Socomec DIRIS A-40 Handleiding

Type
Handleiding
DIRISA-40
PMD - Multifunctionele meter
NL
INSTRUCTIE-
HANDLEIDING
www.socomec.com/
catalogues-brochures_en.html
2 NL
DIRIS A-40 - 545802B - SOCOMEC
1. DOCUMENTATIE ...............................................................3
2. GEVAREN EN WAARSCHUWINGEN .............................................4
2.1. Gevaar van elektrocutie, brandwonden en explosie .......................4
2.2. Gevaar van schade aan het apparaat ...................................4
2.3. Verantwoordelijkheid ..................................................5
3. VOORBEREIDING ..............................................................6
4. INLEIDING ....................................................................7
4.1. Presentatie van de DIRISA-40 .........................................7
4.1.1. Bereik ....................................................7
4.1.2. Principe ...................................................8
4.1.3. Functies ...................................................9
4.1.4. Afmetingen ...............................................11
4.1.5. Voorpaneel ...............................................11
4.2. Presentatie van bijbehorende stroomsensoren ..........................13
4.2.1. TE solid-core stroomsensoren ...............................14
4.2.2. TR / iTR split-core stroomsensoren ...........................16
4.2.3. TF flexibele stroomsensoren .................................17
4.2.4. Adapters voor sensoren van 5 A .............................18
5. INSTALLATIE .................................................................19
5.1. Aanbevelingen en veiligheid ..........................................19
5.2. Installatie van DIRIS A-40 ............................................19
5.3. TE solid-core sensoren installeren .....................................20
5.3.1. Accessoires voor montage ..................................20
5.3.2. Montage op DIN-rail .......................................20
5.3.3. Montage op plaat ..........................................22
5.3.4. Installeren op een kabel met klemmende kraag .................24
5.3.5. Montage op stang .........................................25
5.3.6. Montage sensoren .........................................26
5.3.7. Accessoires voor afdichting van sensoren .....................26
5.4. TR split-core sensoren installeren .....................................27
5.4.1. Kabelmontage ............................................27
5.5. Montage van flexibele TF-sensoren ....................................28
5.5.1. Baar- of kabelmontage .....................................28
5.6. De 5A-adapter installeren ............................................29
6. AANSLUITING ................................................................30
6.1. Aansluiting van de DIRISA-40 ........................................30
6.2. Aansluiting op het elektriciteitsnet en op de belastingen .................32
6.2.1. Configureerbare belastingen op basis van het type netwerk ......32
6.2.2. Beschrijving van het hoofdnetwerk en belastingcombinaties ......32
7. COMMUNICATIE ..............................................................34
7.1. Algemene informatie over Modbus ....................................34
7.2. Regels RS485 ......................................................34
7.3. Communicatietabellen Modbus en Profibus ............................34
8. CONFIGURATIE ...............................................................35
8.1. Configuratie via Easy Config ..........................................35
8.1.1. Aansluitmodi ..............................................35
8.1.2. Easy Config gebruiken ......................................37
8.2. Configuratie vanaf het display ........................................40
8.2.1. Navigatie .................................................40
8.2.2. Beschrijving van de wizard ..................................40
8.2.3. Volledige configuratie .......................................41
8.3. Structuur van de schermmenu's ......................................43
NL
INHOUD:
3NL
DIRIS A-40 - 545802B - SOCOMEC
1. DOCUMENTATIE
Alle documentatie over de DIRISA-40 is beschikbaar op de
website op het volgende adres:
www.socomec.com/catalogues-brochures_en.html
9. GEBRUIK ....................................................................44
9.1. Bladeren ...........................................................44
9.2. Sneltoetsen ........................................................44
9.3. Favorieten ..........................................................44
9.4. Weergave van metingen op het scherm ................................44
10. ALARMEN ..................................................................45
10.1. Alarmen bij gebeurtenissen ..........................................45
10.1.1. Elektrische parameters ....................................45
10.1.2. Onbalans spanning en stroom (in een driefasig netwerk) ........45
10.1.3. Kwaliteitsgebeurtenissen spanning EN 50160 .................46
10.1.4. Verbruik .................................................46
10.1.5. Digitale ingangen .........................................46
10.1.6. Combinatie van alarmen ...................................46
10.2. Systeemalarmen ...................................................48
10.2.1. Compatibiliteit stroom/spanning ............................48
10.2.2. Verkeerde rotatierichting (driefasig netwerk) ...................48
10.2.3. Defecte stroomsensor .....................................48
10.3. Alarmen instellen ...................................................48
10.3.1. ALARM-LED op voorzijde ..................................48
10.3.2. Activering van een uitgang .................................48
10.3.3. Activering van een uitgang .................................48
10.3.4. RS485 Modbus ..........................................48
10.3.5. Scherm en WEBVIEW .....................................48
11. WEBSERVER ................................................................49
12. EIGENSCHAPPEN ...........................................................50
12.1. Eigenschappen van de DIRISA-40 ...................................50
12.1.1. Mechanische eigenschappen ...............................50
12.1.2. Elektrische specificaties ...................................50
12.1.3. Eigenschappen meting ....................................50
12.1.4. Eigenschappen ingangen/uitgangen .........................51
12.1.5. Specificaties communicatie ................................51
12.1.6. Specificaties omgeving ....................................52
12.1.7. Elektromagnetische compatibiliteit. . . . . . . . . . . . . . . . . . . . . . . . . . .52
12.1.8. Veiligheid ................................................53
12.1.9. Levensduur ..............................................53
12.2. Eigenschappen van de TE-, TR / iTR- and TF-sensoren .................54
13. PRESTATIEKLASSES .........................................................56
13.1. Specificatie van de eigenschappen ...................................56
13.2. Evaluatie van de kwaliteit van de voeding .............................57
4 NL
DIRIS A-40 - 545802B - SOCOMEC
2. GEVAREN EN WAARSCHUWINGEN
De term "paragraaf" in de paragrafen hieronder verwst naar de DIRISA-40.
De montage, het gebruik, reparatie en onderhoud van dit product mag alleen door opgeleide, gekwaliceerde
professionals worden uitgevoerd.
SOCOMEC kan niet verantwoordelk worden gesteld voor het niet naleven van de instructies in deze handleiding.
2.1. Gevaar van elektrocutie, brandwonden en explosie
Let op: gevaar van elektrische schok Ref. ISO 7000-0434B (2004-01)
Let op: zie de bijbehorende documentatie telkens wanneer dit
symbool wordt afgebeeld
Ref. ISO 7010-W001 (2011-05)
Alleen erkend en gekwaliceerd personeel mag onderhoud uitvoeren aan dit apparaat en/of dit apparaat
installeren/verwderen.
De instructies gelden in combinatie met de specieke instructies voor het apparaat.
Het apparaat is uitsluitend ontworpen voor het beoogde gebruik, zoals beschreven in de instructies.
Alleen accessoires die zn goedgekeurd door of aanbevolen door SOCOMEC mogen worden gebruikt in
combinatie met het apparaat.
Voordat u begint met installatie, onderhoud, reiniging, demontage, aansluiting of onderhoudswerkzaamheden
moeten het apparaat en het systeem worden losgekoppeld van de netvoeding om elektrocutie en
beschadiging van het systeem en het apparaat te voorkomen.
Het apparaat is niet ontworpen om te worden gerepareerd door de gebruiker.
Neem contact op met SOCOMEC indien u vragen hebt over het afdanken van het apparaat.
Klem of trek NIET-GEÏSOLEERDE geleiders met GEVAARLKE SPANNING NIET vast; dit kan een
elektrische schok, brand of vlamboog veroorzaken.
Ref. IEC 61010-2-032
Het niet naleven van de instructies van het apparaat en deze veiligheidsinformatie kan lichamelk letsel,
elektrische schok, brandwonen, overlden of schade aan eigendommen veroorzaken.
2.2. Gevaar van schade aan het apparaat
Let op: gevaar van elektrische schok Ref. ISO 7000-0434B (2004-01)
Let op: zie de bijbehorende documentatie telkens wanneer dit
symbool wordt afgebeeld
Ref. ISO 7010-W001 (2011-05)
Om te garanderen dat het apparaat naar behoren werkt, moet u het volgende controleren:
Het apparaat is correct geïnstalleerd.
Er is een maximumspanning b de ingangsklemmen van de spanningsmeting van 520 VAC fase-fase of 300
VAC fase-neutraal.
Er is een maximumspanning b de ingangsklemmen van de hulpvoeding van 400 VAC.
De netwerkfrequentie, zoals aangeduid op het toestel, is nageleefd: 50 of 60 Hz.
Sluit de TE-, TR- of TF-stroomsensoren steeds aan met de aanbevolen aansluitkabels en neem de
voorgeschreven maximale stroom in acht.
Wanneer de omgevingstemperatuur hoger dan +50°C is, moet de minimale temperatuurwaarde van de
koperen kabel die aangesloten moet worden op de klem +85°C zn.
5NL
DIRIS A-40 - 545802B - SOCOMEC
Het niet-naleven van deze voorzorgsmaatregelen kan schade aan het apparaat veroorzaken.
2.3. Verantwoordelkheid
Montage, aansluiting en gebruik moeten worden uitgevoerd volgens de momenteel geldende
installatienormen.
Het apparaat moet worden geïnstalleerd volgens de regels in deze handleiding.
Indien de installatieregels voor deze eenheid niet worden nageleefd, kan dat de intrinsieke bescherming van
het toestel compromitteren.
Het apparaat moet binnen een installatie worden geplaatst die voldoet aan de momenteel geldende normen.
Elke kabel die moeten worden vervangen, mag alleen door een kabel met de juiste specicaties worden
vervangen.
Ondanks het feit dat w voortdurend streven naar kwaliteit in het samenstellen van deze handleiding, kunnen
er altd fouten of ontbrekende informatie voorkomen, en is dit niet de verantwoordelkheid van SOCOMEC.
