Victron energy BatteryProtect 50A 100A 220A de handleiding

Type
de handleiding
Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / The Netherlands
Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sales@victronenergy.com
BatteryProtect
ENGLISH
Installation
1. The BatteryProtect (BP) must be installed in a well-ventilated area and preferably close (max 50
cm) to the battery (but, due to possible corrosive gasses not above the battery!). Voltage drop over
a long or undersized cable between the battery plus and the BP may result in unexpected
shutdown of the BP.
2. A properly sized fuse must be inserted according to local regulations in the cable between the
battery and the BP.
3. Use a 1,5mm² wire (included) for the minus connection, which should be connected directly to
the battery minus. No other equipment should be connected to this wire.
4. The BP will automatically detect the system voltage after connection of plus and minus to the
battery. During voltage detection the 7 segment display shows a series of flashes between the top
and lower part.
5. Do not connect the load output until the BP has been fully programmed.
6. A remote on-off switch can be connected to the two pole connector (see figure 1) or between
pin 2-1 of the two pole connector and the battery plus.
7. A buzzer, LED or relay can be connected between the alarm output and the battery plus (see
figure 1). Maximum load on the alarm output: 50mA (short circuit proof).
Load disconnect events and alarm output options
Buzzer or LED mode (buzzer or LED connected to the alarm output):
In case of under voltage, a continuous alarm will start after 12 seconds. The BP will
disconnect the load after 90 seconds and the alarm will stop.
In case of over voltage, the load will be disconnected immediately and an intermittent alarm
will remain on until the overvoltage problem has been corrected.
Relay mode (relay connected to the alarm output):
In case of under voltage, the relay will engage after 12 seconds. The BP will disconnect the
load after 90 seconds and the relay will disengage.
In case of over voltage, the load will be disconnected immediately and the alarm output will
remain inactive.
Li-ion mode:
Connect the load disconnect output of the VE.Bus BMS to pin 2-1.
The load is disconnected immediately when the load disconnect output of the VE.Bus BMS
switches from ‘high' to ‘free floating’ (due to battery cell under voltage, over voltage or over
temperature). The under voltage thresholds and alarm output of the BP are inactive in this
mode.
Programming
When switched off (remote open), the BP can be programmed for the desired voltages and modes
by connecting the PROG pin to the ground. Please see the programming table.
The display will first step through the shutdown and restart voltages. Disconnect the PROG pin
when the desired voltage is displayed.
The display will confirm the chosen voltage and default mode (
) twice.
Reconnect the PROG to ground if another mode is (
or
) is required. Disconnect when the
required mode is displayed.
The display will confirm the chosen voltage and mode twice.
Operation
There are 4 possible error modes, indicated by the 7 segment display:
E 1 Short circuit detected
E 2 Over load or over temperature
E 3 Under voltage
E 4 Over voltage
After 5 minutes the error is no longer displayed to reduce current consumption.
The decimal point of the 7 segment display is used for status indication:
On solid: the BP attempts to activate the output
Flash every 5s: output is active
Flashing every 2s in Li-ion mode: outputconnecting
Remote control and short circuit
The BP will connect the load 1 second after closing the remote contact.
The BP will disconnect the load immediately when the remote contact is opened.
When in Li-ion mode the BP will connect the load 30 seconds after the remote input of the BP
has been pulled high by the VE.Bus BMS. This delay increases to 3 minutes in case of
frequent switching.
In case of a short circuit, the BP will attempt to connect the load every 5 seconds. After two
attempts the display will show E 1 (short circuit detected).
