию нажмите .
На данном этапе следует скрыть все
предупреждения для перехода к экрану
Home (показан справа).
Две команды внизу дисплея (в данном
случае
Параметры и Меню) указывают
назначение двух функциональных клавиш
и , расположенных под
дисплеем. Команды, назначенные
функциональным клавишам, зависят
от ситуации.
Remote 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Параметры
12:34
Меню
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 115
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
При экране Начальное представление
нажмите (Меню).
Отображается главное Меню (справа).
Выделите пункт меню Настройки с
помощью стрелок и , затем
нажмите (Выбрать).
В меню Настройки выделите пункт Дата
и время (если он еще не выделен) и
нажмите (Выбрать).
В меню Дата и время выделите пункт
Дата (если он еще не выделен) и
нажмите
(Выбрать).
Дистанц. 0.0 rpm
Меню
Параметры
Помощники
Энергоэффективность
Журнал событий
Выход
12:34
Выбрать
Дистанц. 0.0 rpm
Настройки
Язык
Дата и время
Назад
12:34
Выбрать
Правка текстов
Параметры дисплея
Начало след. летнего времени28.03.
Дистанц. 0.0 rpm
Дата и время
Дата
Назад
12:35
Правка
Время
Показывать дату как
01.01.1980
12:34:56
день.месяц.год
Показывать время как
24-часовой формат
Летнее время ЕС
Дистанц. 0.0 rpm
Дата
Отмена
12:35
Сохранить
дн. Мес. Год
Вторник
.01.198001
116 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Задайте надлежащую дату.
Стрелки и позволяют
перемещать курсор влево и вправо.
Для изменения значения используйте
стрелки и .
Чтобы принять новое значение,
нажмите (Сохранить).
Проверьте или задайте все остальные
параметры в меню Дата и время.
Параметр Показать часы указывает,
отображается ли время постоянно на
нижней панели дисплея.
Завершив задание параметров,
нажмите
(Назад или Выход) требуемое
количество раз для отображения экрана
Начальное представление (справа).
2 – Напряжение питания и установка данных двигателя
Для отключения внешнего управления
переключитесь на местное управление,
нажав кнопку . В режиме местного
управления в верхней части экрана
отображается текст "Местн.".
Откройте главное Меню, нажав
( Меню).
Дистанц. 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Параметры
12:35
Меню
Loc./Rem
Местн. 0.0 rpm
0.00
0.00
Motor torque %
%
0.0
Motor current
A
Motor speed used
rpm
Параметры
12:36
Меню
Местн. 0.0 rpm
Меню
Параметры
Помощники
Энергоэффективность
Журнал событий
Выход
12:36
Выбрать
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 117
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Выделите пункт Параметры и нажмите
(Выбрать).
Выделите пункт Полный список с
помощью стрелок и , затем
нажмите (Выбрать).
Отображается список групп параметров.
Выделите группу параметров
95 HW
configuration
и нажмите (
Выбрать
).
Обратите внимание на то, что в списке
предусмотрен циклический переход между
группами 99 и 01 в обоих направлениях.
Вданном случае перейти к группе 95 в
списке удобнее с помощью стрелк
и .
После выбора группы отображается
список входящих в нее параметров.
Выделите параметр 95.01 Supply voltage
(если он еще не выделен) и нажмите
(Правка).
Отображается список допустимых
значений параметра.
Местн. 0.0 rpm
Параметры
Избранное
По функции
Назад
12:36
Выбрать
Полный список
Измененные
Местн. 0.0 rpm
Полный список
01 Actual values
03 Input references
04 Warnings and faults
05 Diagnostics
06 Control and status words
07 System info
Назад
12:36
Выбрать
Местн. 0.0 rpm
95 HW configuration
95.01 Supply voltage
Назад
12:36
Правка
95.02 Adaptive voltage limits
95.04 Control board supply
Not given
Disable
Internal 24V
Местн. 0.0 rpm
95.01 Supply voltage
[0] Not given
[1] 208…240 V
Отмена
12:36
Сохранить
[2] 380…415 V
[3] 440…480 V
[4] 500 V
118 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Выделите в списке подходящее
напряжение питания и нажмите
(Сохранить).
Нажмите (Назад) для возврата к списку групп параметров. Выберите группу
параметров 99 Motor data и установите параметр 99.03 Motor type.
Установите параметр 99.04 Motor ctrl mode.
DTC = прямое регулирование крутящего момента; Scalar
В большинстве случаев подходит режим прямого регулирования крутящего
момента (DTC). Скалярный режим (Scalar) рекомендуется в следующих случаях:
номинальный
ток двигателя составляет менее 1/6 номинального тока привода,
выполняются испытания привода без подключения двигателя или
привод управляет несколькими двигателями, количество которых может
изменяться.
Относительно установки следующих параметров см. данные на паспортной табличке
двигателя. По возможности вводите значения, точно
совпадающие с указанными на
паспортной табличке.
Пример паспортной таблички
асинхронного двигателя:
Пример паспортной таблички двигателя
с постоянными магнитами:
Местн. 0.0 rpm
95 HW configuration
95.01 Supply voltage
Назад
12:36
Правка
95.02 Adaptive voltage limits
95.04 Control board supply
380…415 V
Disable
Internal 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 119
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
99.06 Motor nominal current
Допустимый диапазон
в режиме прямого регулирования крутящего момента: 1/6 × I
Hd
– 2 × I
Hd
привода;
в скалярном режиме: 0 – 2 × I
Hd
.
Примечание. При использовании числовых значений параметров:
Цифры изменяются с помощью стрелок и .
Стрелки и позволяют перемещать курсор влево и вправо.
Для ввода значения нажмите (Сохранить).
Аналогичным образом задайте значения следующих параметров.
99.07 Motor nominal voltage
Допустимый диапазон номинального напряжения двигателя: 1/6 × U
N
– 2 × U
N
привода.
Для двигателей с постоянными магнитами номинальным напряжением является
напряжение противоэдс при номинальной скорости вращения. Если напряжение
указано в вольтах на об/мин (например, 60 В на 1000 об/мин), напряжение при
номинальной скорости вращения 3000 об/мин составляет 3 × 60 В = 180 В. Следует
учитывать, что номинальное напряжение не совпадает с эквивалентным
напряжением двигателя постоянного
тока (EDCM), указываемым некоторыми
изготовителями. Номинальное напряжение можно вычислить путем деления
напряжения EDCM на 1,7 (или квадратный корень из 3).
99.08 Motor nominal frequency
Если номинальная частота переменного тока для двигателя с постоянными
магнитами не указана на паспортной табличке, ее можно рассчитать по следующей
формуле:
f = n × p / 60,
где nноминальная скорость двигателя, pчисло пар полюсов.
99.09 Motor nominal speed
99.10 Motor nominal power
99.11 Motor nominal cosfii
99.12 Motor nominal torque
Эти значения не являются обязательными, но их ввод позволяет повысить точность
регулирования. Если они не известны, оставьте значение 0.
120 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
99.13 Identification run request
Этот параметр позволяет выбрать режим идентификационного прогона (только в
режиме прямого регулирования крутящего момента двигателя).
ПРЕДУПРЕЖДЕНИЕ! В режимах идентификационного прогона, отмеченных
звездочкой (*), двигатель вращается в прямом направлении (подробные
сведения см. ниже). Перед выбором любого из этих режимов убедитесь в безопас-
ности запуска двигателя.
По возможности следует выбирать режим *Normal. Приводимое
в действие
оборудование необходимо отсоединить от двигателя в любой из указанных ниже
ситуаций:
крутящий момент нагрузки превышает 20 % от номинального значения или
машинное оборудование во время идентификационного прогона не может
выдерживать номинальный переходный крутящий момент.
*Reduced (Упрощенный): этот режим следует выбрать в том случае, если механи-
ческие потери превышают 20 %, т.
е. отсоединение нагрузки невозможно, или
освобожденное состояние тормоза двигателя сохраняется только при условии
полного магнитного потока (например, в случае конических электромагнитных
тормозов).
Режим Standstill (Неподвижный двигатель) следует выбрать в том случае, если
работа в режимах *Normal и *Reduced невозможна. Примечания.
Если у двигателя с постоянными магнитами крутящий момент нагрузки превышает
20 % от номинального значения, использовать этот режим нельзя.
Логическая схема не предусматривает освобождения механического тормоза для
идентификационного прогона.
Убедитесь в том, что цепи безопасного отключения крутящего момента и аварийного
останова замкнуты (при их наличии).
Запустите идентификационный прогон
нажатием пусковой кнопки .
Отображается предупреждение о
выполнении идентификационного
прогона.
Проверьте правильность направления вращения двигателя (на следующем рисунке
показано прямое направление).
Идентификационный прогон завершен, когда двигатель останавливается и
параметру 99.13 снова присваивается значение "No".
Если двигатель вращается в неверном направлении, исправьте подключение
кабеля двигателя или измените значение параметра 99.16 Phase order.
3 – Параметры сигналов управления
Проверьте положение перемычек J1 и J2 на блоке управления привода. Эти
перемычки определяют, являются ли аналоговые входы AI1 и AI2 токовыми
входами или входами напряжения.
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 121
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Проверьте/отрегулируйте следующие параметры.
20.01 Ext1 commands
По умолчанию пуск/останов привода осуществляется в соответствии с состоянием
цифрового входа DI1 (0 = останов, 1 = пуск). Вход DI2 определяет направление
вращения (0 = прямое, 1 = обратное).
Если необходимы другие источники, измените значение соответствующим образом.
Источники In1In3 определяются параметрами 20.0320.05.
12.15 AI1 unit selection
Выберите значение mA или V в соответствии с положением перемычки J1.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scaled at AI1 min
12.20 AI1 scaled at AI1 max
По умолчанию сигнал задания скорости поступает на аналоговый вход AI1.
(Назначение функции входу можно изменить с помощью параметров группы 22.)
Параметры 12.17 и 12.18 служат для указания верхнего и нижнего пределов
аналогового входного сигнала. Параметры масштабирования 12.19 и 12.20
определяют соответствующие этим пределам уровни внутреннего сигнала, как
показано на следующем графике
.
Для аналогового входа AI2 соответствующие значения определяются параметрами
12.27 12.30.
AI (после масштабирования)
AI (мА/В)
12.20
12.18
12.17
12.19
122 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
13.12 AO1 source
13.17 AO1 source min
13.18 AO1 source max
13.19 AO1 out at AI1 src min
13.20 AO1 out at AI1 src max
Параметр 13.12 позволяет выбрать источник для аналогового выхода AO1
(по умолчаниюскорость двигателя в об/мин).
Параметры 13.17 и 13.18 служат для указания верхнего и нижнего значений сигнала
источника, которые соответствуют фактическим значениям сигнала на аналоговом
выходе, определяемым параметрами 13.19 и 13.20.
46.10 Speed scaling
23.11 Ramp set selection
23.12 Acceleration time 1
23.13 Deceleration time 1
23.14 Acceleration time 2
23.15 Deceleration time 2
Можно определить два различных набора параметров ускорения
/замедления.
Параметр 23.11 позволяет выбрать источник, определяющий переключение между
этими наборами.
Каждый из параметров 23.12 23.15 указывает время ускорения или замедления
привода между нулевой и масштабированной скоростью (параметр 46.10).
Сигнал источника
AO (мА)
13.18
13.20
13.19
13.17
Время
Скорость
46.10
23.12
23.14
23.13
23.15
Ускорение Замедлени
0
Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной
программой управления 123
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
30.11 Minimum speed
30.12 Maximum speed
30.17 Maximum current
30.19 Minimum torque
30.20 Maximum torque
Эти параметры служат для проверки и установки пределов скорости, тока и
крутящего момента двигателя.
Для запуска привода с положительным задание скорости (в прямом направлении)
выполните следующие действия.
С панели управления (местное управление): при экране начального представ-
ления нажмите (Параметры), выберите Уставка, отрегулируйте задание
кнопками со стрелками , ,
, и , нажмите Сохранить, после чего
нажмите пусковую кнопку.
С модуля ввода-вывода: В режиме дистанционного управления отрегулируйте
аналоговый вход AI1 (задание), для цифрового входа DI2 укажите значение 0
(прямое направление), а для цифрового входа DI1 – значение 1 (пуск).
124 Краткое руководство по вводу в эксплуатацию приводов ACS880 с
основной программой управления
EN
DE
ES
FI
FR
IT
NL
RU
SV
RU
Snabbguide för ACS880 med standardprogramvara 125
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Snabbguide för ACS880 med
standardprogramvara
Om denna guide
Denna guide beskriver den grundggande idrifttagningsproceduren för
frekvensomriktare ACS880, utrustad med standardprogramvara. Fullständig
dokumentation av frekvensomriktaren systemprogramvara finns i Firmware manual
(se listan över dokumentation på den främre pärmens insida).
I denna guide görs alla inställningar i frekvensomriktaren med hjälp av
manöverpanelen ACS-AP-I. Idrifttagningen kan också utföras med hjälp av PC-
verktyget Drive composer.
Innan du börjar
Kontrollera att frekvensomriktare är mekaniskt och elektrisk installerad så som
beskrivs i motsvarande Quick installation guide och/eller Hårdvaruhandledning.
Säkerhet
VARNING! Allt elektriskt installations- och underhållsarbete
frekvensomriktaren skall utföras av behörig elektriker.
Arbeta aldrig med frekvensomriktaren, bromschopperkretsen, motorkabeln eller
motorn när systemet är spänningssatt. Kontrollera alltid genom mätning att ingen
spänning finns.
126 Snabbguide för ACS880 med standardprogramvara
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Idrifttagning
kerhet
Idrifttagningen skall utföras av behörig elektriker.
Säkerhetsanvisningarna måste följas under idrifttagningsproceduren. Se
säkerhetsinstruktioner på de inledande sidorna av motsvarande
Hårdvaruhandledning.
Kontrollera installationen. Se installationschecklistan i motsvarande
Hårdvaruhandledning.
Kontrollera att det inte medför fara om motorn startas.
Koppla bort driven utrustning om
det finns risk för skada vid felaktig rotationsriktning
•en Normal ID-körning krävs under idrifttagning av frekvensomriktaren, om lastmoment
är högre än 20 % eller om mekaniken inte tål de nominella momenttransienterna under
ID-körningen.
1 – Spänningssättning, datum och tid
Spänningssätt frekvensomriktaren.
Obs: Det är normalt att
varningsmeddelanden visas under
idrifttagningsproceduren. För att dölja ett
meddelande och återta
idrifttagningsproceduren, tryck på .
Dölj alla varningar för att komma till
Visningsvy (visas till höger).
De två kommandona längst ner på displayen
(i detta fall, Tillval och Meny), visar
funktionerna hos de båda
funktionstangenterna och som
sitter under displayen.
Funktionstangenternas funktioner beror på
aktuellt sammanhang.
I Visningavy, tryck på (Meny).
Huvudmenyn (till höger) visas.
Fjärr 0.0 rpm
0.00
0.00
Motormoment %
%
0.0
Motorström
A
Motorvarvtal
rpm
Tillval
12:34
Meny
Fjärr 0.0 rpm
Meny
Parametrar
Assistenter
Energieffektivitet
ndelselogg
Avsluta
12:34
Val
Snabbguide för ACS880 med standardprogramvara 127
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Markera Inställningar på menyn med
och och tryck (Välj).
I menyn Inställningar, markera Datum & tid
(om raden inte redan är markerad) och tryck
(Välj).
I menyn Inställningar, markera Datum (om
raden inte redan är markerad) och tryck på
(Välj).
Fjärr 0.0 rpm
Inställningar
Spk
Datum & tid
Tillbaka
12:34
Val
Redigera texter
Visningsinställningar
Välj sedan start för sommartid 28.03.
Fjärr 0.0 rpm
Datum & tid
Datum
Tillbaka
12:35
Ändra
Tid
Visa datum som
01.01.1980
12:34:56
dag.månad.år
Visa tid som 24-tim
Sommartid EU
Fjärr 0.0 rpm
Datum
Radera
12:35
Spara
Dag Månad År
Tisdag
.01.198001
128 Snabbguide för ACS880 med standardprogramvara
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Ställ in rätt datum:
Använd och att flytta markören åt
vänster och höger.
Använd och för att ändra värdet.
Tryck på (Spara) för att acceptera
den nya inställningen.
Kontrollera / justera alla kvarvarande
inställningar i menyn Datum & tid.
Inställningen Visa klocka avgör om tiden
skall visas kontinuerligt på displayens
nederdel.
Efter avslutade inställningar, tryck på
(Tillbaka eller Avsluta) upprepade gånger
tills Visningsvy (höger) återkommer.
2 – Matningsspänning och motordatainställningar
Övergå till lokal styrning för att säkerställa att
extern styrning är deaktiverad. Tryck på
tangenten . Lokal styrning indikeras av
texten ”Lokal” på displayens övre del.
Öppna Huvudmeny genom att trycka på
(Meny).
Fjärr 0.0 rpm
0.00
0.00
Motormoment %
%
0.0
Motorström
A
Motorvarvtal
rpm
Tillval
12:35
Meny
Loc/Rem
Lokal 0.0 rpm
0.00
0.00
Motormoment %
%
0.0
Motorström
A
Motorvarvtal
rpm
Tillval
12:36
Meny
Lokal 0.0 rpm
Meny
Parametrar
Assistenter
Energieffektivitet
ndelselogg
Avsluta
12:36
Val
Snabbguide för ACS880 med standardprogramvara 129
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Markera Parametrar och tryck på
(Välj).
Markera Fullständig lista med och
och tryck på (Välj).
En lista över parametergrupper visas.
Markera parametergrupp 95
Hårdvarukonfig och tryck på (Välj).
Observera att listan övergår direkt mellan
grupperna 99 och 01. I detta fall går det
alltså snabbare att använda för att gå till
grupp 95 på listan.
Efter val av en grupp visas en lista över
parametrarna inom gruppen.
Markera parameter 95.01
Matningsspänning (om den inte redan är
markerad) och tryck på (Redigera).
Tillgängliga parameterinställningar visas.
Lokal 0.0 rpm
Parametrar
Favoriter
Efter funktion
Tillbaka
12:36
Val
Fullständig lista
Ändrade
Lokal 0.0 rpm
Fullständig lista
01 Ärvärden
03 Inreferenser
04 Varningar och fel
05 Diagnostik
06 Styrnings- och statusord
07 Systeminfo
Tillbaka
12:36
Val
Lokal 0.0 rpm
95 Hårdvarukonfig
95.01 Matningsspänning
Tillbaka
12:36
Redigera
95.02 Anpassn spänningsgr
95.04 Styrkorts matn
Ej given
Deaktivera
Intern 24V
Lokal 0.0 rpm
95.01 Matningsspänning
[0] Ej given
[1] 208…240 V
Radera
12:36
Spara
[2] 380…415 V
[3] 440…480 V
[4] 500 V
130 Snabbguide för ACS880 med standardprogramvara
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Markera rätt värde i listan och tryck
(Spara).
Tryck på (Tillbaka) för att återgå till listan över parametergrupper. Välj
parametergruppen 99 Motor data, och ställ in parameter 99.03 Motortyp.
Ställ in parameter 99.04 Motor styrmetod.
DTC = Direkt momentreglering, Skalär
DTC lämpar sig i de flesta fall. Skalär styrning rekommenderas om
motorns märkström är mindre än 1/6 av frekvensomriktarens nominella utström
frekvensomriktaren används för teständamål utan någon ansluten motor
frekvensomriktaren matar flera motorer och antalet matade motorer kan variera.
Se motorns märkskylt för följande parameterinställningar. I mån av jlighet, mata in värdena
exakt
så som de anges på motorns märkskylt.
Exempel på märkskylt på en asynkronmotor: Exempel på märkskylt på en
permanentmagnetmotor:
96.06 Motor nom ström
Tillåtet område är
vid DTC-styrning: 1/6 × I
Hd
… 2 × I
Hd
för frekvensomriktaren
vid skalär styrning: 0 … 2 × I
Hd
Obs: Med numeriska parametervärden:
Använd och för att ändra ett siffervärde.
Använd och för att flytta markören åt vänster och höger.
Tryck på (Spara) för att mata in värdet.
Lokal 0.0 rpm
95 Hårdvarukonfig
95.01 Matningsspänning
Tillbaka
12:36
Redigera
95.02 Anpassn spänningsgr
95.04 Styrkorts matn
380…415 V
Deaktivera
Intern 24 V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Snabbguide för ACS880 med standardprogramvara 131
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Gör följande parameterinställningar på motsvarande sätt.
99.07 Motor nom spänn
Tillåtet område är 1/6 × U
N
… 2 × U
N
för frekvensomriktaren.
Vid permanentmagnetmotorer är märkspänningen lika med mot-EMK-spänningen vid
motorns märkvarvtal. Om spänningen anges i volt/rpm (t.ex. 60 V per 1000 rpm blir
spänningen vid märkvarvtalet 3000 rpm 3 × 60 V = 180 V. Observera att märkspänningen
inte är samma sak som den ekvivalenta DC-motorspänningen (EDCM) som anges av
vissa tillverkare. Märkspänningen kan beräknas genom att man dividerar EDCM-
spänningen med 1,7 (dvs. kvadratroten av 3).
99.08 Motor nom frekv
Med permanentmagnetmotorer, om märkfrekvensen inte anges på märkskylten, kan
värdet beräknas med hjälp av följande ekvation:
f = n × p / 60
där n = motorns märkvarvtal, p = antal polpar.
99.09 Motor nom varvt
99.10 Motor nom effekt
99.11 Motor nom cos fi
99.12 Motor nom moment
Dessa värden måste inte anges, men de kan anges för att förbättra styrnoggrannheten.
Om värdena inte är kända, lämna dem på 0.
99.13 ID körn begäran
Denna parameter väljer metoden för identifieringskörning (endast vid DTC-styrning).
VARNING! Identifieringskörningsmetoderna markerade med * försätter motorn i
rotation i framriktning (se nedan för detaljer). Se till att detta inte medför några
säkerhetsrisker innan en sådan metod väljs.
*Normal skall alltid väljas då så är möjligt. Den drivna utrustningen måste vara
bortkopplad från motorn om
belastningsmoment är högre än 20 %
den drivna utrustningen inte tål de nominella momenttransienterna under ID-körningen.
*Reducerat skall väljas om de mekaniska förlusterna är högre än 20 %, dvs. om den
drivna utrustningen inte kan kopplas bort, eller om fullt flöde krävs för att hålla motorns
broms lyft (t.ex. med koniska motorer).
Stillastående skall väljas om varken *Normal eller *Reducerat kan användas. Obs:
Denna metod kan inte användas för en permanentmagnetmotor om
belastningsmomentet är högre än 20 % av det nominella.
En mekanisk broms lyfts inte av logiken för ID-körning.
Kontrollera att eventuella kretsar för Safe torque-off och nödstopp är slutna.
Starta drivsystemet genom att trycka på
(Start)
Ett varningsmeddelande visar att ID-
körning pågår.
132 Snabbguide för ACS880 med standardprogramvara
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
Kontrollera att motorn går i rätt riktning (riktning framåt visas nedan).
ID-körningen är avslutad när värdet på parameter 99.13 återgår till ”Nej”.
Om motorn roterade åt fel håll, låt två fasledare byta plats, eller ändra parametern 99.16
Fasföljd.
3 – Styrsignalskonfigurering
Kontrollera positionerna hos byglarna J1 och J2 på frekvensomriktarens manöverpanel.
Dessa byglar avgör om de analoga ingångarna AI1 och AI2 fungerar som ström- eller
spänningsingångar.
Kontrollera/justera följande parametrar.
20.01 Ext1 styrning
Som förval gäller att drivsystemet startar och stoppar enligt status för digital ingång DI1
(0 = Stopp, 1 = Start). DI2 anger rotationsriktningen (0 = Fram, 1 = Back).
Om ytterligare källor behövs, ändra deras värden efter behov. Källorna In1In3
definieras av parametrarna 20.0320.05.
12.15 AI1 enhet val
Sätt denna parameter till antingen mA eller V, motsvarande inställningen av bygel J1.
12.17 AI1 min
12.18 AI1 max
12.19 AI1 skalat vid AI1 min
12.20 AI1 skalat vid AI1 max
Förvald ingång för varvtalsreferens är analog ingång AI1. (Detta styrs av parametrarna i
grupp 22.)
Parametrarna 12.17 och 12.18 anger lägsta och högsta gräns för analog insignal.
Skalningsparametrarna 12.19 och 12.20 definierar de interna signalnivåer som motsvarar
dessa gränser, på följande sätt:
Motsvarande parametrar för analog ingång AI2 är 12.2712.30.
AI (skalat)
AI (mA/V)
12.20
12.18
12.17
12.19
Snabbguide för ACS880 med standardprogramvara 133
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
13.12 AO1 källa
13.17 AO1 källa min
13.18 AO1 källa max
13.19 AO1 ut vid AO1 källa min
13.20 AO1 ut vid AO1 källa max
Parameter 13.12 väljer källa för analog utgång AO1 (som förval, motorvarvtalet i rpm).
Parametrarna 13.17 och 13.18 anger lägsta och högsta källsignalvärde som motsvarar
faktiska analoga utsignalvärden, definierade av parametrarna 13.19 och 13.20.
46.10 Skaln varvtal
23.11 Val regulatorramp
23.12 Accelerationstid 1
23.13 Retardationstid 1
23.14 Accelerationstid 2
23.15 Retardationstid 2
Du kan definiera två olika uppsättningar accelerations-/retardationsramper. Källsignalen
som växlar mellan de båda uppsättningarna väljs med parameter 23.11.
Varje accelerations-/retardationsrampuppsättning som ställs in med parametrarna
23.1223.15 avser den tid det tar för frekvensomriktaren att öka eller minska sin
utfrekvens mellan 0 och skalningsvarvtalet (parameter 46.10).
Källsignal
AO (mA)
13.18
13.20
13.19
13.17
Tid
Varvtal
46.10
23.12
23.14
23.13
23.15
Acc. Ret.
0
134 Snabbguide för ACS880 med standardprogramvara
EN
DE
ES
FI
FR
IT
NL
RU
SV
SV
30.11 Min varvtal
30.12 Max varvtal
30.17 Max ström
30.19 Min moment
30.20 Max moment
Kontrollera, och vid behov justera, gränsvärdena för motorvarvtal, ström och moment.
Starta drivsystemet med låg varvtalsreferens (rotationsriktning framåt):
Från manöverpanelen (lokal styrning): I Visningsvy tryck på (Alternativ). Välj
Referens, justera referensen med hjälp av tangenterna , ,
, och , tryck på
Spara, och tryck på Start.
Från I/O: Vid fjärrstyrning, justera analog ingång AI1 (referens), växla digital ingång DI2
till 0 (framåt) och växla digital ingång DI1 till 1 (start).
Birincil kontrol programlı ACS880 için hızlı devreye alma kı lavuzu 135
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Birincil kontrol programlı
ACS880 için hızlı devreye
alma kılavuzu
Kılavuz hakkı nda
Bu kılavuz birincil kontrol programı bulunan bir ACS880 sürücünün temel devreye
alma sıralamasınııklar. Sürücü yazılı mına ilişkin tüm belgeler Yazılım kılavuzunda
bulunabilir (ön kapağın tarafındaki kılavuzlar listesine bakın).
Bu kılavuzda, sürücü ayarları ACS-AP-I kontrol paneli kullanılarak yapılır. Devreye
alma sıralaması Sürücü düzenleyici PC aracı kullanılarak da gerçekleştirilebilir.
Başlamadan önce
Sürücünün mekanik ve elektriksel kurulumunun ilgili Hızlı kurulum kılavuzu ve/veya
Donanım kılavuzundaıklandığı gibi yapıldığından emin olun.
Güvenlik
UYARI! Sürücünün elektrik tesisatı kurulumu ve bakım işleri yalnızca yetkili
elektrikçiler tarafından yapılmalıdır.
Sürücü, fren kesici devresi, motor kablosu ve motor üzerinde sürücüde elektrik
varken kesinlikle çalışmayın. Mutlaka ölçüm yaparak gerilim bulunmadığından her
zaman emin olun.
136 Birincil kontrol programlı ACS880in hızlı devreye alma kılavuzu
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Devreye alma
venlik
Devreye alma sadece yetkili bir elektrikçi tarafından gerçekleştirilebilir.
Devreye alma prosedürü boyunca güvenlik talimatlarına uyulmalıdır. İlgili Donanım
kılavuzunun ilk sayfalarındaki güvenlik talimatlarına başvurun.
Kurulumu kontrol edin. Uygun Donanım kılavuzundaki kurulum kontrol listesine başvurun.
Motoru start etmenin bir tehlikeye yol açmayacağından emin olun.
Aşağıdaki durumlarda motor ile tahrik edilen makine arasındaki mekanik bağlantıyı
sökün
yanlış yönde döş durumunda hasar tehlikesi varsa, veya
sürücü devreye alma sırasında bir Normal ID çalışması gerekli, yük momenti %20'den
daha fazla veya ID çalışması sırasında ekipman nominal momente dayanacak
durumda değilse.
1 – Güç verme, tarih ve saat ayarları
Sürücüye güç verin.
Not: Devreye alma işlemi sırasında çeşitli
noktalarda uyarı mesajlarının belirmesi
normaldir. Bir uyarı mesajını gizlemek ve
devreye alma işlemine devam etmek için,
ğmesine basın.
Ana görünüme (sağ tarafta gösterilmektedir)
tüm uyarıları şimdi gizleyin.
Ekranın alt kısmında iki komut bulunur (bu
durumda, Seçenekler ve Menü) ve ekranın
alt kısmındaki ve olmak üzere iki
programlanabilir tuşun fonksiyonunu
gösterir. Programlanabilir tuşlara atanan
komutlar bağlama göre değişiklik gösterir.
Ana
görünümde, tuşuna basın (
Menü
).
Ana Menü (sağ) belirir.
Uzak 0,0 rpm
0.00
0.00
Motor momenti %
%
0.0
Motor akımı
A
Kullanılan motor hızı
rpm
Seçenekler
12:34
Me
Uzak 0,0 rpm
Me
Parametreler
Asistanlar
Enerji verimliliği
Olay günlüğü
Çıkış
12:34
Seçim
Birincil kontrol programlı ACS880 için hızlı devreye alma kı lavuzu 137
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
ve tuşlarıyla Ayarlar öğesini
vurgulayın ve (Seçim) tuşuna basın.
Ayarlar menüsünde, Tarih ve saat öğesini
vurgulayın (vurgulanmamışsa) ve
(Seçim) tuşuna basın.
Tarih ve saat menüsünde, Tarih öğesini
vurgulayın (vurgulanmamışsa) ve
(Seçim) tuşuna basın.
