Cyrix-i 12/24-200
Intelligent battery combiner
ENGLISH
No voltage loss
The Cyrix-i 200 battery combiner is a microprocessor controlled heavy duty
contactor that automatically connects batteries in parallel when one battery has
reached a preset voltage (indicating that the battery is being charged), and
disconnects when the voltage decreases below float level (indicating that one or
both batteries are being discharged).
Cyrix battery combiners are an excellent replacement for diode isolators. The
main advantage is that there is virtually no voltage loss so that the output voltage
of alternators or battery chargers does not need to be increased.
Prioritising the starter battery
In a typical setup the alternator is directly connected to the starter battery. The
accessory battery, and possibly also a bow thruster and other batteries are each
connected to the starter battery by Cyrix battery combiners. When a Cyrix senses
that the starter battery has reached it’s connect voltage it will engage, to allow for
parallel charging of the other batteries.
Bidirectional voltage sensing
The Cyrix senses the voltage of both connected batteries. It will therefore also
engage if for example the accessory battery is being charged by a battery
charger.
Intelligent battery monitoring
Four different connect/disconnect profiles can be selected to suit local
requirements.
12/24Volt auto ranging
The Cyrix-i 12/24 will automatically adjust to a 12V or 24V system.
Bicolor LED status indicator
Red: contactor open
Red/green: timer
Green: contactor closed
Microswitch for for remote switch status monitoring
Installation (see figure below)
1. The Cyrix can only be used in installations with a negative common.
2. Disconnect the minus of both batteries.
3. Place the Cyrix closest to the smallest battery (in general the starter
battery).
4. Connect the plus of the batteries to the brass bolts of the Cyrix,
(battery 1 and battery 2). Install a fuse in series (see fig). The fuse
should be sized in accordance with the wire cross section used, but
not exceed 200A.
5. Connect the common battery negative to “battery –“ of the Cyrix and
reconnect the minus of both batteries.
6. An emergency start push button can be wired to the “start assist”
connection if required. The relay will engage during 30 seconds after
the “start assist” has been momentarily connected to the battery
plus. Alternatively, a parallel connect switch can be used to engage
the relay as long as the switch remains closed.
7. An auxiliary micro switch is available for remote monitoring.
Cyrix-i 12/24-200
Intelligente accuscheider
NEDERLANDS
Geen spanningsverlies
De Cyrix-i 200 bestaat uit een microprocessor gestuurd power relais dat accu’s
automatisch van elkaar loskoppelt wanneer de spanning daalt tot onder een
bepaalde waarde (een teken dat de accu’s niet geladen worden), en weer parallel
schakelt wanneer de spanning over één van de accu’s stijgt tot boven een
bepaalde waarde (een teken dat de accu geladen wordt).
De Cyrix accuscheider is een uitstekend alternatief voor diode of FET laadstroom
verdelers. Het spanningsverlies is namelijk praktisch nihil.
Voorrang voor de startaccu
De startaccu mag nooit leeg raken. Het is daarom gebruikelijk om de dynamo op
de startaccu aan te sluiten. Andere accu’s, zoals de accessoire accu, en (in een
boot) mogelijk ook de boegschroef accu kunnen vervolgens met een Cyrix
accuscheider op de startaccu aangesloten worden. De Cyrix accuscheiders
zorgen er dan voor dat alle accu’s parallel geschakeld worden zodra de spanning
van de startaccu voldoende gestegen is.
Bidirectioneel
De Cyrix meet de spanning over alle twee de aangesloten accu’s. De accu’s
zullen dus ook parallel geschakeld worden wanneer de accessoire accu geladen
wordt, bijvoorbeeld met een acculader.
Intelligente accuspanning bewaking om herhaald schakelen te voorkomen
Er kunnen bovendien vier verschillend schakel profielen ingesteld worden.
Twee modellen, geschikt voor 12V/24V accuspanning
De Cyrix-i kiest automatisch de juiste systeem spanning.
Twee kleuren LED voor status indicatie
Rood: open
Rood/groen: timer loopt
Groen: gesloten
Microswitch voor open/gesloten signalering op afstand
Installatie (zie schema)
1. De Cyrix is alleen geschikt voor installaties met een negatieve massa.
2. Maak de min polen van beide accu’s los.
3. Plaats de Cyrix dicht in de buurt van de kleinste accu (iha de
startaccu).
4. Verbind de plus polen van de 2 accu’s aan de bout aansluitingen van
de Cyrix (battery 1 and battery 2). Installeer ook een serie zekering
(zie fig). De waarde van de zekering moet afgestemd zijn op de
gebruikte draaddoorsnede en mag niet meer dan 200A bedragen.
5. Verbind de min aansluiting “battery –“ van de Cyrix en sluit de
minnen van de accu’s weer aan.
