Sentera Controls SPD-G-2K0 Mounting Instruction

Type
Mounting Instruction
Montage & gebruiksvoorschriften
SPD DUBBELE
VERSCHILDRUK
TRANSMITTER
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 2 - 14
Inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN 3
PRODUCTBESCHRIJVING 4
ARTIKEL CODE 4
GEBRUIKSTOEPASSING 4
TECHNISCHE GEGEVENS 4
STANDAARDEN 5
WERKINGSSCHEMA 5
BEKABELING EN AANSLUITING 5
MONTAGE VOORSCHRIFTEN IN STAPPEN 6
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE 8
WERKINGSINSTRUCTIE 8
MODBUS REGISTER MAPPEN 10
TRANSPORT EN BEWAAR INFORMATIE 14
GARANTIE INFORMATIE EN BEPERKINGEN 14
ONDERHOUD 14
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 3 - 14
terug naar inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN
Voor u aan het werk gaat met ons product, lees aandachtig de technische fiche,
installatie instructie en het aansluitschema. Om uw persoonlijke veiligheid en die
van het toestel te garanderen, evenals de optimale prestaties van het product, zorg
ervoor dat u de volledige technische inhoud begrijpt voordat u het toestel installeert,
in gebruik neemt, of onderhoud doet.
Omwille van de veiligheid en de homologatie (CE) is het eigenhandig ombouwen en /
of veranderen van het product niet toegestaan.
Het product mag niet worden blootgesteld aan abnormale omstandigheden zoals:
extreme temperaturen, direct zonlicht of trillingen. Chemische dampen met een hoge
concentratie in combinatie met een lange blootstellingstijd kunnen de prestaties van
het product beïnvloeden. Zorg ervoor dat de werkomgeving zo droog mogelijk is;
controleer daarom ook op condensatie plekken.
Alle installaties moeten voldoen aan de lokale gezondheids- en veiligheidsvoorschrif ten
evenals de plaatselijke elektrische normen. Dit product kan enkel worden geïnstalleerd
door een ingenieur of technicus die een deskundige kennis heeft van het product en
de veiligheidsvoorschriften.
Vermijd contact met onder spanning staande onderdelen; behandel daarom steeds
het product alsof het onder spanning staat.. Schakel steeds de stroombron uit
voordat u de voedingskabels aansluit, onderhoud of reparatie werken uitvoert op
het toestel.
Controleer altijd of u de juiste stroomvoorziening toepast op het product en gebruik
kabels met de juiste diameter en kenmerken. Zorg ervoor dat alle bouten, moeren en
schroeven goed zijn aangedraaid en de zekeringen (indien aanwezig) goed geplaatst
zijn.
Het recycleren van de toestellen of verpakking zou men in overweging moeten nemen,
het weggooien van deze moet volgens nationale wetgeving / regels gebeuren.
Indien u nog vragen heeft, contacteer dan uw technische dienst of een andere
deskundige.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 4 - 14
terug naar inhoudstafel
PRODUCTBESCHRIJVING
De SPD series zijn compacte tweevoudige multi-bereik verschildruk opnemers die een
analoge/digitale uitgang voor elke sensor voorziet en Modbus RTU communicatie
heeft. Ze hebben twee ingebouwde state-of-the-art silicone druksensoren met acht
mogelijke meetbereiken. De SPD piezoresistieve omvormers zijn temperatuur en
druk gecompenseerd, waardoor ze u een hoge nauwkeurigheid en betrouwbaarheid
verschaffen. Een eenvoudige sensor kalibratie en een aan te passen oset is er voor
elke sensor aanwezig.