Uzak 0,0 rpm
Ayarlar
Dil
Tarih ve saat
Geri
12:34
Seçim
Metinleri düzenle
Ekran ayarları
Sonraki gün ışığı tasarrufu başlangıcı28.03.
Uzak 0,0 rpm
Tarih ve saat
Tarih
Geri
12:35
Yaz
Saat
Tarihi şu şekilde göster:
01.01.1980
12:34:56
gün.ay.yıl
Saati şu şekilde göster: 24 saat
Gün ışığı tasarrufu EU
Uzak 0,0 rpm
Tarih
İptal
12:35
Kaydet
Gün Ay Yıl
Salı
.01.198001
138 Birincil kontrol programlı ACS880in hızlı devreye alma kılavuzu
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Doğru tarihi ayarlayın:
İmleci sola ve sağa kaydırmakin ve
tuşlarını kullanın.
•Değeri değiştirmekin ve tuşlarını
kullanın.
Yeni ayarı kabul etmek için (Kaydet)
tuşuna basın.
Tarih ve saat menüsünde kalan tüm ayarları
kontrol edin/ayarlayın.
Saati göster ayarı ekranın alt bölmesinde
saatin sürekli gösterilip gösterilmeyeceğini
belirler.
Ayarları yaptıktan sonra, Ana görünüm (sağ)
belirinceye kadar arka arkaya (Geri
veya Çıkış) tuşuna basın.
2 – Besleme gerilimi ve motor verisi ayarları
Harici kontrolün devre dışı kaldığından emin
olmak için, kontrol panelindeki tuşuna
basın. Lokal kontrol, üst bölmedeki “Lokal”
metni ile gösterilir.
(Menü) tuşuna basarak ana Menü'yü
ın.
Uzak 0,0 rpm
0.00
0.00
Motor momenti %
%
0.0
Motor akımı
A
Kullanılan motor hızı
rpm
Seçenekler
12:35
Me
Loc/Rem
Lokal 0,0 rpm
0.00
0.00
Motor momenti %
%
0.0
Motor akımı
A
Kullanılan motor hızı
rpm
Seçenekler
12:36
Me
Lokal 0,0 rpm
Me
Parametreler
Asistanlar
Enerji verimliliği
Olay günlüğü
Çıkış
12:36
Seçim
Birincil kontrol programlı ACS880 için hızlı devreye alma kı lavuzu 139
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Parametreler öğesini vurgulayın ve
(Seçim) tuşuna basın.
ve tuşlarıyla Tam liste öğesini
vurgulayın ve (Seçim) tuşuna basın.
Bir parametre grubu listesi görüntülenir.
95 Donanım konfigürasyonu parametre
grubunu vurgulayın ve (Seçim) tuşuna
basın.
Listenin 99 ve 01 grupları arasında her iki
yönde de kullanılabildiğini unutmayın. Bu
durumda, listede grup 95'i bulmak için
tuşunun kullanılması işlemi hızlandıracaktır.
Bir grup seçildikten sonra, gruptaki bir
parametre listesi görüntülenir.
95 Besleme gerilimi parametresini
vurgulayın (vurgulanmamışsa) ve
(Yaz) tuşuna basın.
Mevcut parametre ayarları listelenir.
Lokal 0,0 rpm
Parametreler
Favoriler
Fonksiyona göre
Geri
12:36
Seçim
Tam liste
Değiştirilen
Lokal 0,0 rpm
Tam liste
01 Gerçek değerler
03 Giriş referansları
04 Uyarı ve hatalar
05 Tanı
06 Kontrol ve durum word'leri
07 Sistem bilgisi
Geri
12:36
Seçim
Lokal 0,0 rpm
95 Donanım konfigürasyonu
95.01 Besleme gerilimi
Geri
12:36
Yaz
95.02 Uyarlamalı gerilim limitleri
95.04 Kontrol kartı beslemesi
Belirtilmedi
Devre dışı
Dahili 24V
Lokal 0,0 rpm
95.01 Besleme gerilimi
[0] Belirtilmedi
[1] 208…240 V
İptal
12:36
Kaydet
[2] 380…415 V
[3] 440…480 V
[4] 500 V
140 Birincil kontrol programlı ACS880in hızlı devreye alma kılavuzu
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Listede doğru ayarı vurgulayın ve
(Kaydet) tuşuna basın.
Parametre grupları listesini tekrar görüntülemek için (Geri) tuşuna basın. 99 Motor
verileri parametre grubunu seçin ve 99.03 Motor tipi parametresini girin.
99.04 Motor kntrl modu parametresini girin.
DTC = Doğrudan moment kontrolü; Skaler
DTC, birçok durum için uygundur. Skaler mod aşağıdaki durumlarda önerilir
motor nominal akımının sürücü nominal akımının 1/6’sından düşük olması,
sürücünün, motor bağlanmadan test amaçlı kullanılması veya
sürücünün birden fazla motoru kontrol etmesi ve bağlı motor sayısının değişken
olması.
Aşağıdaki parametre ayarları için motor plakasına bakın. Mümkünse, değerleri motor
plakasında gösterildiği gibi tam olarak girin.
Bir endüksiyon (asenkron) motoru plaka
örneği:
Bir sabit mıknatıslı motor plaka örneği:
99.06 Motor nominal akımı
İzin verilen aralık
DTC modunda: 1/6 × I
Hd
… 2 × sürücü I
Hd
Skaler modda: 0 … 2 × I
Hd
Not:merik parametre değerlerinde:
Bir hanenin değerini değiştirmek için, ve tuşunu kullanın.
İmleci sola ve sağa kaydırmak için ve tuşlarını kullanın.
•Değeri girmek için (Kaydet) tuşuna basın.
Lokal 0,0 rpm
95 Donanım konfigürasyonu
95.01 Besleme gerilimi
Geri
12:36
Yaz
95.02 Uyarlamalı gerilim limitleri
95.04 Kontrol kartı beslemesi
380…415 V
Devre dışı
Dahili 24V
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1
Birincil kontrol programlı ACS880 için hızlı devreye alma kı lavuzu 141
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Aşağıdaki parametre ayarlarını aynı şekilde yapın.
99.07 Motor nominal gerilimi
İzin verilen aralık: sürücünün 1/6 × U
N
… 2 × U
N
değeri.
Sabit mıknatıslı motorlarda, nominal gerilim nominal hızdaki BackEMF gerilimidir. Gerilim
volt/rpm (örn. 60 V / 1000 rpm) olarak verilirse, 3000 rpm nominal hızdaki gerilim 3 × 60 V
= 180 V şeklindedir. Nominal gerilimin, bazı üreticiler tarafından belirlenen eşdeğer DC
motor gerilimine (EDCM) eşit olmadığını unutmayın. Nominal gerilim, EDCM gerilimini
1,7'ye (veya 3'ün kareköküne) bölerek hesaplanabilir.
99.08 Motor nominal frekansı
Sabit mıknatıslı motorlarda, motor plakasında nominal frekans gösterilmemişse, şu
formül kullanılarak hesaplanabilir:
f = n × p / 60
burada n = nominal motor hızı, p = kutup çifti sayısı.
99.09 Motor nominal hızı
99.10 Motor nominal gücü
99.11 Motor nominal cosfii
99.12 Motor nominal momenti
Bu değerlere g
erek duyulmaz, ancak kontrol doğruluğunu artırmak için girilebilir. Bilinmediği durumlarda
0 olarak bırakın.
99.13 Tanımlama çal
ıştırması talebi
Bu parametre tanımlama çalıştırması modunun seçilmesini sağlar (sadece DTC motor
kontrol modu).
UYARI! Bu nedenle * ile işaretlenmiş tanımlama çalıştırması modları motorun ileri
yönde dönmesini sağlayacaktır (ayrıntılarin aşağı bakın). Bu modlardan
herhangi birini seçmeden önce motorun çalıştırılmasının güvenli olduğundan emin olun.
Mümkün olan her durumda *Normal mod seçilmelidir. Tahrik edilen makine aşağıdaki
durumlarda motordan ayrılmalıdır:
yük momenti %20'den daha yüksekse veya
•tanımlama çalıştırması sırasında makine nominal momente dayanacak durumda
değilse.
*Mekanik kayı
pların %20'den daha yüksek olması, yani yükün ayrılamaması veya motor
freninin açık tutulmasıin tam akının gerekli olması durumunda, şük mod seçilmelidir.
*Normal ya da *Düşük mod kullanılamıyorsa, Sabit mod seçilmelidir. Notlar:
Bu mod, yük momenti nominal değerin %20'sinden fazlaysa sabit mıknatıslı motorda
kullanılamaz.
•Tanımlama çalıştırmasıin lojik tarafından için mekanik fren açılmaz.
Güvenli moment kapatma ve acil durdurma devrelerinin (varsa) kapalı olduğundan emin
olun.
(Start) düğmesine basarak tanımlama
çalıştırmasını başlatın.
Tanımlama çalıştırması devam ederken bir
uyarı
rüntülenecektir.
142 Birincil kontrol programlı ACS880in hızlı devreye alma kılavuzu
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
Motorun doğru yönde çalıştığını kontrol edin (aşağıda ileri yön gösterilmektedir).
Sürücü durduğunda ve 99.13 parametresinin değeri “Hayır” olarak değiştiğinde
tanımlama çalıştırması tamamlanmıştır.
Motor yanlış yönde çalıştıysa, motor kablolarınızeltin veya 99.16 Faz sırası
parametresini ayarlayın.
3 – Kontrol sinyali ayarları
sürücünün denetleme birimindeki J1 ve J2 jumper'larının konumunu kontrol edin. Bu
jumper'lar AI1 ve AI2 analog girişlerinin akım ya da gerilim olmasını belirler.
Aşağıdaki parametreleri kontrol edin/ayarlayın.
20.01 Har1 komutlar
Varsayılan olarak, dijital giriş DI1 durumuna göre başlar/durur (0 = Stop, 1 = Start). DI2
dönüş yönünü belirler (0 = İleri, 1 = Geri).
Başka kaynaklar gerekiyorsa, değeri uygun şekilde değiştirin. In1In3 kaynakları
20.0320.05 parametreleriyle tanımlanır.
12.15 AI1 birimi seçimi
Bunu J1 jumper'ı ayarına göre mA ya da V olarak ayarlayın.
12.17 AI1 min
12.18 AI1 maks
12.19 AI1, AI1 min'de ölçeklendirilmiş
12.20 AI1, AI1 maks'da ölçeklendirilmiş
Hız referansıin varsayılan giriş AI1 analog girişidir. (Bu, grup 22'deki parametrelerle
kontrol edilir.)
12.17 ve 12.18 parametreleri analog giriş sinyalinin alt ve üst limitlerini ayarlar. 12.19 ve
12.20 ölçeklendirme parametreleri bu limitlere karşı
lık gelen dahili sinyal seviyelerini
aşağıdaki şekilde tanımlar:
AI2 analog girişi için karşılık gelen parametreler 12.2712.30 şeklindedir.
AI (ölçeklendirilmiş)
AI (mA/V)
12.20
12.18
12.17
12.19
Birincil kontrol programlı ACS880 için hızlı devreye alma kı lavuzu 143
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
13.12 AO1 kaynağı
13.17 AO1 kaynağı min
13.18 AO1 kaynağı maks
13.19 AO1 çıkışı AI1 src min'de
13.20 AO1 çıkışı AI1 src maks'da
13.12 parametresi AO1 analog girişi için kaynağı seçer (varsayılan olarak, motor hızı rpm
cinsindendir).
13.17 ve 13.18 parametreleri, 13.19 ve 13.20 parametreleriyle tanımlanan gerçek analog
çıkış değerlerine karşılık gelen alt ve üst kaynak sinyali değerlerini ayarlar.
46.10 Hız ölçeklendirme
23.11 Rampa ayarı seçimi
23.12 Hızlanma süresi 1
23.13 Yavaşlama süresi 1
23.14 Hızlanma süresi 2
23.15 Yavaşlama süresi 2
İki farklı hızlanma/yavaşlama rampası ayarı tanımlayabilirsiniz. İki ayar arasında değ
işen
kaynak 23.11 parametresiyle silebilir.
23.1223.15 parametrelerindeki her bir hızlanma/yavaşlama süresi ayarı sürücünün 0
ve ölçeklendirilen hız (46.10 parametresi) arasında hızlanması veya yavaşlaması için
geçen süreyi ifade eder.
Kaynak sinyali
AO (mA)
13.18
13.20
13.19
13.17
Süre
Hız
46.10
23.12
23.14
23.13
23.15
Hız. Yav.
0
144 Birincil kontrol programlı ACS880in hızlı devreye alma kılavuzu
TR
DE
ES
FI
FR
IT
NL
RU
SV
TR
30.11 Minimum hız
30.12 Maksimum hız
30.17 Maksimum akım
30.19 Minimum moment
30.20 Maksimum moment
Motor hızı, akımı ve momentinin limitlerini kontrol edin ve gerekirse ayarlayın.
rücüyü pozitif (ileri) hız referansıyla başlatın:
Kontrol panelinden (Lokal kontrol): Ana görünümde, (Seçenekler) tuşuna basın,
Referans öğesini seçin, , ,
, ve tuşlarını kullanarak referansı ayarlayın,
Kaydet tuşuna ve ardından Start düğmesine basın.
I/O'dan: Uzaktan kontrolde, AI1 analog girişini (referans) ayarlayın, DI2 dijital girişini 0
(ileri) olarak değiştirin ve DI1 dijital girişini 1 (start) olarak değiştirin.
3AUA0000098062 Rev D (MUL) EFFECTIVE: 2012-10-22

Documenttranscriptie

ABB industrial drives Quick start-up guide ACS880 drives with primary control program English . . . . . . . . 3 EN Dansk . . . . . . . .13 DA Deutsch. . . . . . . 23 DE Español. . . . . . .35 ES Suomi . . . . . . . .47 FI Français . . . . . .57 FR Italiano . . . . . . . 69 IT Nederlands . . . . 81 NL Polski . . . . . . . . 91 PL Português . . . . 103 PT Русский . . . . . 113 RU Svenska . . . . . 125 SV Türkçe. . . . . . . 135 TR List of related manuals in English Drive hardware manuals ACS880-01 drives hardware manual ACS880-01 quick installation guide for frames R1 to R3 ACS880-01 quick installation guide for frames R4 and R5 ACS880-01 quick installation guide for frames R6 to R9 ACS880-07 drives hardware manual ACS880-104 inverter modules hardware manual ACS880-107 inverter units hardware manual Code (English) 3AUA0000078093 3AUA0000085966 3AUA0000099663 3AUA0000099689 3AUA0000105718 3AUA0000104271 3AUA0000102519 Drive firmware manuals and guides ACS880 primary control program firmware manual ACS880 drives with primary control program, quick startup guide 3AUA0000085967 3AUA0000098062 Option manuals and guides ACS-AP-x assistant control panels user’s manual 3AUA0000085685 Drive composer Start-up and maintenance PC tool User’s 3AUA0000094606 manual Manuals and quick guides for I/O extension modules, fieldbus adapters, encoder interfaces, etc. 3AUA0000098062 Rev D MUL EFFECTIVE: 2012-10-22  2012 ABB Oy. All Rights Reserved. Quick start-up guide for ACS880 drives with primary control program 3 Quick start-up guide for ACS880 drives with primary control program About this guide This guide describes the basic start-up sequence of an ACS880 drive equipped with the primary control program. Complete documentation of the drive firmware can be found in Firmware manual (see list of manuals on the inside of the front cover). DE In this guide, the drive is set up using the ACS-AP-I control panel. The start-up sequence can also be carried out using the Drive composer PC tool. ES Before you start FI Ensure that the drive has been mechanically and electrically installed as described in the appropriate Quick installation guide and/or Hardware manual. FR Safety EN IT NL WARNING! All electrical installation and maintenance work on the drive should be carried out by qualified electricians only. Never work on the drive, the braking chopper circuit, the motor cable or the motor when power is applied to the drive. Always ensure by measuring that no voltage is actually present. RU SV 4 Quick start-up guide for ACS880 drives with primary control program Start-up Safety The start-up may only be carried out by a qualified electrician. The safety instructions must be followed during the start-up procedure. See the safety instructions on the first pages of the appropriate Hardware manual. Check the installation. See the installation checklist in the appropriate Hardware manual. Check that the starting of the motor does not cause any danger. EN DE ES FI FR IT NL RU SV De-couple the driven machine if • there is a risk of damage in case of an incorrect direction of rotation, or • a Normal ID run is required during the drive start-up, when the load torque is higher than 20% or the machinery is not able to withstand the nominal torque transient during the ID run. 1 – Power-up, date and time settings Power up the drive. Note: It is normal that warning messages appear at various points along the start-up process. To hide a message and to resume the start-up process, press . Hide any warnings now to enter the Home view (shown on the right). The two commands at the bottom of the display (in this case, Options and Menu), show the functions of the two softkeys and located below the display. The commands assigned to the softkeys vary depending on the context. In the Home view, press (Menu). The main Menu (right) appears. Remote 0.0 rpm Motor speed used rpm Motor current A Motor torque % % Options 12:34 Remote Menu 0.00 0.00 0.0 Menu 0.0 rpm Parameters Assistants Energy efficiency Exit Event log 12:34 Select Quick start-up guide for ACS880 drives with primary control program 5 Highlight Settings on the menu using and and press (Select). In the Settings menu, highlight Date & time (if not already highlighted) and press (Select). In the Date & time menu, highlight Date (if not already highlighted) and press (Select). Remote Settings Language Date & time Edit texts Display settings 0.0 rpm Back Select 12:34 Remote 0.0 rpm Date & time Date 01.01.1980 Time 12:34:56 Show date as day.month.year Show time as 24-hour Daylight saving EU Next daylight saving start 28.03. Back 12:35 Edit Remote Date 0.0 rpm DE ES FI FR IT NL Day Month Year RU 01 .01.1980 SV Tuesday Cancel EN 12:35 Save 6 Quick start-up guide for ACS880 drives with primary control program Set the correct date: • Use and and right. to move the cursor left • Use and to change the value. • Press (Save) to accept the new setting. Check/adjust all the remaining settings in the Date & time menu. The Show clock setting determines whether the time is shown at all times in the bottom pane of the display. EN DE ES FI FR Remote Motor speed used rpm Motor current A Motor torque % % Options Menu 2 – Supply voltage and motor data settings Switch to local control to ensure that external control is disabled by pressing the Loc/Rem key. Local control is indicated by the text “Local” in the top pane. Local 0.0 rpm Motor speed used rpm Motor current A Motor torque % % NL Options SV 12:35 0.00 0.00 0.0 After you have made the settings, press (Back or Exit) repeatedly until the Home view (right) reappears. IT RU 0.0 rpm Open the main Menu by pressing (Menu). 12:36 Local Menu 0.00 0.00 0.0 Menu 0.0 rpm Parameters Assistants Energy efficiency Exit Event log 12:36 Select Quick start-up guide for ACS880 drives with primary control program 7 Highlight Parameters and press (Select). Local Parameters Favorites By function Complete list Modified Back Highlight Complete list using and and press (Select). A listing of parameter groups is displayed. Highlight parameter group 95 HW configuration and press (Select). Note that the list wraps around in either direction between groups 99 and 01. In this case, it is quicker to use to locate group 95 on the list. 0.0 rpm 12:36 Local Complete list 01 Actual values 03 Input references 04 Warnings and faults 05 Diagnostics 06 Control and status words 07 System info Back 12:36 Select 0.0 rpm DE ES FI Select Local 0.0 rpm 95 HW configuration 95.01 Supply voltage Not given 95.02 Adaptive voltage limits Disable 95.04 Control board supply Internal 24V After selecting a group, a listing of parameters within the group is displayed. FR IT NL RU SV Back Highlight parameter 95.01 Supply voltage (if not already highlighted) and press (Edit). The available parameter settings are listed. EN 12:36 Local 95.01 Supply voltage [0] Not given [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Cancel 12:36 Edit 0.0 rpm Save 8 Quick start-up guide for ACS880 drives with primary control program Highlight the correct setting on the list and press (Save). Local 0.0 rpm 95 HW configuration 95.01 Supply voltage 380…415 V 95.02 Adaptive voltage limits Disable 95.04 Control board supply Internal 24V Back 12:36 Edit EN Press (Back) to display the list of parameter groups again. Select parameter group 99 Motor data, and set parameter 99.03 Motor type. DE Set parameter 99.04 Motor ctrl mode. DTC = Direct torque control; Scalar ES FI FR IT DTC is suitable for most cases. Scalar mode is recommended if • the nominal current of the motor is less than 1/6 of the nominal current of the drive, • the drive is used for test purposes with no motor connected, or • the drive controls multiple motors and the number of motors connected is variable. Refer to the motor nameplate for the following parameter settings. Whenever possible, enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors NL 3 motor RU SV Example of a nameplate of a permanent magnet motor: V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 1475 32.5 0.83 30 50 56 1475 0.83 50 30 50 1470 34 0.83 30 1470 59 0.83 30 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 to change the value of a digit. to move the cursor left and right. (Save) to enter the value. IP 55 kW • in DTC mode: 1/6 × IHd … 2 × IHd of the drive • in Scalar mode: 0 … 2 × IHd Note: With numerical parameter values: • Press Ins.cl. F Hz 99.06 Motor nominal current The allowable range is and and No 3424522 V IEC 34-1 • Use • Use M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Quick start-up guide for ACS880 drives with primary control program 9 Make the following parameter settings in the same manner. 99.07 Motor nominal voltage The allowable range is 1/6 × UN … 2 × UN of the drive. With permanent magnet motors, the nominal voltage is the BackEMF voltage at nominal speed. If the voltage is given in volt/rpm (eg. 60 V per 1000 rpm), the voltage at a nominal speed of 3000 rpm is 3 × 60 V = 180 V. Note that nominal voltage is not the same as equivalent DC motor voltage (EDCM) given by some manufacturers. The nominal voltage can be calculated by dividing the EDCM voltage by 1.7 (or square root of 3). 99.08 Motor nominal frequency With permanent magnet motors, if the nominal frequency is not shown on the nameplate, it can be calculated using the following formula: f = n × p / 60 where n = nominal motor speed, p = number of pole pairs. EN 99.09 Motor nominal speed DE 99.10 Motor nominal power ES 99.11 Motor nominal cosfii 99.12 Motor nominal torque FI These values are not required, but can be entered to improve control accuracy. If not known, leave at 0. FR 99.13 Identification run request This parameter selects the mode of the identification run (DTC motor control mode only). IT WARNING! The identification run modes marked thus * will run the motor in the forward direction (see below for details). Make sure it is safe to run the motor before choosing any of these modes. *Normal mode should be selected whenever possible. The driven machinery must be decoupled from the motor if • the load torque is higher than 20%, or • the machinery is not able to withstand the nominal torque transient during the identification run. *Reduced mode should be selected if the mechanical losses are higher than 20%, ie. the load cannot be de-coupled, or full flux is required to keep the motor brake open (eg. with conical motors). NL The Standstill mode should be selected if neither the *Normal or *Reduced mode can be used. Notes: • This mode cannot be used with a permanent magnet motor if the load torque is higher than 20% of nominal. • Mechanical brake is not opened by the logic for the identification run. Ensure that the Safe torque off and emergency stop circuits (if present) are closed. Start the identification run by pressing the (Start) button. A warning will indicate that the identification run is in progress. RU SV 10 Quick start-up guide for ACS880 drives with primary control program Check that the motor runs in the correct direction (forward direction shown below). The identification run has completed when the drive stops and the value of parameter 99.13 reverts to “No”. If the motor ran in the wrong direction, correct the motor cabling or adjust parameter 99.16 Phase order. 3 – Control signal settings EN DE ES Check the positions of jumpers J1 and J2 on the control unit of the drive. These jumpers determine whether analog inputs AI1 and AI2 are current or voltage. Check/adjust the following parameters. 20.01 Ext1 commands FI By default, the drive starts/stops according to the status of digital input DI1 (0 = Stop, 1 = Start). DI2 determines the direction of rotation (0 = Forward, 1 = Reverse). If other sources are required, change the value accordingly. The sources In1…In3 are defined by parameters 20.03…20.05. FR 12.15 AI1 unit selection IT NL RU SV Set this to either mA or V corresponding to the setting of jumper J1. 12.17 AI1 min 12.18 AI1 max 12.19 AI1 scaled at AI1 min 12.20 AI1 scaled at AI1 max The default input for speed reference is analog input AI1. (This is controlled by the parameters in group 22.) Parameters 12.17 and 12.18 set the low and high limits of the analog input signal. Scaling parameters 12.19 and 12.20 define the internal signal levels that correspond to these limits as follows: AI (scaled) 12.20 AI (mA/V) 12.17 12.18 12.19 The corresponding parameters for analog input AI2 are 12.27…12.30. Quick start-up guide for ACS880 drives with primary control program 11 13.12 AO1 source 13.17 AO1 source min 13.18 AO1 source max 13.19 AO1 out at AI1 src min 13.20 AO1 out at AI1 src max Parameter 13.12 selects the source for analog output AO1 (by default, motor speed in rpm). Parameters 13.17 and 13.18 set low and high source signal values that correspond to the actual analog output values defined by parameters 13.19 and 13.20. Source signal 13.18 EN DE AO (mA) 13.19 ES 13.20 FI 13.17 FR 46.10 Speed scaling 23.11 Ramp set selection 23.12 Acceleration time 1 23.13 Deceleration time 1 23.14 Acceleration time 2 23.15 Deceleration time 2 You can define two different sets of acceleration/deceleration ramps. The source that switches between the two sets is selected by parameter 23.11. Each acceleration/deceleration time set in parameters 23.12…23.15 refers to the time it takes for the drive to accelerate or decelerate between 0 and scaling speed (parameter 46.10). Speed 46.10 Acc. Dec. 23.12 23.14 23.13 23.15 0 Time IT NL RU SV 12 Quick start-up guide for ACS880 drives with primary control program 30.11 Minimum speed 30.12 Maximum speed 30.17 Maximum current 30.19 Minimum torque 30.20 Maximum torque Check, and set if necessary, the limits for motor speed, current and torque. EN DE ES FI FR IT NL RU SV Start the drive with a positive (forward) speed reference: • From control panel (Local control): In the Home view,press (Options), select Reference, adjust the reference using the , , , and keys, press Save, and press the Start button. • From I/O: In Remote control, adjust analog input AI1 (reference), switch digital input DI2 to 0 (forward), and switch digital input DI1 to 1 (start). Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 13 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram Om denne vejledning Denne guide beskriver den grundlæggende opstartssekvens for en ACS880frekvensomformer med standardstyreprogram. Den komplette dokumentation til frekvensomformerens firmware findes i firmwaremanualen. Se listen over manualer på indersiden af forsiden. I denne guide er frekvensomformeren indstillet til at bruge ACS-AP-I-kontrolpanelet. Opstartssekvensen kan også udføres ved hjælp af pc-værktøjet Drive composer. DA DA ES FI Inden du starter Du skal sikre dig, at frekvensomformeren er blevet mekanisk og elektrisk installeret som beskrevet i den tilhørende Hurtig installationsvejledning og/eller hardwaremanualen. Sikkerhed FR IT NL RU ADVARSEL! Al elektrisk installation og alt vedligeholdelsesarbejde på frekvensomformeren må kun udføres af en autoriseret installatør. Arbejd aldrig på frekvensomformeren, bremsechopperkredsen, motorkablet eller motoren, når netspændingen er tilsluttet frekvensomformeren. Sørg altid for at sikre dette ved at måle, at der ikke er nogen spænding til stede. SV 14 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram Opstart Sikkerhed Opstartsproceduren må kun gennemføres af en kvalificeret elektriker. Sikkerhedsinstruktionerne skal følges under opstartsproceduren. Se sikkerhedsinstruktionerne på de første sider af den tilhørende hardwaremanual. Kontroller installationen. Se installationstjeklisten i den tilhørende hardwaremanual. Kontroller, at start af motoren ikke medfører fare. DA Belastningsmaskinen frakobles, hvis: • Der er risiko for ødelæggelse i tilfælde af forkert omløbsretning, eller DA • en normal identifikationstest kræves under opstarten af frekvensomformeren, hvis belastningsmomentet er højere end 20 %, eller hvis maskinen ikke kan tåle det nominelle transiente moment under identifikationstesten. ES 1 – Opstart, angivelse af dato og klokkeslæt FI FR IT NL RU SV Start frekvensomformeren op. Bemærk! Det er normalt, at der der vises advarsler på forskellige tidspunkter i opstartsprocessen. Tryk på , hvis du vil skjule en meddelelse og fortsætte opstartsprocessen. Skjul alle advarsler nu for at få vist skærmbilledet Home (vist til højre). De to kommandoer nederst i displayet (i dette tilfælde Indstillinger og Menu), viser funktionerne for de to taster og nederst i displayet. Tasternes tilknyttede kommandoer varierer alt efter sammenhængen. Tryk i Startsiden på (Menu). Hovedmenuen (højre) vises. Fjern 0,0 o/min Benyttet motorhastighed o/min Motorstrøm A Motormoment % % Indstillinger 12:34 Fjern Menu 0.00 0.00 0.0 Menu 0,0 o/min Parametre Assistenter Energieffektivitet Afslut Hændelseslog 12:34 Vælg Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 15 Marker Indstillinger i menuen ved at bruge og , og tryk på (Vælg). Fjern Indstillinger Sprog Dato og klokkeslæt Rediger tekst Vis indstillinger Tilbage I menuen Indstillinger kan du markere Dato og klokkeslæt (hvis valget ikke allerede er markeret). Tryk herefter på (Vælg). I menuen Dato og klokkeslæt kan du markere Dato (hvis valget ikke allerede er markeret). Tryk herefter på (Vælg). 0,0 o/min 12:34 Vælg Fjern 0,0 o/min Dato og klokkeslæt Dato 01.01.1980 Klokkeslæt 12:34:56 Vis dato som dag.måned.