6 NL
DIRIS A-40 - 545802B - SOCOMEC
3. VOORBEREIDING
Om de veiligheid van personeel en de apparatuur te garanderen, is het van essentieel belang om de inhoud van
deze instructies grondig te lezen en in u op te nemen voordat u het apparaat in werking stelt.
Controleer de volgende punten zodra u het pakket met het apparaat heeft ontvangen:
De verpakking is in goede staat
Het apparaat is niet beschadigd tdens het transport
Het onderdeelnummer van het apparaat komt overeen met uw bestelling
Het pakket bevat:
- 1 apparaat met verwderbare klemmen
- 1 lnweerstand (ref. 48990019)
- 1 handleiding ‘Snel aan de slag’
7NL
DIRIS A-40 - 545802B - SOCOMEC
4. INLEIDING
4.1. Presentatie van de DIRISA-40
De DIRISA-40 is een compacte PMD* met een 96*96 formaat. Deze is ontworpen om elektrische energie te
meten, te bewaken en te melden. De DIRISA-40 biedt tal van functies om spanning, stroom, vermogen, energie en
kwaliteit te meten. Met het apparaat kan een enkelfasige of driefasige belasting worden geanalyseerd.
De DIRISA-40 heeft 3 digitale ingangen (pulsmeting, statuscontrole) en 2 uitgangen (alarm of pulsen). De
standaarduitvoering van het apparaat beschikt over RS485 Modbus-communicatie. Afhankelk van het model
kan ook ethernet- of Probus-communicatie worden geleverd. Het ethernet-model heeft tevens een ingebouwde
webserver.
De aansluitwze voor de stroomsensoren zorgt voor een snelle, eenvoudige installatie. De automatische identicatie
(type en klasse) door de DIRISA-40 beperkt de kans op fouten tdens de installatie aanzienlk. Bovendien betekent
deze aanpak, gebaseerd op de combinatie van de sensor en de DIRISA-40, dat de algehele nauwkeurigheid van
de meetketen bestaande uit de DIRISA-40 + stroomsensor kan worden gegarandeerd voor alle gemeten waarden.
Het product wordt gecongureerd vanaf het display of via de Easy Cong-software. De metingen kunnen
worden geopend via de WEBVIEW-webserver, beschikbaar op de DIRIS G-30, G-40, G-50 en G-60
communicatiegateways, voor realtime bewaking van de elektrische waarden en rapportage van de
energiegegevens. De gegevens kunnen eveneens worden geopend via de N’VIEW-software voor energiebeheer.
*PMD: Performance Measuring and Monitoring Device (apparaat voor prestatiemeting en -bewaking) conform IEC
61557-12.
4.1.1. Bereik
DIRISA-40
Ref. 4825 0500: Model met Modbus-communicatie
Ref. 4825 0501: Model met Modbus + Ethernet-communicatie
Ref. 4825 0502: Model met Modbus + Profibus-communicatie
8 NL
DIRIS A-40 - 545802B - SOCOMEC
4.1.2. Principe
L1
L2
L3
N
Stroomsensoren
TE, TR of TF
9NL
DIRIS A-40 - 545802B - SOCOMEC
4.1.3. Functies
De DIRISA-40 beschikt over tal van functies, waaronder:
Algemene metingen
- Elektrische waarden, spanning, stroom, frequentie
- Vermogen, vermogensfactor, cos phi en tan phi
- Werking met 4 kwadranten
- Voorspellend vermogen
- Algemene nauwkeurigheid van de meetketen bestaande uit DIRIS A-40 + sensoren gegarandeerd tot klasse
0,5
(afhankelk van de gebruikte stroomsensor) voor vermogen en actieve energie, in overeenstemming met IEC
61557-12
Kwaliteit
- Stroom, fase-naar-neutraal-spanning en fase-naar-fase-spanning
- THD, TDD en harmonischen tot niveau 63 voor spanning en stroom
- Piekfactor spanning en stroom
- Onbalans spanning en stroom
- K-factor
- EN50160 gebeurtenissen (Uswl, Udip, Uint) en stroomoverbelastingen
Gegevenslog
- Registratie van gemiddelde elektrische waarden
- Registratie en tdregistratie van min./max. elektrische waarden
Meting
- Actieve, reactieve, schnbare energie, totaal en gedeeltelk
- Belastingscurven
- Multi-tariefmeting
Alarm
- Tdgeregistreerde alarmen met booleaanse combinatie
- Geavanceerde alarmen
Aansluiting op het netwerk
-
3 stroomingangen met automatische herkenning van de stroomsensoren via snelle aansluiting (type RJ12)
- Regeling van de aansluiting, detectie van de stroomsensoren en automatische conguratie van de
netwerken
- Gegarandeerde algemene nauwkeurigheid van meetketen bestaande uit DIRIS A-40 + sensoren in
overeenstemming met IEC 61557-12
Ingangen/uitgangen
- 3 logische ingangen
- 2 logische uitgangen
Communicatie
- RS485 Modbus RTU
- RS485 Modbus RTU en Probus
- RS485 Modbus RTU en Ethernet
(Modbus TCP, BACnet)
Webserver
- Geïntegreerde webserver voor DIRIS A-40 ethernet (Ref. 4825 0501)
10 NL
DIRIS A-40 - 545802B - SOCOMEC
DIRISA-40
Referentie
4825 0500 4825 0501 4825 0502
Aantal stroomingangen 3 3 3
Meting
Totale en gedeeltelke Ea+, Ea-, Er+,
Er-, Eap
Multi-tarief (max. 8)
Multi-meting
V1, V2, V3, Vn, U12, U23, U31, f
I1, I2, I3, IN
P, Q, S, PF per fase, ∑P, ∑Q, ∑S, ∑PF
Voorspellend vermogen P, Q, S
Phi, cos Phi, tan Phi
Kwaliteit
Onbalans spanning Vnba, Vnb, Unba,
Unb
Onbalans stroom
Inba, Inb
THDV1, THDV2, THDV3, THDVn,
THDU12, THDU23, THDU31
THDI1, THDI2, THDI3, THDIn, THD
Isys, TDD
Individuele harmonischen V, U, I (tot
niveau 63)
Piekfactor, k-factor
Overspanningen, spanningsdalingen,
onderbrekingen van de netspanning
volgens EN 50160
Overstroom
Alarmen
Drempelwaarden
Digitaal
Booleaans
Ingangen/uitgangen:
Aantal 3/2 3/2 3/2
Trends
Belastingscurven
Energie-index
Gemiddelde waarden
Webserver
Vermogens- en Energiebewaking
Communicatie
RS485 RTU Modbus
RS485 Modbus RTU en Probus
DPV1
RS485 Modbus RTU en Ethernet
(Modbus TCP, BACnet)
SNTP, SMTP, FTP
11NL
DIRIS A-40 - 545802B - SOCOMEC
4.1.4. Afmetingen
Afmetingen: inch/mm
3,62
92
3,62
92
3,86
98
3,86
98
2,68
68
0,67
17
4.1.5. Voorpaneel
3.
2.
1.
1. Scherm 350 x 160
2. Leds
3. 10 capacitieve tiptoetsen
12 NL
DIRIS A-40 - 545802B - SOCOMEC
Het display bestaat uit een scherm en 10 toetsen:
Sneltoetsen voor belastingsmetingen: stroom, actief vermogen, reactief
vermogen, schnbaar vermogen vermogensfactor, cos phi
Sneltoetsen voor metingen van het elektriciteitsnet: fase-naar-neutraal-
spanning, fase-naar-fase-spanning, frequentie
Sneltoetsen voor de wizard door deze ingedrukt te houden
Sneltoetsen voor actieve, reactieve, schnbare energiemeters (totale en
gedeeltelke waarden)
Pltoetsen voor navigatie
Gebruik deze toets om één niveau omhoog te gaan in de
schermnavigatiemenu's en om terug te keren naar het hoofdmenu door de
toets ingedrukt te houden
Gebruik deze toets om favoriete schermen op te slaan door de toets ingedrukt
te houden en om ze vervolgens te bekken door een korte druk op de toets
Gebruik deze toets om favoriete schermen te verwderen door de toets
ingedrukt te houden
Gebruik deze toets om uw navigatie of invoerselectie te bevestigen
Led-display:
- Knipperend: meting van verbruikspulsen
pulsgewicht: 0,1 Wh
/ALARM
- Uit: geen alarm actief
- Knipperend: systeemalarm actief
- Vast brandend: alarm actief of alarm geëindigd en niet bevestigd
COM
- Uit: geen communicatie
- Knipperend: communicatie actief op de RS485-bus
ON
- Uit: apparaat is uit
- Aan: product werkt OK
OPMERKING: Als de 4 leds knipperen: er is een probleem gedetecteerd in het
apparaat
13NL
DIRIS A-40 - 545802B - SOCOMEC
4.2. Presentatie van bbehorende stroomsensoren
Er worden diverse soorten stroomsensoren aangesloten op de DIRISA-40: solid-core (TE), split-core (TR) of
exibel (TF). Het verschil tussen deze sensoren betekent dat ze kunnen worden aangepast aan elk soort nieuwe,
bestaande of sterkstroominstallatie. De DIRIS A-40 herkent de afmetingen en het type sensor. Door ze te
combineren kan de algemene nauwkeurigheid van de meetketen bestaande uit DIRISA-40 + stroomsensoren
worden gegarandeerd over een groot meetbereik.
DIRISA-40
Stroom-
sensoren
TE, TR of TF
Om de stroomsensoren aan te sluiten, mag u alleen kabels van SOCOMEC gebruiken, RJ12 rechte
kabels, met getwist aderpaar, zonder afscherming, 600VCAT III., -10°C / +70°C conform IEC 61010-1
editie 3.0.
Het is raadzaam dat alle stroomsensoren in dezelfde richting worden geïnstalleerd.