ARTIKEL CODE
Code Voedingsspanning Behuizing
SPD-G-2K0 15—24 VAC ± 10% / 18—34 VDC 3 - draads*
SPD-F-2K0 18—34 VDC 4 - draads
SPD-G-6K0 1524 VAC ± 10% / 18—34 VDC 3 - draads*
SPD-F-6K0 18—34 VDC 4 - draads
GEBRUIKSTOEPASSING
Verschildruk, luchtvolume meeting in HVAC toepassingen
Verschildruk, luchtvolume** meeting in HVAC toepassingen
Druk / luchtstroom bewaking in clean rooms
Zuivere lucht, niet-agressieve en niet-ontvlambare gassen
TECHNISCHE GEGEVENS
Breed voedingsspanningsbereik
Op lange termijn stabiel en accuraat
2 Analogue / digitale (PWM open collector) uitgangen
8 selecteerbare werkingsbereiken
Modbus RTU (RS485) communicatie
Modbus register reset functie (naar de fabriek pre-set waarde) voor elke sensor
Geïmplementeerd K-factor (voor luchtdebietsmeeting)
Een sensor kalibratie van de sensoren
Verschildruk, luchtvolume** uitlezing via Modbus RTU
Klemmenstrook met 0.75 mm² aansluitingen
Reactie tijd: 0,5 / 1 / 2 / 5 s
Nauwkeurigheid: ± 3% rH
Op lange termijn stabiel: ± 1 % per jaar
Behuizing: Versterkt ABS plastiek, grijs (RAL 7035
Maximaal opgenomen vermogen
SPD-F: 1,44 W
SPD-G: 2,16 W
Gemiddeld opgenomen vermogen bij normaal gebruik
SPD-F: 1,08 W
SPD-G: 1,62 W
Imax
SPD-F: 60 mA
SPD-G: 90 mA
Bedrijfsomgevingsvoorwaarden:
Temperatuur: 10—60 °C
relatieve vochtigheid: < 95 % rH (niet-condenserend)
Opslagtemperatuur: -20—70 °C
*In het geval van een 3-draads verbinding, is bij de analoge uitgang de GND intern verbonden met de GND van de voeding. Daarom, kan de G en F-type toe-
stellen niet in een gezamelijk netwerk gebruikt worden. G en F-type toestellen moeten gevoed worden via separate voeding. Connecteer de GND aansluitingen
van de G en F-type toestellen niet aan elkaar.
** Enkel van toepassing als de K-factor van de ventilator is gekend. Als de K-factor niet gekend is, kan het luchtdebiet berekend worden via de leiding door-
snede (A) te vermenigvuldigen met de luchtstroomsnelheid(V) met behulp van volgende formule Q = A * V
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 5 - 14
terug naar inhoudstafel
STANDAARDEN
Laagspanning richtlijn 2006/95/EC
WEEE richtlijn 2002/96/EC
RoHs richtlijn 2011/65/EC
EMC richtlijnen 2004/108/EC
WERKINGSSCHEMA
0102030405060708090100
10
20
30
40
50
60
70
80
90
100
Verschildruk [%]
Uitgang 1, 2 [%]
VDC
mA
PWM
Pa
BEKABELING EN AANSLUITING
Vin Voedingsspanning
GND Aarding / AC ~
AModbus RTU (RS485), signaal A
/B Modbus RTU (RS485), signaal /B
AO1 Аnaloge / digitale uitgang 1
GND Massa
AO2 Аnaloge / digitale uitgang 2
Verbindingen
Kabel diameter: max. 1,5 mm2
Kabelwartel opspanbereik van de wartel: 3,5 mm
Aansluit einde diameter: 6—7 mm
ATTENTIE
G en F-type toestellen kunnen niet in een gezamelijk netwerk worden gebruikt. G
en F-type toestellen moeten gevoed worden via separate voeding. Connecteer de
GND aansluitingen van de G en F-type toestellen niet aan elkaar.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 6 - 14
terug naar inhoudstafel
MONTAGE VOORSCHRIFTEN IN STAPPEN
Voordat u start aan de installatie van de DPS verschildruk transmitter, lees dan
zorgvuldig deVeiligheid en voorzorgsmaatregelen”. Kies een makkelijke effen
oppervlakte als installatielocatie (een muur, een paneel, etc.):
1. Draai de vier schroeven aan de voorzijde van de behuizing los en verwijder het
deksel.
2. Bevestig de achterzijde van de behuizing op het oppervlak dit door middel van
geschikte bevestigingsmiddelen te gebruiken volgens de afmetingen en de juiste
montagestand getoond in Fig. 1 Montageafmetingen en Fig. 2 Montage positie.