år Vis klokkeslæt som 24-timer Sommertid EU Næste sommertid starter 28.03. Tilbage 12:35 Rediger Fjern Dato 0,0 o/min DA ES FI FR IT NL Dag Måned År RU 01 .01.1980 SV Tirsdag Annuller DA 12:35 Gem 16 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram Indstil den korrekte dato: • Brug og til at flytte markøren til venstre eller højre. • Brug og til at ændre værdien. • Tryk på (Gem) for at acceptere den nye indstilling. Kontrollér/juster de andre indstillinger i menuen Dato og klokkeslæt DA DA ES FI FR Indstillingen Vis ur angiver, om klokkeslæt altid skal vises nederst i displaypanelet. Når du har udført indstillingerne, skal du trykke på (Tilbage eller Afslut) gentagne gange, indtil Startsiden (højre) vises igen. Fjern 0,0 o/min Benyttet motorhastighed o/min Motorstrøm A Motormoment % % Indstillinger Skift til lokal styring for at sikre, at ekstern styring er deaktiveret, ved at trykke på tasten Loc/Rem . Lokalstyring er angivet med teksten "Lokal" øverst i panelet. Lokal Menu 0,0 o/min Benyttet motorhastighed o/min Motorstrøm A Motormoment % % NL Indstillinger SV 12:35 2 – Indstillinger for forsyningsspænding og motordata IT RU 0.00 0.00 0.0 Aktiver hovedmenuen ved at trykke på (Menu). 12:36 Lokal Menu 0.00 0.00 0.0 Menu 0,0 o/min Parametre Assistenter Energieffektivitet Afslut Hændelseslog 12:36 Vælg Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 17 Marker Parametre, og tryk på (Vælg). Lokal Parametre Favoritter Efter funktion Komplet liste Ændret Tilbage Marker Komplet liste i menuen ved at bruge og , og tryk på (Vælg). Der vises en liste med parametergrupper. Marker parametergruppe 95 HWkonfiguration, og tryk på (Vælg). Bemærk, at listen vil fortsætte i retning mod gruppe 99 eller 01. I dette tilfælde er det hurtigere at bruge til at finde gruppe 95 på listen. 0,0 o/min 12:36 Lokal Komplet liste 01 Aktuel værdi 03 Inputreferencer 04 Advarsler og fejl 05 Diagnostik 06 Kontrol- og statusord 07 Systemoplysninger Tilbage 12:36 Vælg 0,0 o/min DA ES FI Vælg Lokal 0,0 o/min 95 HW konfiguration 95.01 Forsyningsspæn. Ikke angivet 95.02 Adaptive spænd.grænse Inaktiv Intern 24V 95.04 Styrekort forsyning Når du har valgt en gruppe, vises en liste med parametre for gruppen. FR IT NL RU SV Tilbage Marker parameteren Forsyningsspænding (hvis den ikke allerede er markeret), og tryk på (Rediger). De tilgængelige parameterindstillinger vises. DA 12:36 Rediger Lokal 0,0 o/min 95.01 Forsyningsspænding [0] Ikke angivet [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Annuller 12:36 Gem 18 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram Marker den korrekte indstilling på listen og tryk på (Gem). Lokal 0,0 o/min 95 HW konfiguration 95.01 Forsyningsspæn. 380…415 V 95.02 Adaptive spæn.grænser Inaktiv Intern 24V 95.04 Styrekort forsyning Tilbage 12:36 Rediger DA Tryk på (Tilbage) for igen at få vist listen med parametergrupper. Marker parametergruppe 99 Motordata, og indstil parameter 99.03 Motortype. DA Indstil parameter 99.04 Motorstyringstilstand. DTC = Direkte momentstyring, Skalar ES FI FR IT DTC er egnet i de fleste tilfælde. Skalarmode anbefales, hvis • motorens nominelle strøm er mindre end 1/6 af frekvensomformerens nominelle strøm • frekvensomformeren anvendes til test, hvor der ikke er tilsluttet en motor til den, eller • frekvensomformeren styrer flere motorer, og antallet af tilsluttede motorer er variabelt. Se motorens mærkeplade for oplysninger om de følgende parameterindstillinger. Indtast, hvis det er muligt, værdierne nøjagtigt som de er angivet på motormærkepladen. Eksempel på en mærkeplade fra en (asynkron) induktionsmotor: ABB Motors NL 3 motor RU SV Eksempel på en mærkeplade fra en permamagnetmotor: V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 1475 32.5 0.83 30 50 56 1475 0.83 50 30 50 1470 34 0.83 30 1470 59 0.83 30 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 S1 SPEC INSUL. JK-21640-1 kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 2GBJ285220-ADA405445477 6316/C3 180 • i DTC-tilstand: 1/6 × IHd … 2 × IHd for frekvensomformeren • i skalartilstand: 0 … 2 × IHd Bemærk! Med numeriske parameterværdier: • Tryk på IP 55 Hz 99.06 Nominel motorstrøm Det tilladte interval er og og Ins.cl. F V IEC 34-1 • Brug • Brug No 3424522 til at ændre værdien for et ciffer. til at flytte markøren til venstre eller højre. (Gem) for at indsætte værdien. 6316/C3 630kg IEC 34-1 t E/s Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 19 Foretag indstillinger for de følgende parametre på samme måde. 99.07 Nominel motorspænding Det tilladte interval er 1/6 × UN … 2 × UN for frekvensomformeren. Med permanmagnetmotorer er den nominelle spænding BackEMF-spændingen ved nominel hastighed. Hvis spændingen angives i volt / o/min (f.eks. 60 V pr. 1000 o/min), er spændingen ved en nominel hastighed på 3000 o/min 3 × 60 V = 180 V. Bemærk, at nominel spænding ikke svarer til den tilsvarende DC-motorspændingsværdi (EDCM), der angives af nogle producenter. Den nominelle spænding kan beregnes ved at dividere EDCM-spændingen med 1,7 (= kvadratroden af 3). 99.08 Nominel motorfrekvens For permanmagnetmotorer vises den nominelle frekvens ikke på mærkepladen. Den kan beregnes ved hjælp af følgende formel: f = n × p / 60 hvor n = nominel motorhastighed, p = antal polpar. 99.09 Nominel motorhastighed DA DA ES 99.10 Motorens nominelle effekt FI 99.11 Nominel motor-cosfii 99.12 Nominel motormoment Disse værdier kræves ikke, men de kan indtastes for at forbedre styrenøjagtigheden. Hvis værdien ikke kendes, kan du lade den forblive 0. 99.13 Identifikationskørsel anmodn. Denne parameter vælger tilstanden for identifikationskørslen (kun i DTCmotorstyringstilstand). ADVARSEL! De med * markerede tilstande for identifikationskørsel vil køre motoren i forlæns omløbsretning (se oplysningerne herunder). Du skal kontrollere, at det er sikkert at køre motoren, inden du vælger en af disse tilstande. *Normal tilstand bør altid vælges, når det er muligt. Den drevne maskine skal være frakoblet motoren, hvis • belastningsmomentet er højere end 20 %, eller • hvis maskinanlægget ikke kan tåle det nominelle transiente moment under identifikationskørslen. *Reduceret tilstand bør vælges, hvis de mekaniske tab er højere end 20%, dvs. hvis belastningen ikke kan frakobles, eller der kræves fuld flux for at holde motorbremsen åben (konisk motor). Tilstanden Stilstand bør vælges, hvis du hverken kan benytte *Normal eller *Reduceret tilstand. Bemærk! • Denne tilstand kan ikke benyttes med en permamagnetmotor, hvis belastningsmomentet er højere end 20 % af det nominelle. • Mekanisk bremsning åbnes ikke af logikken for identifikationskørslen Sørg for, at Safe toque of- og nødstopskredsløbene (hvis sådanne findes) er lukkede. Start identifikationskørslen ved at trykke på knappen (Start). En advarsel vil angive, at idetifikationskørslen er i gang. FR IT NL RU SV 20 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram Kontroller at motorer kører i den rigtige omløbsretning (forlæns omløbsretning er vist herunder). Identifikationskørslen er afsluttet, når frekvensomformeren stopper og værdien for parameter 99.13 skifter tilbage til "Nej". Hvis motoren kørte i den forkerte retning, skal du kontrollere motorkablingen eller indstille parameteren 99.16 Faserækkefølge. DA DA 3 – Indstillinger for styresignaler Kontrollér positionen af jumperne J1 og J2 på frekvensomformerens styreenhed. Disse jumpere bestemmer, om analogindgange AI1 og AI2 angiver strøm eller spænding. Kontrollér/juster følgende parametre. ES 20.01 Ext1-kommandoer FI Som standard starter/stopper frekvensomformeren i overensstemmelse med status for digitalindgang DI1 (0 = Stop, 1 = Start). DI2 Bestemmer rotationsretningen (0 = Forlæns, 1 = Baglæns). FR Hvis der skal bruges andre kilder, skal du ændre værdien tilsvarende. Kilderne In1…In3 defineres med parametrene 20.03…20.05. IT 12.15 AI1-enhedsvalg Indstil denne til enten mA eller V i overensstemmelse med indstillingerne for jumper J1. NL RU SV Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 21 12.17 AI1-min 12.18 AI1-maks. 12.19 AI1-skala ved AI1-min 12.20 AI1-skala ved AI1-maks. Standardindgang for hastighedsreference er analogindgang AI1. (Denne styres af parametrene i gruppe 22). Parametrene 12.17 og 12.18 indstiller grænserne for laveste og højeste analoge indgangssignal. Skalaparametrene 12.19 og 12.20 definerer de interne signalniveauer, som svarer til følgende grænser: AI (skaleret) 12.20 DA AI (mA/V) 12.17 DA ES 12.18 FI 12.19 FR De tilsvarende parametre for analogindgang AI2 er 12.27…12.30. 13.12 AO1-kilde 13.17 AO1-kilde min 13.18 AO1-kilde maks. 13.19 AO1 ud ved AI1-kilde min 13.19 AO1 ud ved AI1-kilde maks. IT NL RU Parameter 13.12 vælger kilde for analogudgang AO1 (standard er motorhastighed angivet i o/min). Parametrene 13.17 og 13.18 indstiller lav og høj signalværdi, som svarer til analogudgangsværdierne defineret med parametrene 13.19 og 13.20. Kildesignal 13.18 AO (mA) 13.19 13.20 13.17 SV 22 Quick Start-up Guide for ACS880-frekvensomformere med standardstyreprogram 46.10 Hastighedsskaler 23.11 Valg af rampesæt 23.12 Accelerationstid 1 23.13 Decelerationstid 1 23.14 Accelerationstid 2 23.15 Decelerationstid 2 Du kan definere to forskellige rampesæt for acceleration/deceleration. Skift mellem de to sæt foretages ved at vælge indstilling med parameter 23.11. Valgene for accelerations-/decelerationstid indstillet med parametrene 23.12…23.15 henviser til den tid, det tager frekvensomformeren at accelerere eller decelerere mellem 0 og hastighedsskalering (parameter 46.10). Hastighed DA 46.10 DA ES Acc. Dec. 23.12 23.14 23.13 23.15 FI 0 FR IT NL RU SV Tid 30.11 Minimum hastighed 30.12 Maksimum hastighed 30.17 Maksimum strøm 30.19 Minimum moment 30.20 Maksimum moment Kontroller og indstil (hvis det er nødvendigt) grænserne for motorens hastighed, strøm og moment. Start frekvensomformeren med en positiv (forlæns) hastighedsreference: • På betjeningspanelet (Lokal styring): Tryk i startbilledet på (Indstillinger), vælg Reference, tilpas referencen ved hjælp af tasterne , , , og , tryk på Gem, og tryk på knappen Start. • Fra I/O: I fjernkontrol skal du justere analogindgangen AI1 (reference), skifte digitalindgang DI2 til 0 (forlæns) og skifte digitalindgang DI1 til 1 (start). Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 23 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm Informationen über diese Anleitung In dieser Anleitung wird die Basis-Inbetriebnahme des ACS880 mit dem Haupt-Regelungsprogramm beschrieben. Die vollständige Dokumentation der Frequenzumrichter-Firmware ist im Firmware-Handbuch (siehe Liste der Handbücher auf der vorderen Einband-Innenseite) enthalten. EN DE In dieser Anleitung erfolgt die Inbetriebnahme des Frequenzumrichters mithilfe des Bedienpanels ACS-AP-I. Die Inbetriebnahme kann auch mit dem PC-Tool Drive Composer erfolgen. DE Bevor Sie beginnen FR Stellen Sie sicher, dass der Frequenzumrichter mechanisch und elektrisch entsprechend den Anweisungen in der jeweiligen Kurzanleitung und/oder im HardwareHandbuch installiert wurde. IT Sicherheit RU WARNUNG! Alle elektrischen Installations- und Wartungsarbeiten an dem Antrieb dürfen nur von qualifiziertem Fachpersonal durchgeführt werden. Arbeiten Sie niemals bei eingeschalteter Spannungsversorgung an dem Frequenzumrichter, dem Brems-Chopper, dem Motorkabel oder dem Motor. Stellen Sie immer durch eine Messung sicher, dass keine Spannung anliegt. FI NL SV 24 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm Inbetriebnahme Sicherheit Die Inbetriebnahme darf nur durch qualifiziertes Fachpersonal vorgenommen werden. Die Sicherheitsvorschriften müssen bei der Inbetriebnahme befolgt werden. Siehe die Sicherheitsvorschriften auf den ersten Seiten des jeweiligen Hardware-Handbuchs. Prüfung der Installation. Siehe Installations-Checkliste im jeweiligen HardwareHandbuch. EN DE DE FI FR IT NL RU SV Prüfen Sie, dass durch den Start des Motors keine Gefährdungen entstehen. Die angetriebene Maschine abkoppeln, wenn: • durch eine falsche Drehrichtung des Motors eine Gefährdung entstehen kann, oder • bei der Inbetriebnahme des Antriebs ein normaler ID-Lauf erforderlich ist, wenn das Lastmoment höher als 20% ist oder die angetriebene Maschine den Lastwechseln mit Nennmoment während des ID-Laufs nicht standhält. 1 – Einschalten, Datum- und Zeiteinstellung Den Frequenzumrichter einschalten. Hinweis: Es ist normal, dass zu verschiedenen Punkten während des Startprozesses Warnmeldungen erscheinen. Zum Ausblenden einer Meldung und zum Fortsetzen des Startprozesses Taste drücken. Jetzt alle Warnmeldungen ausblenden, um in die Startansicht (rechts dargestellt) zu gelangen. Fernsteuerung 0.0 U/min Motordrehzahl benutzt U/min Motorstrom A Motordrehmoment % % Die zwei Befehlsanzeigen am unteren Rand des Displays (in diesem Fall Optionen und Menü) zeigen die Funktionen der zwei Funktionstasten und an, die unter dem Display sind. Die den Funktionstasten zugeordneten Befehlsanzeigen sind vom Betriebszustand abhängig. Optionen In der Startansicht die Taste (Menü) drücken. Das Hauptmenü (rechts) wird angezeigt. Fernsteuerung Menü 12:34 0.00 0.00 0.0 Menü 0.0 U/min Parameter Assistenten Energieeffizienz Ereignisprotokoll Beenden 12:34 Auswählen Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 25 Im Menü Einstellungen mit den Tasten und auswählen und Taste (Auswählen) drücken. Zurück Im Menü Einstellungen - Datum & Zeit auswählen (wenn nicht bereits ausgewählt) und Taste (Auswählen) drücken. Im Menü Datum & Zeit - Datum auswählen (wenn noch nicht markiert) und dann Taste (Auswählen) drücken. 0.0 U/min Fernsteuerung Einstellungen Sprache Datum & Zeit Texte bearbeiten Display-Einstellungen 12:34 Auswählen 0.0 U/min Fernsteuerung Datum & Zeit Datum 01.01.1980 Zeit 12:34:56 Datum anzeigen als Tag.Monat.Jahr Zeitanzeige als 24 STD Sommerzeit EU Start nächste Sommerzeit 28.03. Zurück 12:35 Bearbeiten 0.0 U/min Fernsteuerung Datum DE DE FI FR IT NL Tag Monat Jahr 01 .01.1980 Dienstag Abbruch EN 12:35 Speichern RU SV 26 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm Das korrekte Datum einstellen. • Mit den Tasten und den Cursor nach links und rechts bewegen. • Mit den Tasten und den Einstellwert ändern. • Mit der Funktionstaste (Speichern) die neue Einstellung übernehmen. Alle Einstellungen im Menü Datum & Zeit vornehmen bzw. prüfen. EN DE DE FI FR IT Durch die Einstellung Uhr zeigen wird festgelegt, ob die Zeit immer am unteren Rand des Displays angezeigt wird. Motordrehzahl benutzt U/min Motorstrom A Motordrehmoment % % Optionen 12:35 0.00 0.00 0.0 Menü Wenn die Einstellungen korrekt sind, Taste (Zurück oder Beenden) mehrmals drücken, bis die Startansicht (rechts) erscheint. 2 – Einspeisespannung und Motordaten einstellen Sicherstellen, dass die Fernsteuerung (externe Steuerung) deaktiviert ist und mit Taste Loc/Rem auf Lokalsteuerung umschalten. Die Lokalsteuerung wird durch “Lokal” oben im Display angezeigt. NL Lokal 0.0 U/min Motordrehzahl benutzt U/min Motorstrom A Motordrehmoment % % RU SV 0.0 U/min Fernsteuerung Optionen Das Hauptmenü mit Taste öffnen. (Menü) 12:36 Lokal Menü 0.00 0.00 0.0 Menü 0.0 U/min Parameter Assistenten Energieeffizienz Ereignisprotokoll Beenden 12:36 Auswählen Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 27 Parameter auswählen und Taste (Auswählen) drücken. Lokal Parameter Favoriten Nach Funktion Komplette Liste Geändert Zurück Komplette Liste mit den Tasten und auswählen und Taste (Auswählen) drücken. Eine Liste mit Parametergruppen wird angezeigt. 12:36 0.0 U/min Auswählen Lokal 0.0 U/min Komplette Liste 01 Istwerte 03 Eingangssollwerte 04 Warnungen und Störungen 05 Diagnosen 06 Steuer- und Statusworte 07 System-Info Zurück 12:36 Auswählen Parametergruppe 95 HardwareKonfiguration auswählen und Taste (Auswählen) drücken. Lokal 0.0 U/min 95 Hardware-Konfiguration 95.01 EinspeisespannungNicht gegeben Beachten Sie, dass die Liste in beiden 95.02 Adaptive Spannu... Deaktivieren Richtungen nach den Gruppen 99 und 01 durchblättert werden kann. In diesem Fall ist 95.04 Spann.Vers.Regel... Interne 24V es schneller, die Taste zu betätigen, um zur Gruppe 95 in der Liste zu gelangen. Nach der Auswahl einer Gruppe wird eine Parameterliste mit den Parametern der Parametergruppe angezeigt. Parameter 95.01 Einspeisespannung auswählen (wenn nicht bereits ausgewählt) und Taste (Bearbeiten) drücken. Die verfügbaren Parametereinstellungen werden aufgelistet. EN DE DE FI FR IT NL RU SV Zurück 12:36 Bearbeiten Lokal 95.01 Einspeisespannung [0] Nicht gegeben [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Abbruch 12:36 0.0 U/min Speichern 28 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm Die richtige Einstellung aus der Liste auswählen und Taste (Speichern) drücken. Lokal 0.0 U/min 95 Hardware-Konfiguration 95.01 Einspeisespannung 380…415 V 95.02 Adaptive Spannu... Deaktivieren 95.04 Spann.Vers.Regelu... Interne 24V Zurück EN 12:36 Bearbeiten Die Taste (Zurück) drücken, um wieder die Liste der Parametergruppen anzuzeigen. Die Parametergruppe 99 Motordaten wählen und den Parameter 99.03 Motorart einstellen. DE Parameter 99.04 Motor-Regelmodus einstellen. DTC = Direkte Drehmomentregelung; Skalar DE DTC ist für die meisten Anwendungen geeignet. Skalarregelung wird empfohlen, wenn • der Nennstrom des Motors weniger als 1/6 des Nennausgangsstroms des Frequenzumrichters beträgt. • der Frequenzumrichter ohne angeschlossenen Motor betrieben wird (z.B. für Prüfzwecke) oder • der Frequenzumrichter mehrere Motoren regelt und die Anzahl der angeschlossenen Motoren variabel ist. FI FR IT NL RU SV Für die folgenden Parametereinstellungen die Daten vom Motor-Typenschild verwenden. Wenn möglich, die auf dem Motor-Typenschild angegeben Werte genau eingeben. Beispiel für ein Typenschild eines Asynchronmotors: Beispiel für ein Typenschild eines Permanentmagnetmotors: ABB Motors 3 motor V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 29 99.06 Motor-Nennstrom Der zulässige Bereich ist • im DTC-Modus: 1/6 × IHd … 2 × IHd des Frequenzumrichters • im Skalarmodus: 0 … 2 × IHd Hinweis: Bei numerischen Parameterwerten: • Mit den Tasten • Mit den Tasten • Die Taste und und den Wert einer Ziffer ändern. den Cursor nach links und rechts bewegen. (Speichern) zum Sichern des Werts drücken. Nehmen Sie folgenden Parametereinstellungen wie gerade beschrieben vor. 99.07 Motor-Nennspannung Der zulässige Bereich ist 1/6 × UN … 2 × UN des Frequenzumrichters. Bei Permanentmagnetmotoren ist die Nennspannung die Gegen-EMK-Spannung bei Nenndrehzahl. Wenn die Spannung als Spannung pro U/min angegeben ist, z.B. 60 V pro 1000 U/min, dann beträgt die Spannung für eine Nenndrehzahl von 3000 U/min = 3× 60 V = 180 V. Beachten Sie, dass die Spannung nicht der äquivalenten DC-Motorspannung (EDCM) entspricht, die von einigen Motorenherstellern angegeben wird. Die Nennspannung kann berechnet werden, indem die EDCM-Spannung durch 1,7 (oder Quadratwurzel von 3) dividiert wird. 99.08 Motor-Nennfrequenz Wenn bei Permanentmagnetmotoren die Nennfrequenz nicht auf dem Typenschild angegeben ist, kann sie mit der folgenden Formel berechnet werden: f = n × p / 60 wobei n = Motornenndrehzahl, p = Anzahl der Polpaare ist. 99.09 Motor-Nenndrehzahl EN DE DE FI FR IT NL 99.10 Motor-Nennleistung RU 99.11 Motor-Cosphi 99.12 Motor-Nenndrehmoment SV Die Werte sind nicht erforderlich, können aber zur Erhöhung der Regelgenauigkeit eingegeben werden. Wenn die Werte nicht bekannt sind, die Einstellung auf 0 lassen. 30 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 99.13 Ausw. Mot.-ID-Laufmodus Mit diesem Parameter wird der Modus des Identifikationslaufs ausgewählt (nur DTCMotorregelungsart). WARNUNG! Bei * gekennzeichneten Modi des Identifikationslaufs wird der Motor in Drehrichtung vorwärts gedreht (genauere Angaben, siehe unten). Sicherstellen, dass der Motor ohne Gefährdungen gedreht werden kann, bevor einer dieser Modi gewählt wird. EN DE DE FI Der Modus *Normal sollte immer, wenn möglich, gewählt werden. Die angetriebene Maschine muss vom Motor abgekoppelt werden, wenn • das Lastmoment höher als 20% ist oder • die angetriebene Maschine beim ID-Lauf den Lastwechseln mit Nennmoment nicht standhält. *Der Modus *Reduziert sollte ausgewählt werden, wenn die mechanischen Verluste höher als 20% sind, d.h., wenn die Last nicht abgekoppelt werden kann oder ein voller Fluss erforderlich ist, um die Motorbremse geöffnet zu halten (z. B. mit Verschiebeankermotoren). Der Modus Stillstand sollte ausgewählt werden, wenn weder der Modus *Normal noch der Modus *Reduziert verwendet werden kann. Hinweise: IT • Dieser Modus kann bei einem Permanentmagnetmotor nicht verwendet werden, wenn das Lastmoment um 20% höher als das Motor-Nennmoment ist. • Eine mechanische Bremse wird durch die Schaltlogik im Umrichter beim ID-Lauf nicht geöffnet. NL Sicherstellen, dass die Schaltkreise für das sicher abgeschaltete Drehmoment (STO) und für Notstopp (falls vorhanden) geschlossen sind. RU Start des Motor-Identifikationslaufs mit der Taste (Start). SV Prüfen, dass der Motor in die richtige Richtung dreht (vorwärts, siehe wie folgt). FR Mit einer Warnmeldung wird angezeigt, dass der Identifikationslauf gerade durchgeführt wird. Der Identifikationslauf wurde erfolgreich durchgeführt, wenn der Wert des Parameters 99.13 auf “Nein” wechselt. Wenn der Motor die falsche Drehrichtung hatte, den Motorkabelanschluss korrigieren oder Parametereinstellung von 99.16 Phasenfolge ändern. 3 – Einstellung der Steuersignale Die Position der Jumper J1 und J2 der Regelungseinheit des Frequenzumrichters prüfen. Durch diese Jumper wird festgelegt, ob die Analogeingänge AI1 und AI2 als Strom- oder Spannungseingänge verwendet werden. Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 31 Die folgenden Parameter prüfen/anpassen. 20.01 Ext1 Befehlsquellen Standardmäßig startet/stoppt der Frequenzumrichter entsprechend dem Status von Digitaleingang DI1 (0 = Stopp, 1 = Start). DI2 legt die Drehrichtung fest (0 = Vorwärts, 1 = Rückwärts). Wenn andere Quellen erforderlich sind, den Wert entsprechend ändern. Die Quellen In1…In3 werden mit den Parametern 20.03…20.05 festgelegt. 12.15 AI1 Wahl Einheit Auf mA oder V je nach Einstellung von Jumper J1 einstellen. 12.17 AI1 min 12.18 AI1 max 12.19 AI1 skaliert min 12.20 AI1 skaliert max EN Der Standardeingang für den Drehzahl-Sollwert ist Analogeingang AI1. (Dieses wird durch die Parameter in Gruppe 22 gesteuert.) DE Parameter 12.17 und 12.18 bestimmen die Unter- und Obergrenze des Analogeingangssignals. Die Skalierungsparameter 12.19 und 12.20 bestimmen die internen Signalpegel, die diesen Grenzen wie folgt entsprechen: DE AI (skaliert) FI FR 12.20 IT AI (mA / V) 12.17 12.18 12.19 Die entsprechenden Parameter für Analogeingang AI2 sind 12.27…12.30. NL RU SV 32 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 13.12 AO1 Quelle 13.17 AO1 Quelle min 13.18 AO1 Quelle max 13.19 AO1 min 13.20 AO1 max Parameter 13.12 bestimmt die Quelle für Analogausgang AO1 (standardmäßig Motordrehzahl in U/min). Parameter 13.17 und 13.18 setzen niedrige und hohe Quellensignalwerte, die den mit den Parametern 13.19 und 13.20 festgelegten Istwerten der Analogausgänge entsprechen. Quellsignal EN 13.18 DE AO (mA) 13.19 DE 13.20 FI FR 13.17 IT NL RU SV 46.10 Drehzahl-Skalierung 23.11 Auswahl Rampeneinstell. 23.12 Beschleunigungszeit 1 23.13 Verzögerungszeit 1 23.14 Beschleunigungszeit 2 23.15 Verzögerungszeit 2 Der Benutzer kann zwei unterschiedliche Sätze von Beschleunigungs-/Verzögerungsrampen festlegen. Die Quelle, die zwischen den beiden Sätzen umschaltet, wird mit Parameter 23.11 festgelegt. Jede in den Parametern 23.12…23.15 eingestellte Beschleunigungs-/Verzögerungszeit entspricht der Zeit, die der Frequenzumrichter zur Beschleunigung oder Verzögerung zwischen 0 und der skalierten Drehzahl benötigt (Parameter 46.10). Drehzahl 46.10 Beschleunigung Verzögerung 23.12 23.14 23.13 23.15 0 Zeit Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm 33 30.11 Minimal-Drehzahl 30.12 Maximal-Drehzahl 30.17 Maximal Strom 30.19 Minimal-Moment 30.20 Maximal-Moment Die Grenzen für Motordrehzahl, Strom und Drehmoment prüfen und gegebenenfalls einstellen. Den Frequenzumrichter mit einem positiven Drehzahl-Sollwert (vorwärts) starten: • Mit dem Bedienpanel (Lokalsteuerung): In der Startansicht die Taste (Optionen) drücken, den Sollwert wählen und den Sollert mit den Tasten , , , und einstellen, dann Taste Speichern drücken und mit der Start-Taste den Antrieb starten. • Mit E/A-Steuerung: Bei Fernsteuerung den Analogeingang AI1 (Sollwert) einstellen, Digitaleingang DI2 auf 0 (vorwärts) und Digitaleingang DI1 auf 1 (Start) setzen. EN DE DE FI FR IT NL RU SV 34 Kurzanleitung für den Start des ACS880 mit Haupt-Regelungsprogramm EN DE DE FI FR IT NL RU SV Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 35 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario Acerca de esta guía EN En esta guía se describe la secuencia de puesta en marcha básica de un convertidor ACS880 equipado con el programa de control primario. Encontrará toda la documentación del firmware del convertidor en el Manual de firmware (véase la lista de manuales del interior de la portada). DE A los efectos de esta guía, el convertidor se configura con el panel de control ACS-AP-I. La secuencia de puesta en marcha también puede realizarse con la herramienta para PC Drive Composer. ES Antes de empezar IT Asegúrese de que el convertidor esté instalado mecánica y eléctricamente de la forma descrita en su correspondiente Guía rápida de instalación y/o Manual de hardware. NL Seguridad SV ¡ADVERTENCIA! Todos los trabajos de instalación eléctrica y mantenimiento realizados en el convertidor deben ser ejecutados únicamente por electricistas cualificados. Nunca trabaje en el convertidor, el circuito del chopper de frenado, el cable de motor ni el motor con la alimentación del convertidor conectada. Realice siempre una medición para verificar que no exista tensión. ES FR RU 36 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario Puesta en marcha Seguridad La puesta en marcha sólo puede ser efectuada por un electricista cualificado. Deben seguirse las instrucciones de seguridad durante todo el procedimiento de puesta en marcha. Lea las instrucciones de seguridad incluidas en las primeras páginas del Manual de hardware correspondiente. Compruebe la instalación. Lea la lista de comprobación de la instalación en el Manual de Hardware correspondiente. EN DE ES Compruebe que la puesta en marcha del motor no suponga ningún peligro. Desacople la maquinaria accionada si: • existe riesgo de daños en caso de una dirección de giro incorrecta, o • se necesita una marcha de ID Normal durante la puesta en marcha del convertidor, cuando el par de carga es superior al 20% o la maquinaria no es capaz de soportar el par nominal momentáneo durante la marcha de ID. 1 – Puesta en marcha, ajustes de fecha y hora ES FR IT NL RU SV Ponga en marcha el convertidor. Nota: Es normal que aparezcan mensajes de advertencia en distintos momentos del proceso de puesta en marcha. Para ocultar un mensaje y reanudar el proceso de puesta en marcha, pulse . Oculte cualquier advertencia ahora para entrar en la vista Inicio (que se muestra a la derecha). Remote 0.0 rpm 0.00 0.00 0.0 Velocidad Motor Usada rpm Intensidad Motor A Par motor % % Los dos comandos de la parte inferior de la pantalla (en este caso, Opciones y Menú), muestran las funciones de las dos teclas programables y situadas debajo de la pantalla. Los comandos asignados a las teclas programables varían en función del contexto. Opciones En la vista Inicio, pulse (Menú). Aparece el Menú principal (que se muestra a la derecha). Remoto Menú 12:34 Menú 0.0 rpm Parámetros Asistentes Energy Efficiency Registro de eventos Salir 12:34 Seleccionar Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 37 Resalte Ajustes en el menú usando y pulse (Seleccionar). y Remoto Ajustes Idioma Fecha y hora Editar textos Ajustes de pantalla Atrás En el menú Ajustes, resalte Fecha y hora (si no está resaltado) y pulse (Seleccionar). 