Aansluitkabels voor stroomsensoren:
Aansluitkabels
RJ12
Kabellengte (m)
0,1 0,2 0,3 0,5 1 2 5 10
50m haspel
+ 100
connectoren*
Aantal kabels
Onderdeelnummer
Referentie Referentie Referentie Referentie Referentie Referentie Referentie Referentie
1 - - - - - - 4829 0602 4829 0603 4829 0601
3 4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584 - - -
4 4829 0596 4829 0588 4829 0589 - - -
6 4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594 - - -
* B de productie van kabels mag de maximumlengte van 10 meter niet worden overschreden.
14 NL
DIRIS A-40 - 545802B - SOCOMEC
4.2.1. TE solid-core stroomsensoren
De TE solid-core stroomsensoren worden gebruikt om meetpunten op te zetten in een nieuwe of bestaande
installatie. Ze kunnen eenvoudig worden geïntegreerd aangezien ze compact zn en de spoed van de
vermogensschakelaars respecteren. Er is eveneens een ruim assortiment accessoires beschikbaar voor
eenvoudige directe plaatsing op alle soorten bekabeling (kabel, exibele kabel of starre rail) of op een DIN-railsteun
of -plaat.
Dankz deze specieke koppeling worden ze herkend door de DIRISA-40 en wordt er een hoog niveau van
algemene nauwkeurigheid van de meetketen gegarandeerd.
4.2.1.1. Bereik
TE-18 TE-18 TE-25 TE-35 TE-45 TE-55
Spoed
18 mm 18 mm 25 mm 35 mm 45 mm 55 mm
Nominaal
stroombereik
In
5 - 20A 25 - 63A 40 - 160A 63 - 250A 160 - 630A 400 - 1000A
Maximum I
24A 75,6A 192A 300A 756A 1200A
Referentie
4829 0500 4829 0501 4829 0502 4829 0503 4829 0504 4829 0505
TE-90
Spoed
90 mm
Nominaal
stroombereik
In
600 - 2000A
Maximum I
2400A
Referentie
4829 0506
15NL
DIRIS A-40 - 545802B - SOCOMEC
4.2.1.2. Afmetingen
LP
H
ØW
LP
H
ØW
L P
H
T
W
L P
H
T
W
Afmetingen
inch/mm
TE-18 TE-25 TE-35 TE-45 TE-55
Spoed
0,71
18 (verspringende montage)
0,98
25
1,37
35
1,77
45
2,16
55
LxHxD
1,10 x 0,79 x 1,77
28 x 20 x 45
0,98 x 1,28 x 2,56
25 x 32,5 x 65
1,37 x 1,28 x 2,79
35 x 32,5 x 71
1,77 x 1,28 x 3,38
45 x 32,5 x 86
2,16 x 1,28 x 3,93
55 x 32,5 x 100
Opening (B)
ø 0,33
ø 8,4
0,53 x 0,53
13,5 x 13,5
0,82 x 0,82
21 x 21
1,22 x 1,22
31 x 31
1,61 x 1,61
41 x 41
(T)
-
0,69
17,5
0,69
17,5
0,77
19,5
0,85
21,5
3.54
90
0.08
2.2
0.77
19.7
1.42
36
=
==
=
2.52 / 64
4.96
126
0.97
24.6
TE-90
16 NL
DIRIS A-40 - 545802B - SOCOMEC
4.2.2. TR / iTR split-core stroomsensoren
De TR / iTR split-core stroomsensoren worden gebruikt om meetpunten op te zetten in een nieuwe of bestaande
installatie, zonder de bekabeling van de installatie te hinderen. Dankz deze specieke koppeling worden ze
herkend door de DIRISA-40 en wordt de algemene nauwkeurigheid van de meetketen gegarandeerd.
Bovendien detecteren iTR-sensoren de aanwezigheid van spanning in de kabel die erdoorheen loopt.
4.2.2.1. Bereik
Er zn vier modellen beschikbaar, van 25 A tot 600 A, om diverse soorten belastingen te analyseren.
TR-10 / iTR-10 TR-14 / iTR-14 TR-21 / iTR-21 TR-32 / iTR-32
Diameter
kabeldoorgang
diameter 10mm diameter 14mm diameter 21mm diameter 32mm
Nominaal
stroombereik In
25 - 63 A 40 - 160 A 63 - 250 A 160 - 600 A
Aanbevolen
kabeldoorsnede
6 mm² (iTR-10) 10 mm² (iTR-14) 50 mm² (iTR-21) 50 mm² (iTR-32)
Maximum I
75,6A 192A 300A 720A
Referentie
4829 0555 / 4829 0655 4829 0556 / 4829 0656 4829 0557 / 4829 0657 4829 0558 / 4829 0658
4.2.2.2. Afmetingen
D
B C
A
E
Afmetingen
inch/mm
TR-10 / i TR-10 TR-14 / i TR-14 TR-21 / iTR-21 TR-32 / iTR-32
A
1,74
44
2,63
67
2,56
65
3,38
86
B
1,02
26
1,14
29
1,45
37
2,08
53
C
1,10
28
1,10
28
1,69
43
1,85
47
D
-
0,55
14
0,82
21
1,26
32
T
-
0,59
15
0,90
23
1,30
33
Diameter
0,39
10
0,55
14
0,82
21
1,26
32
17NL
DIRIS A-40 - 545802B - SOCOMEC
4.2.3. TF exibele stroomsensoren
De TF exibele stroomsensoren maken gebruik van het Rogowski-principe, waardoor een groot stroombereik
kan worden gedekt zonder saturatie. Flexibel ontwerp en eenvoudig openend systeem voor snelle installatie in
elektriciteitskasten. Deze zn bzonder geschikt om meetpunten toe te voegen aan bestaande installaties en voor
testcampagnes.
4.2.3.1. Bereik
Er zn drie modellen beschikbaar, voor een groot stroombereik tot 6000 A met openingen in verschillende vormen
en formaten.
Om het stroomsignaal vorm te geven, is een integrator vereist. Dankz deze specieke koppeling worden ze
herkend door de DIRISA-40 en wordt de algemene nauwkeurigheid van de meetketen gegarandeerd.
Wegens de specieke RJ12-aansluiting, kunnen de TF-stroomsensoren alleen worden gebruikt met DIRIS
Digiware I, DIRIS B en DIRIS A-40. Bij gebruik samen met deze PMD uitgerust met RJ12-aansluitingen,
is de algemene nauwkeurigheid van de meetketen gegarandeerd.
TF-40 TF-80 TF-120 TF-200 TF-300 TF-600
Ø (mm)
40 80 120 200 300 600
I nom. (a.c.)
100 … 400A 150 … 600A 400 … 2000A 600 … 4000A 1600 … 6000A 1600 … 6000A
Referentie
4829 0573 4829 0574 4829 0575 4829 0576 4829 0577 4829 0578
4.2.3.2. Dimensions
Dimensions in/mm
TF-40 TF-80 TF-120 TF-200 TF-300 TF-600
Diameter D
1.57
40
3.15
80
4.72
120
7.87
200
11.81
300
23.62
600
Perimeter P
4.96
126
9.88
251
14.84
377
24.72
628
37.09
942
74.21
1885
Integrator
8.04 x 0.75 x 0.6
128 x 19 x 15
L
D
3.94
3.94
Ø 0.33
100
100
Ø 8.3
18 NL
DIRIS A-40 - 545802B - SOCOMEC
4.2.4. Adapters voor sensoren van 5 A
Met deze adapter kunt u een standaardsensor gebruiken, die 1 A of 5 A stroom naar de secundaire sensor voert.
Als dit type sensor wordt gebruikt, is de algemene nauwkeurigheid van de DIRISA-40 + sensor niet gegarandeerd
en zal deze afhankelk zn van de gekoppelde sensor (zie de norm “IEC 61557-12” voor meer informatie).
De primaire stroom is max. 10.000 A/5 A of 2000 A/1 A.
4.2.4.1. Bereik
Adapter 5 A
I nom.
5A
I max.
6A
Referentie
4829 0599
4.2.4.2. Afmetingen
LP
H
ØW
LP
H
ØW
Afmetingen
inch/mm
Adapter 5 A
LxHxD
1,10 x 0,79 x 1,77
28 x 20 x 45
Opening (B)
ø 0,33
ø 8,4
19NL
DIRIS A-40 - 545802B - SOCOMEC
5. INSTALLATIE
In de volgende paragrafen wordt de installatie van de DIRISA-40 en gekoppelde sensoren beschreven.
5.1. Aanbevelingen en veiligheid
Zie de veiligheidsinstructies (deel “2. Gevaren en waarschuwingen”, pagina 4)
Blf uit de buurt van systemen die elektromagnetische interferentie gegenereren.
Vermd trillingen met versnellingen van hoger dan 1 g b frequenties lager dan 60 Hz.
Het apparaat mag niet worden gereinigd.
Niet buiten installeren.
5.2. Installatie van DIRIS A-40
De DIRISA-40 moet geïnstalleerd worden op een deur met een opening van 92 x 92mm.
Afmetingen: inch/mm
3,62
92
3,62
92
20 NL
DIRIS A-40 - 545802B - SOCOMEC
5.3. TE solid-core sensoren installeren
5.3.1. Accessoires voor montage
De b de sensoren geleverde accessoires voor montage staan hieronder:
Referentie Spoed
Montage op DIN-rail en
plaat
Montage op DIN-rail Montage op plaat Montage op rail
4829 0500
4829 0501
TE-18 18 mm
x 1
4829 0502
TE-25 25 mm
x 2 x 4
4829 0503
TE-35 35 mm
x 2 x 4 x 2
4829 0504
TE-45 45 mm
x 2 x 4 x 2
4829 0505
TE-55 55 mm
x 2 x 4 x 2
4829 0506
TE-90 90 mm
x 2 x 6
5.3.2. Montage op DIN-rail
TE-18 -> TE-55
21NL
DIRIS A-40 - 545802B - SOCOMEC
TE-90
2
1
Klemmen verwderen
of
Opmerking: Monteer sensor TE-90 op de DIN-rail om de installatie te vereenvoudigen. Dit is een tdelke installatie.