Programming table
7 segment display
Under voltage shut
down
12V / 24V system
Under voltage restart
12V / 24V system
10,5V / 21V
12V / 24V
10V / 20V
11,5V / 23V
9,5V / 19V
11,5V / 23V
11,25V / 22,5V
13,25V / 26,5V
11,5V / 23V
13,8V / 27,6V
10,5V / 21V
12,8V / 25,6V
11,5V / 23V
12,8V / 25,6V
11,8V / 23,6V
12,8V / 25,6V
12V / 24V
13V / 26V
10V / 20V
13,2V / 26,4V
Buzzer or LED mode
Relay mode
Li-ion mode
Specifications
BatteryProtect
BP-50
BP-100
BP-220
Maximum cont. load current 50A 100A 220A
Peak current 200A 600A 600A
Operating voltage range 6 –35V
Current consumption When on: 1,5 mA When off or low voltage shutdown : 0,6 mA
Alarm output delay 12 seconds
Max. load on alarm output 50mA (short circuit proof)
Load disconnect delay 90 seconds (immediate if triggered by the VE.Bus BMS)
Default thresholds Disengage: 10,5V or 21V Engage: 12V or 24V
Operating temperature range Full load: -40°C to +40°C (up to 60% of nominal load at 50°C)
Weight 0,2kg 0.5lbs
0,5kg 0.6lbs
0,8kg 1.8lbs
Dimensions (hxwxd)
40 x 48 x 106m m
1.6 x 1.9 x 4.2 inch
59 x 42 x 115mm
2.4 x 1.7 x 4.6 inch
62 x 123 x 120m m
2.5 x 4.9 x 4.8 inch
BatteryProtect
NEDERLANDS
Installatie
1. De BatteryProtect (BP) moet worden geïnstalleerd in een goed geventileerd gebied en bij voorkeur dicht
(max. 50 cm) bij de accu (maar in verband met de mogelijke corrosieve gassen niet boven de accu). Een
spanningsverlies over een lange of te klein bemeten kabel tussen de pluspool van de accu en de BP kan
leiden tot een onverwachte uitschakeling van de BP.
2. Een voldoende groot bemeten zekering moet conform de plaatselijke voorschriften worden geplaatst in
de kabel tussen de accu en de BP.
3. Gebruik een 1,5mm² draad (meegeleverd) voor de min-aansluiting die direct op de minpool van de accu
moet worden aangesloten. Op deze draad mag geen andere apparatuur worden aangesloten.
4. De BP detecteert automatisch de systeemspanning na aansluiting van de plus en min op de accu.
Tijdens de spanningsdetectie gaat het uit 7 segmenten bestaande display meermaals knipperen.
5. Sluit de belastingsuitgang pas aan als BP volledig is geprogrammeerd.
6. Een schakelaar voor in-/uitschakelen op afstand kan worden aangesloten op de twee poolaansluitingen
(zie afbeelding 1) of tussen pin 2-1 of de twee poolaansluitingen en de plus van de accu.
7. Een zoemer, LED of relais kan worden aangesloten tussen de alarmuitgang en de plus van de accu (zie
afbeelding 1). Maximale belasting op de alarmuitgang: 50 mA (bestand tegen kortsluiting).
Belasting ontkoppelingsgebeurtenissen en alarm-uitgangsopties
Zoemer- of LED modus (zoemer of LED aangesloten op de alarmuitgang):
In geval van onderspanning wordt na 12 seconden een continu alarm afgegeven. De BP zal de
belasting na 90 seconden ontkoppelen en het alarm wordt gestopt.
In geval van overspanning wordt de belasting direct ontkoppeld en wordt het alarm intermitterend
afgegeven tot het overspanningsprobleem is verholpen.
Relaismodus (relais aangesloten op de alarmuitgang):
In geval van onderspanning wordt het relais na 12 seconden geactiveerd. De BP zal de belasting na
90 seconden ontkoppelen en het relais wordt gedeactiveerd.
In geval van overspanning wordt de belasting direct ontkoppeld en blijft het alarm inactief.
Li-ionmodus:
Sluit de belasting ontkoppelingsuitgang van het VE.Bus BMS aan op pin 2-1.