6. Noodstart drukknop. Indien pen “start assist” kort met de accu plus
verbonden wordt zal het relais gedurende 30 seconden sluiten. Indien
een schakelaar gebruikt wordt ipv een drukknop zal het relais
gesloten blijven zolang de schakelaar gesloten is.
7. Gebruik indien gewenst de microswitch voor open/gesloten
signalering op afstand
Model
Cyrix
-
i 12/24
-
200
Continuous current 200A
Peak current 2000A during 1 second
Input voltage 12/24V model 10-36VDC
Connect/disconnect profiles See table
Over voltage disconnect 16V / 32 / 64V
Current consumption when open 4 mA
Emergency start Yes, 30s
Microswitch for remote monitoring
Yes
Status indication Bicolor LED
Model
Cyrix
-
i 12/24
-
200
Continu stroom 200A
Piek stroom 2000A gedurende 1 seconde
Ingangsspanning 12/24V model 10-36VDC
Schakel profielen Zie tabel
Afschakelen bij overspanning 16V / 32 / 64V
Stroomverbruik (open) 4 mA
Start Assist Ja, 30s
Microswitch voor status indicatie
Ja
Status indicatie op de Cyrix Twee kleuren LED
Revision : Rev 02
Date : 14-10-2008
Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands
Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sales@victronenergy.com
Four different connect/disconnect profiles
Profile 0 (default)
Connect (V)
Disconnect (V)
Less than
13V
Remains open
More than
12.8V
Remains closed
Closes after Opens after
13V 10min 12.8V 10 min
13.2V 5min 12.4V 5 min
13.4V 3 min 12.2V 1 min
13.6V 1 min 12V 20 sec
13.8V 4 sec Less than 11V Immediate
Profile 1
Connect (V)
Disconnect (V)
Less than
13.25V
Remains open
More than
12.75V
Remains closed
More than
13.25V
Closes after
30 sec
From 10.5V
to 12.75V
Opens after 2 min
Less than 10.5V Immediate
Profile 2
Connect (V)
Disconnect (V)
Less than
13.2V
Remains open
More than
12.8V
Remains closed
More than
13.2V
Closes after
6 sec
From 10.5V
to 12.8V
Opens after 30 sec
Less than 10.5V Immediate
Profile 3
Connect (V)
Disconnect (V)
Less than
13V
Remains open
More than
12.8V
Remains closed
Closes after Opens after
13V 10min 12.8V 30 min
13.2V 5min 12.4V 12 min
13.4V 3 min 12.2V 2 min
13.6V 1 min
12V 1 min
11.8V 10 sec
13.8V 4 sec Less than 10.5V Immediate
Notes
1. After connecting 3 times, the minimum time to reconnect is 1
minute (to prevent “rattling”)
2. The Cyrix will not connect if the voltage on one of the battery
connections is less than 2V*. (to prevent unexpected switching
during installation)
3. The Cyrix will always connect if the start assist is activated, as
long as the voltage on one of the battery connections is sufficient
to operate the Cyrix (approximately 10V*).
* Multiply voltage x2 for 24V systems
Vier verschillende schakel profielen
Profiel 0 (default)
Verbinden (V)
*
Verbreken (V)
*
Minder dan 13V Blijft open Meer dan 12,8V Blijft gesloten
Sluit na Opent na
13V 10min 12,8V 10 min
13,2V 5min 12,4V 5 min
13,4V 3 min 12,2V 1 min
13,6V 1 min 12V 20 sec
13,8 4 sec Minder dan 11V Meteen
Profiel 1
Verbinden (V)*
Verbreken (V)*
Minder dan 13,25V Blijft open Meer dan 12,75V Blijft gesloten
Meer dan 13,25V Sluit na 30 sec
Van 10,5V
tot 12,75V
Opent na 2 min
Minder dan 10,5V Meteen
Profiel 2
Verbinden (V)*
Verbreken (V)*
Minder dan 13,2V Blijft open Meer dan 12,8V Blijft gesloten
Meer dan 13,2V Sluit na 6 sec
Van10,5V
tot 12,8V
Opent na 30 sec
Minder dan 10,5V Meteen
Profiel 3
Verbinden (V)*
Verbreken (V)*
Minder dan 13V Blijft open Meer dan 12,8V Blijft gesloten
Sluit na Opent na
13V 10min 12,8V 30 min
13,2V 5min 12,4V 12 min
13,4V 3 min 12,2V 2 min
13,6V 1 min
12V 1 min
11,8V 10 sec
13,8V 4 sec Minder dan 10,5V Meteen
Opmerkingen
1. Na 3x inschakelen duurt het minstens 1 minuut tot de volgende
inschakel poging.
2. De Cyrix schakelt niet in als de op één van de accu aansluitingen
de spanning minder dan 2V* is
3. De Cyrix schakelt altijd in als de start assist geactiveerd wordt,
tenzij op beide accu aansluitingen de spanning lager is dan ca.