Fig. 1 Bevestigingsafmetingen Fig. 2 Montage positie
SPD
+_
80
65
85
2x Ø 6
46
24 15 10,5
10
2x Ø 3,
4
49
52
Acceptabel Niet acceptabel
SPD
+_
SPD
+_
SPD
+_
3. Breng de kabel via de wartel naar binnen.
4. Sluit aan zoals aangegeven in Fig. 3 Aansluitingen en die voldoen aan de
informatie in de sectie ”Bekabeling en aansluiting”.
Fig. 3 Aansluitingen
Voedingsspanning
G: 15—24 VAC ± 10%/
18—34 VDC
F: 18—34 VDC
Modbus RTU
A /B
Аnaloge / digitale uitgang 1
010 VDC / 0—20 mA
Аnaloge / digitale uitgang 2
010 VDC / 0—20 mA
5. Bevestig de slangpilaar met de slangen. De positie van de slangpilaren wordt in
Fig. 4 Slangpilaar positie hier beneden weergegeven:
Fig. 4 Slangpilaar
Sensor 2
Sensor 1
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 7 - 14
terug naar inhoudstafel
NOTA
Zie de positie van
Voor de Callibratie en Modbus register reset procedure is meer te vinden in sectie
Werkingsinstructie”.
Analoge / digitale uitgang Ao1 en Ao2 selectie
Gebruik de driestanden schakelaar 1 en 2 (SW1 en SW2) om de uitgang modus
van respectievelijk sensor 1 en sensor 2 te selecteren. Zie Fig. 5 Analoge / digitale
uitgang selectie voor de overeenkomende positie
Fig. 5 Analoge / digitale uitgang selectie
Positie 1 0—10 VDC
Positie 2 0—20 mA
Positie 3 PWM (open collector)
31 2
Sensor kalibratie en Modbus register reset
Gebruik de twee tact drukknoppen – SW3 en SW4 voor de kalibratie en Modbus
register reset(naar hun fabrieksinstellingen) dit voor hun respectievelijk sensor 1
en sensor 2.
Resetten van de Modbus communicatie registers druk gelijktijdig SW3 en
SW4 knoppen gedurende 4 seconden in totdat de blauwe LED2 en LED3 op de
printplaat viermaal knipperen. Na 2 seconden gaan de LEDs opnieuw drie keer
knipperen om aan te geven dat de Modbus holding registers gereste zijn naar hun
fabrieksinstellingen.
Optionele instellingen
Wanneer het toestel een netwerk start of afsluit (zie Voorbeeld 1 en Voorbeeld 2),
kijk dan zeker na dat de NBT jumper correct op de pinnen zoals aangetoond in Fig.
2 zit. In alle andere gevallen, moet de jumper niet geconnecteerd zijn. Standaard
zal, NBT jumper is ontkoppeld - Zie Fig. 6 Bus Netwerk weerstand jumper.
Plaats de afdekplaat van de voorzijde terug en bevestig deze.
Schakel de voedingsspanning aan.
Example 1 Example 2 Fig. 6 Netwerk bus weerstand
RX
ТX
NBT
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTA Sluit de NBT terminator enkel in de twee verste van elkaar verwijderde eenheden
op het netwerk!
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 8 - 14
terug naar inhoudstafel
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE
Continue groen LED indicatie zoals in Fig. 6 LED indicatie – a. Voeding aan indicatie
weergegeven duid erop dat de voeding aanwezig is. Als deze Led niet aan is,
controleer dan de connecties opnieuw.
Knippert blauwe LED2 en LED3 zoals in Fig. 6 LED indicatie – b.
Kalibratie en Modbus reset aangeven dan betekent dit dat respectievelijk sensor
1 en sensor 2 gekalibreerd zijn en dat de Modbus holding registers terug in hun
fabrieksinstellingen staan.
Knipperend groen LED op de linkse zijde indiceert dat een signaal verstuurd wordt
op de RS485 lijn.
Knipperend groen LED op de rechter zijde indiceert dat er een signaal ontvangen
wordt op de RS485 Lijn. Zie Fig. 6 LED indicaties – c. Actieve communicatie
indicatie.