12:34 0.0 rpm Seleccionar Remoto 0.0 rpm Fecha y hora Fecha 01.01.1980 Hora 12:34:56 Mostrar fecha como día.mes.año Mostrar hora como 24 horas Ahorro diurno UE Próximo inicio de ahorro diurno 28.03. EN DE ES ES FR IT En el menú Fecha y hora, resalte Fecha (si no está resaltado) y pulse (Seleccionar). Remoto Fecha 0.0 rpm Día Mes NL RU Año 01 .01.1980 SV Martes Cancelar 12:35 Guardar Atrás 12:35 Editar 38 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario Ajuste la fecha correcta: • Use y para mover el cursor hacia la izquierda y la derecha. • Use y para cambiar el valor. • Pulse (Guardar) para aceptar el nuevo ajuste. Compruebe y ajuste todos los demás ajustes del menú Fecha y hora. El ajuste Mostrar reloj determina si debe mostrarse la hora en todo momento en el panel inferior de la pantalla. EN DE ES ES FR Remoto 0.0 rpm Intensidad Motor A Par motor % % Opciones 12:35 Menú Una vez hechos los ajustes, pulse (Atrás o Salir) repetidamente hasta que reaparezca la vista Inicio (que se muestra a la derecha). 2 – Ajustes de tensión de alimentación y datos de motor Cambie a control local para asegurarse de que se ha inhabilitado el control externo. Para ello pulse la tecla Loc/Rem . El control local se indica a través del texto “Local” en el panel superior. Local 0.0 rpm Intensidad Motor A NL Par motor % % Opciones RU Vaya al Menú principal pulsando (Menú). 0.00 0.00 0.0 Velocidad Motor Usada rpm IT SV 0.00 0.00 0.0 Velocidad Motor Usada rpm 12:36 Menú Local Menú 0.0 rpm Parámetros Asistentes Energy Efficiency Registro de eventos Salir 12:36 Seleccionar Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 39 Resalte Parámetros y pulse (Seleccionar). Local Parámetros Favoritos Por función Lista completa Modificado Atrás Resalte Lista completa usando y y pulse (Seleccionar). Aparece una lista de grupos de parámetros. Recuerde que la lista se muestra de forma continua en ambas direcciones entre los grupos 99 y 01. En este caso, resulta más rápido usar para llegar al grupo 95 de la lista. Tras seleccionar un grupo, aparece una lista con los parámetros del grupo. 12:36 Seleccionar Local 0.0 rpm Lista completa 01 Valores actuales 03 Entradas de Referencia 04 Alarmas y Fallos 05 Diagnósticos 06 Palabras de Control y Estado 07 Info Sistema Atrás Resalte el grupo de parámetros 95 Configuración Hardware y pulse (Seleccionar). 0.0 rpm 12:36 Seleccionar Local 0.0 rpm 95 Configuracion Hardware No se indica 95.01 Tension Alimentacion 95.02 Limites Tension Adaptativos Deshabilitar 95.04 Aliment Tarjeta Control 24 V interna Atrás 12:36 Resalte el parámetro 95.01 Tension Alimentacion (si no está resaltado) y pulse (Editar). Local 95.01 Tension Alimentacion Se enumeran los ajustes de los parámetros disponibles. [0] No se indica [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Cancelar 12:36 Editar 0.0 rpm Guardar EN DE ES ES FR IT NL RU SV 40 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario Resalte el ajuste correcto en la lista y pulse (Guardar). Local 0.0 rpm 95 Configuracion Hardware 380…415 V 95.01 Tension Alimentacion 95.02 Limites Tension Adaptativos Deshabilitar 24 V interna 95.04 Aliment Tarjeta Control Atrás EN 12:36 Editar Pulse (Atrás) para mostrar nuevamente la lista de grupos de parámetros. Seleccione el grupo de parámetros 99 Datos Motor y ajuste el parámetro 99.03 Tipo de Motor. DE Ajuste el parámetro 99.04 Modo Ctrl Motor. DTC = Control directo del par; Escalar ES El DTC es adecuado en la mayoría de los casos. Se recomienda el modo escalar si: • la intensidad nominal del motor es inferior a 1/6 de la intensidad nominal del convertidor, • el convertidor se usa con fines de prueba sin un motor conectado, o • el convertidor controla diferentes motores y el número de motores conectados varía. ES FR IT NL Consulte la placa de características del motor para conocer los siguientes ajustes de parámetros. Siempre que sea posible, introduzca los valores exactamente de la forma mostrada en la placa de características del motor. Ejemplo de placa de características de un motor de inducción (asíncrono): RU SV Ejemplo de placa de características de un motor de imanes permanentes: ABB Motors 3 motor V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 41 99.06 Intensidad Nominal Motor El rango permisible es • en el modo DTC: 1/6 × IHd … 2 × IHd del convertidor • en el modo escalar: 0 … 2 × IHd Nota: Con valores de parámetro numéricos: • Use • Use • Pulse y y para cambiar el valor de un dígito. para mover el cursor hacia la izquierda y la derecha. (Guardar) para introducir el valor. Realice los siguientes ajustes de parámetros, siguiendo el mismo método. 99.07 Tension Nominal Motor El rango permitido es 1/6 × UN … 2 × UN del convertidor. En el caso de los motores de imanes permanentes, la tensión nominal es la tensión BackEMF a la velocidad nominal. Si la tensión se expresa en voltios/rpm (p. ej. 60 V por cada 1.000 rpm), la tensión a la velocidad nominal de 3.000 rpm es de 3 × 60 V = 180 V. Recuerde que la tensión nominal no es la misma que la tensión de CC equivalente del motor (EDCM) indicada por algunos fabricantes. Es posible calcular la tensión nominal si se divide la tensión EDCM por 1,7 (o la raíz cuadrada de 3). 99.08 Frecuencia Nominal Motor En el caso de los motores de imanes permanentes, si la frecuencia nominal no aparece en la placa de características, debe calcularse con ayuda de la siguiente formula: f = n × p / 60 donde n = velocidad nominal del motor, p = número de pares de polos. 99.09 Velocidad Nominal Motor 99.10 Potencia Nominal Motor 99.11 Cosfi Nominal Motor 99.12 Par Nominal Motor Estos valores no son obligatorios, pero pueden introducirse para aumentar la exactitud del control. Si los desconoce, deje el valor 0. EN DE ES ES FR IT NL RU SV 42 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 99.13 Peticion Marcha Ident Este parámetro selecciona el modo de la marcha de identificación (sólo en el modo DTC de control de motor). ¡ADVERTENCIA! Los modos de marcha de identificación marcados con * hacen que el motor se mueva en el sentido de avance (para más detalles, véase la información que aparece a continuación). Asegúrese de que resulte seguro poner en marcha el motor antes de seleccionar cualquiera de estos modos. ES *Siempre que sea posible, debe seleccionarse el modo Normal. La maquinaria accionada debe desacoplarse del motor si • el par de carga es superior al 20%, o • la maquinaria no puede resistir la oscilación del par nominal durante la marcha de identificación. *El modo Reducido debe seleccionarse si las pérdidas mecánicas son superiores al 20%, es decir, si no es posible desacoplar la carga o si se requiere un flujo completo para mantener abierto el freno del motor (por ejemplo en el caso de los motores cónicos). El modo En reposo debe seleccionarse si no es posible utilizar los modos *Normal ni *Reducido. Notas: ES • Este modo no puede usarse en el caso de los motores de imanes permanentes si el par de carga es superior al 20% del valor nominal. EN DE • El freno mecánico no es abierto por la lógica para la marcha de identificación. FR Asegúrese de que los circuitos de la función Safe Torque Off y de paro de emergencia estén cerrados (si los hubiere). IT NL Inicie la marcha de identificación pulsando el Aparecerá una advertencia para indicar botón (Marcha). que la marcha de identificación está en curso. RU Compruebe que el motor funcione en el sentido correcto (el sentido de avance mostrado abajo). SV La marcha de identificación se ha completado cuando el convertidor se detiene y el valor del parámetro 99.13 vuelve a ser “No”. Si el motor funcionó en el sentido incorrecto, corrija el cableado del motor o ajuste el parámetro 99.16 Orden Fases. 3 – Ajustes de señal de control Compruebe las posiciones de los puentes J1 y J2 en la unidad de control del convertidor. Estos puentes determinan si las entradas analógicas AI1 y AI2 son de intensidad o de tensión. Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 43 Compruebe/ajuste los siguientes parámetros. 20.01 Ext1 Marcha/Paro/Dir Por defecto, el convertidor se pone en marcha o se detiene en función del estado de la entrada digital DI1 (0 = Paro, 1 = Marcha). DI2 determina el sentido de giro (0 = Avance, 1 = Retroceso). Si se requieren otras fuentes, cambie el valor según corresponda. Las fuentes In1…In3 se definen con los parámetros 20.03…20.05. 12.15 AI1 Seleccion Unidad Cambie este ajuste a mA o V en función del ajuste del puente J1. 12.17 AI1 Min 12.18 AI1 Max 12.19 AI1 Escala en AI1 Min 12.20 AI1 Escala en AI1 Max EN La entrada por defecto para la referencia de velocidad es la entrada analógica AI1. (Se controla con los parámetros del grupo 22.) DE Los parámetros 12.17 y 12.18 establecen los límites bajo y alto de la señal de entrada analógica. Los parámetros de escala 12.19 y 12.20 definen de la siguiente forma los niveles de señal internos que corresponden a estos límites: ES AI (escalada) ES FR 12.20 IT AI (mA/V) 12.17 12.18 12.19 Los parámetros correspondientes para la entrada analógica AI2 son 12.27…12.30. NL RU SV 44 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 13.12 AO1 Fuente 13.17 AO1 Fuente Min 13.18 AO1 Fuente Max 13.19 AO1 mA en Fuente Min 13.20 AO1 mA en Fuente Max El parámetro 13.12 selecciona el origen de la salida analógica AO1 (por defecto, la velocidad del motor en rpm). Los parámetros 13.17 y 13.18 definen los valores bajo y alto de señal de origen que se corresponden con los valores de salida analógica actuales definidos por los parámetros 13.19 y 13.20. Señal fuente EN 13.18 DE AO (mA) 13.19 ES 13.20 ES FR 13.17 IT NL RU SV 46.10 Escalado Velocidad 23.11 Seleccion Rampa 1/2 23.12 Tiempo Aceleracion 1 23.13 Tiempo Deceleracion 1 23.14 Tiempo Aceleracion 2 23.15 Tiempo Deceleracion 2 Usted puede definir dos conjuntos diferentes de rampas de aceleración/deceleración. La fuente que conmuta entre los dos conjuntos se selecciona con el parámetro 23.11. Los distintos conjuntos de tiempos de aceleración/deceleración de los parámetros 23.12…23.15 se refieren al tiempo que el convertidor necesita para acelerar o decelerar entre 0 y la velocidad de escalado (parámetro 46.10). Velocidad 46.10 Acel. Decel. 23.12 23.14 23.13 23.15 0 Tiempo Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario 45 30.11 Velocidad Minima 30.12 Velocidad Maxima 30.17 Intensidad Maxima 30.19 Par Minimo 30.20 Par Maximo Compruebe y ajuste en caso necesario los límites de velocidad del motor, intensidad y par. Ponga en marcha el convertidor con una referencia de velocidad positiva (avance): • Desde el panel de control (control local): En la vista Inicio, pulse (Opciones), seleccione Referencia, ajuste la referencia con las teclas , , ,y , pulse Guardar y pulse el botón Inicio. • Desde E/S: En el control remoto, ajuste la entrada analógica AI1 (referencia), cambie la entrada digital DI2 a 0 (avance) y cambie la entrada digital DI1 a 1 (marcha). EN DE ES ES FR IT NL RU SV 46 Guía rápida de puesta en marcha para los convertidores ACS880 con programa de control primario EN DE ES ES FR IT NL RU SV Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 47 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille Johdanto Tässä oppaassa kuvataan perusohjausohjelmalla varustetun ACS880taajuusmuuttajan käyttöönoton perustoimenpiteet. Kattavat tiedot taajuusmuuttajan ohjelmistosta on ohjelmointioppaassa (käyttöoppaat on lueteltu etukannen sisäpuolella). EN DE Tässä oppaassa taajuusmuuttajan asetukset määritetään ACS-AP-I-ohjauspaneelin avulla. Käyttöönoton toimenpiteet voidaan suorittaa myös Drive composer -PCtyökalun avulla. ES Ennen käynnistystä FI Varmista, että taajuusmuuttajan mekaaninen asennus ja sähköasennus on suoritettu asianmukaisessa pika-asennusoppaassa ja/tai laiteoppaassa kuvatulla tavalla. IT Turvallisuus FI NL RU VAROITUS! Taajuusmuuttajan sähköliitännät ja huoltotyöt saa suorittaa vain pätevä sähköalan ammattilainen. Mitään taajuusmuuttajan, jarrukatkojan, moottorikaapelin tai moottorin asennustöitä ei saa tehdä, kun taajuusmuuttajaan on kytketty jännite. Taajuusmuuttajan jännitteettömyys tulee aina varmistaa mittaamalla. SV 48 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille Käyttöönotto Turvallisuus Käyttöönoton saa suorittaa vain pätevä sähköalan ammattilainen. Käyttöönoton aikana on noudatettava turvaohjeita. Turvaohjeet ovat vastaavan laiteoppaan alussa. Tarkista asennus. Laiteoppaassa on asennuksen tarkistuslista. Varmista, ettei moottorin käynnistäminen aiheuta vaaraa. EN DE ES FI FI IT NL RU SV Kytke käytettävä laite irti, • jos väärä pyörimissuunta voi aiheuttaa vahinkoa tai • jos taajuusmuuttajan käyttöönoton yhteydessä on suoritettava normaali tunnistusajo, kuormamomentti on suurempi kuin 20 prosenttia tai laitteisto ei kestä tunnistusajon aikana esiintyvää nimellistä momenttia. 1 – Virran kytkeminen, , päivämäärän ja ajan asetukset Kytke taajuusmuuttajan virta. Huomautus: On normaalia, että käyttöönoton aikana näyttöön tulee varoitusviestejä useassa eri vaiheessa. Voit piilottaa viestin ja jatkaa käyttöönottoa painamalla -painiketta. Piilota nyt kaikki varoitukset, jotta pääset kotinäyttöön (näkyy oikealla). Näytön alareunan kaksi komentoa (tässä tapauksessa Valinnat ja Valikko), osoittavat näytön alla olevien kahden valintapainikkeen ja toiminnot. Valintapainikkeilla annettavat komennot vaihtelevat tilanteen mukaan. Paina kotinäytössä (Valikko). -painiketta Näyttöön tulee Valikko (oikealla). Kauko 0.0 kierr./min Moottorin nopeus käytetty kierr./min Moottorin virta A Moottorin momentti % % Valinnat 12:34 Kauko Valikko 0.00 0.00 0.0 Valikko 0.0 kierr./min Parametrit Assistantit Energiatehokkuus Tapahtumaloki Lopeta 12:34 Valitse Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 49 Korosta Asetukset valikosta - tai painikkeella ja paina -painiketta (Valitse). - Kauko Asetukset Kieli Päiväys ja kellonaika Muokkaa tekstejä Näytön asetukset Takaisin Korosta Asetukset-valikossa Päiväys ja kellonaika (jos se ei näy korostettuna) ja paina -painiketta (Valitse). Korosta Päiväys-valikossa Päiväys ja kellonaika (jos se ei näy korostettuna) ja paina -painiketta (Valitse). 0.0 kierr./min 12:34 Valitse Kauko 0.0 kierr./min Päiväys ja kellonaika Päiväys 01.01.1980 Aika 12:34:56 Päivämäärän näyttötapa pp.kk.vv Ajan näyttötapa 24-tuntinen Daylight saving EU Seuraavan kesäajan alku 28.03. Takaisin 12:35 Muokkaa Kauko Päiväys 0.0 kierr./min DE ES FI FI IT NL Päivä Kuuk. Vuosi 01 .01.1980 Tiistai Peruuta EN 12:35 Tallenna RU SV 50 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille Aseta oikea päivämäärä: • Siirrä kohdistinta vasemmalle ja oikealle - ja -painikkeilla. • Muuta arvoa - ja -painikkeilla. • Hyväksy uusi asetus painamalla painiketta (Tallenna). - Tarkista loput Päiväys ja kellonaika -valikon asetukset. EN DE ES FI FI Näytä kello -asetus määrittää, näytetäänkö aika aina näytön alareunassa. Kun olet määrittänyt asetukset, paina painiketta (Takaisin tai Lopeta) toistuvasti, kunnes kotinäyttö (oikealla) tulee uudestaan näyttöön. Kauko 0.0 kierr./min Moottorin nopeus käytetty kierr./min Moottorin virta A Moottorin momentti % % Valinnat Varmista, että ulkoinen ohjaus on poistettu käytöstä: vaihda paikallisohjaukseen painamalla ohjauspaneelin Loc/Rem -painiketta. Paikallisohjaus on ilmaistu näytön yläreunassa näkyvällä Paikallinen-tekstillä. Paikallinen 0.0 kierr./min Moottorin nopeus käytetty kierr./min Moottorin virta A Moottorin momentti % % NL Valinnat SV Valikko 2 – Syöttöjännitteen ja moottoritietojen asetukset IT RU 12:35 0.00 0.00 0.0 Avaa Valikko painamalla (Valikko). -painiketta 12:36 Paikallinen Valikko 0.00 0.00 0.0 Valikko 0.0 kierr./min Parametrit Assistantit Energiatehokkuus Tapahtumaloki Lopeta 12:36 Valitse Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 51 Korosta vaihtoehto Parametrit ja paina -painiketta (Valitse). Paikallinen Parametrit Suosikit Toiminnon mukaan Täydellinen luettelo Muokattu Takaisin Korosta Täydellinen luettelo - tai painikkeella ja paina -painiketta (Valitse). - Näyttöön tulee parametriryhmien luettelo. Korosta parametriryhmä 95 Laitteiston konfigurointi ja paina -painiketta (Valitse). Huomaa, että lista pyörii ympäri ryhmien 99 ja 01 välillä. Ryhmän 95 voi siis hakea nopeasti -painikkeella. 12:36 Paikallinen Täydellinen luettelo 01 Oloarvot 03 Tulon ohjearvot 04 Varoitukset ja viat 05 Vianhaku 06 Ohjaus- ja tilasanat 07 Järjestelmän tiedot Takaisin 12:36 0.0 kierr./min Valitse 0.0 kierr./min DE ES FI Valitse Paikallinen 0.0 kierr./min 95 Laitteiston konfigurointi 95.01 Syöttöjännite Ei annettu 95.02 Adapt. jänniterajat Poista käyt. 95.04 Ohj.kortin syöttö Sisäinen 24 V Kun ryhmä on valittu, näyttöön tulee luettelo ryhmän sisäisistä parametreista. FI IT NL RU SV Takaisin Korosta parametri 95.01 Syöttöjännite (jos sitä ei ole jo korostettu) ja paina painiketta (Muokkaa). Käytettävissä olevat parametriasetukset on lueteltu. EN 12:36 Paikallinen 95.01 Syöttöjännite [0] Ei annettu [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Peruuta 12:36 Muokkaa 0.0 kierr./min Tallenna 52 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille Korosta oikea asetus luettelosta ja paina -painiketta (Tallenna). Paikallinen 0.0 kierr./min 95 Laitteiston konfigurointi 95.01 Syöttöjännite 380…415 V 95.02 Adapt. jänniterajat Poista käyt. 95.04 Ohj.kortin syöttö Sisäinen 24 V Takaisin 12:36 Muokkaa EN Palaa parametriryhmien luetteloon painamalla -painiketta (Takaisin). Valitse parametriryhmä 99 Moottorin tiedot ja aseta parametri 99.03 Moottorin tyyppi. DE Aseta parametri 99.04 Moottorisäätötila. DTC = suora momentinsäätö; Skalaari ES FI FI DTC on sopiva useimmissa tapauksissa. Skalaarisäätöä suositellaan, jos • moottorin nimellisvirta on alle 1/6 taajuusmuuttajan nimellisvirrasta • taajuusmuuttajaa käytetään testitarkoituksiin ilman moottoria tai • taajuusmuuttaja ohjaa useita moottoreita ja kytkettyjen moottorien määrä vaihtelee. Tarkista seuraavat parametriasetukset moottorin arvokilvestä. Syötä arvot tarkalleen moottorin arvokilvessä kuvatulla tavalla, mikäli mahdollista. Esimerkki epätahtimoottorin arvokilvestä: IT ABB Motors NL 3 motor RU SV Esimerkki kestomagneettimoottorin arvokilvestä: V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 1475 32.5 0.83 30 50 56 1475 0.83 50 30 50 1470 34 0.83 30 1470 59 0.83 30 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 2GBJ285220-ADA405445477 6316/C3 IEC 34-1 99.06 Moottorin nimellisvirta Sallittu alue on • DTC-tilassa: 1/6 × IHd … 2 × IHd taajuusmuuttajasta • Skalaaritilassa: 0 … 2 × IHd Huomautus: Kun parametriarvo on numero: • Syötä arvo painamalla 6316/C3 630kg IEC 34-1 180 • Muuta arvoa - ja -painikkeilla. • Siirrä kohdistinta vasemmalle ja oikealle IP 55 V - ja -painiketta (Tallenna). -painikkeilla. t E/s Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 53 Tee seuraavat parametriasetukset samalla tavalla. 99.07 Moottorin nimellisjännite Sallittu alue on 1/6 × UN … 2 × UN taajuusmuuttajan jännitteeseen verrattuna. Kestomagneettimoottoreissa nimellisjännite on BackEMF-jännite moottorin nimellisnopeudella. Jos jännite annetaan voltteina kierroslukua kohden (esim. 60 V / 1000 rpm), jännite 3 000 rpm:n nimellisnopeudella on 3 × 60 V = 180 V. Huomaa, että nimellisjännite ei ole sama kuin joidenkin valmistajien ilmoittama moottorin DC-jännite (EDCM). Nimellisjännite voidaan laskea jakamalla EDCM-jännite 1,7:llä (kolmen neliöjuurella). 99.08 Moottorin nimellistaajuus Jos kestomagneettimoottorin nimellistaajuutta ei ole merkitty arvokilpeen, se voidaan laskea seuraavalla kaavalla: f = n × p / 60 jossa n = moottorin nimellisnopeus, p = napaparien määrä. 99.09 Moottorin nimellisnopeus EN DE ES 99.10 Moottorin nimellisteho FI 99.11 Moottorin nimellinen cosfii 99.12 Moottorin nimellismomentti Nämä arvot eivät ole pakollisia, mutta voidaan syöttää ohjaustarkkuuden parantamiseksi. Jos arvot eivät ole tiedossa, jätä arvoksi 0. 99.13 Tunnistusajopyyntö Tällä parametrilla valitaan tunnistusajon tila (vain DTC-moottoriohjaustilassa). VAROITUS! Tunnistusajon tilat, joissa on merkintä *, pyörittävät moottoria eteenpäin (lisätietoja alla). Varmista ennen näiden tilojen valitsemista, että moottorin pyörittäminen on turvallista. *Normaali tila kannattaa valita aina, kun se on mahdollista. Moottori on kytkettävä irti käytetystä laitteesta, jos • kuormamomentti on suurempi kuin 20 prosenttia tai • laitteisto ei kestä tunnistusajon aikana esiintyvää nimellistä momenttia. *Supistettu tila tulee valita, jos mekaaniset häviöt ylittävät 20 prosenttia eli kuormaa ei voi kytkeä irti, tai moottorin jarrun auki pitämiseen tarvitaan täysi vuo (esimerkiksi kartiojarrumoottoreilla). Paikallaanajotila tulee valita, jos *normaalia tai *supistettua tilaa ei voi käyttää. Huomautukset: • Tätä tilaa ei voi käyttää kestomagneettimoottoreilla, jos kuorman momentti on yli 20 prosenttia nimellisarvosta. • Logiikka ei avaa mekaanista jarrua tunnistusajoa varten. Varmista, että Safe torque off- ja hätäpysäytyspiirit (jos käytössä) ovat suljettuina. Käynnistä moottori painamalla (Käynnistys) -painiketta. Varoitus ilmoittaa, että tunnistusajo on käynnissä. FI IT NL RU SV 54 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille Tarkista, että moottori pyörii oikeaan suuntaan (eteen alla olevassa kuvassa esitetyllä tavalla). Tunnsitusajo on suoritettu, kun taajuusmuuttaja pysähtyy ja parametrin 99.13 arvoksi palaa Ei. Jos moottori pyörii väärään suuntaan, korjaa moottorin kaapelointi tai säädä parametria 99.16 Vaihejärjestys. EN DE 3 – Ohjaussignaalin asetukset Tarkista taajuusmuuttajan ohjausyksikön siirtoliittimien J1 ja J2 asennot. Nämä siirtoliittimet määrittävät, ovatko analogiatulot AI1 ja AI2 virta- vai jännitetuloja. Tarkista/säädä seuraavat parametrit. ES 20.01 Ulk1 komennot FI Oletusarvoisesti taajuusmuuttaja käynnistyy/pysähtyy digitaalitulon DI1 tilan mukaisesti (0 = pysäytys, 1 = käynnistys). DI2 määrittää pyörimissuunnan (0 = eteen, 1 = taakse). FI Jos muita lähteitä tarvitaan, muuta arvoa sen mukaisesti. Lähteet In1…In3 määritetään parametreilla 20.03…20.05. IT 12.15 AI1 yksikön valinta Määritä asetukseksi mA tai V siirtoliittimen J1 asetuksen mukaisesti. NL RU SV 12.17 AI1 min. 12.18 AI1 maks. 12.19 AI1 skaalattu AI1-minimiin 12.20 AI1 skaalattu AI1-maksimiin Nopeusohjeen oletustulo on analogiatulo AI1. (Tämä valitaan ryhmän 22 parametreilla.) Parametrit 12.17 ja 12.18 määrittävät analogiatulon signaalin ala- ja ylärajat. Skaalausparametrit 12.19 ja 12.20 määrittävät sisäiset signaalitasot, jotka vastaavat rajoja seuraavasti: AI (skaalattu) 12.20 AI (mA/V) 12.17 12.18 12.19 Vastaavat parametrit analogiatulolle AI2 ovat 12.27…12.30. Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 55 13.12 AO1 lähde 13.17 AO1 lähteen minimi 13.18 AO1 lähteen maksimi 13.19 AO1 out at AI1 src min 13.20 AO1 out at AI1 src max Parametrilla 13.12 valitaan lähde analogiatulolle AO1 (oletusarvo on moottorin nopeus kierroksina minuutissa). Parametreilla 13.17 ja 13.18 asetetaan lähdesignaalin ala- ja ylärajan arvot, jotka vastaavat parametreilla 13.19 ja 13.20 määritettyjä analogiatulon oloarvoja. Lähdesignaali 13.18 EN DE AO (mA) 13.19 ES 13.20 FI 13.17 FI 46.10 Nopeuden skaalaus 23.11 Ramppiasetuksen valinta 23.12 Kiihdytysaika 1 23.13 Hidastusaika 1 23.14 Kiihdytysaika 2 23.15 Hidastusaika 2 Voit määrittää kaksi eri kiihdytys-/hidastusaikaa. Kahden eri ajan välillä vaihteleva lähde valitaan parametrilla 23.11. Jokainen parametreilla 23.12…23.15 määritetty kiihdytys-/hidastusaika viittaa aikaan, jonka kuluessa taajuusmuuttaja kiihdyttää nollasta skaalattavaan nopeuteen tai hidastaa skaalatusta nopeudesta nollaan (parametri 46.10). Nopeus 46.10 Kiihd. Hid. 23.12 23.14 23.13 23.15 0 Aika IT NL RU SV 56 Pika-aloitusopas perusohjausohjelmalla varustetuille ACS880-taajuusmuuttajille 30.11 Miniminopeus 30.12 Maksiminopeus 30.17 Maksimivirta 30.19 Minimimomentti 30.20 Maksimimomentti Tarkista ja tarvittaessa aseta moottorin nopeuden, virran ja momentin rajat. EN DE ES FI FI IT NL RU SV Käynnistä taajuusmuuttaja positiivisella nopeusohjeella (eteen): • Ohjauspaneelista (paikallisohjaus): Paina kotinäkymässä -painiketta (Valinnat), valitse Ohje, säädä ohjetta -, -, - ja -painikkeilla, valitse Tallenna ja paina käynnistyspainiketta. • I/O-ohjauksesta: Säädä kauko-ohjauksessa analogiatuloa AI1 (ohje), aseta digitaalitulon DI2 arvoksi 0 (eteen) ja digitaalitulon DI1 arvoksi 1 (käynnistys). Guide de mise en route pour l'ACS880 avec programme de contrôle standard 57 Guide de mise en route pour l'ACS880 avec programme de contrôle standard Introduction Ce guide présente sommairement la séquence de mise en route d'un variateur ACS880 équipé du programme de contrôle standard. Vous trouverez une documentation complète dans le manuel d'exploitation (Firmware Manual) (cf. liste des manuels au dos de la page de couverture). EN DE Dans ce guide, nous décrivons la configuration du variateur avec la micro-console ACS-AP-I. La séquence de mise en route peut aussi être effectuée à l'aide de l'outil logiciel PC Drive composer. ES Avant de commencer FR Vérifiez que le montage et les raccordements du variateur sont conformes aux consignes du Guide d'installation et/ou du Manuel d'installation approprié. FR Sécurité FI NL RU ATTENTION ! Seuls des électriciens qualifiés sont autorisés à procéder à l'installation et à la maintenance du variateur. N'intervenez jamais sur le variateur, le circuit du hacheur de freinage, le câble moteur ou le moteur lorsque le variateur est sous tension. Vous devez toujours vérifier l'absence effective de tension par une mesure. SV 58 Guide de mise en route pour l'ACS880 avec programme de contrôle standard Mise en route Sécurité La mise en route doit uniquement être réalisée par un électricien qualifié. Les consignes de sécurité doivent être respectées pendant toute la procédure. Ces consignes figurent au début du Manuel d’installation correspondant. Vérification de l'installation de l'appareil Cf. liste des points à vérifier dans le Manuel d'installation correspondant. Vérifiez que le moteur peut être démarré en toute sécurité. Vous devez désaccoupler la machine entraînée dans les cas suivants : EN DE ES FI FR FR NL RU SV • si elle risque d'être endommagée en cas d'erreur de sens de rotation du moteur ou • si une identification normale du moteur est requise : si le couple de charge est supérieur à 20 % ou si la mécanique n’est pas capable de supporter le couple nominal sur une période transitoire lors de l’exécution de la fonction d’identification moteur. 1 - Mise sous tension, réglage de la de la date et de l'heure Mettez le variateur sous tension. N.B. : Il est normal que des messages d'alarme s'affichent à divers moments de la procédure de mise en route. Pour masquer un message et continuer la procédure, appuyez sur . Masquez toutes les alarmes éventuelles pour passer en vue Accueil (affichée à droite). Distant 0.0 tr/min Vitesse moteur utilisee tr/min Courant moteur A Couple moteur % % Les deux commandes en bas de l'écran (dans ce cas, Options et Menu) représentent les fonctions des deux touches et situées sous l'écran. Les commandes des touches de fonction varient selon le contexte. Options Dans la vue Accueil, enfoncez la touche (Menu). Le menu principal apparaît (à droite). Distant Menu 0.00 0.00 0.0 12:34 Menu 0.0 tr/min Paramètres Assistants Efficacité énergétique Sortie Pile Événements 12:34 Sel Guide de mise en route pour l'ACS880 avec programme de contrôle standard 59 Mettez Réglages en surbrillance en naviguant à l'aide des touches et enfoncez la touche (Sel) puis Distant Réglages Langue Date & Heure Edition textes Réglages affichage Retour Dans le menu Reglages, mettez Date & Heure en surbrillance (si ce n'est pas encore le cas) et enfoncez (Sel). Dans le menu Date & Heure, mettez Date en surbrillance (si ce n'est pas encore le cas) et enfoncez (Sel). 