Gebruik de klemmen om de TE-90 sensoren op de DIN-rail te installeren.
22 NL
DIRIS A-40 - 545802B - SOCOMEC
5.3.3. Montage op plaat
TE-18
1x
diameter0,17 /
4,2 M4max.
1Nm
0,81
20,5
1,05
26,8
1
1
2
2
2
2
3
3
TE-25 - > TE-55
4x
diameter0,20
/ 5,2 M5max.
1Nm
23NL
DIRIS A-40 - 545802B - SOCOMEC
TE-90
2
1
Klemmen verwderen
x6
diameter 0,20
diameter 5,2
Opmerking: Gebruik de klemmen om de TE-90 sensoren op het paneel te installeren.
24 NL
DIRIS A-40 - 545802B - SOCOMEC
5.3.4. Installeren op een kabel met klemmende kraag
TE-18 TE-25 - > TE-55
2
3
1
TE-90
2
1
Klemmen verwderen
I
Opmerking: Gebruik de klemmen om de TE-90 sensoren op een kabel met klemmende kraag te installeren.
Klem of trek NIET-GEÏSOLEERDE geleiders met GEVAARLKE SPANNING NIET vast; dit kan een
elektrische schok, brand of vlamboog veroorzaken.
Ref. IEC 61010-2-032
25NL
DIRIS A-40 - 545802B - SOCOMEC
5.3.5. Montage op stang
TE-35 - > TE-55
A
A A
C
B
Installatieopties:
A+B, A+C
0,4Nm, 4 mm
sleutel
B
C
TE-90
of
Oefen druk uit om de bek
-
ken aan beide zden van de
kabel aan te spannen.
De bekken moeten lood
-
recht op de inkepingen voor
bevestiging staan.
60x10mm50x10mm
I
I
21
Klem of trek NIET-GEÏSOLEERDE geleiders met GEVAARLKE SPANNING NIET vast; dit kan een
elektrische schok, brand of vlamboog veroorzaken.
Ref. IEC 61010-2-032
26 NL
DIRIS A-40 - 545802B - SOCOMEC
5.3.6. Montage sensoren
TE-18 TE-25 - > TE-55 TE-35 - > TE-55
1,42
36
Verspringende montage
2x
Lineaire montage
1x
Verspringende montage
Accessoires monteren voor sensorcombinatie:
Referentie
Lineaire montage Verspringende montage
4829 0598
x30
Deze accessoires moeten afzonderlk worden besteld.
5.3.7. Accessoires voor afdichting van sensoren
2
1
Referentie
Afdichtbehuizing voor klem
4829 0600
x20
Deze accessoires moeten afzonderlk worden besteld.
27NL
DIRIS A-40 - 545802B - SOCOMEC
5.4. TR split-core sensoren installeren
5.4.1. Kabelmontage
2
Alleen installeren op 300V
geïsoleerde kabels!
1
K
L
I
3
Scherpe randen
Aanbevolen
installatie
Klem of trek NIET-GEÏSOLEERDE geleiders met GEVAARLKE SPANNING NIET vast; dit kan een
elektrische schok, brand of vlamboog veroorzaken.
Ref. IEC 61010-2-032
Controleer dat de luchtspleet schoon is (geen verontreiniging of corrosie) vooraleer de TR-sensor te
sluiten
28 NL
DIRIS A-40 - 545802B - SOCOMEC
5.5. Montage van exibele TF-sensoren
5.5.1. Baar- of kabelmontage
!
1 2
3 4
I
DIRIS Digiware I
DIRIS B
DIRIS A-40
=
=
=
=
=
=
=
=
Gecentreerde positie voor de beste meting
Gecentreerde positie voor de beste meting
=
=
=
=
=
=
=
=
Klem of trek NIET-GEÏSOLEERDE
geleiders met GEVAARLKE
SPANNING NIET vast; dit kan
een elektrische schok, brand of
vlamboog veroorzaken.
Ref. IEC 61010-2-032
29NL
DIRIS A-40 - 545802B - SOCOMEC
5.6. De 5A-adapter installeren
4
3
1
2
5 A secundaire
stroomtransformator
Klem of trek NIET-GEÏSOLEERDE geleiders met GEVAARLKE SPANNING NIET vast; dit kan een
elektrische schok, brand of vlamboog veroorzaken.
Ref. IEC 61010-2-032
30 NL
DIRIS A-40 - 545802B - SOCOMEC
6. AANSLUITING
6.1. Aansluiting van de DIRISA-40
DIRIS A-40 ref. 4825 0501
x
1
2 x UITGANG
0
1
30 VDC - 20 mA max. - SELV
x= 7 mm
0,14 mm² - 1,5 mm²
0,25 Nm max.
2
3 x INGANG
12 VDC - 27 mA max. - SELV
0
1
x= 7 mm
0,14 mm² - 1,5 mm²
0,25 Nm max.
3
RS485 MODBUS
SELV
x= 7 mm
0,14 mm² - 1,5 mm²
0,25 Nm max.
4
VOEDING
110-400VAC 50-60Hz
120-300VDC
x= 7 mm
0,2 mm² - 2,5 mm²
0,6 Nm max.
5
V1-V2-V3-VN
50-300VAC (Ph/N)
87-520VAC (Ph/Ph)
x= 7 mm
0,2 mm² - 2,5 mm²
0,6 Nm max.
6
ETHERNET
(Ref. 4825 0501)
PROFIBUS
(Ref. 4825 0502)
- -
7
x= 8 mm
0,2 mm² - 4 mm²
0,6 Nm max.
Type B micro-
USB
TE- / TR- / TF-sensoren
3 x I
ETH
1
2
3
4
5
6
7
SELV: Safety Extra Low Voltage
DIRIS A-40 ref. 4825 0500 DIRIS A-40 ref. 4825 0502
Communicatie
PROFIBUS
31NL
DIRIS A-40 - 545802B - SOCOMEC
Beschrving van de klemmen
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETHETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETHETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTAGE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETHETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTAGE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
Ethernet
DIRIS A-40 ref. 4825 0501
PROFIBUS
DIRIS A-40 ref. 4825 0502
RS485
DIRISA-40
ref. 48250500
ref. 48250501
ref. 48250502
RS485
VOEDING
SPANNING
VOEDING
4
Hulpvoeding
Digitale ingangen Digitale uitgangen
TE-/TR-/TF-SENSOREN
0,5 A gG / BS 88 2 A gG / 0,5 A klasse CC
Vermelde zekeringen voor UL-toepassing
N / -
L / +
110-277VAC L/N 50-60Hz
277-400VAC L/L' 50-60Hz
120-300 VDC
I 01 I 02 I 03
1
2
3
12VDC
1
2
3
10-30VDC
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETH
ETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTAGE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETH
ETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTA GE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTA GE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTA GE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
N
L1
L2
L3
V2
VN
V3
110-230VAC
110-230VAC
V1
VNV1
N
L1
L2
L3
V2
VN
V3
V1
VNV1
N
L
N
L
1
2
IN
NC
RS485
LIYCY-CY
**
*
1
2
IN
10-30VDC
12VDC
RS485 MODBUS
3 x INGANG
2
2 x UITGANG
1
Communicatie
3
6
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETHETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTAGE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
PROFIBUS
FE
V2 V3 VNV1
N / -
L / +
NC
-
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
OUTPUT
ETHETH
I 01 I 02 I 03
TE/TR/TF
SENSORS
FE
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Instructions: 545801 Instructions: 545801 Instructions: 545801
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
FE
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Probus
DPV1
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
I 01 I 02 I 03
TE/TR/TF
SENSORS
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
VOLTAGE
110/400 V
~
50-60Hz (10VA)
120/300V
5 4 3 2 1
D-SUB 9
9 8 7 6
FE
V2 V3 VNV1
50-300 V~(Ph/N) 87-520V~(Ph/Ph) CAT. III
SUPPLY
N / -
L / +
RS485
NC
10 to 30 Vd.c.
27mA max
-
+
IN1
IN2
IN3
INPUT
1+ 1- 2+ 2-
30 Vd.c. max
20mA max
OUTPUT
Mac address: XX:XX:XX:XX:XX:XX
ETHETH
VOLTAGE
I 01 I 02 I 03
TE/TR/TF
SENSORS
110/400 V
~
50-60Hz (10VA)
120/300V
ETHERNET
of
1: NC
2: NC
3: B
4: NC
5: GND
6: VCC
7: NC
8: A
9: NC
Middelen om losraking van de geleiders te voorkomen moeten worden gemonteerd op de dichtstbznde aansluiting.
32 NL
DIRIS A-40 - 545802B - SOCOMEC
6.2. Aansluiting op het elektriciteitsnet en op de belastingen
De DIRISA-40 kan worden gebruikt op enkelfasige, tweefasige of driefasige netwerken.
6.2.1. Congureerbare belastingen op basis van het type netwerk
De onderstaande tabel biedt een overzicht van de belasting die gecongureerd kan worden, afhankelk van het
type netwerk b de installatie.
Netwerktype Configureerbare belasting
1P+N enkelfasig
1P+N – 1CT
2P tweefasig
2P – 1CT
2P+N tweefasig
2P+N - 2CT
3P driefasig
3P – 3CT / 3P – 2CT / 3P – 1CT
3P+N driefasig
3P+N – 3CT / 3P+N – 1CT
6.2.2. Beschrving van het hoofdnetwerk en belastingcombinaties
Legenda:
3P+N – 3CT
2 2 2
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
333
I01 I02 I03
1 1 1
I01
V1 V2 V3 VN
V
I
L1
L2
N
I01 I02 I03
3+ N
3
3
2+ N
3
Driefasige belasting
Stroomsensor (CT)
Stroomklem
Spanningsklem
Driefasig + Neutraal netwerk
met 3 stroomsensoren
= Stroomsensor TE / TR / TF
3
3
= Gebalanceerde belasting
3
3
= Ongebalanceerde belasting
Driefasig + Neutraal
3P+N – 3CT
(1 driefasige belasting + gemeten Neutraal)
Driefasig
3P – 3CT
(1 driefasige belasting)
2 2 2
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
333
I01 I02 I03
1 1 1
I01
V1 V2 V3 VN
V
I
L1
L2
N
I01 I02 I03
3+ N
3
3
2+ N
3
2 2 2
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
333
I01 I02 I03
1 1 1
I01
V1 V2 V3 VN
V
I
L1
L2
N
I01 I02 I03
3+ N
3
3
2+ N
3
33NL
DIRIS A-40 - 545802B - SOCOMEC
Driefasig
3P – 2CT
(1 ongebalanceerde driefasige belasting)
Driefasig
3P+N – 1CT
(1 gebalanceerde driefasige belasting)
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
De 2CT-oplossing vermindert de nauwkeurigheid van de fase waarvoor de stroom wordt afgeleid via een
vectorberekening met 0,5%.