Fig. 6 Communicatie LED indicatie
a. Voeding aan indicatie b. Kalibratie en Modbus
reset indicatie
c. Modbus communicatie
indicatie
NOTA Voor meer informatie over het instellen van de opnemer, verwijzen wij u graag
naar de datasheet, sectie "Instellingen en indicaties".
ATTENTIE De status van de LEDs kan enkel gecontroleerd worden als het toestel aan staat.
Neem de nodige veiligheidsmaatregelen!
WERKINGSINSTRUCTIE
Kalibratie procedure Sensor 1:
1. Maak de verbindingen met de slangpilaar van sensor 1 los.
2. Druk drukknop SW3 gedurende 4 seconden in tot de blauwe LED3 tweemaal
knippert, laat dan los.
3. Na 2 seconden zal de blauwe LED3 terug tweemaal knipperen om aan te geven
dat de kalibratieprocedure gestopt is.
Kalibratie procedure Sensor 2:
1. Maak de verbindingen met de slangpilaar van sensor 2 los.
2. Druk drukknop SW4 gedurende 4 seconden in tot de blauwe LED2 tweemaal
knippert, laat dan los.
3. Na 2 seconden zal de blauwe LED2 terug tweemaal knipperen om aan te geven
dat de kalibratieprocedure gestopt is.
Modbus register reset procedure voor sensor 1:
Druk drukknop SW3 gedurende 4 seconden in tot de blauwe LED3 tweemaal
knippert en houd deze dan ingedrukt tot de LED3 driemaal knippert. Het holding
register is naar de fabrieksinstellingen gereset.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 9 - 14
terug naar inhoudstafel
Modbus register reset procedure voor sensor 2:
Druk drukknop SW4 gedurende 4 seconden in tot de blauwe LED2 tweemaal
knippert en houd deze dan ingedrukt tot de LED2 driemaal knippert. Het holding
register is naar de fabrieksinstellingen gereset. 1:
NOTA Houd de knop ingedrukt totdat beide LED's op de PCB twee keer knipperen en
houd dit vast totdat de LED’s drie keer knipperen. Als de toets wordt losgelaten
voordat de LED’s drie keer knipperde dan heeft de sensor een kalibratie procedure
uitgevoerd in plaats van een Modbus-registers reset procedure.
Communicatie holding register reset procedure :
Druk beide drukknoppen(SW3 en SW4) gelijktijdig gedurende 4 seconden in tot
de blauwe LED2 en LED3 driemaal knippert en laat dan los. Na 2 seconden gaan
de blauwe LEDs terug driemaal knipperen om aan te geven dat de communicatie
holding registers naar hun fabrieksinstelling is gereset.
ATTENTIE Zorg dat de slangpilaren vrij en niet aangesloten zijn.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 10 - 14
terug naar inhoudstafel
MODBUS REGISTER MAPPEN
INPUT REGISTERS - SPD-X-2K0
Data type Description Data Values
1Differential pressure Sensor 1 signed int. Measured differential pressure Sensor 1 -100—2.000 1.000 = 1.000 Pa
2Output Sensor 1 unsigned int. Analogue / digital output value Sensor 1 0—1.000 100 = 10.0 %
3Max. pressure limit flag Sensor 1 unsigned int. Flag indicates that the pressure is out of the max. limit
range for Sensor 1 0 =
1 = Below the limit
Above the limit
4Min. pressure limit flag Sensor 1 unsigned int. Flag indicates that the pressure is out of the min. limit
range for Sensor 1 0 =
1 = Below the limit
Above the limit
5Volume flow rate Sensor 1 unsigned int. Air Volume flow rate in m3/h from Sensor 1 0—44.000 1.000 = 1.000 m3
6Differential pressure range Sensor 1 unsigned int. Flag indicates the current differential pressure range of
Sensor 1
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—100 Pa
0—250 Pa
0—500 Pa
0—750 Pa
0—1.000 Pa
0—2.000 Pa
-50—50 Pa
-100—100 Pa
2.000 = 2.000 Pa
7Diff. pressure response time -
Sensor 1 unsigned int. Flag indicates the current response time of Sensor 1
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
8-10 Reserved, return 0
11 Differential pressure Sensor 2 signed int. Measured differential pressure Sensor 2 -100—2.000 1.000 = 1.000 Pa