0.0 tr/min 12:34 Sel Distant 0.0 tr/min Date & Heure Date 01.01.1980 Heure 12:34:56 Format date jour.mois.année Format heure 24 heures Heure d'été UE Prochain passage heure d'été 28.03. Retour 12:35 Edition Distant Date 0.0 tr/min DE ES FI FR FR NL Jour Mois Année 01 .01.1980 Mardi Annuler EN 12:35 Sauvegarder RU SV 60 Guide de mise en route pour l'ACS880 avec programme de contrôle standard Réglez la date : • Déplacez le curseur vers la droite ou la gauche avec les touches et . • Ajustez la valeur avec et . • Sauvegardez votre réglage avec (Sauvegarder). Vérifiez et ajustez au besoin tous les autres réglage du menu Date & Heure. Le réglage Visu horloge vous permet de choisir si vous voulez afficher l'heure en bas de l'écran en permanence. EN DE ES FI FR Distant 0.0 tr/min Vitesse moteur utilisee tr/min Courant moteur A Couple moteur % % Options Menu 2 - Réglage de la tension réseau et des données moteur Sélectionnez le mode de commande Local pour vous assurer que la commande à distance est désactivée. Pour cela, enfoncez la touche Loc/Rem . Lorsque le variateur est en commande locale, «Local» s'affiche en haut de l'écran. Local 0.0 tr/min Vitesse moteur utilisee tr/min Courant moteur A Couple moteur % % NL Options SV 12:35 Une fois le réglage effectué, enfoncez la touche (Retour ou Sortie) jusqu'à revenir à la vue Accueil (à droite). FR RU 0.00 0.00 0.0 Ouvrez le menu principal en enfonçant la touche (Menu). 0.00 0.00 0.0 12:36 Local Menu Menu 0.0 tr/min Paramètres Assistants Efficacité énergétique Sortie Pile Événements 12:36 Sel Guide de mise en route pour l'ACS880 avec programme de contrôle standard 61 Mettez Paramètres en surbrillance et enfoncez la touche (Sel). Local Paramètres Favoris Par fonction Liste complète Modifie Retour 0.0 tr/min 12:36 Sel Mettez Liste complète en surbrillance à l'aide des touches et puis enfoncez la touche (Sel) Local 0.0 tr/min Liste complète 01 Valeurs actives La liste des groupes de paramètres s'affiche. 03 References entree 04 Alarmes et defauts 05 Diagnostic 06 Mots de commande et etat 07 Info système Retour 12:36 Sel Mettez le groupe de paramètres 95 Configuration materiel en surbrillance et enfoncez la touche (Sel). Local 0.0 tr/min 95 Configuration materiel 95.01 Tension reseau Vide La liste défile dans les deux sens entre les 95.02 Limite tension adaptative Desactive groupes de paramètres 99 et 01. Dans ce cas, il est donc plus rapide d'utiliser pour 95.04 Alim carte commande Interne 24V atteindre le groupe 95. Une fois le groupe sélectionné, la liste des paramètres de ce groupe s'affiche. DE ES FI FR FR NL RU SV Retour Mettez le paramètre 95.01 Tension reseau en surbrillance (s'il ne l'est pas déjà) et enfoncez (Edition). La liste des réglages disponibles s'affiche. EN 12:36 Local 95.01 Tension reseau [0] Vide [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Annuler 12:36 Edition 0.0 tr/min Sauvegarder 62 Guide de mise en route pour l'ACS880 avec programme de contrôle standard Mettez en surbrillance le réglage correct et enfoncez la touche (Sauvegarder). Local 0.0 tr/min 95 Configuration materiel 95.01 Tension reseau 380…415 V 95.02 Limite tension adaptative Desactive 95.04 Alim carte commande Interne 24V Retour 12:36 Edition EN Enfoncez (Retour) pour afficher la liste des groupes de paramètres. Sélectionnez le groupe de paramètre 99 Donnees moteur et réglez le paramètre 99.03 Type moteur. DE Réglez le paramètre 99.04 Mode commande moteur. DTC = Contrôle direct de couple ; Scalaire ES FI FR FR NL Le mode DTC est parfaitement adapté à la plupart des applications. Le mode Scalaire est préconisé si : • le courant nominal du moteur est inférieur à 1/6 du courant de sortie nominal du variateur ; • le variateur est utilisé à des fins d’essais sans moteur raccordé ; • le variateur commande plusieurs moteurs et le nombre de moteurs raccordés est variable. Reportez-vous à la plaque signalétique du moteur pour régler les paramètres suivants. Vous devez autant que possible entrer les valeurs exactes de la plaque signalétique du moteur. Exemple de plaque signalétique d'un moteur asynchrone : RU SV Exemple de plaque signalétique d'un moteur à aimants permanents : ABB Motors 3 motor V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Guide de mise en route pour l'ACS880 avec programme de contrôle standard 63 99.06 Courant nominal moteur Plage de réglage autorisée : • en mode DTC : 1/6 × Iint … 2 × Iint du variateur • en mode Scalaire : 0 … 2 × Iint N.B. : Avec des valeurs numériques : • Incrémentez et décrémentez les valeurs avec les touches et • Déplacez le curseur vers la droite ou la gauche avec les touches • Enfoncez . et . (Sauvegarder) pour enregistrer la valeur. Procédez de la même manière pour régler les autres paramètres. 99.07 Tension nominale moteur La plage de réglage autorisée est 1/6 × UN … 2 × UN du variateur. Moteurs à aimants permanents : la tension nominale est la tension inverse FEM (BackEMF) à la vitesse nominale. Si la tension est spécifiée par tr/min (ex., 60 V pour 1000 tr/min), la tension pour une vitesse nominale de 3000 tr/min est 3 × 60 V = 180 V. Vous noterez que la tension nominale n’est pas égale à la valeur de tension d’un moteur c.c. équivalent donnée par certains constructeurs de moteur La tension nominale peut être calculée en divisant la tension d’un moteur c.c. équivalent par 1,7 (= racine carrée de 3). 99.08 Fréquence nominale moteur Moteurs à aimants permanents : si la fréquence nominale ne figure pas sur la plaque signalétique du moteur, elle doit être calculée avec la formule suivante : f = n × p / 60 avec n = vitesse nominale moteur et p = nombre de paires de pôles. 99.09 Vitesse nominale moteur EN DE ES FI FR FR NL 99.10 Puissance nominale moteur RU 99.11 Cosfii nominal moteur 99.12 Couple nominal moteur SV Ces valeurs sont facultatives mais peuvent améliorer la précision de la commande. Si vous ne les connaissez pas, n'indiquez rien. 64 Guide de mise en route pour l'ACS880 avec programme de contrôle standard 99.13 Demande identif moteur EN DE ES FI FR FR Ce paramètre sélectionne le type d'identification moteur (en mode DTC uniquement). ATTENTION ! Lorsque le mode d'identification est précédé d'un astérisque (*), le moteur tournera dans le sens avant (voir détails ci-dessous). Vous devez vous assurer qu'il peut fonctionner en toute sécurité avant de choisir un de ces modes. Le mode *Normal doit être sélectionné chaque fois que cela est possible. Le moteur doit être désaccouplé de la machine entraînée • si le couple de charge est supérieur à 20 % ou • si la machine n’est pas capable de supporter le couple nominal sur une période transitoire lors de l’exécution de la fonction. *Le mode Reduced doit être sélectionné si les pertes mécaniques sont supérieures à 20 %, par exemple s'il est impossible de désaccoupler la charge ou si un flux complet est exigé pour maintenir le frein moteur ouvert (moteur conique). Le mode Standstill convient si vous ne pouvez utiliser ni le mode *Normal ni le mode *Reduced. N.B. : • Vous ne devez pas utiliser ce mode avec un moteur à aimants permanents si le couple de charge est supérieur à 20 % du couple nominal. • Le frein mécanique n'est pas ouvert par la logique de la fonction d'identification moteur. Vérifiez que les éventuels circuits d’Interruption sécurisée du couple (STO) et d'arrêt d'urgence sont fermés. Lancez l'identification moteur en enfonçant la touche (Start). Une alarme vous indique que l'identification est en cours. Vérifiez que le moteur tourne dans le bon sens (sens avant illustré ci-dessous). NL RU SV L'identification moteur est terminée lorsque le variateur s'arrêt et que la valeur du paramètre 99.13 revient sur «Non» Si le moteur a tourné dans le mauvais sens, rectifiez sont câblage ou modifier le réglage du paramètre 99.16 Ordre des phases. Guide de mise en route pour l'ACS880 avec programme de contrôle standard 65 3 – Réglage des signaux de commande Vérifiez l'emplacement des cavaliers J1 et J2 sur l'unité de commande du variateur. Leur position détermine l'utilisation des entrées analogiques 1 et 2 (courant ou tension). Réglez/ajustez les paramètres suivants. 20.01 Commandes Ext1 Le variateur est préréglé pour démarrer/s'arrêter selon le statut de l'entrée logique 1 (DI1) (0 = arrêt ; 1 = démarrage). L'entrée logique 2 (DI2) règle le sens de rotation (0 = avant ; 1 = arrière). Si vous souhaitez utiliser d'autres sources, réglez les valeurs en conséquence. Les sources Src1 à Src3 sont réglées aux paramètres 20.03 à 20.05. 12.15 Selection unite AI1 Choisissez mA ou V selon le réglage du cavalier J1. EN 12.17 Mini AI1 12.18 Maxi AI1 12.19 Mini echelle AI1 12.20 Maxi echelle AI1 La référence de vitesse est préréglée sur l'entrée analogique 1 (AI1). (réglage commandé par les paramètres du groupe 22) DE Les paramètres 12.17 et 12.18 définissent les limites haute et basse du signal d'entrée analogique. Les paramètres de mise à l'échelle 12.19 et 12.20 règlent le niveau de signal interne correspondant à ces limites comme suit : FR ES FI FR AI (mise à l'échelle) NL 12.20 RU AI (mA / V) 12.17 12.18 12.19 Les paramètres correspondants pour l'entrée analogique 2 (AI2) sont 12.27…12.30. SV 66 Guide de mise en route pour l'ACS880 avec programme de contrôle standard 13.12 Source AO1 13.17 Mini source AO1 13.18 Maxi source AO1 13.19 Valeur mini sortie AO1 13.20 Valeur maxi sortie AO1 Le paramètre 13.12 sélectionne la source pour l'entrée analogique 1 (AO1). Le préréglage usine est la vitesse moteur en tr/min. Les paramètres 13.17 et 13.18 règlent les valeurs haute et basse des signaux sources correspondant aux valeurs actives des sorties analogiques définies aux paramètres 13.19 et 13.20. Signal source EN 13.18 DE AO (mA) 13.19 ES 13.20 FI FR 13.17 FR NL RU SV 46.10 Echelle vitesse 23.11 Selection jeu rampe 23.12 Temps acceleration 1 23.13 Temps deceleration 1 23.14 Temps acceleration 2 23.15 Temps deceleration 2 Vous pouvez définir deux jeux de rampe d'accélération/décélération. Indiquez la source pour la permutation entre les deux jeux au paramètre 23.11. Chaque jeu de temps d'accélération/décélération des paramètres 23.12 à 23.15 indique le temps nécessaire au variateur pour passer de la vitesse nulle à la vitesse mise à l'échelle (paramètre 46.10). Vitesse 46.10 Acc. Déc. 23.12 23.14 23.13 23.15 0 Temps Guide de mise en route pour l'ACS880 avec programme de contrôle standard 67 30.11 Vitesse minimum 30.12 Vitesse maximum 30.17 Courant maximum 30.19 Couple minimum 30.20 Couple maximum Vérifiez et réglez si nécessaire les limites de vitesse, courant et couple moteur. Démarrez le variateur avec une référence de vitesse positive (rotation en sens avant). • Avec la micro-console (commande locale) : Dans la vue Accueil, enfoncez la touche (Options), sélectionnez Référence et réglez la référence à l'aide des touches , , et . Enfoncez la touche Sauvegarder puis la touche Start. • Avec les E/S : En commande distante, réglez l'entrée analogique 1 (AI1, référence), mettez l'entrée logique 2 (DI2) sur 0 (avant) et l'entrée logique 1 (DI1) sur 1 (démarrage). EN DE ES FI FR FR NL RU SV 68 Guide de mise en route pour l'ACS880 avec programme de contrôle standard EN DE ES FI FR FR NL RU SV Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 69 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario Informazioni sulla guida EN Questa guida descrive la sequenza di avviamento base dei convertitori di frequenza ACS880 dotati di Programma di controllo primario. La documentazione completa sul firmware dei convertitori è contenuta nel Manuale firmware (vedere l'elenco delle pubblicazioni nella seconda di copertina). DE In questa guida, il convertitore viene impostato utilizzando il pannello di controllo ACS-AP-I. La sequenza di avviamento può essere eseguita anche utilizzando il tool PC Drive Composer. FI Prima di iniziare IT Verificare che l'installazione meccanica ed elettrica del convertitore di frequenza sia stata eseguita correttamente, secondo le istruzioni contenute nella rispettiva Guida rapida all'installazione e/o nel Manuale hardware. IT Sicurezza SV AVVERTENZA! L'installazione elettrica e gli interventi di manutenzione sul convertitore di frequenza devono essere eseguiti solo da elettricisti qualificati. Non intervenire mai sul convertitore, sul circuito del chopper di frenatura, sul cavo motore o sul motore quando il convertitore è sotto tensione. Verificare sempre che non sia presente tensione. ES FR RU 70 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario Avviamento Sicurezza L'avviamento deve essere eseguito solo da elettricisti qualificati. Rispettare scrupolosamente le norme di sicurezza durante la procedura di avviamento. Leggere le norme di sicurezza riportate nelle prime pagine del Manuale hardware del convertitore. Controllare l'installazione. Vedere la checklist di installazione nel Manuale hardware. EN DE ES FI FR IT IT RU SV Controllare che l'avviamento del motore non determini situazioni di pericolo. Disaccoppiare la macchina comandata se • vi è il rischio di danni in caso di direzione di rotazione non corretta, o • è necessario eseguire una routine di identificazione (ID run) Normale all'avviamento del convertitore, quando la coppia di carico è superiore al 20% o la macchina non è in grado di sostenere il transitorio della coppia nominale durante l'ID run. 1 – Accensione e impostazione di data e ora Accendere il convertitore. Nota: è normale che durante la procedura di avviamento vengano visualizzati dei messaggi di allarme. Per cancellare i messaggi e riprendere l'avviamento, premere . Cancellare i messaggi eventualmente presenti per accedere alla vista Home (figura a destra). Remoto 0.0 rpm Vel motore utilizzata rpm Corrente motore A Coppia motore % % I due comandi in basso sullo schermo (in questo caso, Opzioni e Menu) corrispondono alle funzioni dei due tasti software e posizionati sotto il display. I comandi assegnati ai tasti software variano in base al contesto. Opzioni Nella vista Home, premere (Menu). Viene visualizzato il Menu principale (a destra). Remoto Menu 0.00 0.00 0.0 12:34 Menu 0.0 rpm Parametri Assistenti Efficienza energetica Esci Log eventi 12:34 Seleziona Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 71 Evidenziare Impostazioni sul menu utilizzando e e premere (Seleziona). Remoto Imposta Lingua Data e ora Modifica testi Impostazioni display Indietro Nel menu Impostazioni, evidenziare Data e ora (se non è già evidenziato) e premere (Seleziona). Nel menu Data e ora, evidenziare Data (se non è già evidenziato) e premere (Seleziona). 12:34 0.0 rpm Seleziona Remoto 0.0 rpm Data e ora Data 01.01.1980 Ora 12:34:56 Formato data giorno.mese.anno Formato ora 24 ore Ora legale EU Inizio prossima ora legale 28.03. Indietro 12:35 Modifica Remoto Data 0.0 rpm DE ES FI FR IT IT Giorno Mese Anno RU 01 .01.1980 SV Martedì Annulla EN 12:35 Salva 72 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario Impostare la data: Remoto • Per spostare il cursore a destra e a sinistra, premere e . • Per modificare il valore, premere e • Premere (Salva) per confermare l'impostazione visualizzata. Verificare/regolare tutte le altre impostazioni del menu Data e ora. La voce Mostra orologio attiva o nasconde la visualizzazione dell'orologio in basso sul display. EN DE ES FI FR . 0.0 rpm Vel motore utilizzata rpm Corrente motore A Coppia motore % % Opzioni 12:35 Menu Una volta completate le impostazioni, premere ripetutamente (Indietro o Esci) fino a tornare alla vista Home (a destra). 2 – Impostazione della tensione di alimentazione e dei dati del motore Passare al controllo locale per assicurarsi che il controllo esterno sia disabilitato premendo il tasto Loc/Rem . Quando è attivo il controllo locale, in alto sul display compare la scritta "Locale". Locale 0.0 rpm Vel motore utilizzata rpm IT Corrente motore A IT Coppia motore % % Opzioni RU SV 0.00 0.00 0.0 Aprire il Menu principale premendo (Menu). 0.00 0.00 0.0 12:36 Locale Menu Menu 0.0 rpm Parametri Assistenti Efficienza energetica Esci Log eventi 12:36 Seleziona Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 73 Evidenziare Parametri e premere (Seleziona). Locale Parametri Preferiti Per funzione Elenco completo Modificati Indietro Evidenziare Elenco completo utilizzando e e premere (Seleziona). Viene visualizzato un elenco di gruppi di parametri. 12:36 Locale Elenco completo 01 Valori effettivi 03 Riferimenti ingressi 04 Allarmi e guasti 05 Diagnostica 06 Word controllo e stato 07 Info sistema Indietro 12:36 0.0 rpm Seleziona 0.0 rpm DE ES FI Seleziona Evidenziare il gruppo di parametri 95 Configurazione HW e premere (Seleziona). Locale 0.0 rpm 95 Configurazione HW Non dato L'elenco dei gruppi è continuo, da 99 a 01, e 95.01 Tensione alimentaz 95.02 Limiti tensione adattiva Disabilita consultabile in entrambe le direzioni. In questo caso, è più rapido utilizzare per 95.04 Alimentaz scheda ctrl 24V interna trovare il gruppo 95 in elenco. Quando si seleziona un gruppo, vengono visualizzati tutti i parametri di quel gruppo. FR IT IT RU SV Indietro Evidenziare il parametro 95.01 Tensione alimentaz (se non è già evidenziato) e premere (Modifica). Vengono mostrate le impostazioni disponibili per il parametro. EN 12:36 Locale 95.01 Tensione alimentaz [0] Non dato [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Annulla 12:36 Modifica 0.0 rpm Salva 74 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario Evidenziare l'impostazione corretta nell'elenco e premere (Salva). Locale 0.0 rpm 95 Configurazione HW 95.01 Tensione alimentaz 380…415 V 95.02 Limiti tensione adattiva Disabilita 95.04 Alimentaz scheda ctrl 24V interna Indietro 12:36 Modifica EN Premere (Indietro) per tornare all'elenco dei gruppi di parametri. Selezionare il gruppo 99 Dati motore e impostare il parametro 99.03 Tipo motore. DE Impostare il parametro 99.04 Modo controllo motore. DTC = Direct Torque Control (controllo diretto di coppia); Scalare ES FI FR IT IT Il modo DTC è adatto nella maggior parte dei casi. Il modo scalare è raccomandato se • la corrente nominale del motore è inferiore a 1/6 della corrente nominale del convertitore di frequenza, • il convertitore viene utilizzato a scopo di collaudo senza un motore collegato, o • il convertitore controlla più motori e il numero di motori collegati è variabile. Per le seguenti impostazioni parametriche, fare riferimento ai dati riportati sulla targa del motore. Quando possibile, i valori devono essere inseriti esattamente come compaiono sulla targa del motore. Esempio di targa di un motore a induzione (asincrono): Esempio di targa di un motore a magneti permanenti: ABB Motors RU 3 motor SV V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 75 99.06 Corrente nomin motore Il range consentito è • modo DTC: 1/6 × IHd … 2 × IHd del convertitore • modo scalare: 0 … 2 × IHd Nota: per i valori dei parametri in forma numerica: • Per modificare il valore di una unità, premere e . • Per spostare il cursore a destra e a sinistra, premere e • Premere . (Salva) per confermare il valore. Impostare nello stesso modo i seguenti parametri. 99.07 Tensione nomin motore Il range consentito è 1/6 × UN … 2 × UN del convertitore. Con i motori a magneti permanenti, la tensione nominale è la tensione controelettromotrice alla velocità nominale del motore. Se la tensione è espressa in volt/rpm (es. 60 V a 1000 rpm), la tensione alla velocità nominale di 3000 rpm è 3 × 60 V = 180 V. Si noti che la tensione nominale non è uguale alla tensione equivalente del motore in c.c. (EDCM) fornita da alcuni costruttori di motori. La tensione nominale può essere calcolata dividendo la tensione EDCM per 1.7 (o radice quadrata di 3). 99.08 Frequenza nomin motore Nel caso dei motori a magneti permanenti, se la frequenza nominale non è indicata sulla targa, si può calcolare con la formula seguente: f = n × p / 60 dove n = velocità nominale del motore, p = numero di coppie di poli. 99.09 Velocità nomin motore 99.10 Potenza nomin motore 99.11 cosfii nomin motore 99.12 Coppia nomin motore Questi valori non sono obbligatori, ma si possono ugualmente inserire per migliorare la precisione del controllo. Se non sono noti, lasciare l'impostazione su 0. EN DE ES FI FR IT IT RU SV 76 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 99.13 Richiesta ID-run Questo parametro seleziona la modalità per la routine di identificazione (solo con il controllo motore DTC). AVVERTENZA! Nelle modalità di ID run contrassegnate dall'asterisco (*), il motore ruota in direzione "avanti" (vedere oltre per i dettagli). Assicurarsi che il funzionamento del motore non comporti alcun rischio quando si selezionano queste modalità. ES *Normale: se possibile, selezionare sempre questa modalità. Il motore deve essere disaccoppiato dalla macchina comandata se • la coppia di carico è superiore al 20%, o • la macchina non è in grado di sostenere il transitorio della coppia nominale durante l'ID run. *Ridotta: selezionare questa modalità se le perdite meccaniche sono superiori al 20%, cioè se il carico non può essere disaccoppiato, oppure se è richiesto il flusso completo per tenere aperto il freno motore (es. con motori conici). Statica: selezionare questa modalità quando non è possibile utilizzare le modalità *Normale e *Ridotta. Note: FI • Questa modalità non può essere utilizzata con motori a magneti permanenti se la coppia di carico è superiore al 20% del valore nominale. EN DE • Il freno meccanico non viene aperto dalla logica per l'ID run. FR Verificare che il circuito della funzione Safe Torque Off e il circuito di arresto di emergenza (se presenti) siano chiusi. IT Avviare l'ID run premendo il pulsante (Start). IT Verificare che il motore ruoti nella direzione corretta (direzione "avanti", come illustrato sotto). Un allarme indica che la routine di identificazione è in corso. RU SV La routine termina quando il convertitore si arresta e il valore del parametro 99.13 torna a "No". Se il motore ha ruotato nella direzione sbagliata, correggere il cablaggio del motore o regolare il parametro 99.16 Ordine fasi. 3 – Impostazioni dei segnali di controllo Verificare le posizioni dei ponticelli J1 e J2 sull'unità di controllo del convertitore. Questi ponticelli determinano la funzione degli ingressi analogici AI1 e AI2 come ingressi di corrente o tensione. Verificare/regolare i seguenti parametri. 20.01 Comandi Est1 Di default, il convertitore si avvia e si arresta in base allo stato dell'ingresso digitale DI1 (0 = arresto, 1 = marcia). DI2 determina la direzione di rotazione (0 = avanti, 1 = indietro). Se è necessario avere altre sorgenti, modificare opportunamente i valori. Le sorgenti In1…In3 sono definite dai parametri 20.03…20.05. Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 77 12.15 Selezione unità AI1 Impostare su mA o V in base all'impostazione del ponticello J1. 12.17 AI1 min 12.18 AI1 max 12.19 AI1 scalato a AI1 min 12.20 AI1 scalato a AI1 max L'ingresso di default per il riferimento di velocità è l'ingresso analogico AI1. (Si controlla con i parametri del gruppo 22.) I parametri 12.17 e 12.18 impostano i limiti inferiore e superiore del segnale di ingresso analogico. I parametri di adattamento con fattore di scala 12.19 e 12.20 definiscono i livelli dei segnali interni che corrispondono a questi limiti, nel modo seguente: EN AI (scalato) DE 12.20 ES AI (mA/V) 12.17 12.18 FI FR 12.19 I parametri corrispondenti per l'ingresso analogico AI2 sono 12.27…12.30. IT IT RU SV 78 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 13.12 Sorgente AO1 13.17 Min sorgente AO1 13.18 Max sorgente AO1 13.19 Usc AO1 a min sorg AI1 13.20 Usc AO1 a max sorg AI1 Il parametro 13.12 seleziona la sorgente per l'uscita analogica AO1 (di default, la velocità del motore in rpm). I parametri 13.17 e 13.18 impostano i valori minimo e massimo del segnale sorgente che corrispondono ai valori effettivi dell'uscita analogica definiti dai parametri 13.19 e 13.20. Segnale sorgente 13.18 EN DE AO (mA) 13.19 ES 13.20 FI 13.17 FR IT IT RU SV 46.10 Adattam velocità 23.11 Selezione set rampe 23.12 Tempo accelerazione 1 23.13 Tempo decelerazione 1 23.14 Tempo accelerazione 2 23.15 Tempo decelerazione 2 L'utente può definire due diversi set di rampe di accelerazione/decelerazione. La sorgente che determina il passaggio dall'uno all'altro set si seleziona con il parametro 23.11. Ogni set di tempi di accelerazione/decelerazione nei parametri 23.12…23.15 esprime il tempo richiesto dal convertitore per accelerare o decelerare tra la velocità 0 e la velocità scalata (parametro 46.10). Velocità 46.10 Acc. Dec. 23.12 23.14 23.13 23.15 0 Tempo Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario 79 30.11 Velocità minima 30.12 Velocità massima 30.17 Corrente massima 30.19 Coppia minima 30.20 Coppia massima Verificare e, se necessario, impostare i limiti di velocità motore, corrente e coppia. Avviare il convertitore con un riferimento di velocità positivo (avanti): • Dal pannello di controllo (controllo locale): nella vista Home, premere (Opzioni), selezionare Riferimento, regolare il riferimento utilizzando i tasti , , e , premere Salva e premere il pulsante Start. • Tramite I/O: in modalità di controllo remoto, regolare l'ingresso analogico AI1 (riferimento), commutare l'ingresso digitale DI2 su 0 (avanti) e commutare l'ingresso digitale DI1 su 1 (marcia). EN DE ES FI FR IT IT RU SV 80 Guida rapida all'avviamento dei convertitori ACS880 con Programma di controllo primario EN DE ES FI FR IT IT RU SV Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 81 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma Inleiding EN Deze gids beschrijft de basis opstartcyclus van een ACS880 omvormer voorzien van het primaire besturingsprogramma. Complete documentatie van de firmware van de omvormer is te vinden in de Firmwarehandleiding (zie de lijst met handleidingen aan de binnenkant van het voorblad). DE In deze gids wordt de omvormer ingesteld via het ACS-AP-I bedieningspaneel. De opstartcyclus kan ook uitgevoerd worden met de Drive composer PC tool. FI Vóór het starten ES FR IT Zorg er voor dat de omvormer mechanisch en elektrisch geïnstalleerd is zoals beschreven in de betreffende Beknopte installatiegids en/of Hardwarehandleiding. NL Veiligheid NL WAARSCHUWING! Alle werkzaamheden wat betreft elektrische installatie en onderhoud van de omvormer mogen alleen door gekwalificeerde elektriciens uitgevoerd worden. Voer nooit werkzaamheden uit aan de omvormer, het remchoppercircuit, de motorkabel of de motor wanneer de omvormer onder spanning staat. Verzeker u er altijd van dat er geen spanning aanwezig is door meting. SV 82 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma Opstarten Veiligheid Het opstarten mag uitsluitend worden uitgevoerd door een gekwalificeerd elektricien. Gedurende het opstarten moeten de veiligheidsinstructies worden opgevolgd. Zie de veiligheidsinstructies op de eerste pagina's van de betreffende Hardwarehandleiding. Controleer de installatie. Zie de installatiechecklist in de betreffende Hardwarehandleiding. EN DE ES Controleer of het starten van de motor geen gevaar oplevert. Ontkoppel de aangedreven machine als • er een risico van schade bestaat bij een eventueel verkeerde draairichting of • een normale ID-run vereist is tijdens het opstarten van de omvormer, wanneer het lastkoppel hoger is dan 20% of de machine niet bestand is tegen de nominale koppelpiek tijdens de ID-run. 1 – Inschakelen, instelling van datum en tijd FI FR IT NL NL SV Schakel de voeding van de omvormer in. Opmerking: Het is normaal dat er waarschuwingsberichten verschijnen op diverse punten in het opstartproces. Om een bericht te verbergen en het opstartproces te hervatten, drukt u op . Verberg nu eventuele waarschuwingen om naar het Home-scherm te gaan (hiernaast getoond). Afstand Gebruikte motortoerental rpm Motorstroom A Motor koppel % % De twee commando's onder aan het display (in dit geval, Opties en Menu), tonen de functies van de twee softkeys en die zich onder het display bevinden. De commando's die aan de softkeys toegewezen zijn variëren afhankelijk van de context. Opties In het Home-scherm, drukt u op (Menu). Afstand Menu Het hoofdmenu (rechts) verschijnt. 