De belasting wordt direct ontkoppeld als de belasting ontkoppelingsuitgang van het VE.Bus BMS van
hoognaar free floatingoverschakelt (door onderspanning, overspanning of overtemperatuur van de
accucel). De onderspanningsdrempel en alarmuitgang van de BP zijn in deze modus inactief.
Programmeren
Wanneer uitgeschakeld (remote geopend), kan de BP worden geprogrammeerd voor de gewenste
spanningen en modi door de pin PROG met de aarde te verbinden. Zie hiervoor de
programmeringstabel.
Het display doorloopt eerst de uitschakel- en herstartspanningen. Koppel de pin PROG los als de
gewenste spanning wordt weergegeven.
Het display zal de gekozen spanning en de standaardmodus (
) twee keer bevestigen.
Verbind de pin PROG weer met de aarde als een andere modus (
of
) is gewenst. Koppel de pin
weer los als de gewenste modus wordt weergegeven.
Het display zal de gekozen spanning en modus twee keer bevestigen.
Bediening
Er zijn 4 mogelijke storingsmodi die door het uit 7 segmenten bestaande display worden
weergegeven:
E 1 Kortsluiting gedetecteerd
E 2 Overbelasting of overtemperatuur
E 3 Onderspanning
E 4 Overspanning
Na 5 minuten wordt de storing niet meer weergegeven om het stroomverbruik te verminderen.
De decimale punt van het uit 7 segmenten bestaande display wordt gebruikt voor de
statusindicatie:
Brandt continu: de BP probeert om de uitgang te activeren
Knippert om de 5 sec: de uitgang is actief
Knippert om de 2 sec in li-ionmodus: uitgang ‘wordt verbonden’
Afstandsbesturing en kortsluiting
De BP verbindt de belasting 1 seconde na het sluiten van het contact voor in-/uitschakelen
op afstand.
De BP zal de belasting direct ontkoppelen als het contact voor in-/uitschakelen op afstand
wordt geopend.
In de li-ionmodus zal de BP de belasting 30 seconden nadat de ingangsspanning van de BP
door het VE.Bus BMS omhoog is gedreven, koppelen. Deze vertraging kan tot 3 minuten
worden verhoogd als er herhaaldelijk wordt overgeschakeld.
In geval van kortsluiting zal de BP proberen om de belasting om de 5 seconden te koppelen.
Na twee pogingen zal op het display E 1 (kortsluiting gedetecteerd) worden weergegeven.
Programmeringstabel
7-segment-display
Onderspanningsherstart
12V- / 24V-systeem
12V / 24V
11,5V / 23V
11,5V / 23V
13,25V / 26,5V
13,8V / 27,6V
12,8V / 25,6V
12,8V / 25,6V
12,8V / 25,6V
13V / 26V
13,2V / 26,4V
Zoemer- of LED modus
Relaismodus
Li-ionmodus
Specificaties
BatteryProtect
BP-50
BP-100
BP-220
Max. continue belastingsstroom 50A 100A 220A
Piekstroom
200A
600A
600A
Bedrijfsspanningsbereik
6 – 35V
Stroomverbruik
Ingeschakeld: 1,5mA Uitgeschakeld of bij laagspanningsuitschakeling:
0,6mA
Alarmuitgangsvertraging
12 seconden
Max. belasting op alarmuitgang
50mA (bestand tegen kortsluiting)
Belastingsontkoppelingsvertraging
90 seconden (direct als geactiveerd door VE.Bus BMS)
Standaarddrempels
Ontkoppelen: 10,5V of 21V Koppelen: 12V of 24V
Bedrijfstemperatuurbereik
Volledige belasting: -40°C tot +40°C (tot 60% van de nominale belasting
bij 50°C)
Gewicht
0,2kg 0,5lbs
0,5kg 0,6lbs
0,8kg 1,8lbs
Afmetingen (hxbxd)
4 0 x 48 x 106 m
1,6 x 1,9 x 4,2 inch
59 x 42 x 115mm
2,4 x 1,7 x 4,6 inch
62 x 123 x 120m m
2,5 x 4,9 x 4,8 inch

Documenttranscriptie