Driefasig
3P – 1CT
(1 gebalanceerde driefasige belasting)
Tweefasig + Neutraal
2P+N – 2CT
(1 tweefasige belasting + gemeten Neutraal)
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
Tweefasig
2P – 1CT
(1 tweefasige belasting)
Enkelfasig
1P+N – 1CT
(1 enkelfasige belasting)
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
V1 V2 V3 VN
V
I
L1
L2
I01 I02 I03
V1 V2 V3 VN
V
I
L1
N
I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
1
I01
3+ N
3
3
V1 V2 V3 VN
V
I
L1
L2
L3
N
I01 I02 I03
2
V1 V2 V3 VN
V
L1
L2
N
I01 I02 I03
2+ N
I
3 + N
I
I01 I02 I03
I
V
I
V
V
I
111
N
V1 V2 V3 VN
L1
L2
L3
I01 I02 I03
V1 V2 V3 VN
V
L1
L2
I01 I02 I03
V1 V2 V3 VN
L1
N
I02 I03
N
V1 V2 V3 VN
I
L1
L2
L3
3
I01 I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
3
I01 I02 I03
N
V1 V2 V3 VN
V
I
L1
L2
L3
333
I01 I02 I03
I01
N
V1 V2 V3 VN
V
I
L1
L2
L3
I01 I02 I03
3+ N
N
V1 V2 V3 VN
V
L1
L2
L3
222
3+ N
1 1 1
Zekering: 0,5 A gG / 0,5 A klasse CC
34 NL
DIRIS A-40 - 545802B - SOCOMEC
7. COMMUNICATIE
7.1. Algemene informatie over Modbus
De Modbus RTU die aanwezig is op de DIRISA-40 communiceert via een RS485-koppeling (2 of 3 draden) die
gebruikt wordt voor het besturen van producten vanaf een pc of een API.
In een standaardconguratie wordt een RS485-aansluiting gebruikt om 32 producten aan te sluiten op een pc of
een controller over 1200 meter.
+ - NC
N 1
+ - NC
N 2
+ - NC
N n
+ - NC
N 1
+ - NC NC - + + - NC
N n
Programmeerbare
machines
Programmeerbare
machines
Overige systemen
Overige systemen
Repeater
7.2. Regels RS485
Er moet een afgeschermde LIYCY-kabel met getwist aderpaar worden gebruikt. W adviseren het gebruik van een
afgeschermd getwist aderpaar met een algemene LIYCY-CY afscherming in een omgeving waarin er interferentie is
of in een zeer lang netwerk met meerdere producten.
Als de afstand van 1200 m overschreden wordt en/of het aantal producten groter is dan 32, dan moet er een
repeater worden toegevoegd om extra producten te kunnen aansluiten.
Aan beide uiteinden van de koppeling moet een weerstand van 120 ohm worden aangebracht.
7.3. Communicatietabellen Modbus en Probus
De Modbus- en Probus-communicatietabellen en de bbehorende
toelichten zn beschikbaar op de documentatiepagina van DIRIS
A-40 op de website, op het volgende adres:
35NL
DIRIS A-40 - 545802B - SOCOMEC
8. CONFIGURATIE
Het apparaat kan rechtstreeks vanaf het scherm van de DIRIS A-40 worden gecongureerd of met de Easy Cong-
software. In de volgende paragrafen wordt conguratie met Easy Cong beschreven voor verschillende typen
communicatieprotocollen en verschillende typen SOCOMEC-producten.
8.1. Conguratie via Easy Cong
8.1.1. Aansluitmodi
Directe conguratie met Easy Cong (USB)
DIRISA-40 RS485
USB-kabel voor
conguratie:
ref.48290050
Easy
Cong
Pc
USB
Conguratie met Easy Cong via een DIRIS G gateway (USB)
RS485 RS485 RS485
DIRIS Digiware C-31
DIRIS G
DIRISA-40
RS485
DIRIS B-30
Easy
Cong
Pc
USB
Conguratie met Easy Cong via een DIRIS G monitor (USB)
Easy
Cong
Pc
USB
DIRIS Digiware D-50 / D-70
RS485
RS485
DIRIS B-30
DIRISA-40
36 NL
DIRIS A-40 - 545802B - SOCOMEC
Conguratie met Easy Cong via een DIRIS G gateway (Ethernet)
RS485 RS485 RS485
DIRIS Digiware C-31
DIRIS G
DIRIS
A-40
RS485
DIRIS B-30
Ethernet
Easy
Cong
DIRISA-40
Pc
Conguratie met Easy Cong via een DIRIS D-50 / D-70 monitor (Ethernet)
DIRISA-40
Ethernet
Easy
Cong
Pc
DIRIS Digiware D-50 / D-70
RS485
RS485
DIRIS B-30
DIRIS
A-40
37NL
DIRIS A-40 - 545802B - SOCOMEC
8.1.2. Easy Cong gebruiken
Easy Cong is conguratiesoftware die wordt gebruikt om productparameters snel en eenvoudig in te stellen.
Parameters worden stapsgews ingesteld:
(1)
(2)
Voor elke geselecteerde instelling (1) wordt een aangepast scherm weergegeven, afhankelk van het aangesloten
product (2).
38 NL
DIRIS A-40 - 545802B - SOCOMEC
Conguratie van de belasting
Het type belasting is beschikbaar in het conguratiemenu van de belastingen. De gebruiker kan ook de nominale
stroom, de naam van de belasting, het gebruik en de locatie ervan in de elektrische installatie deniëren.
De gebruiker selecteert de nominale spanning, de netwerkfrequentie, de richting van de faserotatie en of er een
spanningstransformator wordt gebruikt of niet.
Berekeningsmethode
De integratieperiode en de synchronisatiemethoden van de verschillende elektrische parameters worden
gedenieerd op dit scherm.
39NL
DIRIS A-40 - 545802B - SOCOMEC
Alarmen
Het type alarm en de conguratie worden ingesteld in Easy Cong, zie deel "10. ALARMEN” voor verdere
informatie.
Overige instellingen
De overige instellingen, zoals geheugentoewzing, multi-tarief, ingangen/uitgangen, kwaliteitsgebeurtenissen,
communicatie en andere regelingen worden ook uitgevoerd met Easy Cong.
Voorbeeld van het scherm voor het instellen van de kwaliteitsparameters van het elektrische netwerk:
40 NL
DIRIS A-40 - 545802B - SOCOMEC
8.2. Conguratie vanaf het display
8.2.1. Navigatie
Om toegang te krgen tot navigatie drukt u op "OK" om de verschillende menu's te bekken:
HOME
|
load 1
MEASURES
INPUTS/OUTPUTS
EVENTS
WIZARD CONFIG
PARAMETERS
...
8.2.2. Beschrving van de wizard
Met de wizard kunnen de belangrkste parameters van de DIRIS A-40 zeer snel gecongureerd worden:
De wizard wordt automatisch gestart b het eerste gebruik en op verzoek b later gebruik. Het is ook mogelk om
de wizard te openen door de
toets ingedrukt te houden of via het menu op het scherm met de navigatietoetsen
"PL OMHOOG" en "PL OMLAAG" en te bevestigen met "OK".
HOME
|
load 1
MEASURES
INPUTS/OUTPUTS
EVENTS
CONFIG-WIZARD
PARAMETERS
...
De wizard begint met het kiezen van de taal, waarna de belangrkste parameters van de DIRIS A-40 gecongureerd
kunnen worden door middel van een serie schermen:
Datum/td
Type belasting
Integratieperiode
Communicatie
De wizard kan worden gestart met behulp van 2 modi die gekozen worden door de gebruiker:
"SMART CONFIG"-modus: Het type elektrische netwerk en de belasting worden automatisch gedetecteerd
"MANUAL CONFIG"-modus: de gebruiker congureert zelf de parameters van het elektrische netwerk en van
de belasting
41NL
DIRIS A-40 - 545802B - SOCOMEC
Opmerking: de standaard toegangscode voor conguratie is 100
8.2.3. Volledige conguratie
Om toegang te krgen tot de volledige conguratie van het product en in het bzonder tot de conguratie van de
alarmen en de aanvullende parameters die niet voorkomen in de wizard, selecteert u het menu "PARAMETERS":
HOME
|
LOADS
MEASURES
EVENTS
PARAMETERS
ABOUT
Voer het wachtwoord "100” in met de plen (4 pltoetsen) en bevestig met "OK":
HOME
|
LOADS
CODE 100
MEASURES
EVENTS
PARAMETERS
ABOUT
dit geeft toegang tot de volledige conguratie van de DIRIS A-40:
PARAMETERS
|
DISPLAY
LOAD
SENSORS
CALCULATION
INPUTS/OUTPUTS
PARAMETERS
|
...