0.0 rpm 12:34 0.00 0.00 0.0 Menu 0.0 rpm Parameters Assistenten Energie rendement Logboek Afsluiten 12:34 Selecteren Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 83 Markeer Instellingen in het menu via en druk op (Selecteren). en Afstand Instellingen Taal Datum & tijd Teksten bewerken Display-instellingen Terug In het menu Instellingen markeert u Datum & tijd (als dit nog niet gemarkeerd is) en drukt u op (Selecteren). In het menu Datum & tijd markeert u Datum (als dit nog niet gemarkeerd is) en drukt u op (Selecteren). 12:34 0.0 rpm Selecteren Afstand 0.0 rpm Datum & tijd Datum 01.01.1980 Tijd 12:34:56 Toon datum als dag.maand.jaar Toon tijd als 24-uur Zomer-/wintertijd EU Volgende omzetting naar zomertijd 28.03. Terug 12:35 Bewerken Afstand Datum 0.0 rpm EN DE ES FI FR IT NL Dag Maand Jaar 01 .01.1980 Dinsdag Annuleren 12:35 Opslaan NL SV 84 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma Stel de juiste datum in: • Gebruik en om de cursor naar links en rechts te verplaatsen. • Gebruik en om de waarde te wijzigen. • Druk op (Opslaan) om de nieuwe instelling te accepteren. Controleer/ pas alle overige instellingen aan in het menu Datum & tijd. EN DE ES FI FR IT De instelling van Toon klok bepaalt of de tijd continu op de onderste regel van het display getoond wordt. 0.0 rpm Gebruikte motortoerental rpm Motorstroom A Motor koppel % % Opties 0.00 0.00 0.0 12:35 Menu Nadat u de instellingen aangepast hebt, drukt u herhaaldelijk op (Terug of Afsluiten) totdat het Home-scherm (rechts) verschijnt. 2 – Instelling van voedingsspanning en motorgegevens Schakel over op lokale besturing om er zeker van te zijn dat externe besturing geblokkeerd is door op de Loc/Rem toets te drukken. Lokale besturing wordt aangegeven met de tekst “Lokaal” op de bovenste regel. NL Lokaal 0.0 rpm Gebruikte motortoerental rpm Motorstroom A Motor koppel % % NL SV Afstand Opties Open het hoofdmenu door op te drukken. (Menu) 12:36 Lokaal Menu 0.00 0.00 0.0 Menu 0.0 rpm Parameters Assistenten Energie rendement Logboek Afsluiten 12:36 Selecteren Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 85 Markeer Parameters en druk op (Selecteren). Lokaal Parameters Favorieten Naar functie Complete lijst Gewijzigd Terug Markeer Complete lijst via en en druk op (Selecteren). Er wordt een lijst met parametergroepen getoond. 0.0 rpm 12:36 Selecteren Lokaal 0.0 rpm Complete lijst 01 Actuele waarden 03 Ingang referenties 04 Waarschuwingen en fouten 05 Diagnostiek 06 Control- en status woorden 07 Systeem info Terug 12:36 Selecteren Markeer parametergroep 95 HW configuratie en druk op (Selecteren). Lokaal 0.0 rpm 95 HW configuratie Merk op dat de lijst in beide richtingen doorloopt, tussen de groepen 99 en 01. In dit 95.01 Voedingsspanning Niet gegeven 95.02 Adaptieve spanningslimieten Blokkeren geval is het sneller om te gebruiken om groep 95 in de lijst te lokaliseren. 95.04 Stuurkaart voeding Interne 24V Nadat een groep gekozen is, wordt een lijst met parameters binnen de groep getoond. DE ES FI FR IT NL NL SV Terug Markeer parameter 95.01 Voedingsspanning (indien nog niet gemarkeerd) en druk op (Bewerken). De beschikbare parameterinstellingen worden weergegeven. EN 12:36 Lokaal 95.01 Voedingsspanning [0] Niet gegeven [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Annuleren 12:36 Bewerken 0.0 rpm Opslaan 86 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma Markeer de juiste instelling uit de lijst en druk op (Opslaan). Lokaal 0.0 rpm 95 HW configuratie 95.01 Voedingsspanning 380…415 V 95.02 Adaptieve spanningslimieten Blokkeren 95.04 Stuurkaart voeding Interne 24V Terug 12:36 Bewerken EN Druk op (Terug) om de lijst met parametergroepen weer te tonen. Selecteer parametergroep 99 Motorgegevens, en stel parameter 99.03 Motor type in. DE Stel parameter 99.04 Motor besturing modus in. DTC = Direct torque control; Scalar ES FI FR IT DTC voldoet in de meeste gevallen. Scalarmodus wordt aanbevolen indien • de nominale motorstroom minder is dan 1/6 van de nominale stroom van de omvormer, • de omvormer voor testdoeleinden zonder aangesloten motor wordt gebruikt, of • de omvormer meerdere motoren bestuurt en het aantal aangesloten motoren variabel is. Raadpleeg het motortypeplaatje voor de volgende parameterinstellingen. Voer de waarden, indien mogelijk exact hetzelfde in als op het motortypeplaatje. Voorbeeld van een typeplaatje van een (asynchrone) inductiemotor: NL NL Voorbeeld van een typeplaatje van een permanentmagneetmotor: ABB Motors 3 motor SV V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 2GBJ285220-ADA405445477 6316/C3 6316/C3 180 IEC 34-1 99.06 Nominale motorstroom Het toegestane bereik is • in DTC modus: 1/6 × IHd … 2 × IHd van de omvormer • in Scalar modus: 0 … 2 × IHd Opmerking: Bij numerieke parameterwaarden: • Gebruik en om de waarde van een cijfer te veranderen. • Gebruik • Druk op IP 55 V en om de cursor naar links en rechts te verplaatsen. (Opslaan) om de waarde te bevestigen. 630kg IEC 34-1 t E/s Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 87 Voer de volgende parameterinstellingen op dezelfde manier uit. 99.07 Nominale motorspanning Het toegestane bereik is 1/6 × UN … 2 × UN van de omvormer. Bij permanentmagneetmotoren is de nominale spanning de BackEMF spanning bij nominaal toerental. Als de spanning gegeven is in volt/rpm (bijv. 60 V per 1000 rpm), dan is de spanning bij een nominaal toerental van 3000 rpm, 3 × 60 V = 180 V. Merk op dat nominale spanning niet hetzelfde is als equivalente DC motorspanning (EDCM) die door sommige fabrikanten opgegeven wordt. De nominale spanning kan berekend worden door de EDCM spanning te delen door 1,7 (of vierkantswortel uit 3). 99.08 Nominale motorfrequentie Bij permanentmagneetmotoren kan de nominale frequentie, indien deze niet op het typeplaatje gegeven is, berekend worden via de volgende formule: f = n × p / 60 waarbij n = nominaal motortoerental, p = aantal poolparen. 99.09 Nominaal motortoerental EN DE ES 99.10 Nominaal motorvermogen FI 99.11 Nominale motor cosfii 99.12 Nominaal motorkoppel Deze waarden zijn niet vereist, maar ze kunnen ingevoerd worden om de regelnauwkeurigheid te verbeteren. Indien onbekend, laat dan op 0 staan. 99.13 Identificatierun verzoek Deze parameter kiest de modus van de identificatierun (alleen in DTCmotorbesturingsmodus). WAARSCHUWING! De identificatierun-modi gemarkeerd met * zullen de motor in voorwaartse richting doen draaien (zie hieronder voor details). Zorg er voor dat de het veilig is om de motor te laten draaien voordat u een van deze modi kiest. *Normale modus dient gekozen te worden wanneer mogelijk. De aangedreven apparatuur moet ontkoppeld zijn van de motor indien • het lastkoppel hoger is dan 20%, of • de machines niet bestand zijn tegen de nominale koppelpiek tijdens de identificatierun. *Gereduceerde modus dient gekozen te worden als de mechanische verliezen hoger zijn dan 20%, d.w.z. de last kan niet worden ontkoppeld, of volledige flux is vereist om de motorrem open te houden bijv. bij conische motoren). De Stilstand modus dient gekozen te worden als noch de *Normale, noch *Gereduceerde modus gebruikt kan worden. Opmerkingen: • Deze modus kan niet gebruikt worden bij een permanentmagneetmotor als het lastkoppel hoger is dan 20% van het nominale koppel. • De mechanische rem wordt niet geopend door de logica voor de identificatierun. Zorg er voor dat de Safe Torque Off- en noodstopcircuits (indien aanwezig) gesloten zijn. Start de identificatierun door op de knop (Start) te drukken. Een waarschuwing zal aangeven dat de identificatierun bezig is. FR IT NL NL SV 88 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma Controleer dat de motor in de juiste richting draait (hieronder wordt voorwaartse richting getoond). De identificatierun is voltooid wanneer de omvormer stopt en de waarde van parameter 99.13 terugkeert naar “Nee”. Als de motor in de verkeerde richting draaide, corrigeer dan de motorbekabeling of pas parameter 99.16 Fasevolgorde aan. EN DE ES FI 3 – Instellen van de stuursignalen Controleer de posities van de jumpers J1 en J2 op de besturingsunit van de omvormer. Deze jumpers bepalen of de analoge ingangen AI1 en AI2 stroom- of spanningsingangen zijn. Controleer /pas de volgende parameters aan. 20.01 Ext1 opdrachten Standaard start/stopt de omvormer volgens de status van digitale ingang DI1 (0 = Stop, 1 = Start). DI2 bepaalt de draairichting (0 = Voorwaarts, 1 = Achterwaarts). FR Als andere bronnen vereist zijn, verander dan de waarde dienovereenkomstig. De bronnen In1…In3 worden bepaald door parameters 20.03…20.05. IT 12.15 AI1 eenheid selectie Stel dit in op mA of V in overeenstemming met de instelling van jumper J1. NL NL SV Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 89 12.17 AI1 min 12.18 AI1 max 12.19 AI1 geschaald bij AI1 min 12.20 AI1 geschaald bij AI1 max De standaard ingang voor toerentalreferentie is analoge ingang AI1. (Dit wordt bestuurd door de parameters in groep 22.) Parameters 12.17 en 12.18 stellen de onder- en bovenlimieten van het analoge ingangssignaal in. Schalingsparameters 12.19 en 12.20 bepalen als volgt de interne signaalniveaus die overeenkomen met deze limieten: AI (geschaald) 12.20 EN AI (mA/V) 12.17 DE ES 12.18 FI 12.19 FR De corresponderende parameters voor analoge ingang AI2 zijn 12.27…12.30. 13.12 AO1 bron 13.17 AO1 bron min 13.18 AO1 bron max 13.19 AO1 uit bij AI1 bron min 13.20 AO1 uit bij AI1 bron max IT NL NL Parameter 13.12 kiest de bron voor analoge uitgang AO1 (standaard, motortoerental in rpm). Parameters 13.17 en 13.18 stellen lage en hoge waarden van bronsignalen in die corresponderen met de actuele analoge uitgangswaarden gedefinieerd door parameters 13.19 en 13.20. Bronsignaal 13.18 AO (mA) 13.19 13.20 13.17 SV 90 Beknopte opstartgids voor ACS880 omvormers met primair besturingsprogramma 46.10 Toerentalschaling 23.11 Hellingset selectie 23.12 Acceleratietijd 1 23.13 Deceleratietijd 1 23.14 Acceleratietijd 2 23.15 Deceleratietijd 2 U kunt twee verschillende sets acceleratie-/deceleratiehellingen definiëren. De bron die tussen de twee sets schakelt wordt gekozen door parameter 23.11. Elke acceleratie-/deceleratietijd die in parameters 23.12…23.15 ingesteld wordt, verwijst naar de tijd die de omvormer nodig heeft om te accelereren of decelereren tussen 0 en het geschaalde toerental (parameter 46.10). Toerental EN 46.10 DE ES Acc. Dec. 23.12 23.14 23.13 23.15 FI 0 FR IT NL NL SV Tijd 30.11 Minimum toerental 30.12 Maximum toerental 30.17 Maximum stroom 30.19 Minimum koppel 30.20 Maximum koppel Controleer de limieten voor motortoerental, -stroom en -koppel, en stel ze in, indien nodig. Start de omvormer met een positieve (voorwaartse) toerentalreferentie: • Vanaf het bedieningspaneel (Lokale besturing): Druk in het Home-scherm op (Opties), selecteer Referentie, pas de referentie aan via de toetsen , , , en , druk op Opslaan, en druk op de Start-knop. • Vanaf I/O: Pas, onder afstandsbediening, analoge ingang AI1 (referentie) aan, schakel digitale ingang DI2 naar 0 (voorwaarts), en schakel digitale ingang DI1 naar 1 (start). Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 91 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym PL DE Informacje o tej instrukcji ES W tej instrukcji opisano podstawową sekwencję uruchamiania przemiennika częstotliwości ACS880 wyposażonego w Standardowe Oprogramowanie Aplikacyjne. Pełna dokumentacja tego oprogramowania znajduje się w Podręczniku Standardowego Oprogramowania Aplikacyjnego (patrz lista podręczników na wewnętrznej stronie przedniej okładki). FI W tym podręczniku opisano konfigurację przemiennika częstotliwości wykonywaną za pomocą panelu sterowania ACS-AP-I. Proces uruchamiania można także przeprowadzić za pomocą narzędzia komputerowego Drive Composer. Przed rozpoczęciem Należy upewnić się, że instalacja mechaniczna i elektryczna przemiennika częstotliwości została przeprowadzona zgodnie z opisem zawartym w skróconej instrukcji montażu i/lub podręczniku użytkownika. Bezpieczeństwo OSTRZEŻENIE! Wszelkie elektryczne prace instalacyjne i konserwacyjne związane z przemiennikiem częstotliwości powinny być wykonywane tylko przez wykwalifikowanych elektryków. Nie należy wykonywać czynności serwisowych na przemienniku częstotliwości, układzie czopera hamowania, kablu silnikowym i silniku, gdy przemiennik jest podłączony do napięcia zasilania. Zawsze należy sprawdzać, czy w danym momencie przemiennik nie jest pod napięciem, wykonując odpowiedni pomiar. FR IT NL RU PL 92 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym Uruchamianie Bezpieczeństwo Uruchomienie może przeprowadzić tylko wykwalifikowany elektryk. Podczas procedury uruchamiania należy przestrzegać instrukcji bezpieczeństwa. Instrukcje bezpieczeństwa znajdują się na pierwszych stronach odpowiedniego podręcznika użytkownika. Sprawdzić instalację. Lista kontrolna instalacji znajduje się w odpowiednim podręczniku użytkownika. PL DE ES FI FR IT NL RU PL Sprawdzić, czy uruchomienie silnika nie spowoduje żadnego niebezpieczeństwa. Należy odłączyć napędzane urządzenie, jeśli: • istnieje ryzyko uszkodzenia spowodowanego przez niewłaściwy kierunek obrotów silnika lub • wymagane jest przeprowadzenie Normalnego Biegu Identyfikacyjnego silnika podczas uruchomienia przemiennika częstotliwości, gdy moment obciążenia jest wyższy niż 20% lub gdy maszyna nie wytrzyma chwilowego znamionowego momentu obrotowego podczas wykonywania Biegu Identyfikacyjnego. 1. Włączanie, daty i godziny Włączyć przemiennik częstotliwości. Uwaga: pojawianie się komunikatów ostrzegawczych w różnych momentach procesu uruchamiania jest normalne. Aby ukryć komunikat i wznowić proces uruchamiania, należy nacisnąć przycisk . Następnie należy ukryć wszystkie ostrzeżenia, aby włączyć widok główny Home (widoczny po prawej stronie). Remote 0.0 rpm Motor speed used rpm Motor current A Motor torque % % Options 12:34 0.00 0.00 0.0 Menu Dwa wskaźniki znajdujące się w dolnej części wyświetlacza (w tym przypadku Options — Opcje i Menu) odpowiadają funkcjom przycisków i . Te dwie funkcje przypisane do przycisków mogą być różne w zależności od kontekstu. W widoku głównym Home nacisnąć przycisk (Menu). Pojawi się menu główne (widoczne po prawej stronie). Remote Menu 0.0 rpm Parameters Assistants Energy efficiency Exit Event log 12:34 Select Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 93 Wybrać opcję Settings (Ustawienia) w menu, naciskając przyciski i ,a następnie nacisnąć przycisk (Select — Wybierz). W menu Settings (Ustawienia) wybrać opcję Date & time (Data i godzina), jeśli nie została jeszcze wybrana, i nacisnąć przycisk (Select — Wybierz). W menu Date & time (Data i godzina) wybrać opcję Date (Data), jeśli nie została jeszcze wybrana, i nacisnąć przycisk (Select — Wybierz). Remote Settings Language Date & time Edit texts Display settings 0.0 rpm Back Select 12:34 Remote 0.0 rpm Date & time Date 01.01.1980 Time 12:34:56 Show date as day.month.year Show time as 24-hour Daylight saving EU Next daylight saving start 28.03. Back 12:35 Edit Remote Date 0.0 rpm DE ES FI FR IT NL Day Month Year RU 01 .01.1980 PL Tuesday Cancel PL 12:35 Save 94 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym Ustawić prawidłową datę: • Za pomocą przycisków i przesunąć kursor w lewo lub prawo. PL DE ES FI FR IT NL • Za pomocą przycisków i zmienić wartość. • Nacisnąć przycisk (Save — Zapisz), aby zaakceptować nowe ustawienie. Sprawdzić/dostosować wszystkie pozostałe ustawienia w menu Date & time (Data i godzina). Ustawienie Show clock (Pokaż zegar) określa, czy godzina ma być widoczna cały czas w dolnej części wyświetlacza. Po skonfigurowaniu tych ustawień nacisnąć przycisk (Back lub Exit) (Wstecz lub Wyjdź) wielokrotnie, aż do pojawienia się widoku głównego Home (widocznego po prawej stronie). Remote 0.0 rpm Motor speed used rpm Motor current A Motor torque % % Options 12:35 0.00 0.00 0.0 Menu 2. Ustawienia napięcia zasilania i danych silnika Przełączyć się na sterowanie lokalne, aby upewnić się, że sterowanie zewnętrzne jest wyłączone, naciskając przycisk Loc/Rem . Sterowanie lokalne wskazuje tekst „Local” w górnym lewym rogu wyświetlacza. RU Local 0.0 rpm Motor speed used rpm Motor current A Motor torque % % PL Options Otworzyć menu główne, naciskając przycisk (Menu). 12:36 Local Menu 0.00 0.00 0.0 Menu 0.0 rpm Parameters Assistants Energy efficiency Exit Event log 12:36 Select Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 95 Wybrać opcję Parameters (Parametry) i nacisnąć przycisk (Select — Wybierz). Local Parameters Favorites By function Complete list Modified Back Wybrać opcję Complete list (Cała lista), naciskając przyciski i , a następnie nacisnąć przycisk (Select — Wybierz). Pojawi się lista grup parametrów. Wybrać grupę parametrów 95 HW configuration (95 Konfiguracja sprzętowa) i nacisnąć przycisk (Select — Wybierz). Należy pamiętać, że lista parametrów jest zapętlona i możliwe jest przejście między grupami 99 a 01 w obu kierunkach. W tym przypadku pozycję 95 można znaleźć szybciej, naciskając przycisk . Po wybraniu danej grupy pojawi się lista zawartych w niej parametrów. Wybrać parametr 95.01 Supply voltage (napięcie zasilania), jeśli jeszcze nie został wybrany, i nacisnąć przycisk (Edit — Edycja). Pojawi się lista dostępnych ustawień parametru. 0.0 rpm 12:36 Local Complete list 01 Actual values 03 Input references 04 Warnings and faults 05 Diagnostics 06 Control and status words 07 System info Back 12:36 Select 0.0 rpm PL DE ES FI Select Local 0.0 rpm 95 HW configuration 95.01 Supply voltage Not given 95.02 Adaptive voltage limits Disable 95.04 Control board supply Internal 24V FR IT NL RU PL Back 12:36 Local 95.01 Supply voltage [0] Not given [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Cancel 12:36 Edit 0.0 rpm Save 96 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym Wybrać poprawne ustawienie z listy i nacisnąć przycisk (Save — Zapisz). Local 0.0 rpm 95 HW configuration 95.01 Supply voltage 380…415 V 95.02 Adaptive voltage limits Disable 95.04 Control board supply Internal 24V Back PL 12:36 Edit Nacisnąć przycisk (Back — Wstecz), aby ponownie wyświetlić listę grup parametrów. Wybrać grupę parametrów 99 Motor data (Dane silnika) i ustawić parametr 99.03 Motor type (Typ silnika). DE Ustawić parametr 99.04 Motor ctrl mode (Tryb sterowania silnikiem). DTC = Direct torque control (Bezpośrednie sterowanie momentem); Scalar (Skalarne) ES Tryb DTC jest najczęściej odpowiedni. Tryb sterowania skalarnego jest zalecany, jeśli: • prąd znamionowy silnika nie jest większy niż 1/6 prądu znamionowego przemiennika częstotliwości, • przemiennik częstotliwości jest używany w celach testowych bez podłączonego silnika, • przemiennik częstotliwości steruje wieloma silnikami, a liczba podłączonych silników jest zmienna. FI FR IT NL RU PL Tabliczka znamionowa silnika przedstawia dane techniczne silnika, które należy wpisać do odpowiednich parametrów. Należy wprowadzić wartości dokładnie takie jakie przedstawia tabliczka znamionowa silnika. Przykładowa tabliczka znamionowa silnika indukcyjnego (asynchronicznego): Przykładowa tabliczka znamionowa silnika synchronicznego z magnesami trwałymi: ABB Motors 3 motor V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 97 99.06 Motor nominal current (Prąd znamionowy silnika) Dozwolony zakres wynosi: • w trybie DTC: 1/6 × IHd … 2 × IHd przemiennika częstotliwości • w trybie skalarnym: 0 … 2 × IHd Uwaga: w przypadku numerycznych wartości znamionowych: • Za pomocą przycisków • Za pomocą przycisków • Nacisnąć przycisk i i zmienić wartość liczbową. przesunąć kursor w lewo lub prawo. (Save — Zapisz), aby zapisać nowo wprowadzoną wartość. Wprowadzić następujące ustawienia parametru w ten sam sposób. 99.07 Motor nominal voltage (Napięcie znamionowe silnika) Dozwolony zakres wynosi 1/6 × UN … 2 × UN silnika. W przypadku silnika synchronicznego z magnesami trwałymi napięcie znamionowe jest napięciem BackEMF przy prędkości znamionowej. Jeśli napięcie jest podane w jednostce V/obr./min (np. 60 V na 1000 obr./min), napięcie przy prędkości znamionowej 3000 obr./min wynosi 3 × 60 V = 180 V. Należy pamiętać, że napięcie znamionowe nie jest tym samym co równoważne napięcie silnika DC (EDCM) podawane przez niektórych producentów. Napięcie znamionowe można obliczyć, dzieląc napięcie EDCM przez 1,7 (pierwiastek kwadratowy z 3). 99.08 Motor nominal frequency (Znamionowa częstotliwość silnika) W przypadku silnika synchronicznego z magnesami trwałymi, jeśli częstotliwość znamionowa nie jest podana na tabliczce znamionowej, można ją obliczyć za pomocą tego wzoru: f = n × p / 60 gdzie n = znamionowa prędkość silnika, p = liczba par biegunów. 99.09 Motor nominal speed (Znamionowa prędkość silnika) PL DE ES FI FR IT NL RU 99.10 Motor nominal power (Znamionowa moc silnika) PL 99.11 Motor nominal cosfii (Znamionowa wartość cosinus fi silnika) 99.12 Motor nominal torque (Znamionowy moment obrotowy silnika) Te wartości nie są wymagane, ale można je wprowadzić, aby zwiększyć dokładność sterowania. Jeśli nie są znane, należy zostawić wartość 0. 98 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 99.13 Identification run request (Żądanie biegu identyfikacyjnego) Ten parametr określa tryb biegu identyfikacyjnego (tylko w trybie DTC sterowania silnikiem). OSTRZEŻENIE! Tryby biegu identyfikacyjnych oznaczonych symbolem * powodują uruchomienie silnika w kierunku do przodu (patrz szczegóły poniżej). Przed wybraniem któregokolwiek z tych trybów, należy się upewnić, że uruchomienie silnika jest bezpieczne. ES Tryb *Normal (Normalny) należy wybierać zawsze, gdy jest to możliwe. Sterowane urządzenie musi zostać odłączone od silnika, jeśli: • moment obciążenia jest wyższy niż 20% lub • urządzenie nie wytrzyma chwilowego znamionowego momentu obrotowego podczas wykonywania biegu identyfikacyjnego. *Tryb-Reduced ( Zredukowany) należy wybrać, jeśli straty mechaniczne są wyższe niż 20%, tzn. nie można odłączyć obciążenia lub wymagany jest pełny strumień, aby hamulec silnika pozostawał otwarty (np. w przypadku silników stożkowych). Tryb Standstill (Nieruchomy) należy wybrać, jeśli nie można użyć trybu *Normal (Normalny) ani *Reduced (Zredukowany). Uwagi: FI • Tego trybu nie można używać z silnikiem synchronicznym z magnesami trwałymi, jeśli moment obciążenia jest wyższy niż 20% wartości znamionowej. FR • Hamulec mechaniczny nie jest otwierany przez układ sterujący na potrzeby biegu identyfikacyjnego. IT Upewnić się, że obwody bezpiecznego wyłączania momentu i zatrzymywania awaryjnego (jeśli są obecne) są zamknięte. NL Uruchomić bieg identyfikacyjny, naciskając przycisk (Start). RU Sprawdzić, czy silnik obraca się we właściwym kierunku (do przodu, jak pokazano poniżej). PL DE Pojawi się ostrzeżenie, że bieg identyfikacyjny trwa. PL Bieg identyfikacyjny zakończy się, gdy silnik się zatrzyma, a wartość parametru 99.13 zmieni się z powrotem na „No” (Nie). Jeśli silnik obracał się w niewłaściwą stronę, należy poprawić okablowanie silnika lub ustawić parametr 99.16 Phase order (Kolejność faz). 3. Ustawienia sygnału sterowania Sprawdzić pozycję zworek J1 i J2 na jednostce sterującej przemiennika częstotliwości. Zworki te określają, czy wejścia analogowe AI1 i AI2 pracują w trybie prądowym, czy napięciowym. Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 99 Sprawdzić/dostosować następujące parametry. 20.01 Ext1 commands (Polecenia Zew1) Domyślnie przemiennik częstotliwości włącza się lub wyłącza w zależności od stanu na wejściu cyfrowym DI1 (0 = Stop, 1 = Start). Wejście DI2 określa kierunek obrotów (0 = do przodu , 1 = do tyłu). Jeśli są wymagane inne źródła sygnałów sterowania, należy odpowiednio skonfigurować parametry od 20.03 do 20.05 (źródła od In1 do In3). 12.15 AI1 unit selection (Wybór jednostki AI1) Wybrać wartość mA lub V odpowiadającą ustawieniu zworki J1. 