BatteryProtect ENGLISH BatteryProtect NEDERLANDS Installation 1. The BatteryProtect (BP) must be installed in a well-ventilated area and preferably close (max 50 cm) to the battery (but, due to possible corrosive gasses not above the battery!). Voltage drop over a long or undersized cable between the battery plus and the BP may result in unexpected shutdown of the BP. 2. A properly sized fuse must be inserted according to local regulations in the cable between the battery and the BP. 3. Use a 1,5mm² wire (included) for the minus connection, which should be connected directly to the battery minus. No other equipment should be connected to this wire. 4. The BP will automatically detect the system voltage after connection of plus and minus to the battery. During voltage detection the 7 segment display shows a series of flashes between the top and lower part. 5. Do not connect the load output until the BP has been fully programmed. 6. A remote on-off switch can be connected to the two pole connector (see figure 1) or between pin 2-1 of the two pole connector and the battery plus. 7. A buzzer, LED or relay can be connected between the alarm output and the battery plus (see figure 1). Maximum load on the alarm output: 50mA (short circuit proof). Load disconnect events and alarm output options Buzzer or LED mode (buzzer or LED connected to the alarm output): • In case of under voltage, a continuous alarm will start after 12 seconds. The BP will disconnect the load after 90 seconds and the alarm will stop. • In case of over voltage, the load will be disconnected immediately and an intermittent alarm will remain on until the overvoltage problem has been corrected. Relay mode (relay connected to the alarm output): • In case of under voltage, the relay will engage after 12 seconds. The BP will disconnect the load after 90 seconds and the relay will disengage. • In case of over voltage, the load will be disconnected immediately and the alarm output will remain inactive. Li-ion mode: • Connect the load disconnect output of the VE.Bus BMS to pin 2-1. The load is disconnected immediately when the load disconnect output of the VE.Bus BMS switches from ‘high' to ‘free floating’ (due to battery cell under voltage, over voltage or over temperature). The under voltage thresholds and alarm output of the BP are inactive in this mode. Programming When switched off (remote open), the BP can be programmed for the desired voltages and modes by connecting the PROG pin to the ground. Please see the programming table. The display will first step through the shutdown and restart voltages. Disconnect the PROG pin when the desired voltage is displayed. The display will confirm the chosen voltage and default mode () twice. Reconnect the PROG to ground if another mode is ( or ) is required. Disconnect when the required mode is displayed. The display will confirm the chosen voltage and mode twice. Operation There are 4 possible error modes, indicated by the 7 segment display: • E 1 Short circuit detected • E 2 Over load or over temperature • E 3 Under voltage • E 4 Over voltage After 5 minutes the error is no longer displayed to reduce current consumption. The decimal point of the 7 segment display is used for status indication: • On solid: the BP attempts to activate the output • Flash every 5s: output is active • Flashing every 2s in Li-ion mode: output ‘connecting’ Remote control and short circuit • The BP will connect the load 1 second after closing the remote contact. • The BP will disconnect the load immediately when the remote contact is opened. • When in Li-ion mode the BP will connect the load 30 seconds after the remote input of the BP has been pulled high by the VE.Bus BMS. This delay increases to 3 minutes in case of frequent switching. • In case of a short circuit, the BP will attempt to connect the load every 5 seconds. After two attempts the display will show E 1 (short circuit detected).              