RS485 COMMUNICATION
ETHERNET COMMUNICATION
LOAD CURVES
CONSUMPTION CURVES
ALARMS CONFIGURATION
METRO LED
42 NL
DIRIS A-40 - 545802B - SOCOMEC
DISPLAY: selectie van de taal, van de datum en td en van de toegangscode
LOAD: selectie van het type belasting, de nominale stroom, rotatie en de spanningstransformator
SENSORS: selectie van de stroomrichting
CALCULATION: selectie van de onmiddellke en gemiddelde integratieperiode
INPUTS/OUTPUTS: instellingen voor de in- en uitgangen
RS485 COMMUNICATION: instellingen van de RS485-communicatieparameters
ETHERNET COMMUNICATION: instellingen van de Ethernet-communicatieparameters
PROFIBUS COMMUNICATION: instellingen van de Probus-communicatieparameters
LOAD CURVES: instellingen van de integratieperiode, synchronisatie en selectie van de berekende
belastingscurven
CONSUMPTION CURVES: instellingen van de integratieperiode en synchronisatie van de verbruikscurven
ALARMS CONFIGURATION: conguratie van de alarmen
METRO LED: instellingen van de metrologische LED-parameters
43NL
DIRIS A-40 - 545802B - SOCOMEC
8.3. Structuur van de schermmenu's
Menustructuur
Metingen
Spanningen
Spanning fase-neutraal
Spanning fase-fase
Frequentie
Onbalans spanning fase-neutraal
THD spanning fase-neutraal
THD netwerk fase-neutraal
Harmonischen spanning fase-neutraal
Piekfactor spanning fase-neutraal
Onbalans spanning fase-fase
THD spanning fase-fase
Harmonischen spanning fase-fase
Piekfactor spanning fase-fase
Stroom
Stroom
Stroom systeem
Onbalans stroom
THD stroom
K-factor stroom
Harmonischen stroom
Piekfactor stroom
Vermogen
Actief vermogen
Reactief vermogen
Schnbaar vermogen
Voorspellend vermogen
Vermogensfactor
Cos phi
Tan phi
Energie
Positieve actieve energie
Negatieve actieve energie
Positieve reactieve energie
Negatieve reactieve energie
Positieve/negatieve inductieve/capacitieve reactieve energie
Schnbare energie
Reset
Resetten van alle min./max. waarden
Ingangen/uit-
gangen:
Digitale ingangen
Status
Digitale uitgangen
Status
Gebeurtenis-
sen
Bezig
Alarmen en kwaliteitsgebeurtenissen bezig
Geschiedenis
Alarmen en kwaliteitsgebeurtenissen beëindigd en geregistreerd
Conguratiewizard
Wizardconguratieschermen
Parameters
Scherm
Talen, datumnotatie, datum, td, toegangscode conguratie
Belastingen
Type belastingen, nominale waarden (V, I, f), rotatie, spanningstransformator
Sensoren
Gedetecteerde stroomrichting, transformatieverhouding
Integratieperiode
Onmiddellke en gemiddelde waarden van de integratieperiode
Ingangen/uitgangen:
Naam, functie (status, stroomonderbreker, pulsmeter), modus (N.O., N.C.)
RS485-communicatie
Modemsnelheid, stopbit, pariteit, adres
Ethernet-communicatie
DHCP, IP-adres, template, router
Probus-communicatie
Adres, uitwisselingen met de master (parameters en diagnostiek)
Belastingscurven
Integratieperiode, synchronisatie, keuze welke belastingscurven moeten worden opgeslagen (P+, P-, Q+, Q-, S)
Verbruikscurven
Integratieperiode, synchronisatie
Alarmconguratie
Alarm b onmiddellke meting, alarm b digitale ingang, systeemalarm
Metrologische LED
Keuze welke energie wordt toegewezen aan de led (Ea+, Ea-, Er+, Er-, Es)
Informatie
IP-adres
MAC-adres
Serienummer
Softwareversie
Reboot
Opmerking: welke menu's beschikbaar zn is afhankelk van het productmodel.
44 NL
DIRIS A-40 - 545802B - SOCOMEC
9. GEBRUIK
9.1. Bladeren
Door te bladeren door het menu "MEASUREMENTS" krgt u toegang tot alle metingen.
3 sec. indrukken
Charge
Measurements
Voltage Phase-neutral load
Events Current Phase-phase load
Parameters Power Net. frequency
. . .
. . . . . .
9.2. Sneltoetsen
Met de sneltoetsen op het scherm "IP", "E", "VF" krgt u snel toegang tot de stroom-, vermogen-, energie-,
spannings- en frequentiemetingen.
Sneltoetsen voor belastingsmetingen: stroom, actief vermogen, reactief
vermogen, schnbaar vermogen vermogensfactor, cosinus phi
Sneltoetsen voor metingen van het elektriciteitsnet: fase-naar-neutraal-
spanning, fase-naar-fase-spanning, frequentie
Sneltoetsen voor de wizard door deze ingedrukt te houden
Sneltoetsen voor actieve, reactieve, schnbare vermogensmeters (totale en
gedeeltelke uitlezingen)
9.3. Favorieten
Gebruik de functie Favorieten om specieke schermen op te slaan en ze direct te openen, zonder door de menu's
te hoeven bladeren.
Gebruik deze toets om favoriete schermen op te slaan door de toets ingedrukt
te houden en om ze vervolgens te bekken door een korte druk op de toets
Gebruik deze toets om favoriete schermen te verwderen door de toets
ingedrukt te houden
9.4. Weergave van metingen op het scherm
De onmiddellke en/of gemiddelde waarden worden weergegeven afhankelk van het type metingen, als numerieke
waarde of in grasche vorm.
45NL
DIRIS A-40 - 545802B - SOCOMEC
10. ALARMEN
10.1. Alarmen b gebeurtenissen
Er kunnen alarmen worden gegenereerd wanneer een drempelwaarde wordt overschreden voor de elektrische
metingen, verbruik, variaties in niveau of verandering van ingangsstatus. Er kunnen eveneens combinaties van de
gecreëerde alarmen worden gemaakt.
Maximaal 50 gedetecteerde alarmen worden opgeslagen met tdregistratie; een alarm kan 3 verschillende
statussen hebben: Alarm actief, Alarm voltooid, Alarm voltooid en bevestigd. Alarmen kunnen, naar wens,
automatisch of door een actie van de gebruiker worden bevestigd.
Per apparaat kunnen maximaal 8 alarmen voor een elektrische meting worden gecongureerd en 9 voor
veranderingen van de status van een digitale ingang.
De alarmen worden gecongureerd op het scherm of via de Easy Cong-software.
10.1.1. Elektrische parameters
Alarm b variatie in de ogenblikkelke of gemiddelde waarde van een elektrische waarde: Stroom, spanning,
frequentie, vermogen, vermogensfactor, Cos phi, harmonische vervorming
Selectie van de hysterese en hoge/lage drempel
Vertraging instellen b begin en einde van het alarm
Voor de gekoppelde waarden voor totale harmonische vervorming, driefasige spanning en stroom kan een
alarm worden gegenereerd indien aan de voorwaarde is voldaan op een combinatie van fasen:
- B enkelfasig: Fase1, Fase2, Fase3
- B alle fasen gelktdig: Fase1 en Fase2 en Fase3
- B één van de drie fasen: Fase1 of Fase2 of Fase3
Voorbeeld van een conguratie van een alarm op de stroom via Easy Cong:
10.1.2. Onbalans spanning en stroom (in een driefasig netwerk)
Alarmen b onbalans spanning: Unba, Unb
Alarm b onbalans stroom: Inba, Inb
Selectie van de hysterese en hoge/lage drempel
Vertraging instellen b begin en einde van het alarm
46 NL
DIRIS A-40 - 545802B - SOCOMEC
10.1.3. Kwaliteitsgebeurtenissen spanning EN 50160
Alarmen b kwaliteitsgebeurtenissen voor de geleverde spanning: spanningsdalingen (Udip), tdelke
overspanningen (Uswl) en spanningsonderbrekingen (Uint).
10.1.4. Verbruik
Alarmen b energie: Ea+, Ea-, Er+, Er-, Eap
Selectie van een hoge drempel (excessief verbruik)
10.1.5. Digitale ingangen
Alarm b verandering van status voor een digitale ingang
Keuze van een stgende of dalende rand
Vertraging instellen b begin en einde van het alarm
Voorbeeld van een conguratie van een alarm op een digitale ingang via Easy Cong:
10.1.6. Combinatie van alarmen
4 booleaanse combinaties (OF, EN) op de gedenieerde alarmen (elektrische waarden, energie, ingangen,
47NL
DIRIS A-40 - 545802B - SOCOMEC
enz.)
48 NL
DIRIS A-40 - 545802B - SOCOMEC
10.2. Systeemalarmen
Indien een installatiefout wordt gedetecteerd tdens het instellen, wordt automatisch een alarm gegenereerd.
10.2.1. Compatibiliteit stroom/spanning
Alarm b aansluitfout tussen de stroom en de spanning
Bepaald belastingniveau vereist: 0,6< PF < 1 en I > 2% In
10.2.2. Verkeerde rotatierichting (driefasig netwerk)
Alarm b identicatie van de verkeerde richting b faserotatie (bvoorbeeld 3-2-1 in plaats van 1-2-3)
10.2.3. Defecte stroomsensor
Alarm b detectie van een afwezige stroomsensor
10.3. Alarmen instellen
De installatiealarmen worden automatisch gedetecteerd en alarmen b gebeurtenissen worden gecongureerd met
de Easy Cong-software.
Er zn diverse manieren om de aanwezigheid van een alarm te detecteren:
10.3.1. ALARM-LED op voorzde
Knipperend: Systeemalarm
Vast: Alarm b gebeurtenis (krgt prioriteit indien er tegelk een systeemalarm is)
10.3.2. Activering van een uitgang
Indien een uitgang aanwezig is op het product, kan deze worden geactiveerd wanneer een alarm is
gedetecteerd
10.3.3. Activering van een uitgang
Indien een ingangsalarm aanwezig is, kan het alarm vanaf deze ingang worden bevestigd. Bevestiging van
een alarm kan slechts gebeuren indien het alarm is voltooid
10.3.4. RS485 Modbus
Informatie over de alarmen met tdregistratie beschikbaar via de RS485-communicatiebus
Bevestiging alarm verzenden
10.3.5. Scherm en WEBVIEW
Informatie over de alarmen met tdregistratie
Bevestiging alarm verzenden
49NL
DIRIS A-40 - 545802B - SOCOMEC
11. WEBSERVER
De ethernetversie van de DIRIS A-40, referentie 4825 0501, heeft een geïntegreerde webserver. Deze webserver
geeft toegang tot alle metingen van de elektrische parameters en de energie die gemeten wordt door de DIRIS A-40.