12 Output Sensor 2 unsigned int. Analogue / digital output value Sensor 2 0—1.000 100 = 10.0 %
13 Max. pressure limit flag Sensor 2 unsigned int. Flag indicates that the pressure is out of the max. limit
range for Sensor 2 0 =
1 = Below the limit
Above the limit
14 Min. pressure limit flag Sensor 2 unsigned int. Flag indicates that the pressure is out of the min. limit
range for Sensor 2 0 =
1 = Below the limit
Above the limit
15 Volume flow rate Sensor 2 unsigned int. Air Volume flow rate in m3/h from Sensor 2 0—44.000 1.000 = 1.000 m3
16 Differential pressure range Sensor 2 unsigned int. Flag indicates the current differential pressure range of
Sensor 2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—100 Pa
0—250 Pa
0—500 Pa
0—750 Pa
0—1.000 Pa
0—2.000 Pa
-50—50 Pa
-100—100 Pa
2.000 = 2.000 Pa
17 Diff. pressure response time -
Sensor 2 unsigned int. Flag indicates the current response time of Sensor 2
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
18-20 Reserved, return 0
INPUT REGISTERS - SPD-X-6K0
Data type Description Data Values
1Differential pressure Sensor 1 signed int. Measured differential pressure Sensor 1 0—6.000 1.000 = 1.000 Pa
2Output Sensor 1 unsigned int. Analogue / digital output value Sensor 1 0—1.000 100 = 10.0 %
3Max. pressure limit flag Sensor 1 unsigned int. Flag indicates that the pressure is out of the max. limit
range for Sensor 1 0 =
1 = Below the limit
Above the limit
4Min. pressure limit flag Sensor 1 unsigned int. Flag indicates that the pressure is out of the min. limit
range for Sensor 1 0 =
1 = Below the limit
Above the limit
5Volume flow rate high word Sensor 1 unsigned int. Air Volume flow rate high word in m3/h of Sensor 1 0—77.000 1.000 = 1.000 m3/h
6Volume flow rate low word Sensor 1 unsigned int. Air Volume flow rate low word in m3/h of Sensor 1
7Differential pressure range Sensor 1 unsigned int. Flag indicates the current differential pressure range of
Sensor 1
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—1.000 Pa
0—1.500 Pa
0—2.000Pa
0—2.500 Pa
0—3.000 Pa
0—4.000 Pa
0—5.000 Pa
0—6.000 Pa
2.000 = 2.000 Pa
8Diff. pressure response time - Sensor
1unsigned int. Flag indicates the current response time of Sensor 1
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
9-10 Reserved, return 0
11 Differential pressure Sensor 2 signed int. Measured differential pressure Sensor 2 0—6.000 1.000 = 1.000 Pa
12 Output Sensor 2 unsigned int. Analogue / digital output value Sensor 2 0—1.000 100 = 10.0 %
13 Max. pressure limit flag Sensor 2 unsigned int. Flag indicates that the pressure is out of the max. limit
range for Sensor 2 0 =
1 = Below the limit
Above the limit
14 Min. pressure limit flag Sensor 2 unsigned int. Flag indicates that the pressure is out of the min. limit
range for Sensor 2 0 =
1 = Below the limit
Above the limit
15 Volume flow rate high word Sensor 2 unsigned int. Air Volume flow rate high word in m3/h of Sensor 2 0—77.000 10.000 = 10.000 m3/h
16 Volume flow rate low word Sensor 2 unsigned int. Air Volume flow rate low word in m3/h of Sensor 2
17 Differential pressure range Sensor 2 unsigned int. Flag indicates the current differential pressure range of
Sensor 2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—1.000 Pa
0—1.500 Pa
0—2.000 Pa
0—2.500 Pa
0—3.000 Pa
0—4.000 Pa
0—5.000 Pa
0—6.000 Pa
2.000 = 2.000 Pa
18 Diff. pressure response time - Sensor
2unsigned int. Flag indicates the current response time of Sensor 2
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
19-20 Reserved, return 0
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 11 - 14
terug naar inhoudstafel
HOLDING REGISTERS - SPD-X-2K0 -6 & SPD-X-6K0