Maximum cont. load current 50A 100A 220A Peak current 200A 600A 600A Operating voltage range Full load: -40°C to +40°C (up to 60% of nominal load at 50°C) 0.5lbs 40 x 48 x 106mm 1.6 x 1.9 x 4.2 inch 0,5kg 0.6lbs 59 x 42 x 115mm 2.4 x 1.7 x 4.6 inch 200A 600A 600A Bedrijfsspanningsbereik 0,8kg Standaarddrempels Bedrijfstemperatuurbereik Disengage: 10,5V or 21V Engage: 12V or 24V 0,2kg 220A Piekstroom Belastingsontkoppelingsvertraging 50mA (short circuit proof) 90 seconds (immediate if triggered by the VE.Bus BMS) Default thresholds BP-220 100A Max. belasting op alarmuitgang 12 seconds Load disconnect delay BP-100 50A 6 – 35V Ingeschakeld: 1,5mA Uitgeschakeld of bij laagspanningsuitschakeling: 0,6mA Alarmuitgangsvertraging When on: 1,5 mA When off or low voltage shutdown : 0,6 mA Max. load on alarm output BP-50 Max. continue belastingsstroom Stroomverbruik 6 –35V Alarm output delay Dimensions (hxwxd) Onderspanningsuitschakeling Onderspanningsherstart 12V- / 24V-systeem 12V- / 24V-systeem 10,5V / 21V 12V / 24V 10V / 20V 11,5V / 23V 9,5V / 19V 11,5V / 23V 11,25V / 22,5V 13,25V / 26,5V 11,5V / 23V 13,8V / 27,6V 10,5V / 21V 12,8V / 25,6V 11,5V / 23V 12,8V / 25,6V 11,8V / 23,6V 12,8V / 25,6V 12V / 24V 13V / 26V 10V / 20V 13,2V / 26,4V Zoemer- of LED modus Relaismodus Li-ionmodus BatteryProtect BP-220 Weight Bediening Er zijn 4 mogelijke storingsmodi die door het uit 7 segmenten bestaande display worden weergegeven: • E 1 Kortsluiting gedetecteerd • E 2 Overbelasting of overtemperatuur • E 3 Onderspanning • E 4 Overspanning Na 5 minuten wordt de storing niet meer weergegeven om het stroomverbruik te verminderen. De decimale punt van het uit 7 segmenten bestaande display wordt gebruikt voor de statusindicatie: • Brandt continu: de BP probeert om de uitgang te activeren • Knippert om de 5 sec: de uitgang is actief • Knippert om de 2 sec in li-ionmodus: uitgang ‘wordt verbonden’ Afstandsbesturing en kortsluiting • De BP verbindt de belasting 1 seconde na het sluiten van het contact voor in-/uitschakelen op afstand. • De BP zal de belasting direct ontkoppelen als het contact voor in-/uitschakelen op afstand wordt geopend. • In de li-ionmodus zal de BP de belasting 30 seconden nadat de ingangsspanning van de BP door het VE.Bus BMS omhoog is gedreven, koppelen. Deze vertraging kan tot 3 minuten worden verhoogd als er herhaaldelijk wordt overgeschakeld. • In geval van kortsluiting zal de BP proberen om de belasting om de 5 seconden te koppelen. Na twee pogingen zal op het display E 1 (kortsluiting gedetecteerd) worden weergegeven. Specificaties BP-100 Operating temperature range Programmeren Wanneer uitgeschakeld (remote geopend), kan de BP worden geprogrammeerd voor de gewenste spanningen en modi door de pin PROG met de aarde te verbinden. Zie hiervoor de programmeringstabel. Het display doorloopt eerst de uitschakel- en herstartspanningen. Koppel de pin PROG los als de gewenste spanning wordt weergegeven. Het display zal de gekozen spanning en de standaardmodus () twee keer bevestigen. Verbind de pin PROG weer met de aarde als een andere modus ( of ) is gewenst. Koppel de pin weer los als de gewenste modus wordt weergegeven. Het display zal de gekozen spanning en modus twee keer bevestigen.              