12.17 AI1 min (wartość min. dla AI1) 12.18 AI1 max (wartość maks. dla AI1) 12.19 AI1 scaled at AI1 min (AI1 skalowane przy min. wartości AI1) 12.20 AI1 scaled at AI1 max (AI1 skalowane przy maks. wartości AI1) Domyślnym wejściem do podłączenia wartości zadanej prędkości jest wejście analogowe AI1. (Jest ono skonfigurowane w parametrach w grupie 22). Parametry 12.17 i 12.18 określają górne i dolne wartości limitów wejściowych sygnałów analogowych. Skalowanie parametrów 12.19 i 12.20 określa poziomy sygnałów wewnętrznych odpowiadające tym limitom w następujący sposób: PL DE ES FI AI (skalowane) FR 12.20 IT AI (mA/V) 12.17 NL 12.18 RU 12.19 Parametry od 12.27 do 12.30 odpowiadają analogicznie konfiguracji wejścia analogowego AI2 . PL 100 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym PL 13.12 AO1 source (Źródło AO1) 13.17 AO1 source min (Min. wartość AO1) 13.18 AO1 source max (Maks. wartość AO1) 13.19 AO1 out at AO1 src min (Wartość na wyjściu A01 przy minimalnej wartości źródła A01) 13.20 AO1 out at AO1 src max (Wartość na wyjściu A01 przy maksymalnej wartości źródła A01) Parametr 13.12 określa źródło dla wyjścia analogowego AO1 (domyślnie: prędkość silnika w obr./min). Parametry 13.17 i 13.18 określają górne i dolne wartości sygnałów źródłowych odpowiadające rzeczywistym wartościom wyjściowych sygnałów analogowych określonym przez parametry 13.19 i 13.20. Sygnał źródłowy DE 13.18 ES AO (mA) 13.19 FI 13.20 FR 13.17 IT NL RU PL 46.10 Speed scaling (Skalowanie prędkości) 23.11 Ramp set selection (Wybór pary czasów przyspieszania i hamowania) 23.12 Acceleration time 1 (Czas przyspieszania 1) 23.13 Deceleration time 1 (Czas hamowania 1) 23.14 Acceleration time 2 (Czas przyspieszania 2) 23.15 Deceleration time 2 (Czas hamowania 2) Można określić dwa różne zestawy ramp czasów przyspieszania/hamowania. Źródło przełączania między dwoma zestawami wybiera się za pomocą parametru 23.11. Każdy czas przyspieszania/hamowania ustawiony w parametrach od 23.12 do 23.15 odnosi się do czasu, jaki potrzebuje przemiennik częstotliwości na przyspieszenie lub wyhamowanie (między wartością 0 a prędkością skalowania, parametr 46.10). Prędkość 46.10 Przysp. Ham.. 23.12 23.14 23.13 23.15 0 Czas Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym 101 30.11 Minimum speed (Prędkość min.) 30.12 Maximum speed (Prędkość maks.) 30.17 Maximum current (Prąd maks.) 30.19 Minimum torque (Moment min.) 30.20 Maximum torque (Moment maks.) Sprawdzić i w razie konieczności ustawić limity prędkości silnika, prądu i momentu obrotowego. Uruchomić przemiennik częstotliwości z dodatnią wartością odniesienia prędkości (do przodu): • W panelu sterowania (Local control — Sterowanie lokalne): w widoku głównym Home nacisnąć przycisk (Options — Opcje), wybrać opcję Reference (Zadawanie), ustawić wartość zadaną za pomocą przycisków , , i , nacisnąć przycisk Save (Zapisz), a następnie nacisnąć przycisk Start. • W sekcji I/O (We/Wy): w trybie Remote control (Sterowanie zdalne) ustawić wejście analogowe AI1 (odniesienie), przełączyć wejście cyfrowe DI2 na wartość 0 (do przodu) i przełączyć wejście cyfrowe DI1 na wartość 1 (start). PL DE ES FI FR IT NL RU PL 102 Skrócona instrukcja uruchamiania przemienników częstotliwości ACS880 ze Standardowym Oprogramowaniem Aplikacyjnym PL DE ES FI FR IT NL RU PL Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 103 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário Sobre este guia Este guia descreve a sequência básica de arranque de um acionamento ACS880 equipado com o programa de controlo primário. Está disponível documentação completa do firmware do acionamento no Manual de firmware (consulte a lista de manuais no interior da capa frontal). PT DE Neste guia, o acionamento é configurado usando a consola de programação ACS-AP-I. A sequência de arranque também pode ser efetuada usando a ferramenta para PC, Drive composer. ES Antes de arrancar FR Certifique-se de que o acionamento foi mecânica e eletricamente instalado, conforme descrito no Guia rápido de instalação e/ou no Manual de hardware apropriado. IT Segurança RU AVISO!Todas as tarefas de instalação elétrica e de manutenção efetuadas no acionamento devem ser realizadas por eletricistas qualificados. Nunca trabalhe no acionamento, no circuito do chopper de travagem, no cabo do motor ou no motor quando a alimentação está aplicada ao acionamento. Efetue sempre uma medição para verificar que não existe tensão presente. FI NL SV PT 104 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário Arranque Segurança O arranque só pode ser executado por um eletricista qualificado. As instruções de segurança devem ser seguidas durante o procedimento de arranque. Veja as instruções de segurança nas primeiras páginas do Manual de hardware apropriado. Verificar a instalação. Consulte a lista de verificação da instalação no Manual de hardware apropriado. PT DE ES Verifique se o arranque do motor não provoca nenhum perigo. Desacoplar a máquina acionada se: • existir risco de danos no caso de um sentido de rotação incorreto, ou • um ID run normal durante o arranque do acionamento, quando o binário de carga é superior a 20% ou a maquinaria não suportar o binário nominal transitório durante o ID run. 1 – Configurações de ligação, data e hora FI FR IT Arranque do acionamento. Nota: É normal que apareçam mensagens de aviso em diversos pontos ao longo do processo de arranque. Para ocultar uma mensagem e para retomar o processo de arranque, pressione . NL Ocultar todos os avisos para aceder à vista Início (apresentada no lado direito). RU Os dois comandos na parte inferior do ecrã (neste caso, Opções e Menu), apresentam as funções das duas softkeys e estão localizadas por baixo do ecrã. Os comandos atribuídos às softkeys variam dependendo do contexto. SV PT Na vista Início , prima (Menu). O Menu principal (direita) aparece. Remoto 0.0 rpm Velocidade motor usada rpm Corrente motor A Binário motor % % Opções 0.00 0.00 0.0 12:34 Menu Remoto Menu 0.0 rpm Parâmetros Assistentes Eficiência energética Registo de eventos Sair 12:34 Selecionar Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 105 Assinalar Ajustes no menu usando e premindo (Selecionar). e Remoto Ajustes Idioma Data & hora Editar textos Ajustes ecrã Voltar No menu Ajustes, assinale Data & hora (se não estiver assinalado) e prima (Selecionar). 0.0 rpm 12:34 Selecionar Remoto 0.0 rpm Data & hora Data 01.01.1980 Tempo 12:34:56 Apresentar data como dia.mês.ano Apresentar hora como 24-horas Poupança diurna EU Próximo início poupança diurna 28.03. Voltar 12:35 Editar PT DE ES FI FR IT No menu Data & hora, assinale Data (se não estiver assinalada) e prima (Selecionar). Remoto Data 0.0 rpm Dia Mês RU Ano 01 .01.1980 Terça Cancelar 12:35 NL SV PT Guardar 106 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário Definir a data correta: • Use e para mover o cursor para a esquerda e direita. • Use e para ajustar o valor. • Pressione (Guardar) para aceitar novo ajuste. Verifique/ajuste todas as configurações no menu Data & hora. O ajuste Mostrar relógio determina se a hora é sempre apresentada na parte inferior do ecrã. PT DE ES FI FR Remoto Velocidade motor usada rpm Corrente do motor A Binário motor % % Opções 0.00 0.00 0.0 12:35 Menu Após efetuar os ajustes, prima (Voltar ou Sair) repetidamente até reaparecer a vista Início (lado direito). 2 – Ajuste da tensão de alimentação e dados do motor Mude para controlo local para assegurar que o controlo externo é desativado pressionando a teclaTecla Loc/Rem . O controlo local é indicado pelo texto “Local” na parte superior da consola. IT Local 0.0 rpm Velocidade motor usada rpm Corrente do motor A Binário motor % % NL Opções RU 0.0 rpm Abra o Menu inicial premindo SV (Menu). 12:36 Local Menu 0.00 0.00 0.0 Menu 0.0 rpm Parâmetros PT Assistentes Eficiência energética Sair Assinale Parâmetros e pressione (Selecionar). Registo de eventos 12:36 Local Parâmetros Favoritos Por função Lista completa Modificados Voltar Selecionar 0.0 rpm 12:36 Selecionar Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 107 Assinale Lista completa usando e e prima (Selecionar). É apresentada uma lista completa de grupos de parâmetros. Local Lista cpl 0.0 rpm 01 Valores atuais 03 Referências entrada 04 Avisos e falhas 05 Diagnósticos 06 Palavras de controlo e estado 07 Info Sistema Voltar 12:36 Selecionar Assinale o grupo de parâmetros 95 Configuração HW e pressione (Selecionar). Note que a lista pode ser percorrida em ambos os sentidos entre os grupos 99 e 01. Neste caso, é mais rápido usar para localizar o grupo 95 na lista. Depois de selecionar um grupo, é apresentada a lista de parâmetros dentro do grupo. Local 95 Configuração HW Assinale o parâmetro 95.01 Tensão alimentação (se não estiver assinalado) e prima (Editar). Os ajustes dos parâmetros disponíveis são listados. Local 95.01 Tensão alimentação Assinale o ajuste correto na lista e prima (Guardar). 95.01 Tensão alimentação 0.0 rpm Não indicada 95.02 Limites tensão adaptativa 95.04 Aliment. carta controlo Desativar PT DE ES 24 V Interna FI Voltar 12:36 [0] Não indicada [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Cancelar 12:36 Local 0.0 rpm 12:36 FR IT NL RU SV Guardar 0.0 rpm 95 Configuração HW 95.01 Tensão alimentação 95.02 Lim tensão adaptativa 95.04 Alim. carta de controlo Voltar Editar 380…415 V Desativar 24 V Interna Editar Prima (Voltar) para apresentar novamente a lista dos grupos de parâmetros. Selecione o grupo de parâmetros 99 Dados motor, e ajuste o parâmetro 99.03 Tipo motor. PT 108 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário Ajuste o parâmetro 99.04 Modo ctrl motor. DTC = Controlo direto de binário; Escalar O DTC é apropriado para a maioria dos casos. O modo Escalar é recomendado se • a corrente nominal do motor for inferior a 1/6 da corrente nominal de saída do acionamento, • o acionamento for usado para testes sem nenhum motor ligado, ou • o acionamento controlar múltiplos motores e o número de motores ligados for variável. Consulte a chapa de características do motor para os ajustes de parâmetros seguintes. Sempre que possível, introduza os valores exatamente como apresentados na chapa de características do motor. PT Exemplo de uma chapa de características de um motor de indução (assíncrono): ABB Motors DE 3 motor ES FI FR IT NL Exemplo de uma chapa de características de um motor de ímanes permanentes: V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code t E/s 2GBJ285220-ADA405445477 6316/C3 180 6316/C3 630kg IEC 34-1 IEC 34-1 RU SV PT 99.06 Corrente nominal motor A gama permitida é • em modo DTC: 1/6 × IHd … 2 × IHd do acionamento • em modo Escalar: 0 … 2 × IHd Nota: Com valores de parâmetros numéricos: • Use e para alterar o valor de um dígito. • Use • Prima e para mover o cursor para a esquerda e direita. (Guardar) para inserir o valor. Ajuste os parâmetros seguintes da mesma forma. 99.07 Tensão nominal motor A gama permitida é 1/6 × UN … 2 × UN do acionamento. Com motores de ímanes permanentes, a tensão nominal é a tensão BackEMF à velocidade nominal. Se a tensão é apresentada em volts/rpm (ex. 60 V por 1000 rpm), a tensão à velocidade nominal de 3000 rpm é 3 × 60 V = 180 V. Note que a tensão nominal não é o mesma que a tensão do motor CC equivalente (EDCM) apresentada por alguns fabricantes. A tensão nominal pode ser calculada dividindo a tensão EDCM por 1.7 (ou raiz quadrada de 3). Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 109 99.08 Frequência nominal motor Com motores de ímanes permanentes, se a frequência nominal não for apresentada na chapa de características, pode ser calculada usando a seguinte fórmula: f = n × p / 60 onde n = velocidade nominal do motor, p = número de pares de pólos. 99.09 Velocidade nominal motor 99.10 Potência nominal motor 99.11 Cosfii nominal motor 99.12 Binário nominal motor Estes valores não são necessários, mas podem ser introduzidos para melhorar a precisão do controlo. Se não forem conhecidos, deixe em 0. PT 99.13 Pedido volta de identificação (ID Run) DE Este parâmetro seleciona o modo da volta de identificação (apenas modo DTC de controlo do motor). ES AVISO! Os modos da volta de identificação assinalados com * fazem o motor funcionar no sentido direto (veja detalhes abaixo). Certifique-se de que é seguro fazer funcionar o motor antes de selecionar qualquer um destes modos. FI O modo *Normal deve ser selecionado sempre que possível. A máquina acionada deve ser desacoplada do motor se • o binário de carga for superior a 20%, ou • a máquina não for capaz de suportar o binário nominal transitório durante o ID Run. *O modo Reduzido deve ser selecionado se as perdas mecânicas forem superiores a 20%, ie. a carga não puder ser desacoplada, ou se for necessário fluxo total para manter o travão do motor aberto (ex. com motores cónicos). O modo Imobilizado deve ser selecionado se nenhum dos modos *Normal ou *Reduzido puder ser usado. Notas: • Este modo não pode ser usado com um motor de ímanes permanentes se o binário de carga for superior a 20% do nominal. FR • O travão mecânico não é aberto pela lógica para o ID Run. PT Certifique-se que os circuitos da função de Binário seguro off e de paragem de emergência (se presentes) estão fechados. Arranque o motor pressionando o botão (Arrancar). Um aviso indica que a volta de identificação está em progresso. Verifique se o motor funciona no sentido correto (sentido direto apresentada abaixo). A volta de identificação está completa quando o acionamento para e o valor do parâmetro 99.13 reverte para “Não”. Se o motor funcionar no sentido errado, corrija a cablagem do motor ou ajuste o parâmetro 99.16 Ordem fases. IT NL RU SV 110 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 3 – Ajustes do sinal de controlo Verificar as posições dos jumpers J1 e J2 na unidade de controlo do acionamento. Estes jumpers determinam se as entradas analógicas EA1 e EA2 são corrente ou tensão. Verifique/ajuste os seguintes parâmetros. 20.01 Comandos Ext1 Por defeito, o acionamento arranca/para de acordo com o estado da entrada digital ED1 (0 = Parar, 1 = Arrancar). ED2 determina o sentido de rotação (0 = Direto, 1 = Inverso). Se forem necessárias outras fontes, altere o valor de acordo. As fontes In1…In3 são definidas pelos parâmetros 20.03…20.05. 12.15 EA1 seleção unidade PT Ajuste para mA ou V em correspondência com o ajuste do jumper J1. ES 12.17 EA1 Min 12.18 EA1 Max 12.19 EA1 escalada em EA1 Min 12.20 EA1 escalada em EA1 Max FI A entrada por defeito para a referência de velocidade é a entrada analógica EA1. (Isto é controlado pelos parâmetros no grupo 22.) DE FR Os parâmetros 12.17 e 12.18 ajustam os limites inferior e superior para o sinal da entrada analógica. A escala dos parâmetros 12.19 e 12.20 define os níveis do sinal interno que corresponde a estes limites, como se segue: IT EA (escalada) NL 12.20 RU EA (mA/V) 12.17 SV 12.18 PT 12.19 Os parâmetros correspondentes para a entrada analógica EA2 são 12.27…12.30. Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 111 13.12 SA1 Fonte 13.17 SA1 Fonte min 13.18 SA1 Fonte max 13.19 SA1 em EA1 src min 13.20 SA1 em EA1 src max O parâmetro 13.12 seleciona a fonte para a saída analógica SA1 (por defeito, velocidade do motor em rpm). Os parâmetros 13.17 e 13.18 ajustam os valores inferior e superior do sinal fonte correspondentes aos valores atuais da saída analógica definidos pelos parâmetros 13.19 e 13.20. Sinal fonte PT 13.18 DE SA (mA) 13.19 ES 13.20 FI FR 13.17 IT 46.10 Escala velocidade 23.11 Seleção rampa 23.12 Tempo aceleração 1 23.13 Tempo desaceleração 1 23.14 Tempo aceleração 2 23.15 Tempo desaceleração 2 É possível definir dois conjuntos diferentes de rampas de aceleração/desaceleração. A fonte que comuta entre os dois conjuntos é selecionada pelo parâmetro 23.11. Cada tempo de aceleração/desaceleração ajustado nos parâmetros 23.12…23.15 refere-se ao tempo que o acionamento demora a acelerar ou desacelerar entre 0 e a velocidade escalada (parâmetro 46.10). Velocidade 46.10 Acel. Desacel. 23.12 23.14 23.13 23.15 0 Tempo NL RU SV PT 112 Guia rápido de arranque para acionamentos ACS880 com programa de controlo primário 30.11 Velocidade mínima 30.12 Velocidade máxima 30.17 Corrente máxima 30.19 Binário mínimo 30.20 Binário máximo Verifique e ajuste se necessário, os limites para a velocidade, corrente e binário do motor. PT DE ES FI FR IT NL RU SV PT Arranque o acionamento com uma referência de velocidade positiva (direta): • Desde a consola de programação (controlo local): Na vista Início, prima (Opções), selecione Referência, ajuste a referência usando as teclas , , ,e , prima Guardar, e prima o botão Arrancar. • Desde E/S: Em controlo Remoto, ajuste a entrada analógica EA1 (referência), comute a entrada digital ED2 para 0 (direto) e a entrada digital ED1 para 1 (arrancar). Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 113 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления EN О настоящем руководстве DE В этом руководстве приведено описание базовой процедуры ввода в эксплуатацию привода ACS880, снабженного основной программой управления. Полная документация по микропрограммному обеспечению привода содержится в Руководстве по микропрограммному обеспечению (см перечень руководств на внутренней стороне передней обложки). ES В этом руководстве рассматривается настройка привода с панели управления ACS-AP-I. Процедуру ввода в эксплуатацию можно выполнить также с помощью компьютерного средства настройки приводов. Подготовительные операции Проверьте правильность механического и электрического монтажа привода по соответствующему Краткому руководству по монтажу и/или Руководству по монтажу и вводу в эксплуатацию. Техника безопасности ПРЕДУПРЕЖДЕНИЕ! Все работы по электрическому монтажу и техническому обслуживанию привода должны проводиться только квалифицированными электриками. Запрещается выполнять работы на приводе, в цепи тормозного прерывателя, на двигателе и его кабеле при включенном питании привода. Обязательно убедитесь в фактическом отсутствии напряжения путем его измерения. FI FR IT NL RU SV RU 114 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления Ввод в эксплуатацию Техника безопасности Ввод привода в эксплуатацию должен выполняться только квалифицированным электриком. При вводе привода в эксплуатацию необходимо соблюдать правила техники безопасности. Указания по технике безопасности приведены в начале соответствующего Руководства по монтажу и вводу в эксплуатацию. Проверьте правильность монтажа. См. контрольный перечень операций проверки монтажа в соответствующем Руководстве по монтажу и вводу в эксплуатацию. EN Убедитесь в том, что запуск двигателя не представляет опасности. Отсоедините ведомый механизм в следующих случаях: DE • существует опасность повреждения в случае неправильного направления вращения или ES FI FR • во время ввода привода в эксплуатацию требуется идентификационный прогон в режиме Normal (Нормальный) в связи с тем, что крутящий момент нагрузки превышает 20 % или машинное оборудование во время идентификационного прогона не может выдерживать номинальный переходный крутящий момент. 1 – Включение питания, установка даты и времени Включите питание привода. IT NL RU SV RU Примечание. Предупреждающие сообщения, отображаемые на различных этапах процесса ввода в эксплуатацию, не свидетельствуют о нарушении нормальной работы. Для скрытия сообщения и возобновления процесса ввода в эксплуатацию нажмите . На данном этапе следует скрыть все предупреждения для перехода к экрану Home (показан справа). Две команды внизу дисплея (в данном случае – Параметры и Меню) указывают назначение двух функциональных клавиш и , расположенных под дисплеем. Команды, назначенные функциональным клавишам, зависят от ситуации. Remote 0.0 rpm Motor speed used rpm Motor current A Motor torque % % Параметры 12:34 0.00 0.00 0.0 Меню Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 115 При экране Начальное представление нажмите (Меню). Отображается главное Меню (справа). Дистанц. Меню 0.0 rpm Параметры Помощники Энергоэффективность Журнал событий Выход 12:34 Выделите пункт меню Настройки с помощью стрелок и , затем нажмите (Выбрать). Выбрать Дистанц. Настройки Язык Дата и время Правка текстов Параметры дисплея 0.0 rpm EN DE ES FI Назад В меню Настройки выделите пункт Дата и время (если он еще не выделен) и нажмите (Выбрать). В меню Дата и время выделите пункт Дата (если он еще не выделен) и нажмите (Выбрать). 12:34 Выбрать Дистанц. 0.0 rpm Дата и время Дата 01.01.1980 12:34:56 Время Показывать дату как день.месяц.год Показывать время как 24-часовой формат Летнее время ЕС Начало след. летнего времени28.03. Назад 12:35 Правка Дистанц. Дата 0.0 rpm дн. Мес. Год 01 .01.1980 Вторник Отмена 12:35 Сохранить FR IT NL RU SV RU 116 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления Задайте надлежащую дату. • Стрелки и позволяют перемещать курсор влево и вправо. • Для изменения значения используйте стрелки и . • Чтобы принять новое значение, нажмите (Сохранить). Проверьте или задайте все остальные параметры в меню Дата и время. EN DE ES FI FR IT Параметр Показать часы указывает, отображается ли время постоянно на нижней панели дисплея. Motor speed used rpm Motor current A Motor torque % % Параметры 0.00 0.00 0.0 12:35 Меню 2 – Напряжение питания и установка данных двигателя Для отключения внешнего управления переключитесь на местное управление, нажав кнопку Loc./Rem . В режиме местного управления в верхней части экрана отображается текст "Местн.". Местн. 0.0 rpm Motor speed used rpm Motor current A Motor torque % % RU RU 0.0 rpm Завершив задание параметров, нажмите (Назад или Выход) требуемое количество раз для отображения экрана Начальное представление (справа). NL SV Дистанц. Параметры Откройте главное Меню, нажав ( Меню). 0.00 0.00 0.0 12:36 Меню Местн. Меню 0.0 rpm Параметры Помощники Энергоэффективность Журнал событий Выход 12:36 Выбрать Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 117 Выделите пункт Параметры и нажмите (Выбрать). Местн. Параметры Избранное По функции Полный список Измененные Назад Выделите пункт Полный список с помощью стрелок и , затем нажмите (Выбрать). Отображается список групп параметров. 12:36 0.0 rpm Выбрать Местн. 0.0 rpm Полный список 01 Actual values 03 Input references 04 Warnings and faults 05 Diagnostics 06 Control and status words 07 System info Назад 12:36 Выбрать Выделите группу параметров 95 HW configuration и нажмите (Выбрать). Местн. 0.0 rpm 95 HW configuration Обратите внимание на то, что в списке Not given предусмотрен циклический переход между 95.01 Supply voltage Disable 95.02 Adaptive voltage limits группами 99 и 01 в обоих направлениях. В данном случае перейти к группе 95 в 95.04 Control board supply Internal 24V списке удобнее с помощью стрелки После выбора группы отображается список входящих в нее параметров. . DE ES FI FR IT NL RU SV Назад Выделите параметр 95.01 Supply voltage (если он еще не выделен) и нажмите (Правка). Отображается список допустимых значений параметра. EN 12:36 Местн. 95.01 Supply voltage [0] Not given [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Отмена 12:36 Правка 0.0 rpm Сохранить RU 118 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления Выделите в списке подходящее напряжение питания и нажмите (Сохранить). Местн. 0.0 rpm 95 HW configuration 95.01 Supply voltage 380…415 V 95.02 Adaptive voltage limits Disable 95.04 Control board supply Internal 24V Назад 12:36 Правка EN Нажмите (Назад) для возврата к списку групп параметров. Выберите группу параметров 99 Motor data и установите параметр 99.03 Motor type. DE Установите параметр 99.04 Motor ctrl mode. DTC = прямое регулирование крутящего момента; Scalar ES FI FR IT NL В большинстве случаев подходит режим прямого регулирования крутящего момента (DTC). Скалярный режим (Scalar) рекомендуется в следующих случаях: • номинальный ток двигателя составляет менее 1/6 номинального тока привода, • выполняются испытания привода без подключения двигателя или • привод управляет несколькими двигателями, количество которых может изменяться. Относительно установки следующих параметров см. данные на паспортной табличке двигателя. По возможности вводите значения, точно совпадающие с указанными на паспортной табличке. Пример паспортной таблички асинхронного двигателя: RU SV RU Пример паспортной таблички двигателя с постоянными магнитами: ABB Motors 3 motor V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F IP 55 V Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 6316/C3 180 IEC 34-1 M2BJ 280SMB 10 B3 2GBJ285220-ADA405445477 6316/C3 630kg IEC 34-1 t E/s Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 119 99.06 Motor nominal current Допустимый диапазон • в режиме прямого регулирования крутящего момента: 1/6 × IHd – 2 × IHd привода; • в скалярном режиме: 0 – 2 × IHd. Примечание. При использовании числовых значений параметров: • Цифры изменяются с помощью стрелок и . • Стрелки и позволяют перемещать курсор влево и вправо. • Для ввода значения нажмите (Сохранить). Аналогичным образом задайте значения следующих параметров. 99.07 Motor nominal voltage Допустимый диапазон номинального напряжения двигателя: 1/6 × UN – 2 × UN привода. Для двигателей с постоянными магнитами номинальным напряжением является напряжение противоэдс при номинальной скорости вращения. Если напряжение указано в вольтах на об/мин (например, 60 В на 1000 об/мин), напряжение при номинальной скорости вращения 3000 об/мин составляет 3 × 60 В = 180 В. Следует учитывать, что номинальное напряжение не совпадает с эквивалентным напряжением двигателя постоянного тока (EDCM), указываемым некоторыми изготовителями. Номинальное напряжение можно вычислить путем деления напряжения EDCM на 1,7 (или квадратный корень из 3). 99.08 Motor nominal frequency Если номинальная частота переменного тока для двигателя с постоянными магнитами не указана на паспортной табличке, ее можно рассчитать по следующей формуле: f = n × p / 60, где n – номинальная скорость двигателя, p – число пар полюсов. EN DE ES FI FR IT NL RU 99.09 Motor nominal speed SV 99.10 Motor nominal power 99.11 Motor nominal cosfii 99.12 Motor nominal torque Эти значения не являются обязательными, но их ввод позволяет повысить точность регулирования. Если они не известны, оставьте значение 0. RU 120 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 99.13 Identification run request Этот параметр позволяет выбрать режим идентификационного прогона (только в режиме прямого регулирования крутящего момента двигателя). ПРЕДУПРЕЖДЕНИЕ! В режимах идентификационного прогона, отмеченных звездочкой (*), двигатель вращается в прямом направлении (подробные сведения см. ниже). Перед выбором любого из этих режимов убедитесь в безопасности запуска двигателя. EN DE ES По возможности следует выбирать режим *Normal. Приводимое в действие оборудование необходимо отсоединить от двигателя в любой из указанных ниже ситуаций: • крутящий момент нагрузки превышает 20 % от номинального значения или • машинное оборудование во время идентификационного прогона не может выдерживать номинальный переходный крутящий момент. *Reduced (Упрощенный): этот режим следует выбрать в том случае, если механические потери превышают 20 %, т.е. отсоединение нагрузки невозможно, или освобожденное состояние тормоза двигателя сохраняется только при условии полного магнитного потока (например, в случае конических электромагнитных тормозов). FI Режим Standstill (Неподвижный двигатель) следует выбрать в том случае, если работа в режимах *Normal и *Reduced невозможна. Примечания. FR • Если у двигателя с постоянными магнитами крутящий момент нагрузки превышает 20 % от номинального значения, использовать этот режим нельзя. • Логическая схема не предусматривает освобождения механического тормоза для идентификационного прогона. IT NL Убедитесь в том, что цепи безопасного отключения крутящего момента и аварийного останова замкнуты (при их наличии). RU Запустите идентификационный прогон нажатием пусковой кнопки . SV Отображается предупреждение о выполнении идентификационного прогона. Проверьте правильность направления вращения двигателя (на следующем рисунке показано прямое направление). RU Идентификационный прогон завершен, когда двигатель останавливается и параметру 99.13 снова присваивается значение "No". Если двигатель вращается в неверном направлении, исправьте подключение кабеля двигателя или измените значение параметра 99.16 Phase order. 3 – Параметры сигналов управления Проверьте положение перемычек J1 и J2 на блоке управления привода. Эти перемычки определяют, являются ли аналоговые входы AI1 и AI2 токовыми входами или входами напряжения. Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 121 Проверьте/отрегулируйте следующие параметры. 20.01 Ext1 commands По умолчанию пуск/останов привода осуществляется в соответствии с состоянием цифрового входа DI1 (0 = останов, 1 = пуск). Вход DI2 определяет направление вращения (0 = прямое, 1 = обратное). Если необходимы другие источники, измените значение соответствующим образом. Источники In1…In3 определяются параметрами 20.03…20.05. 12.15 AI1 unit selection Выберите значение mA или V в соответствии с положением перемычки J1. 