Het standaard IP-adres voor toegang tot de webserver is: 192.168.0.4
Hieronder ziet u enkele voorbeelden van het scherm van de webserver:
50 NL
DIRIS A-40 - 545802B - SOCOMEC
12. EIGENSCHAPPEN
12.1. Eigenschappen van de DIRISA-40
12.1.1. Mechanische eigenschappen
Type behuizing Gemonteerd op een deur met formaat 96 x 96
Beschermingsgraad Voorpaneel IP52 / achterpaneel IP20
Type scherm
Aanraakscherm met capacitieve technologie, 10 toetsen
Schermresolutie: 350 x 160 pixels
Gewicht
ref 4825 0500: 326 g
ref 4825 0501: 341 g
ref 4825 0502: 349 g
12.1.2. Elektrische specicaties
Hulpvoeding
Spanning 110-277 VAC L/N
277-400 VAC L/L'
120-300 VDC
Overspanningscategorie III
Frequentie
50-60Hz
Stroomverbruik 4825 0500:
110-277 VAC L/N: 4 VA
277-400 VAC L/L’: 5 VA
120-300 VDC: 1,5 VA
4825 0501:
110-277 VAC L/N: 6 VA
277-400 VAC L/L’: 8 VA
120-300 VDC: 2,5 VA
4825 0502:
110-277 VAC L/N: 6 VA
277-400 VAC L/L’: 8 VA
120-300 VDC: 2,5 VA
Aansluiting Verwijderbaar klemmenblok met klemveer, 2x 2 posities,
0,5-2,5 mm² vaste kabel of 0,25-1,5 mm² gevlochten kabel met eindstuk
12.1.3. Eigenschappen meting
Meetnauwkeurigheid
Nauwkeurigheid Conform IEC 61557-12
PMD DD-classificatie gekoppeld aan speciale sensoren (TE
(1)
, TR, TF
(2)
)
Meting van energie en vermogen
Nauwkeurigheid actieve energie en actief vermogen Klasse 0,2 alleen DIRIS A-40
Klasse 0,5 met TE-, iTR- of TF-sensoren
Klasse 1 met TR-sensoren
Nauwkeurigheid van reactieve energie
Klasse 2 met TE-, TR-, iTR- of TF-sensoren
Meting vermogensfactor
Nauwkeurigheid Klasse 0,5 met TE-, iTR- of TF-sensoren
Klasse 1 met TR-sensoren
Spanningsmeting
Eigenschappen van het gemeten netwerk
50-300VAC (L/N) - 87-520VAC (L/L') - CAT III
Frequentiebereik
45 tot 65 Hz
Nauwkeurigheid frequentie
Klasse 0,02
Netwerktype Enkelfasig / Tweefasig / Tweefasig met neutraal / Driefasig / Driefasig met
neutraal
Meting via spanningstransformator Primair: 400 000 VAC
Secundair: 60, 100, 110, 173, 190VAC
Verbruik ingang
≤ 0,1 VA
Nauwkeurigheid van spanningsmeting
Klasse 0,2
Aansluiting Verwijderbaar klemmenblok met klemveer, 4 posities,
0,5-2,5 mm² vaste kabel of 0,25-1,5 mm² gevlochten kabel met eindstuk
(1) Prestatieklassen verkregen als sensoren niet zijn beïnvloed door nabije stroomkabels.
(2) Prestatieklassen alleen verkregen met de kabel gecentreerd in het midden van de wikkeling.
51NL
DIRIS A-40 - 545802B - SOCOMEC
Stroommeting
Aantal stroomingangen
3
Gekoppelde stroomsensoren
Solid-core TE-, split-core TR & iTR-, flexibele TF-stroomsensoren
Nauwkeurigheid Klasse 0,2 alleen DIRIS A-40
Klasse 0,5 met TE-, iTR- of TF-sensoren
Klasse 1 met TR-sensoren
Aansluiting Specifieke kabel van Socomec met RJ12-connectoren
12.1.4. Eigenschappen ingangen/uitgangen
Ingangen
Aantal
3
Type / voeding Optocoupler met interne (12 VDC ± 10%) of externe (12-24 VDC± 20%)
polarisatie
Ingangsfunctie Logische status, pulsmeter, status stroomonderbreker of synchronisatiepuls
(ingang 1)
Aansluiting Verwijderbaar klemmenblok met schroef, 5 posities, gevlochten of vaste
0,14-1,5mm² kabel
Uitgangen
Aantal
2
Type
Optocoupler 30 VDC max. 20 mA max. - SELV
UItgangsfunctie Configureerbaar alarmsignaal (stroom, vermogen enz.) wanneer de
drempelwaarde overschreden wordt of status afstandsbediening
Aansluiting Verwijderbaar klemmenblok met schroef, 4 posities, gevlochten of vaste
0,14-1,5mm² kabel
12.1.5. Specicaties communicatie
RS485
Product
DIRISA-40
Koppeling
RS485
Type aansluiting
2 tot 3 half-duplex draden - SELV
Protocol
Modbus RTU
Baudsnelheid
9600 tot 115200 bauds
Functie
Gegevens congureren en lezen
Aansluiting
Verwderbaar klemmenblok met schroef, 3 posities, gevlochten of
vaste 0,14-1,5mm² kabel
ETHERNET
Product
DIRIS A-40 ref. 4825 0501
Koppeling
Ethernet
Type aansluiting
Ethernet 10/100 Base-T - SELV
Protocol Modbus TCP (poort 502), Modbus RTU over TCP (poort 503)BACnet, SNTP,
SMTP, FTP
SNTP-protocol
Wordt geactualiseerd vanaf een NTP-server.
SMTP-protocol
Verzendt een mail in geval van een alarm
FTP-protocol
Slaat de metingsbestanden op een FTP-server op
Functies
Gegevens configureren en lezen
Aansluiting
RJ45-poort
PROFIBUS
Product
DIRIS A-40 ref. 4825 0502
Koppeling
RS485 - SELV
Protocol
PROFIBUS DPV1
52 NL
DIRIS A-40 - 545802B - SOCOMEC
Functies
PROFIBUS-communicatie
Aansluiting
SubD9-connector
USB
Aansluiting USB 2
Protocol Modbus RTU op USB
Functie Conguratie
Aansluiting Type B micro-USB-connector
12.1.6. Specicaties omgeving
IP
IP52 voorkant
IP20 achterkant
Bedrijfstemperatuur
-10-+70°C (IEC 60068-2-1 / IEC 60068-2-2)
Opslagtemperatuur
-25-+85°C (IEC 60068-2-1 / IEC 60068-2-2)
Bedrijfsvochtigheid
+70°C / 97%HR (IEC 60068-2-30)
Bedrijfshoogte
< 2000 m
Vibratie
0,35mm, 25Hz, 20 min/as (IEC 61557-12)
PEP ecopassport - ISO 14025 SOCO-000007-V01.01-EN
Schokbestendigheid Voorpaneel: 5J - behuizing: 1J (IEC 61010-1 Ed 3.0)
12.1.7. Elektromagnetische compatibiliteit
Immuniteit voor elektrostatische ontladingen bij
contact
IEC 61000-4,-2 NIVEAU III Criterium A
Immuniteit voor elektrostatische ontladingen in de
lucht
IEC 61000-4,-2 NIVEAU III Criterium A
Immuniteit voor straling radiofrequentievelden
IEC 61000-4,-3
80-1000MHz NIVEAU III
1400-2700MHz NIVEAU III
Criterium A
Immuniteit voor snelle elektrische transiënten/
uitbarstingen
IEC 61000-4,-4
Voeding NIVEAU III
Spanningsmeting NIVEAU
IV
Stroomingangen NIVEAU
III
RS485
NIVEAU
III
Ethernet
NIVEAU
III
Profibus
NIVEAU
III
E/S
NIVEAU
III
Aarde
NIVEAU
III
Criterium B
Criterium B
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Immuniteit voor impulsgolven IEC 61000-4,-5
Voeding NIVEAU III
Spanningsmeting
NIVEAU
III
RS485
NIVEAU
II
Ethernet
NIVEAU
II
Profibus
NIVEAU
II
E/S
NIVEAU
II
Criterium A
Criterium A
Criterium A
Criterium B
Criterium A
Criterium A
Immuniteit voor geleide storingen, opgewekt door
radiofrequentievelden
IEC 61000-4,-6
Voeding
NIVEAU
III
Spanningsmeting NIVEAU
III
Stroomingangen NIVEAU
III
RS485
NIVEAU
III
Ethernet
NIVEAU
II
Profibus
NIVEAU
III
E/S
NIVEAU
III
Aarde
NIVEAU
III
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Criterium A
Immuniteit voor vermogensfrequentie
magnetische velden
IEC 61000-4,-8 400 A/m Criterium A
53NL
DIRIS A-40 - 545802B - SOCOMEC
Immuniteit voor spanningsdalingen, korte
onderbrekingen en spanningsvariaties
IEC 61000-4,-11 Spanningsdaling:
0% gedurende 1
cyclus
40% gedurende 10/12
cycli
70% gedurende 25/30
cycli
Korte onderbreking:
0% gedurende 250/300 cycli
Criterium A
Criterium A
Criterium A
Criterium C
Emissies via straling CISPR11 Gr:1 - KLASSE A N.v.t.
Geleide emissies CISPR11 Gr:1 - KLASSE B N.v.t.