Data type Description Data Default Values
1Address unsigned
int. Device address 1—247 1
2RS485 baud rate unsigned
int. Modbus communication baud rate 1 =
2 =
3 =
9.600
19.200
38.400 2
3RS485 Parity mode unsigned
int. Parity check mode 0 =
1 =
2 =
8N1
8E1
8O1 10 =
1 =
2 =
8N1
8E1
8O1
4Device type unsigned
int. Device type (Read only) SPD-X-2K0 =
SPD-X-6K0 = 1020
1052
5HW version unsigned
int. Hardware version of the device
(Read only) XXX 100 = HW version
1.00
6FW version unsigned
int. Firmware version of the device (Read
only) XXX 100 = FW version
1.00
7-10 Reserved, return 0
11 Mode - Sensor 1 unsigned
int. Operating mode of Sensor 1 1 =
2 = Standalone mode
Modbus mode 1
12 Range Sensor 1 unsigned
int. Range selection for Sensor 1
SPD-X-2K0 SPD-X-6K0
4
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—100 Pa
0—250 Pa
0—500 Pa
0—750 Pa
0—1.000 Pa
0—2.000 Pa
-50—50 Pa
-100—100 Pa
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—1.000 Pa
0—1.500 Pa
0—2.000 Pa
0—2.500 Pa
0—3.000 Pa
0—4.000 Pa
0—5.000 Pa
0—6.000 Pa
13 Response Time Sensor 1 unsigned
int. Response time selection for Sensor
1
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
1
14 Max. pressure limit -
Sensor 1 unsigned
int. Max. pressure limit selection for
Sensor 1 SPD-X-2K0 =
SPD-X-6K0 = -100—2.000
0—6.000 SPD-X-2K0 =
SPD-X-6K0 = 1.000
3.000 1.000 = 1.000 Pa
15 Min. pressure limit -
Sensor 1 unsigned
int. Min. pressure limit selection for
Sensor 1 SPD-X-2K0 =
SPD-X-6K0 = -100—2.000
0—6.000 SPD-X-2K0 =
SPD-X-6K0 = 0
01.000 = 1.000 Pa
16 Power-up timer - Sensor 1 unsigned
int. Power up timer before measuring
the lower limit for Sensor 1 0—1.000 s 60 s 100 = 100 s
17 K-factor Sensor 1 unsigned int K-factor selection according to the
fan / drive type for Sensor 1 01.000 0
18-20 Reserved, return 0
21 Mode - Sensor 2 unsigned
int. Operating mode of Sensor 2 1 =
2 = Standalone mode
Modbus mode 1
22 Range Sensor 2 unsigned
int. Range selection for Sensor 2
SPD-X-2K0 SPD-X-6K0
4
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—100 Pa
0—250 Pa
0—500 Pa
0—750 Pa
0—1.000 Pa
0—2.000 Pa
-50—50 Pa
-100—100 Pa
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
0—1.000 Pa
0—1.500 Pa
0—2.000 Pa
0—2.500 Pa
0—3.000 Pa
0—4.000 Pa
0—5.000 Pa
0—6.000 Pa
23 Response Time Sensor 2 unsigned
int. Response time selection - Sensor 2
0 =
1 =
2 =
3 =
0,5 s
1 s
2 s
5 s
1
24 Max. pressure limit -
Sensor 2 unsigned
int. Max. pressure limit selection for
Sensor 2 SPD-X-2K0 =
SPD-X-6K0 = -100—2.000
0—6.000 SPD-X-2K0 =
SPD-X-6K0 = 1.000
3.000 1.000 = 1.000 Pa
25 Min. pressure limit -
Sensor 2 unsigned
int. Min. pressure limit selection for
Sensor 2 SPD-X-2K0 =
SPD-X-6K0 = -100—2.000
0—6.000 SPD-X-2K0 =
SPD-X-6K0 = 0
01.000 = 1.000 Pa
26 Power-up timer - Sensor 2 unsigned
int. Power up timer before measuring
the lower limit for Sensor 2 0—1.000 s 60 s 100 = 100 s
27 K-factor Sensor 2 unsigned int K-factor selection according to the
fan / drive type for Sensor 2 01.000 0
28-30 Reserved, return 0
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 12 - 14
terug naar inhoudstafel
INPUT REGISTERS (zie Tabellen Input registers hierboven)
De input registers zijn enkel uitlees. Alle data kan uitgelezen worden door het ‘Read
Inputs Registers’ commando te gebruiken. De input registers van de SPD-X-2K0 en
SPD-X-6K0 zijn verschillend, daarom zijn deze in twee aparte Input register tabellen
weergegeven. De twee Input register tabellen hierboven tonen de data type zoals
weergegeven en de wijze hoe die te interpreteren. Als een register niet wordt
gebruikt dan staat deze gedefinieerd als "gereserveerd" en duid deze “0” wanneer
die wordt uitgelezen.