12.17 AI1 min 12.18 AI1 max 12.19 AI1 scaled at AI1 min 12.20 AI1 scaled at AI1 max EN По умолчанию сигнал задания скорости поступает на аналоговый вход AI1. (Назначение функции входу можно изменить с помощью параметров группы 22.) DE Параметры 12.17 и 12.18 служат для указания верхнего и нижнего пределов аналогового входного сигнала. Параметры масштабирования 12.19 и 12.20 определяют соответствующие этим пределам уровни внутреннего сигнала, как показано на следующем графике. ES AI (после масштабирования) FI FR IT 12.20 NL AI (мА/В) 12.17 12.18 RU SV 12.19 Для аналогового входа AI2 соответствующие значения определяются параметрами 12.27 – 12.30. RU 122 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 13.12 AO1 source 13.17 AO1 source min 13.18 AO1 source max 13.19 AO1 out at AI1 src min 13.20 AO1 out at AI1 src max Параметр 13.12 позволяет выбрать источник для аналогового выхода AO1 (по умолчанию – скорость двигателя в об/мин). Параметры 13.17 и 13.18 служат для указания верхнего и нижнего значений сигнала источника, которые соответствуют фактическим значениям сигнала на аналоговом выходе, определяемым параметрами 13.19 и 13.20. Сигнал источника EN 13.18 DE AO (мА) 13.19 ES 13.20 FI FR 13.17 IT NL RU SV RU 46.10 Speed scaling 23.11 Ramp set selection 23.12 Acceleration time 1 23.13 Deceleration time 1 23.14 Acceleration time 2 23.15 Deceleration time 2 Можно определить два различных набора параметров ускорения/замедления. Параметр 23.11 позволяет выбрать источник, определяющий переключение между этими наборами. Каждый из параметров 23.12 – 23.15 указывает время ускорения или замедления привода между нулевой и масштабированной скоростью (параметр 46.10). Скорость 46.10 Ускорение Замедлени 23.12 23.14 23.13 23.15 0 Время Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления 123 30.11 Minimum speed 30.12 Maximum speed 30.17 Maximum current 30.19 Minimum torque 30.20 Maximum torque Эти параметры служат для проверки и установки пределов скорости, тока и крутящего момента двигателя. Для запуска привода с положительным задание скорости (в прямом направлении) выполните следующие действия. • С панели управления (местное управление): при экране начального представления нажмите (Параметры), выберите Уставка, отрегулируйте задание кнопками со стрелками , , ,и , нажмите Сохранить, после чего нажмите пусковую кнопку. • С модуля ввода-вывода: В режиме дистанционного управления отрегулируйте аналоговый вход AI1 (задание), для цифрового входа DI2 укажите значение 0 (прямое направление), а для цифрового входа DI1 – значение 1 (пуск). EN DE ES FI FR IT NL RU SV RU 124 Краткое руководство по вводу в эксплуатацию приводов ACS880 с основной программой управления EN DE ES FI FR IT NL RU SV RU Snabbguide för ACS880 med standardprogramvara 125 Snabbguide för ACS880 med standardprogramvara Om denna guide Denna guide beskriver den grundläggande idrifttagningsproceduren för frekvensomriktare ACS880, utrustad med standardprogramvara. Fullständig dokumentation av frekvensomriktaren systemprogramvara finns i Firmware manual (se listan över dokumentation på den främre pärmens insida). EN I denna guide görs alla inställningar i frekvensomriktaren med hjälp av manöverpanelen ACS-AP-I. Idrifttagningen kan också utföras med hjälp av PCverktyget Drive composer. DE Innan du börjar FI Kontrollera att frekvensomriktare är mekaniskt och elektrisk installerad så som beskrivs i motsvarande Quick installation guide och/eller Hårdvaruhandledning. FR Säkerhet ES IT NL VARNING! Allt elektriskt installations- och underhållsarbete på frekvensomriktaren skall utföras av behörig elektriker. Arbeta aldrig med frekvensomriktaren, bromschopperkretsen, motorkabeln eller motorn när systemet är spänningssatt. Kontrollera alltid genom mätning att ingen spänning finns. RU SV SV 126 Snabbguide för ACS880 med standardprogramvara Idrifttagning Säkerhet Idrifttagningen skall utföras av behörig elektriker. Säkerhetsanvisningarna måste följas under idrifttagningsproceduren. Se säkerhetsinstruktioner på de inledande sidorna av motsvarande Hårdvaruhandledning. Kontrollera installationen. Se installationschecklistan i motsvarande Hårdvaruhandledning. EN DE ES Kontrollera att det inte medför fara om motorn startas. Koppla bort driven utrustning om • det finns risk för skada vid felaktig rotationsriktning • en Normal ID-körning krävs under idrifttagning av frekvensomriktaren, om lastmoment är högre än 20 % eller om mekaniken inte tål de nominella momenttransienterna under ID-körningen. 1 – Spänningssättning, datum och tid FI FR IT Spänningssätt frekvensomriktaren. Obs: Det är normalt att varningsmeddelanden visas under idrifttagningsproceduren. För att dölja ett meddelande och återta idrifttagningsproceduren, tryck på . NL Dölj alla varningar för att komma till Visningsvy (visas till höger). RU De två kommandona längst ner på displayen (i detta fall, Tillval och Meny), visar funktionerna hos de båda funktionstangenterna och som sitter under displayen. Funktionstangenternas funktioner beror på aktuellt sammanhang. SV SV I Visningavy, tryck på (Meny). Huvudmenyn (till höger) visas. Fjärr 0.0 rpm Motorvarvtal rpm Motorström A Motormoment % % Tillval 12:34 Fjärr Meny 0.00 0.00 0.0 Meny 0.0 rpm Parametrar Assistenter Energieffektivitet Händelselogg Avsluta 12:34 Val Snabbguide för ACS880 med standardprogramvara 127 Markera Inställningar på menyn med och och tryck på (Välj). Fjärr Inställningar Språk Datum & tid Redigera texter Visningsinställningar Tillbaka I menyn Inställningar, markera Datum & tid (om raden inte redan är markerad) och tryck på (Välj). I menyn Inställningar, markera Datum (om raden inte redan är markerad) och tryck på (Välj). 0.0 rpm 12:34 Val Fjärr 0.0 rpm Datum & tid Datum 01.01.1980 Tid 12:34:56 Visa datum som dag.månad.år Visa tid som 24-tim Sommartid EU Välj sedan start för sommartid 28.03. Tillbaka 12:35 Ändra Fjärr Datum 0.0 rpm DE ES FI FR IT NL Dag Månad År RU 01 .01.1980 SV Tisdag Radera EN 12:35 Spara SV 128 Snabbguide för ACS880 med standardprogramvara Ställ in rätt datum: • Använd och att flytta markören åt vänster och höger. • Använd och för att ändra värdet. • Tryck på (Spara) för att acceptera den nya inställningen. Kontrollera / justera alla kvarvarande inställningar i menyn Datum & tid. Inställningen Visa klocka avgör om tiden skall visas kontinuerligt på displayens nederdel. EN DE ES FI FR Fjärr Motorvarvtal rpm Motorström A Motormoment % % Tillval Meny 2 – Matningsspänning och motordatainställningar Övergå till lokal styrning för att säkerställa att extern styrning är deaktiverad. Tryck på tangenten Loc/Rem . Lokal styrning indikeras av texten ”Lokal” på displayens övre del. Lokal 0.0 rpm Motorvarvtal rpm Motorström A Motormoment % % NL Tillval SV 12:35 0.00 0.00 0.0 Efter avslutade inställningar, tryck på (Tillbaka eller Avsluta) upprepade gånger tills Visningsvy (höger) återkommer. IT RU 0.0 rpm Öppna Huvudmeny genom att trycka på (Meny). 12:36 Lokal Meny 0.00 0.00 0.0 Meny 0.0 rpm Parametrar Assistenter Energieffektivitet SV Händelselogg Avsluta 12:36 Val Snabbguide för ACS880 med standardprogramvara 129 Markera Parametrar och tryck på (Välj). Lokal Parametrar Favoriter Efter funktion Fullständig lista Ändrade Tillbaka Markera Fullständig lista med och och tryck på (Välj). En lista över parametergrupper visas. Markera parametergrupp 95 Hårdvarukonfig och tryck på (Välj). Observera att listan övergår direkt mellan grupperna 99 och 01. I detta fall går det alltså snabbare att använda för att gå till grupp 95 på listan. 12:36 Lokal Fullständig lista 01 Ärvärden 03 Inreferenser 04 Varningar och fel 05 Diagnostik 06 Styrnings- och statusord 07 Systeminfo Tillbaka 12:36 0.0 rpm Val 0.0 rpm DE ES FI Val Lokal 0.0 rpm 95 Hårdvarukonfig 95.01 Matningsspänning Ej given 95.02 Anpassn spänningsgr Deaktivera 95.04 Styrkorts matn Intern 24V Efter val av en grupp visas en lista över parametrarna inom gruppen. FR IT NL RU SV Tillbaka Markera parameter 95.01 Matningsspänning (om den inte redan är markerad) och tryck på (Redigera). Tillgängliga parameterinställningar visas. EN 12:36 Lokal 95.01 Matningsspänning [0] Ej given [1] 208…240 V [2] 380…415 V [3] 440…480 V [4] 500 V Radera 12:36 Redigera 0.0 rpm SV Spara 130 Snabbguide för ACS880 med standardprogramvara Markera rätt värde i listan och tryck på (Spara). Lokal 0.0 rpm 95 Hårdvarukonfig 95.01 Matningsspänning 380…415 V 95.02 Anpassn spänningsgr Deaktivera 95.04 Styrkorts matn Intern 24 V Tillbaka 12:36 Redigera EN Tryck på (Tillbaka) för att återgå till listan över parametergrupper. Välj parametergruppen 99 Motor data, och ställ in parameter 99.03 Motortyp. DE Ställ in parameter 99.04 Motor styrmetod. DTC = Direkt momentreglering, Skalär FI DTC lämpar sig i de flesta fall. Skalär styrning rekommenderas om • motorns märkström är mindre än 1/6 av frekvensomriktarens nominella utström • frekvensomriktaren används för teständamål utan någon ansluten motor • frekvensomriktaren matar flera motorer och antalet matade motorer kan variera. FR Se motorns märkskylt för följande parameterinställningar. I mån av möjlighet, mata in värdena exakt så som de anges på motorns märkskylt. ES IT Exempel på märkskylt på en asynkronmotor: Exempel på märkskylt på en permanentmagnetmotor: ABB Motors NL 3 motor RU SV SV V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 1475 32.5 0.83 30 50 56 1475 0.83 50 30 50 1470 34 0.83 30 1470 59 0.83 30 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 S1 SPEC INSUL. JK-21640-1 No 3424522 Ins.cl. F Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 2GBJ285220-ADA405445477 6316/C3 180 IEC 34-1 96.06 Motor nom ström Tillåtet område är • vid DTC-styrning: 1/6 × IHd … 2 × IHd för frekvensomriktaren • vid skalär styrning: 0 … 2 × IHd Obs: Med numeriska parametervärden: • Använd • Använd • Tryck på och och IP 55 V för att ändra ett siffervärde. för att flytta markören åt vänster och höger. (Spara) för att mata in värdet. 6316/C3 630kg IEC 34-1 t E/s Snabbguide för ACS880 med standardprogramvara 131 Gör följande parameterinställningar på motsvarande sätt. 99.07 Motor nom spänn Tillåtet område är 1/6 × UN … 2 × UN för frekvensomriktaren. Vid permanentmagnetmotorer är märkspänningen lika med mot-EMK-spänningen vid motorns märkvarvtal. Om spänningen anges i volt/rpm (t.ex. 60 V per 1000 rpm blir spänningen vid märkvarvtalet 3000 rpm 3 × 60 V = 180 V. Observera att märkspänningen inte är samma sak som den ekvivalenta DC-motorspänningen (EDCM) som anges av vissa tillverkare. Märkspänningen kan beräknas genom att man dividerar EDCMspänningen med 1,7 (dvs. kvadratroten av 3). 99.08 Motor nom frekv Med permanentmagnetmotorer, om märkfrekvensen inte anges på märkskylten, kan värdet beräknas med hjälp av följande ekvation: f = n × p / 60 EN DE där n = motorns märkvarvtal, p = antal polpar. 99.09 Motor nom varvt ES 99.10 Motor nom effekt FI 99.11 Motor nom cos fi 99.12 Motor nom moment Dessa värden måste inte anges, men de kan anges för att förbättra styrnoggrannheten. Om värdena inte är kända, lämna dem på 0. 99.13 ID körn begäran Denna parameter väljer metoden för identifieringskörning (endast vid DTC-styrning). VARNING! Identifieringskörningsmetoderna markerade med * försätter motorn i rotation i framriktning (se nedan för detaljer). Se till att detta inte medför några säkerhetsrisker innan en sådan metod väljs. FR IT NL RU *Normal skall alltid väljas då så är möjligt. Den drivna utrustningen måste vara bortkopplad från motorn om • belastningsmoment är högre än 20 % • den drivna utrustningen inte tål de nominella momenttransienterna under ID-körningen. *Reducerat skall väljas om de mekaniska förlusterna är högre än 20 %, dvs. om den drivna utrustningen inte kan kopplas bort, eller om fullt flöde krävs för att hålla motorns broms lyft (t.ex. med koniska motorer). SV Stillastående skall väljas om varken *Normal eller *Reducerat kan användas. Obs: • Denna metod kan inte användas för en permanentmagnetmotor om belastningsmomentet är högre än 20 % av det nominella. SV • En mekanisk broms lyfts inte av logiken för ID-körning. Kontrollera att eventuella kretsar för Safe torque-off och nödstopp är slutna. Starta drivsystemet genom att trycka på (Start) Ett varningsmeddelande visar att IDkörning pågår. 132 Snabbguide för ACS880 med standardprogramvara Kontrollera att motorn går i rätt riktning (riktning framåt visas nedan). ID-körningen är avslutad när värdet på parameter 99.13 återgår till ”Nej”. Om motorn roterade åt fel håll, låt två fasledare byta plats, eller ändra parametern 99.16 Fasföljd. 3 – Styrsignalskonfigurering EN DE ES Kontrollera positionerna hos byglarna J1 och J2 på frekvensomriktarens manöverpanel. Dessa byglar avgör om de analoga ingångarna AI1 och AI2 fungerar som ström- eller spänningsingångar. Kontrollera/justera följande parametrar. 20.01 Ext1 styrning FI Som förval gäller att drivsystemet startar och stoppar enligt status för digital ingång DI1 (0 = Stopp, 1 = Start). DI2 anger rotationsriktningen (0 = Fram, 1 = Back). Om ytterligare källor behövs, ändra deras värden efter behov. Källorna In1…In3 definieras av parametrarna 20.03…20.05. FR 12.15 AI1 enhet val IT NL RU SV Sätt denna parameter till antingen mA eller V, motsvarande inställningen av bygel J1. 12.17 AI1 min 12.18 AI1 max 12.19 AI1 skalat vid AI1 min 12.20 AI1 skalat vid AI1 max Förvald ingång för varvtalsreferens är analog ingång AI1. (Detta styrs av parametrarna i grupp 22.) Parametrarna 12.17 och 12.18 anger lägsta och högsta gräns för analog insignal. Skalningsparametrarna 12.19 och 12.20 definierar de interna signalnivåer som motsvarar dessa gränser, på följande sätt: AI (skalat) 12.20 SV AI (mA/V) 12.17 12.18 12.19 Motsvarande parametrar för analog ingång AI2 är 12.27…12.30. Snabbguide för ACS880 med standardprogramvara 133 13.12 AO1 källa 13.17 AO1 källa min 13.18 AO1 källa max 13.19 AO1 ut vid AO1 källa min 13.20 AO1 ut vid AO1 källa max Parameter 13.12 väljer källa för analog utgång AO1 (som förval, motorvarvtalet i rpm). Parametrarna 13.17 och 13.18 anger lägsta och högsta källsignalvärde som motsvarar faktiska analoga utsignalvärden, definierade av parametrarna 13.19 och 13.20. Källsignal 13.18 EN AO (mA) 13.19 DE 13.20 ES FI 13.17 FR 46.10 Skaln varvtal 23.11 Val regulatorramp 23.12 Accelerationstid 1 23.13 Retardationstid 1 23.14 Accelerationstid 2 23.15 Retardationstid 2 Du kan definiera två olika uppsättningar accelerations-/retardationsramper. Källsignalen som växlar mellan de båda uppsättningarna väljs med parameter 23.11. Varje accelerations-/retardationsrampuppsättning som ställs in med parametrarna 23.12…23.15 avser den tid det tar för frekvensomriktaren att öka eller minska sin utfrekvens mellan 0 och skalningsvarvtalet (parameter 46.10). IT NL RU SV Varvtal SV 46.10 Acc. Ret. 23.12 23.14 23.13 23.15 0 Tid 134 Snabbguide för ACS880 med standardprogramvara 30.11 Min varvtal 30.12 Max varvtal 30.17 Max ström 30.19 Min moment 30.20 Max moment Kontrollera, och vid behov justera, gränsvärdena för motorvarvtal, ström och moment. EN DE ES FI FR IT NL RU SV SV Starta drivsystemet med låg varvtalsreferens (rotationsriktning framåt): • Från manöverpanelen (lokal styrning): I Visningsvy tryck på (Alternativ). Välj Referens, justera referensen med hjälp av tangenterna , , , och , tryck på Spara, och tryck på Start. • Från I/O: Vid fjärrstyrning, justera analog ingång AI1 (referens), växla digital ingång DI2 till 0 (framåt) och växla digital ingång DI1 till 1 (start). Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 135 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu Kılavuz hakkında Bu kılavuz birincil kontrol programı bulunan bir ACS880 sürücünün temel devreye alma sıralamasını açıklar. Sürücü yazılımına ilişkin tüm belgeler Yazılım kılavuzunda bulunabilir (ön kapağın iç tarafındaki kılavuzlar listesine bakın). DE Bu kılavuzda, sürücü ayarları ACS-AP-I kontrol paneli kullanılarak yapılır. Devreye alma sıralaması Sürücü düzenleyici PC aracı kullanılarak da gerçekleştirilebilir. ES Başlamadan önce FI Sürücünün mekanik ve elektriksel kurulumunun ilgili Hızlı kurulum kılavuzu ve/veya Donanım kılavuzunda açıklandığı gibi yapıldığından emin olun. FR Güvenlik TR IT NL UYARI! Sürücünün elektrik tesisatı kurulumu ve bakım işleri yalnızca yetkili elektrikçiler tarafından yapılmalıdır. Sürücü, fren kesici devresi, motor kablosu ve motor üzerinde sürücüde elektrik varken kesinlikle çalışmayın. Mutlaka ölçüm yaparak gerilim bulunmadığından her zaman emin olun. RU SV TR 136 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu Devreye alma Güvenlik Devreye alma sadece yetkili bir elektrikçi tarafından gerçekleştirilebilir. Devreye alma prosedürü boyunca güvenlik talimatlarına uyulmalıdır. İlgili Donanım kılavuzunun ilk sayfalarındaki güvenlik talimatlarına başvurun. Kurulumu kontrol edin. Uygun Donanım kılavuzundaki kurulum kontrol listesine başvurun. Motoru start etmenin bir tehlikeye yol açmayacağından emin olun. TR DE ES FI FR IT NL RU SV Aşağıdaki durumlarda motor ile tahrik edilen makine arasındaki mekanik bağlantıyı sökün • yanlış yönde dönüş durumunda hasar tehlikesi varsa, veya • sürücü devreye alma sırasında bir Normal ID çalışması gerekli, yük momenti %20'den daha fazla veya ID çalışması sırasında ekipman nominal momente dayanacak durumda değilse. 1 – Güç verme, tarih ve saat ayarları Sürücüye güç verin. Not: Devreye alma işlemi sırasında çeşitli noktalarda uyarı mesajlarının belirmesi normaldir. Bir uyarı mesajını gizlemek ve devreye alma işlemine devam etmek için, düğmesine basın. Ana görünüme (sağ tarafta gösterilmektedir) tüm uyarıları şimdi gizleyin. Ekranın alt kısmında iki komut bulunur (bu durumda, Seçenekler ve Menü) ve ekranın alt kısmındaki ve olmak üzere iki programlanabilir tuşun fonksiyonunu gösterir. Programlanabilir tuşlara atanan komutlar bağlama göre değişiklik gösterir. Ana görünümde, Ana Menü (sağ) belirir. tuşuna basın (Menü). Uzak 0,0 rpm Kullanılan motor hızı rpm Motor akımı A Motor momenti % % Seçenekler 12:34 Uzak Menü 0.00 0.00 0.0 Menü 0,0 rpm Parametreler Asistanlar TR Enerji verimliliği Çıkış Olay günlüğü 12:34 Seçim Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 137 ve tuşlarıyla Ayarlar öğesini vurgulayın ve (Seçim) tuşuna basın. Ayarlar menüsünde, Tarih ve saat öğesini vurgulayın (vurgulanmamışsa) ve (Seçim) tuşuna basın. Tarih ve saat menüsünde, Tarih öğesini vurgulayın (vurgulanmamışsa) ve (Seçim) tuşuna basın. Uzak Ayarlar Dil Tarih ve saat Metinleri düzenle Ekran ayarları 0,0 rpm Geri Seçim 12:34 Uzak 0,0 rpm Tarih ve saat Tarih 01.01.1980 Saat 12:34:56 Tarihi şu şekilde göster: gün.ay.yıl Saati şu şekilde göster: 24 saat Gün ışığı tasarrufu EU Sonraki gün ışığı tasarrufu başlangıcı 28.03. Geri 12:35 Yaz Uzak Tarih 0,0 rpm DE ES FI FR IT NL Gün Ay Yıl 01 .01.1980 Salı İptal TR 12:35 RU SV Kaydet TR 138 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu Doğru tarihi ayarlayın: • İmleci sola ve sağa kaydırmak için tuşlarını kullanın. ve • Değeri değiştirmek için ve tuşlarını kullanın. • Yeni ayarı kabul etmek için (Kaydet) tuşuna basın. Tarih ve saat menüsünde kalan tüm ayarları kontrol edin/ayarlayın. TR DE Saati göster ayarı ekranın alt bölmesinde saatin sürekli gösterilip gösterilmeyeceğini belirler. FR 0,0 rpm Kullanılan motor hızı rpm Motor akımı A Motor momenti % % Seçenekler 12:35 Menü 2 – Besleme gerilimi ve motor verisi ayarları Harici kontrolün devre dışı kaldığından emin olmak için, kontrol panelindeki Loc/Rem tuşuna basın. Lokal kontrol, üst bölmedeki “Lokal” metni ile gösterilir. Lokal 0,0 rpm Kullanılan motor hızı rpm IT Motor akımı A NL Motor momenti % % Seçenekler RU SV 0.00 0.00 0.0 Ayarları yaptıktan sonra, Ana görünüm (sağ) belirinceye kadar arka arkaya (Geri veya Çıkış) tuşuna basın. ES FI Uzak (Menü) tuşuna basarak ana Menü'yü açın. 12:36 Lokal Menü 0.00 0.00 0.0 Menü 0,0 rpm Parametreler Asistanlar Enerji verimliliği TR Çıkış Olay günlüğü 12:36 Seçim Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 139 Parametreler öğesini vurgulayın ve (Seçim) tuşuna basın. ve tuşlarıyla Tam liste öğesini vurgulayın ve (Seçim) tuşuna basın. Bir parametre grubu listesi görüntülenir. 95 Donanım konfigürasyonu parametre grubunu vurgulayın ve (Seçim) tuşuna basın. Listenin 99 ve 01 grupları arasında her iki yönde de kullanılabildiğini unutmayın. Bu durumda, listede grup 95'i bulmak için tuşunun kullanılması işlemi hızlandıracaktır. Bir grup seçildikten sonra, gruptaki bir parametre listesi görüntülenir. Lokal Parametreler Favoriler Fonksiyona göre Tam liste Değiştirilen 0,0 rpm Geri Seçim Lokal Tam liste 01 Gerçek değerler 03 Giriş referansları 04 Uyarı ve hatalar 05 Tanı 06 Kontrol ve durum word'leri 07 Sistem bilgisi Geri 12:36 0,0 rpm Lokal 0,0 rpm 95.01 Besleme gerilimi TR DE ES FI Seçim 95 Donanım konfigürasyonu Belirtilmedi 95.02 Uyarlamalı gerilim limitleri Devre dışı 95.04 Kontrol kartı beslemesi Dahili 24V FR IT NL RU SV Geri 95 Besleme gerilimi parametresini vurgulayın (vurgulanmamışsa) ve (Yaz) tuşuna basın. Mevcut parametre ayarları listelenir. 12:36 12:36 Lokal 95.01 Besleme gerilimi [0] [1] [2] [3] [4] İptal Belirtilmedi 208…240 V 380…415 V 440…480 V 500 V 12:36 Yaz 0,0 rpm TR Kaydet 140 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu Listede doğru ayarı vurgulayın ve (Kaydet) tuşuna basın. Lokal 0,0 rpm 95 Donanım konfigürasyonu 95.01 Besleme gerilimi 380…415 V 95.02 Uyarlamalı gerilim limitleri Devre dışı 95.04 Kontrol kartı beslemesi Dahili 24V Geri 12:36 Yaz TR Parametre grupları listesini tekrar görüntülemek için (Geri) tuşuna basın. 99 Motor verileri parametre grubunu seçin ve 99.03 Motor tipi parametresini girin. DE 99.04 Motor kntrl modu parametresini girin. DTC = Doğrudan moment kontrolü; Skaler ES FI FR IT DTC, birçok durum için uygundur. Skaler mod aşağıdaki durumlarda önerilir • motor nominal akımının sürücü nominal akımının 1/6’sından düşük olması, • sürücünün, motor bağlanmadan test amaçlı kullanılması veya • sürücünün birden fazla motoru kontrol etmesi ve bağlı motor sayısının değişken olması. Aşağıdaki parametre ayarları için motor plakasına bakın. Mümkünse, değerleri motor plakasında gösterildiği gibi tam olarak girin. Bir endüksiyon (asenkron) motoru plaka örneği: NL RU Bir sabit mıknatıslı motor plaka örneği: ABB Motors 3 motor SV V 690 Y 400 D 660 Y 380 D 415 D 440 D Cat. no M2AA 200 MLA 4 IEC 200 M/L 55 No Ins.cl. F Hz kW r/min A cos 32.5 0.83 1475 30 50 56 0.83 1475 50 30 50 34 0.83 1470 30 59 0.83 30 1470 50 1475 54 0.83 50 30 59 0.83 35 1770 60 3GAA 202 001 - ADA 6312/C3 ABB Motors 3 ~ motor TR S1 SPEC INSUL. JK-21640-1 IP 55 IA/IN t E/s 6210/C3 M2BJ 280SMB 10 B3 No 3424522 Ins.cl. F Hz kW r/min A cos M IA/IN 400 D 50 55 600 103 0.97 Prod. code 2GBJ285220-ADA405445477 6316/C3 6316/C3 630kg IEC 34-1 180 IEC 34-1 99.06 Motor nominal akımı İzin verilen aralık • DTC modunda: 1/6 × IHd … 2 × sürücü IHd • Skaler modda: 0 … 2 × IHd Not: Nümerik parametre değerlerinde: • Bir hanenin değerini değiştirmek için, IP 55 V ve tuşunu kullanın. • İmleci sola ve sağa kaydırmak için ve tuşlarını kullanın. • Değeri girmek için (Kaydet) tuşuna basın. t E/s Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 141 Aşağıdaki parametre ayarlarını aynı şekilde yapın. 99.07 Motor nominal gerilimi İzin verilen aralık: sürücünün 1/6 × UN … 2 × UN değeri. Sabit mıknatıslı motorlarda, nominal gerilim nominal hızdaki BackEMF gerilimidir. Gerilim volt/rpm (örn. 60 V / 1000 rpm) olarak verilirse, 3000 rpm nominal hızdaki gerilim 3 × 60 V = 180 V şeklindedir. Nominal gerilimin, bazı üreticiler tarafından belirlenen eşdeğer DC motor gerilimine (EDCM) eşit olmadığını unutmayın. Nominal gerilim, EDCM gerilimini 1,7'ye (veya 3'ün kareköküne) bölerek hesaplanabilir. 99.08 Motor nominal frekansı Sabit mıknatıslı motorlarda, motor plakasında nominal frekans gösterilmemişse, şu formül kullanılarak hesaplanabilir: f = n × p / 60 burada n = nominal motor hızı, p = kutup çifti sayısı. TR 99.09 Motor nominal hızı DE 99.10 Motor nominal gücü ES 99.11 Motor nominal cosfii 99.12 Motor nominal momenti FI Bu değerlere g erek duyulmaz, ancak kontrol doğruluğunu artırmak için girilebilir. Bilinmediği durumlarda 0 olarak bırakın. FR IT 99.13 Tanımlama çalıştırması talebi Bu parametre tanımlama çalıştırması modunun seçilmesini sağlar (sadece DTC motor kontrol modu). UYARI! Bu nedenle * ile işaretlenmiş tanımlama çalıştırması modları motorun ileri yönde dönmesini sağlayacaktır (ayrıntılar için aşağı bakın). Bu modlardan herhangi birini seçmeden önce motorun çalıştırılmasının güvenli olduğundan emin olun. Mümkün olan her durumda *Normal mod seçilmelidir. Tahrik edilen makine aşağıdaki durumlarda motordan ayrılmalıdır: • yük momenti %20'den daha yüksekse veya • tanımlama çalıştırması sırasında makine nominal momente dayanacak durumda değilse. *Mekanik kayıpların %20'den daha yüksek olması, yani yükün ayrılamaması veya motor freninin açık tutulması için tam akının gerekli olması durumunda, Düşük mod seçilmelidir. *Normal ya da *Düşük mod kullanılamıyorsa, Sabit mod seçilmelidir. Notlar: NL • Bu mod, yük momenti nominal değerin %20'sinden fazlaysa sabit mıknatıslı motorda kullanılamaz. • Tanımlama çalıştırması için lojik tarafından için mekanik fren açılmaz. TR Güvenli moment kapatma ve acil durdurma devrelerinin (varsa) kapalı olduğundan emin olun. (Start) düğmesine basarak tanımlama çalıştırmasını başlatın. Tanımlama çalıştırması devam ederken bir uyarı görüntülenecektir. RU SV 142 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu Motorun doğru yönde çalıştığını kontrol edin (aşağıda ileri yön gösterilmektedir). Sürücü durduğunda ve 99.13 parametresinin değeri “Hayır” olarak değiştiğinde tanımlama çalıştırması tamamlanmıştır. Motor yanlış yönde çalıştıysa, motor kablolarını düzeltin veya 99.16 Faz sırası parametresini ayarlayın. 3 – Kontrol sinyali ayarları TR DE ES sürücünün denetleme birimindeki J1 ve J2 jumper'larının konumunu kontrol edin. Bu jumper'lar AI1 ve AI2 analog girişlerinin akım ya da gerilim olmasını belirler. Aşağıdaki parametreleri kontrol edin/ayarlayın. 20.01 Har1 komutlar FI Varsayılan olarak, dijital giriş DI1 durumuna göre başlar/durur (0 = Stop, 1 = Start). DI2 dönüş yönünü belirler (0 = İleri, 1 = Geri). Başka kaynaklar gerekiyorsa, değeri uygun şekilde değiştirin. In1…In3 kaynakları 20.03…20.05 parametreleriyle tanımlanır. FR 12.15 AI1 birimi seçimi IT NL RU SV Bunu J1 jumper'ı ayarına göre mA ya da V olarak ayarlayın. 12.17 AI1 min 12.18 AI1 maks 12.19 AI1, AI1 min'de ölçeklendirilmiş 12.20 AI1, AI1 maks'da ölçeklendirilmiş Hız referansı için varsayılan giriş AI1 analog girişidir. (Bu, grup 22'deki parametrelerle kontrol edilir.) 12.17 ve 12.18 parametreleri analog giriş sinyalinin alt ve üst limitlerini ayarlar. 12.19 ve 12.20 ölçeklendirme parametreleri bu limitlere karşılık gelen dahili sinyal seviyelerini aşağıdaki şekilde tanımlar: AI (ölçeklendirilmiş) 12.20 TR AI (mA/V) 12.17 12.18 12.19 AI2 analog girişi için karşılık gelen parametreler 12.27…12.30 şeklindedir. Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 143 13.12 AO1 kaynağı 13.17 AO1 kaynağı min 13.18 AO1 kaynağı maks 13.19 AO1 çıkışı AI1 src min'de 13.20 AO1 çıkışı AI1 src maks'da 13.12 parametresi AO1 analog girişi için kaynağı seçer (varsayılan olarak, motor hızı rpm cinsindendir). 13.17 ve 13.18 parametreleri, 13.19 ve 13.20 parametreleriyle tanımlanan gerçek analog çıkış değerlerine karşılık gelen alt ve üst kaynak sinyali değerlerini ayarlar. Kaynak sinyali 13.18 TR DE AO (mA) 13.19 ES 13.20 FI 13.17 FR 46.10 Hız ölçeklendirme 23.11 Rampa ayarı seçimi 23.12 Hızlanma süresi 1 23.13 Yavaşlama süresi 1 23.14 Hızlanma süresi 2 23.15 Yavaşlama süresi 2 İki farklı hızlanma/yavaşlama rampası ayarı tanımlayabilirsiniz. İki ayar arasında değişen kaynak 23.11 parametresiyle seçilebilir. 23.12…23.15 parametrelerindeki her bir hızlanma/yavaşlama süresi ayarı sürücünün 0 ve ölçeklendirilen hız (46.10 parametresi) arasında hızlanması veya yavaşlaması için geçen süreyi ifade eder. IT NL RU SV Hız 46.10 TR Hız. Yav. 23.12 23.14 23.13 23.15 0 Süre 144 Birincil kontrol programlı ACS880 için hızlı devreye alma kılavuzu 30.11 Minimum hız 30.12 Maksimum hız 30.17 Maksimum akım 30.19 Minimum moment 30.20 Maksimum moment Motor hızı, akımı ve momentinin limitlerini kontrol edin ve gerekirse ayarlayın. TR DE ES FI FR IT NL RU SV TR Sürücüyü pozitif (ileri) hız referansıyla başlatın: • Kontrol panelinden (Lokal kontrol): Ana görünümde, (Seçenekler) tuşuna basın, Referans öğesini seçin, , , , ve tuşlarını kullanarak referansı ayarlayın, Kaydet tuşuna ve ardından Start düğmesine basın. • I/O'dan: Uzaktan kontrolde, AI1 analog girişini (referans) ayarlayın, DI2 dijital girişini 0 (ileri) olarak değiştirin ve DI1 dijital girişini 1 (start) olarak değiştirin. 3AUA0000098062 Rev D (MUL) EFFECTIVE: 2012-10-22
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146

ABB ACS880 Series Quick Start Up Manual

Type
Quick Start Up Manual