Elektromagnetische omgeving Industrieel
12.1.8. Veiligheid
Veiligheid Voldoet aan de Laagspanningsrichtln:
2014/35/EU van 26 februari 2014 (IEC EN61010-1 & IEC EN61010-2-
030)
Voldoet aan de Richtln elektromagnetische compatibiliteit:
2014/30/EU van 26 februari 2014
Isolatie Installatiecategorie III (300VAC Ph/N), vervuilingsgraad 2
UL UL61010-1 & UL61010-2-030
UL-installatie:
DIRIS A-40 en de stroomsensoren moeten omsloten zn in een
door NRTL gecerticeerde elektrische/brandveilige behuizing, Listed
Industrial Control Equipment
of vergelkbare apparatuur.
12.1.9. Levensduur
MTTF (gemiddelde td tot storing) > 100 jaar
54 NL
DIRIS A-40 - 545802B - SOCOMEC
12.2. Eigenschappen van de TE-, TR / iTR- and TF-sensoren
TE - gesloten sensor TE-18 tot TE-55
Model TE-18 TE-18 TE-25 TE-35 TE-45 TE-55
Nominaal stroombereik In (A) 5 - 20 25 - 63 40 - 160 63 - 250
160 - 630 400 - 1000
(1)
Max. stroom (A) 24 75,6 192 300 756 1200
Gewicht (g)
24 24 69 89 140 187
Max. spanning 300V
Nominale weerstandsspanning 3kV
Frequentie 50/60 Hz
Sporadische overbelasting 10x In in 1 seconde
Meetcategorie CAT III
Beschermingsgraad IP30 / IK06
Bedrijfstemperatuur -10-+70°C
Opslagtemperatuur -25-+85°C
Relatieve vochtigheid 95% RH zonder condensatie
Hoogte < 2000m
PEP ecopassport - ISO 14025 TE-sensoren: SOCO-2014-03-v1-fr, SOCO-2014-03-v1-en
UL UL61010
Aansluiting SOCOMEC RJ12-kabel, recht, getwist aderpaar, niet afgeschermd,
600V
CATIII -10 / +70°C - SELV
(1) > 1000A met TC 5A-adapter.
TE - gesloten sensor TE-90
Model TE-90
Nominaal stroombereik In 600A- 2000A
Max. stroom 2400A
Gewicht 163 g (118 g zonder klemmen)
Max. spanning 600V
Nominale weerstandsspanning 3,6 kV AC 1min
Frequentie 50/60 Hz
Sporadische overbelasting 40x In in 0,5sec
Meetcategorie CAT III
Beschermingsgraad IP30
Bedrijfstemperatuur -10-+70°C
Opslagtemperatuur -25-+85°C
Relatieve vochtigheid 95% RH zonder condensatie
Hoogte < 2000m
Aansluiting SOCOMEC RJ12-kabel, recht, getwist aderpaar, niet afgeschermd,
600VCATIII -10 / +70°C - SELV
55NL
DIRIS A-40 - 545802B - SOCOMEC
TR / iTR - Split-core sensor
Model TR-10 /
iTR-10
TR-14 /
iTR-14
TR-21 /
iTR-21
TR-32 /
iTR-32
Nominaal stroombereik In (A) 26 - 63 40 - 160 63 - 250
160 - 600
Max. stroom (A) 75,6 192 300 720
Gewicht (g)
74 117 211 311
Max. spanning 300V
Spanningsdetectie iTR
Nominale weerstandsspanning 3kV
Frequentie 50/60 Hz
Sporadische overbelasting 10x In in 1 seconde
Meetcategorie CAT III
Beschermingsgraad IP20 / IK06
Bedrijfstemperatuur -10-+55°C
Opslagtemperatuur -25-+85°C
Relatieve vochtigheid 95% RH zonder condensatie
Hoogte < 2000m
PEP ecopassport - ISO 14025 SOCO-00007-V01.01-EN
UL UL61010
Aansluiting SOCOMEC RJ12-kabel, recht, getwist aderpaar, niet afgeschermd,
600VCATIII -10 / +70°C - SELV
TF - exibele stroomsensor
Model TF-55 TF-120 TF-300
Nominaal stroombereik In (A) 150 - 600 500 - 2000 1600 - 6000
Gewicht (g)
114 142 220
Max. spanning 600V
Nominale weerstandsspanning 3,6kV
Frequentie 50 / 60Hz
Sporadische overbelasting 10x In in 1 seconde
Meetcategorie CAT III
Beschermingsgraad IP30 / IK07
Bedrijfstemperatuur -10-+70°C
Opslagtemperatuur -25-+75°C
Relatieve vochtigheid 95% RH zonder condensatie
Hoogte < 2000m
UL UL61010
Aansluiting SOCOMEC RJ12-kabel, recht, getwist aderpaar, niet afgeschermd,
600VCATIII -10 / +70°C - SELV
56 NL
DIRIS A-40 - 545802B - SOCOMEC
13. PRESTATIEKLASSES
Prestatieklasses zn opgesteld conform IEC 61557-12 editie 1 (08/2007)
Classicatie van de DIRISA-40 DD in combinatie met speciale sensoren (TE, TR, TF)
Temperatuur K55
Algemene bedrfsprestatieklasse voor actief vermogen of actieve
energie
0,5 in combinatie met TE, iTR of TF solid-core
sensoren 1 in combinatie met TR split-core sensoren
13.1. Specicatie van de eigenschappen
Symbool Functie
Algemene
bedrijfsprestatieklasse
voor DIRISA-40 + speciale
sensoren* (TE, TR, iTR, TF)
conform IEC 61557-12
Meetbereik
Pa Totaal actief vermogen 0,2% alleen DIRIS A-40
0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
10% - 120% In
2% - 120% In
2% - 120% In
Q
A
, Q
V
Totaal reactief vermogen (rekenkundig, vectorieel) 1 met TE-, iTR- of TF-sensoren
2 met TR-sensoren
5% - 120% In
S
A
, S
V
Totaal schnbaar vermogen (rekenkundig, vectori-
eel)
0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
10% - 120% In
Ea Totale actieve energie 0,2% alleen DIRIS A-40
0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
10% - 120% In
2% - 120% In
2% - 120% In
Er
A
, Er
V
Totale reactieve energie (rekenkundig, vectorieel) 2 met TE-, TR-, iTR- of TF-sensoren 5% - 120% In
Eap
A
, Eap
V
Totale schnbare energie (rekenkundig, vectorieel) 0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
10% - 120% In
f Frequentie 0,02 45-65 Hz
Fasestroom 0,2 alleen DIRIS A-40
0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
5% - 120% In
10% - 120% In
10% - 120% In
INc Berekende stroom nulleider 1 met TE-, iTR- of TF-sensoren
2 met TR-sensoren
10% - 120% In
U Spanning (Lp-Lg of Lp-N) 0,2 50-300 VAC Ph/N
PF
A
, PF
V
Vermogensfactor (rekenkundig, vectorieel) 0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
0,5 inductief tot 0,8
capacitief
Pst, Plt Flikkering (korte termn, lange termn) - -
Udip Spanningsdaling (Lp-Lg of Lp-N) 0,5 -
Uswl Spanningsaanzwelling (Lp-Lg of Lp-N) 0,5 -
Uint Spanningsonderbreking (Lp-Lg of Lp-N) 0,2 -
Unba Onbalans amplitude spanning (Lp-N) 0,5 -
Unb Onbalans spanningsfase en amplitude (Lp-Lg of
Lp-N)
0,2 -
THDu,
THD-Ru
Totaal percentage harmonische vervorming van de
spanning (ten opzichte van de fundamentele, ten
opzicht van de efciënte waarde)
1 Rangorde 1 tot 63
Uh Harmonischen spanning 1 -
THDi,
THD-Ri
Totaal percentage harmonische vervorming van
de stroom (ten opzichte van de fundamentele, ten
opzicht van de efciënte waarde)
1 met TE-, TR-, iTR- of TF-sensoren Rangorde 1 tot 63
Ih Harmonischen stroom 1 met TE-, TR-, iTR- of TF-sensoren -
Msv Signalen gecentraliseerde afstandsbediening - -
*Met aansluitkabels van SOCOMEC.
57NL
DIRIS A-40 - 545802B - SOCOMEC
13.2. Evaluatie van de kwaliteit van de voeding
Symbool Functie
Algemene
bedrijfsprestatieklasse
voor DIRISA-40 + speciale
sensoren (TE, TR, iTR, TF)
conform IEC 61557-12
Meetbereik
f Frequentie 0,02 45-65 Hz
I, IN Fasestroom 0,2 alleen DIRIS A-40
0,5 met TE-, iTR- of TF-sensoren
1 met TR-sensoren
5% - 120% In
10% - 120% In
10% - 120% In
INc Berekende stroom nulleider 1 met TE-, iTR- of TF-sensoren
2 met TR-sensoren
10% - 120% In
U Spanning (Lp-Lg of Lp-N) 0,2 50-300 VAC Ph/N
Pst, Plt Flikkering (korte termn, lange termn) - -
Udip Spanningsdaling (Lp-Lg of Lp-N) 0,5 -
Uswl Spanningsaanzwelling (Lp-Lg of Lp-N) 0,5 -
Uint Spanningsonderbreking (Lp-Lg of Lp-N) 0,2 -
Unba Onbalans amplitude spanning (Lp-N) 0,5 -
Unb Onbalans spanningsfase en amplitude (Lp-Lg of
Lp-N)
0,2 -
Uh Harmonischen spanning 1 -
Ih Harmonischen stroom 1 met TE-, TR-, iTR- of TF-sensoren -
Msv Signalen gecentraliseerde afstandsbediening - -
Document niet contractueel bindend. © 2019, Socomec SAS. Alle rechten voorbehouden.
HOOFDKANTOOR CONTACT:
SOCOMEC SAS
1-4 RUE DE WESTHOUSE
67235 BENFELD, FRANKRIJK
www.socomec.nl
545802B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58

Socomec DIRIS A-40 Handleiding

Type
Handleiding