HOLDING REGISTERS (zie Tabel Holding registers hierboven)
Deze registers zijn schrijf / lees registers en deze kunnen gemanaged worden via
“Read Holding Registers”, “Write single register” en “Write Multiple Registers”
commandos. De registers die niet gebruikt worden zijn enkel-lees en, daarom, geeft
het schrijven in deze noch een error weer, noch worden de waardes in deze registers
gewijzigd.
Register 1 omvat het sensoradres op welk de sensor beantwoord binnen het
Modbus netwerk. Het standaard adres is ‘1. Het kan via twee mogelijkheden
aangepast worden.
1. Zend commandoWrite Single Register” met adres ‘1’ en schrijf de nieuwe
adres waarde.
2. Connecteer enkel uw toestel aan een master controller of PC applicatie en
zend het commando “Write Single Register” naar adres ‘0’ (Modbus broadcast
address) en schrijf een nieuw adres waarde.
De twee volgende holding registers 2 en 3 bevatten ook Modbus-instellingen.
Veranderingen aan deze registers wijzigt ook de communicatie instellingen. De
standaard Modbus instellingen zijn als weergegeven in de Modbus Protocol
Specification.
De volgende drie holding registers 4, 5 en 6 zijn enkel-uit te lezen. Zij geven
informatie terug over de sensor hardware en software versie.
De volgende vier registers (7, 8, 9 en 10) worden niet gebruikt. De input registers
zijn enkel uitlees.
NOTA Het schrijven in deze registers geeft u noch een Modbus fout, noch wijzigingen!
Holding register 11 bepaald de modus voor Sensor 1. Stuur het commando “Write
Single Register” met adres ‘11’en data ‘2’ zet de sensor 1 in Modbus Modus. In
Modbus modus wordt het bereik en de respons tijd instellingen enkel via Modbus
gecontroleerd (in standalone modus worden deze instellingen via de on-board
jumpers gecontroleerd). Om de standalone modus te wijzigen, is het noodzakelijk
om het commando “Write Single Register” naar het adres ‘11’ met de data ‘1’ te
schrijven. Zodra de gebruiker Sensor 1 in Modbus modus heeft ingesteld, wordt
het standaardbereik op 0-1.000 Pa voor SPD-X2K0 en op 0-3.000 Pa voor SPD-X-
6K0 ingesteld (waarde ‘4’ in holding register 12) en de responstijd op 1s (waarde
‘1’in holding register 13).
Holding register 12 stelt het gewenste bereik in Modbus modus in voor sensor 1.
De standaard waarde is “4”d.w.z 0-1.000 Pa voor SPD-X-2K0 en 0-3.000 Pa voor
SPD-X-6K0.
Holding register 13 denieert de huidige respons tijd voor Sensor 1. De standaard
waarde is “1”d.w.z. 1 seconde.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 13 - 14
terug naar inhoudstafel
Holding register 14 bevat de maximale verschildruk limiet waarde. Wanner
de gemeten druk hoger of gelijk is aan deze waarde, zal het input register 3
(Max. druk limiet vlag voor sensor 1) op ‘1’ gezet worden, anders is deze ‘0. Dit
register aanvaard waardes tussen ‘-100’ en’2.000’ voor de SPD-X-2K0 en tussen
‘0’ en ‘6.000’ voor de SPD-X-6K0. Wanneer een waarde buiten het bereik wordt
geschreven, dan zal de standaard waarde in dit register weergegeven worden. De
maximum limiet hangt ook van het huidige bereik af. Als de maximum limiet in het
holding register 14 hoger is dan de maximum van het huidige bereik, wordt deze
automatisch gelijk gesteld aan de maximum van het ingestelde bereik.