BP-50 Current consumption Zoemer- of LED modus (zoemer of LED aangesloten op de alarmuitgang): • In geval van onderspanning wordt na 12 seconden een continu alarm afgegeven. De BP zal de belasting na 90 seconden ontkoppelen en het alarm wordt gestopt. • In geval van overspanning wordt de belasting direct ontkoppeld en wordt het alarm intermitterend afgegeven tot het overspanningsprobleem is verholpen. Relaismodus (relais aangesloten op de alarmuitgang): • In geval van onderspanning wordt het relais na 12 seconden geactiveerd. De BP zal de belasting na 90 seconden ontkoppelen en het relais wordt gedeactiveerd. • In geval van overspanning wordt de belasting direct ontkoppeld en blijft het alarm inactief. Li-ionmodus: • Sluit de belasting ontkoppelingsuitgang van het VE.Bus BMS aan op pin 2-1. De belasting wordt direct ontkoppeld als de belasting ontkoppelingsuitgang van het VE.Bus BMS van ‘hoog’ naar ‘free floating’ overschakelt (door onderspanning, overspanning of overtemperatuur van de accucel). De onderspanningsdrempel en alarmuitgang van de BP zijn in deze modus inactief. 7-segment-display Under voltage shut Under voltage restart down 12V / 24V system 12V / 24V system 10,5V / 21V 12V / 24V 10V / 20V 11,5V / 23V 9,5V / 19V 11,5V / 23V 11,25V / 22,5V 13,25V / 26,5V 11,5V / 23V 13,8V / 27,6V 10,5V / 21V 12,8V / 25,6V 11,5V / 23V 12,8V / 25,6V 11,8V / 23,6V 12,8V / 25,6V 12V / 24V 13V / 26V 10V / 20V 13,2V / 26,4V Buzzer or LED mode Relay mode Li-ion mode Specifications BatteryProtect Belasting ontkoppelingsgebeurtenissen en alarm-uitgangsopties Programmeringstabel Programming table 7 segment display Installatie 1. De BatteryProtect (BP) moet worden geïnstalleerd in een goed geventileerd gebied en bij voorkeur dicht (max. 50 cm) bij de accu (maar in verband met de mogelijke corrosieve gassen niet boven de accu). Een spanningsverlies over een lange of te klein bemeten kabel tussen de pluspool van de accu en de BP kan leiden tot een onverwachte uitschakeling van de BP. 2. Een voldoende groot bemeten zekering moet conform de plaatselijke voorschriften worden geplaatst in de kabel tussen de accu en de BP. 3. Gebruik een 1,5mm² draad (meegeleverd) voor de min-aansluiting die direct op de minpool van de accu moet worden aangesloten. Op deze draad mag geen andere apparatuur worden aangesloten. 4. De BP detecteert automatisch de systeemspanning na aansluiting van de plus en min op de accu. Tijdens de spanningsdetectie gaat het uit 7 segmenten bestaande display meermaals knipperen. 5. Sluit de belastingsuitgang pas aan als BP volledig is geprogrammeerd. 6. Een schakelaar voor in-/uitschakelen op afstand kan worden aangesloten op de twee poolaansluitingen (zie afbeelding 1) of tussen pin 2-1 of de twee poolaansluitingen en de plus van de accu. 7. Een zoemer, LED of relais kan worden aangesloten tussen de alarmuitgang en de plus van de accu (zie afbeelding 1). Maximale belasting op de alarmuitgang: 50 mA (bestand tegen kortsluiting). 1.8lbs 62 x 123 x 120mm 2.5 x 4.9 x 4.8 inch Gewicht Afmetingen (hxbxd) 12 seconden 50mA (bestand tegen kortsluiting) 90 seconden (direct als geactiveerd door VE.Bus BMS) Ontkoppelen: 10,5V of 21V Koppelen: 12V of 24V Volledige belasting: -40°C tot +40°C (tot 60% van de nominale belasting bij 50°C) 0,2kg 0,5lbs 0,5kg 0,6lbs 0,8kg 1,8lbs 40 x 48 x 106 m 1,6 x 1,9 x 4,2 inch 59 x 42 x 115mm 2,4 x 1,7 x 4,6 inch Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / The Netherlands Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: [email protected] 62 x 123 x 120mm 2,5 x 4,9 x 4,8 inch