10V*.
* Vermenigvuldig de aangegeven spanningen met 2 voor 24V
systemen.

Documenttranscriptie

Revision : Rev 02 Date : 14-10-2008 Cyrix-i 12/24-200 Intelligent battery combiner Cyrix-i 12/24-200 Intelligente accuscheider ENGLISH NEDERLANDS No voltage loss The Cyrix-i 200 battery combiner is a microprocessor controlled heavy duty contactor that automatically connects batteries in parallel when one battery has reached a preset voltage (indicating that the battery is being charged), and disconnects when the voltage decreases below float level (indicating that one or both batteries are being discharged). Cyrix battery combiners are an excellent replacement for diode isolators. The main advantage is that there is virtually no voltage loss so that the output voltage of alternators or battery chargers does not need to be increased. Geen spanningsverlies De Cyrix-i 200 bestaat uit een microprocessor gestuurd power relais dat accu’s automatisch van elkaar loskoppelt wanneer de spanning daalt tot onder een bepaalde waarde (een teken dat de accu’s niet geladen worden), en weer parallel schakelt wanneer de spanning over één van de accu’s stijgt tot boven een bepaalde waarde (een teken dat de accu geladen wordt). De Cyrix accuscheider is een uitstekend alternatief voor diode of FET laadstroom verdelers. Het spanningsverlies is namelijk praktisch nihil. Prioritising the starter battery In a typical setup the alternator is directly connected to the starter battery. The accessory battery, and possibly also a bow thruster and other batteries are each connected to the starter battery by Cyrix battery combiners. When a Cyrix senses that the starter battery has reached it’s connect voltage it will engage, to allow for parallel charging of the other batteries. Voorrang voor de startaccu De startaccu mag nooit leeg raken. Het is daarom gebruikelijk om de dynamo op de startaccu aan te sluiten. Andere accu’s, zoals de accessoire accu, en (in een boot) mogelijk ook de boegschroef accu kunnen vervolgens met een Cyrix accuscheider op de startaccu aangesloten worden. De Cyrix accuscheiders zorgen er dan voor dat alle accu’s parallel geschakeld worden zodra de spanning van de startaccu voldoende gestegen is. Bidirectional voltage sensing The Cyrix senses the voltage of both connected batteries. It will therefore also engage if for example the accessory battery is being charged by a battery charger. Bidirectioneel De Cyrix meet de spanning over alle twee de aangesloten accu’s. De accu’s zullen dus ook parallel geschakeld worden wanneer de accessoire accu geladen wordt, bijvoorbeeld met een acculader. Intelligent battery monitoring Four different connect/disconnect profiles can be selected to suit local requirements. Intelligente accuspanning bewaking om herhaald schakelen te voorkomen Er kunnen bovendien vier verschillend schakel profielen ingesteld worden. 12/24Volt auto ranging The Cyrix-i 12/24 will automatically adjust to a 12V or 24V system. Bicolor LED status indicator Red: contactor open Red/green: timer Green: contactor closed Twee modellen, geschikt voor 12V/24V accuspanning De Cyrix-i kiest automatisch de juiste systeem spanning. Twee kleuren LED voor status indicatie Rood: open Rood/groen: timer loopt Groen: gesloten Microswitch voor open/gesloten signalering op afstand Microswitch for for remote switch status monitoring Installation (see figure below) 1. The Cyrix can only be used in installations with a negative common. 2. Disconnect the minus of both batteries. 3. Place the Cyrix closest to the smallest battery (in general the starter battery). 4. Connect the plus of the batteries to the brass bolts of the Cyrix, (battery 1 and battery 2). Install a fuse in series (see fig). The fuse should be sized in accordance with the wire cross section used, but not exceed 200A. 5. Connect the common battery negative to “battery –“ of the Cyrix and reconnect the minus of both batteries. 6. An emergency start push button can be wired to the “start assist” connection if required. The relay will engage during 30 seconds after the “start assist” has been momentarily connected to the battery plus. Alternatively, a parallel connect switch can be used to engage the relay as long as the switch remains closed. 