numbers, the gateway exits manual mode after an
additional press.
Turning o all the DALI participants
The gateway is in permanent manual mode.
- Press the
key.
All DALI participants are switched o.
Locking the DALI participants or groups
individually
The gateway is in permanent manual mode.
- Press briefly on the
key ( < 1 second) until the
desired DALI number is displayed.
The
and LEDs display the status.
- Press the
and keys simultaneously for at
least 5 seconds.
The DALI number selected flashes on the display
screen.
The DALI participant or group is locked.
- Enable bus mode (leaving permanent manual
mode).
A locked DALI participant can be controlled in
manual mode.
Unlocking the DALI participants or groups
individually
The gateway is in permanent manual mode
- Press briefly on the key
(<1 second) until the
desired DALI number is displayed.
- Press the
and keys simultaneously for at
least 5 seconds.
The DALI participant or group is released.
The display on the screen no longer flashes.
- Enable bus mode (leaving permanent manual
mode).
Connection
TYA670W
Area
Line
Ptcp.
Nb.
230 V 50/60 Hz
L1
L2
L3
N
da+
da -
da da N L da da N L
Bus 30 V
Electrical connection
Connect the device according to the diagram above.
Observe the temperature range. Ensure adequate
cooling.
When performing installation, perform the
installation in such a way that when the area is
disconnected the lines carrying both the DALI and
also the mains voltage are disconnected.
If multiple circuit breakers supply dangerous
voltages to the device or load, couple the miniature
circuit breakers or label them with a warning, to
ensure disconnection is guaranteed.
DALI devices from some manufacturers have
expanded functions and can be controlled. In the
case of upgrades of existing DALI installations,
remove all the corresponding control devices.
The DALI control voltage is a functional extra-low
voltage (FELV).
Operation of the emergency lighting
The device can be used in centrally-powered
emergency lighting systems.
G
The statutory and standard specifications vary
from country to country. In any event, the user /
technical planner should check whether the specific
specifications should be maintained.
G
Observe the number of DALI devices in the
emergency luminaires used.
Emergency lighting systems with a central safety
supply are required in buildings larger than 2000 m².
Depending on the scope of functions of the system,
only the emergency luminaires are supplied by the
central safety supply (figure 1), or the KNX system and
DALI gateway are also supplied (figure 2). In the latter
case, in emergency operation, the DALI gateway can
transmit the appropriate fault messages to a central
system and other DALI gateways in the system.
Figure 1 : Emergency lighting supplied by the
central emergency power supply
AC 230 V
C/DC 230 V
KNX
L, N
da
KNX
DALI
DALI
L, N
da
Figure 2 : Emergency lighting, KNX supply and
the DALI gateway are supplied by the central
emergency power supply circuit.
C 230 V
C/DC 230 V
KNX
*
L, N
da
KNX
DALI
DALI
L, N
da
*The KNX power supply must be adapted to the
voltage of the AC / DC safety source.
Commissioning
Downloading the physical address and the
application software
- Supply power to the product from the mains
- Connect the KNX bus
- Download the physical address
- Commission DALI system using commissioning
software
- Download the application software into the device
Programming is not possible if the product is not
powered via the mains.
Technical data
Supply
Rated voltage 110 ... 240 V v
Mains frequency 50 / 60 Hz
Rated voltage DC 110 ... 240 V s
Power loss max. 3 W
Ambient conditions
Operating tempertaure -5 ... +45 °C
Storage /transport temperature -25 ... +70 °C
DALI
Rated voltage DALI 16 V (typ.)
Number of DALI subscribers max. 64
DALI transmission rate 1,2 kbit/s
DALI protocol EN 62386
Cable type Sheated cable 230 V,
e.g. NYM
DALI cable lenght
with Ø 1,5 mm² max. 300 m
with Ø 1,0 mm² max. 238 m
with Ø 0,75 mm² max. 174 m
with Ø 0,5 mm² max. 116 m
2 6LE005270A
Housing
Fitting width 72 mm / 4 modules
Connection of power supply and DALI
Connection mode Screw terminal
single stranded 0,5 ... 4 mm²
Finely strande without conductor sleeve 0,5 ... 4 mm²
Finely strande with conductor sleeve 0,5 ... 2,5 mm²
KNX
KNX Medium TP
Commissionning mode S Mode
Rated voltage KNX DC 21 ... 32 V SELV
Power consumption KNX typ. 150 mW
Connection type for bus KNX Terminal
This manual is an integral part of the product
and must be kept by the end user.
Correct Disposal of This product
(Waste Electrical & Electronic Equipment).
(Applicable in the European Union and other European
countries with separate collection systems).
This marking shown on the product or its literature indicates that
it should not be disposed with other household waste at the end
of its working life. To prevent possible harm to the environment or
human health from uncontrolled waste disposal,
please separate this from other types of waste and recycle it re-
sponsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they
purchased this product, or their local government oce, for details
of where and how they can take this item for environmentally safe
recycling.
Business users should contact their supplier and check the terms
and conditions of the purchase contract. This product should not
be mixed with other commercial waste for disposal.
Usable in all Europe M and in Switzerland
What to do if…
The screen displays , the connected DALI
devices have no functions, no control is
possible
Cause : network
voltage on the DALI
bus
Solution : correct the
installation wiring fault
The screen displays bc in manual mode,
control of some light fittings is not possible.
Cause : the device has
not been programmed
or is programmed to
"Broadcast"
Solution :
program the
gateway, commission
the DALI system
Individual DALI devices have no function
Cause 1 : Load is
defective, e.g. lamp
Solution : Exchange
load
Cause 2 : DALI device
is defective
Solution : Exchange
defective device and
switch on voltage
Press buttons 7 and 13 together for at least 10
seconds.
The device detects the exchanges DALI device
and loads in the necessary data. The display
shows
LE
.
G
Simultaneous exchange of multiple DALI
devices is only possible with commissioning
software and project data.
None of the DALI groups can be operated
Cause 1 : All DALI
groups disabled via bus
or manual operation
Solution : Cancel
disabling
Cause 2 : Continuous
manual mode switched on
Solution : Deactivating
permanent manual control
Cause 3 : Application
software has been
stopped, programming
LED is flashing
Solution : Perform reset:
Disconnect device from
bus, switch on again
after approx. 5 seconds
Cause 4 : Application
software missing or faulty
Solution : Check
programming and correct