Holding register 15 definieert de minimale limietvan de druk voor sensor 1. De
standaard waarde is het minimum van het ingestelde bereik. Wanner de gemeten
druk lager is aan deze waarde, zal het input register 4 (Min. limiet vlag voor sensor
1) op ‘0’ gezet worden, anders is deze ‘1. Dit register aanvaard waardes tussen
‘-100’ en’2.000’ voor de SPD-X-2K0 en tussen ‘0’ en ‘6.000’ voor de SPD-X-6K0.
Wanneer een waarde buiten het bereik wordt geschreven, dan zal de standaard
waarde in dit register weergegeven worden. De minimum limiet hangt ook van het
huidige bereik af. Als de minimum limiet in het holding register 15 lager is dan de
minimum van het huidige bereik, wordt deze automatisch gelijk gesteld aan de
minimum van het ingestelde bereik.
NOTA De waarde van het minimum limit kan niet hoger zijn dan die van de maximum
limit. Als een waarde hoger dan de opgegeven maximum wordt ingevoerd in dit
register, zal deze automatisch dezelfde waarde als de maximum limiet weergeven.
Holding register 16 definieert de opstart tijd voor sensor 1. Standaard is deze
60 s. Gedurende deze tijd wordt de minimum limiet instelling niet vergeleken met
de gemeten druk en de min. Druk limiet Flag register blijft op ‘0’ gedurende deze
periode.
NOTA Als een waarde lager dan de opgegeven minimum wordt ingevoerd in holding
register 16, zal deze automatisch dezelfde waarde als de minimum limiet
weergeven. (Bijvoorbeeld: wanneer bij min. 200 en max. 1.000, de max. waarde
veranderd wordt naar 150, d.w.z. lager is dan de min. waarde, dan zal het toestel
automatisch de min. waarde op 150 instellen omdat de min. niet hoger kan zijn
dan de max.)
Holding register 17 is voor de K-factor. Geef de K-factor van de gebruikte ventilator
/ drive, als deze gekend is (controleer de datafiche van de geselecteerde ventilator
/ drive). De standaard waarde is 0, u kan waardes van 01.000 invoeren. Als u hier
een waarde buiten het bereik schrijft zal er niks gewijzigd worden in dit register.
Volgende holding registers19—20 worden niet gebruikt. Wanneer aangesproken,
Zij geven ‘0’ weer.
Holding registers 2130 instellingen Sensor 2. Deze zijn een copy van de
functionaliteiten van de holding registers 1120, maar dan voor sensor 2.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
www.sentera.eu
MIW-SPD-NL-000 - 02 / 07 / 19 14 - 14
terug naar inhoudstafel
TRANSPORT EN BEWAAR INFORMATIE
Vermijd schokken en extreme condities; bewaar in originele verpakking.
GARANTIE INFORMATIE EN BEPERKINGEN
Twee jaar vanaf de leveringsdatum op fabricage fouten. Elke aanpassing of verandering
van het product ontheft de fabrikant van alle mogelijke verantwoordelijkheid. De
fabrikant wijst alle verantwoordelijkheid af voor alle drukfouten of vergissingen
in deze data en aanpassingen of modificaties die zijn aangebracht na de tijd van
publicatie.
ONDERHOUD
Onder normale condities is dit een onderhoudsvrij product. Bij vervuiling, reinig met
een droge of licht vochtige doek. In geval van sterke verontreiniging, reinig met een
niet agressief product. Onder deze omstandigheid koppel het toestel los van de
voeding. Let erop dat geen vloeistoffen het toestel kunnen binnentreden. Enkel
terug aansluiten als het toestel volledig droog is.
DUBBELE
VERSCHILDRUK TRANSMITTER
SPD
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Sentera Controls SPD-G-2K0 Mounting Instruction

Type
Mounting Instruction