7. An auxiliary micro switch is available for remote monitoring. Model Cyrix-i 12/24-200 Continuous current Peak current Input voltage 12/24V model Connect/disconnect profiles Over voltage disconnect Current consumption when open Emergency start 200A 2000A during 1 second 10-36VDC See table 16V / 32 / 64V 4 mA Yes, 30s Yes Bicolor LED Microswitch for remote monitoring Status indication Installatie (zie schema) 1. De Cyrix is alleen geschikt voor installaties met een negatieve massa. 2. Maak de min polen van beide accu’s los. 3. Plaats de Cyrix dicht in de buurt van de kleinste accu (iha de startaccu). 4. Verbind de plus polen van de 2 accu’s aan de bout aansluitingen van de Cyrix (battery 1 and battery 2). Installeer ook een serie zekering (zie fig). De waarde van de zekering moet afgestemd zijn op de gebruikte draaddoorsnede en mag niet meer dan 200A bedragen. 5. Verbind de min aansluiting “battery –“ van de Cyrix en sluit de minnen van de accu’s weer aan. 6. Noodstart drukknop. Indien pen “start assist” kort met de accu plus verbonden wordt zal het relais gedurende 30 seconden sluiten. Indien een schakelaar gebruikt wordt ipv een drukknop zal het relais gesloten blijven zolang de schakelaar gesloten is. 7. Gebruik indien gewenst de microswitch voor open/gesloten signalering op afstand Model Continu stroom Piek stroom Ingangsspanning 12/24V model Schakel profielen Afschakelen bij overspanning Stroomverbruik (open) Start Assist Microswitch voor status indicatie Status indicatie op de Cyrix Cyrix-i 12/24-200 200A 2000A gedurende 1 seconde 10-36VDC Zie tabel 16V / 32 / 64V 4 mA Ja, 30s Ja Twee kleuren LED Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: [email protected] Four different connect/disconnect profiles Vier verschillende schakel profielen Profile 0 (default) Connect (V)* Less than Remains open 13V Closes after 13V 10min 13.2V 5min 13.4V 3 min 13.6V 1 min 13.8V 4 sec Profiel 0 (default) Disconnect (V)* More than Remains closed 12.8V Opens after 12.8V 10 min 12.4V 5 min 12.2V 1 min 12V 20 sec Less than 11V Immediate Verbinden (V)* Verbreken (V)* Minder dan 13V Blijft open Meer dan 12,8V Blijft gesloten 13V 13,2V 13,4V 13,6V 13,8 Sluit na 10min 5min 3 min 1 min 4 sec 12,8V 12,4V 12,2V 12V Minder dan 11V Opent na 10 min 5 min 1 min 20 sec Meteen Profile 1 Connect (V)* Less than Remains open 13.25V More than Closes after 13.25V 30 sec Profiel 1 Disconnect (V)* More than Remains closed 12.75V From 10.5V Opens after 2 min to 12.75V Less than 10.5V Verbinden (V)* Minder dan 13,25V Meer dan 13,25V Verbreken (V)* Blijft open Sluit na 30 sec Immediate Profile 2 Connect (V)* Less than Remains open 13.2V More than 13.2V From 10.5V to 12.8V Less than 10.5V Opens after 30 sec Verbinden (V)* 13.8V Notes 1. 2. 3. 4 sec Blijft gesloten Opent na 2 min Meteen Verbreken (V)* Minder dan 13,2V Blijft open Meer dan 13,2V Sluit na 6 sec Immediate Profile 3 Connect (V)* Less than Remains open 13V Closes after 13V 10min 13.2V 5min 13.4V 3 min 13.6V 1 min Van 10,5V tot 12,75V Minder dan 10,5V Profiel 2 Disconnect (V)* More than Remains closed 12.8V Closes after 6 sec Meer dan 12,75V Disconnect (V)* More than Remains closed 12.8V Opens after 12.8V 30 min 12.4V 12 min 12.2V 2 min 12V 1 min 11.8V 10 sec Less than 10.5V Immediate Meer dan 12,8V Van10,5V tot 12,8V Minder dan 10,5V Blijft gesloten Opent na 30 sec Meteen Profiel 3 Verbinden (V)* Verbreken (V)* Minder dan 13V Blijft open 13V 13,2V 13,4V 13,6V Sluit na 10min 5min 3 min 1 min 13,8V 4 sec Meer dan 12,8V Blijft gesloten 12,8V 12,4V 12,2V 12V 11,8V Minder dan 10,5V Opent na 30 min 12 min 2 min 1 min 10 sec Meteen Opmerkingen After connecting 3 times, the minimum time to reconnect is 1 minute (to prevent “rattling”) The Cyrix will not connect if the voltage on one of the battery connections is less than 2V*. (to prevent unexpected switching during installation) The Cyrix will always connect if the start assist is activated, as long as the voltage on one of the battery connections is sufficient to operate the Cyrix (approximately 10V*). 1. 2. 3. Na 3x inschakelen duurt het minstens 1 minuut tot de volgende inschakel poging. De Cyrix schakelt niet in als de op één van de accu aansluitingen de spanning minder dan 2V* is De Cyrix schakelt altijd in als de start assist geactiveerd wordt, tenzij op beide accu aansluitingen de spanning lager is dan ca. 10V*. * Multiply voltage x2 for 24V systems * Vermenigvuldig de aangegeven spanningen met 2 voor 24V systemen. Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: [email protected]
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Victron energy Cyrix-i 200A de handleiding

Type
de handleiding