Sentera Controls DADCM-44 Mounting Instruction

Type
Mounting Instruction
Montage & gebruiksvoorschriften
ANALOOG NAAR DIGITAAL
OMVORMER VOOR DIN-RAIL
MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 2 - 12
Inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN 3
PRODUCTBESCHRIJVING 4
ARTIKELCODE 4
GEBRUIKSTOEPASSING 4
TECHNISCHE GEGEVENS 4
NORMEN 4
WERKINGSSCHEMA 5
BEKABELING EN AANSLUITING 5
MONTAGE VOORSCHRIFTEN IN STAPPEN 6
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE 7
WERKINGSINSTRUCTIE 8
MODBUS REGISTER MAPPEN 9
TRANSPORT EN OPSLAG 12
GARANTIE INFORMATIE EN BEPERKINGEN 12
ONDERHOUD 12
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 3 - 12
terug naar inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN
Voor u aan het werk gaat met ons product, lees aandachtig de technische fiche,
installatie instructie en het aansluit schema. Om uw persoonlijke veiligheid en die
van het toestel te garanderen, evenals de optimale prestaties van het product, zorg
ervoor dat u de volledige technische inhoud begrijpt voordat u het toestel installeert,
in gebruik neemt, of onderhoud doet.
Omwille van de veiligheid en vergunningverlening (CE) is het eigenhandig ombouwen
en/of veranderen van het product niet toegestaan.
Het product mag niet worden blootgesteld aan abnormale omstandigheden zoals:
extreme temperaturen, direct zonlicht of trillingen. Chemische dampen met een hoge
concentratie in combinatie met een lange blootstellingstijd kunnen de prestaties
van het product beïnvloeden. Zorg ervoor dat de werkomgeving zo droog mogelijk
is; controleer daarom ook op condensatie plekken.
Alle installaties moeten voldoen aan de lokale gezondheids- en
veiligheidsvoorschriften evenals de plaatselijke elektrische normen. Dit product
kan enkel worden geïnstalleerd door een ingenieur of technicus die een deskundige
kennis heeft van het product en de veiligheidsvoorschriften.
Vermijd contact met onder spanning staande onderdelen; behandel daarom steeds
het product alsof het onder spanning staat. Schakel steeds de stroombron uit
voordat u de voedingskabels aansluit, onderhoud of reparatie werken uitvoert op
het toestel.
Controleer altijd of u de juiste stroomvoorziening toepast op het product en
gebruik kabels met de juiste diameter en kenmerken. Zorg ervoor dat alle bouten,
moeren en schroeven goed zijn aangedraaid en de zekeringen (indien aanwezig)
goed geplaatst zijn.
Het recycleren van de toestellen of verpakking zou men in overweging moeten nemen,
het weggooien van deze moet volgens nationale wetgeving / regels gebeuren.
Indien u nog vragen heeft, contacteer dan uw technische dienst of een andere
deskundige.
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 4 - 12
terug naar inhoudstafel
PRODUCTBESCHRIJVING
Onze DADCM is een analoog naar digitaal (Modbus RTU) omvormer voor DIN-
rail montage die gevoed wordt via de voeding over Modbus. De DADCM/08
versie heeft vier analoge/digitale (PWM) en vier analoge ingang signalen
terwijl de DADCM/44 versie u vier analoog/digitaal (PWM) ingangen en vier
temperatuur ingangen biedt. Het type ingangssignaal wordt in de Modbus RTU
registers geselecteerd. De invoerwaarden worden overgezet naar Modbus RTU.
ARTIKELCODE
Code Aantal analoge / modulerende ingangen Aantal analoge ingangen Aantal Temperatuur ingangen Modbus RTU
DADCM/08 4 4 0 ja
DADCM/44 4 0 4
GEBRUIKSTOEPASSING
Gebouwbeheersysteem (GBS) en gecontroleerde ventilatiesystemen
Zuivere lucht, niet-agressieve en niet-ontvlambare gassen
Uitsluitend voor binnen gebruik
TECHNISCHE GEGEVENS
24 VDC / 1 W voedingsspanning, Voeding over Modbus (PoM)
Maximaal opgenomen vermogen: 0,96 W
Gemiddeld opgenomen vermogen bij normaal gebruik: 0,72 W
Imax: 40 mA
Eenvoudig aan te sluiten via de twee aansluitklemmen en de twee RJ45 Modbus
RTU connectoren op de PCB
DIN-rail montage
Er zijn twee productversies
Behuizing: plastic ABS, UL94-V0, grijs RAL 7035
Bedrijfscondities:
Temperatuur: -5—65 °C
Rel. vochtigheid: 5—85 % rH (niet-condenserend)
Opslagtemperatuur: -4050 °C
NORMEN
Laagspanning richtlijn 2014/35/EC
WEEE richtlijn 2012/19/EC
RoHs richtlijn 2011/65/EC
EMC richtlijnen 2014/30/EC EN 61000-6-2 2005/AC:2005, EN 61000-6-3:2007/
A1:2011/AC:2012, EN 61326-2-3:2013
DIN rail EN 60715:2001 compatibel: EN 60730-1:2011
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 5 - 12
terug naar inhoudstafel
WERKINGSSCHEMA
10
0
20
30
40
50
60
70
80
90
100
0100 0—10 VDC,
0—20 mA,
PWM*
Modbus
register
waarde [%]
10
0
20
30
40
50
60
70
80
90
100
-30 70
Temperatuur (˚C)
Modbus
register
waarde [%]
Modbus-uitgangswaarde (%)
* enkel beschikbaar in Ai1 - Ai4
BEKABELING EN AANSLUITING
DADCM/08
Ai1—Ai4 Analoge ingangen
AGND Aarding voor analoge / modulerende ingangen
Ai5—Ai8 Analoge ingangen
AGND Hysteresis for analog input Ai2.
DADCM/44
Ai1—Ai4 Analoge ingangen
AGND Aarding voor analoge / modulerende ingangen
Ti1Ti4 Temperatuur ingangen 2 (PT500 of PT1000)
AGND
Aansluitingen Draad diameter: max. 1,5 mm2
Kabelwartel opspanbereik van de wartel: 3,5 mm
RJ45 connector
24 VDC Voedingsspanning Us 24 VDC
GND Aarding
A Modbus RTU (RS485) communicatie, signaal A
/B Modbus RTU (RS485) communicatie, signaal /B
/B
A
GND
24 VD
C
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 6 - 12
terug naar inhoudstafel
MONTAGE VOORSCHRIFTEN IN STAPPEN
Voordat u start aan de installatie van de DADCM, lees dan zorgvuldig de Veiligheid
en voorzorgsmaatregelen”.
1. Schuif het apparaat langs de geleiders van een standaard 35 mm DIN rail en
bevestig het aan de rail door middel van de zwarte sluitclip op de behuizing.
Let op de juiste positie en inbouwmaten in Fig. 1 Montageafmetingen en Fig. 2
Montage positie.
Fig. 1 Bevestigings afmetingen Fig. 2 Montage positie
DADCM/44 POWER
TX
RX
Modbus
AGND
GND
Ти4
Ti1
Ti3
Ti2
Ai1
AGND
AGND
A14
Ai2
Ai3
70
93,5
65,5
DADCM/44 POWER
TX
RX
Modbus
AGND
GND
Ти4
Ti1
Ti3
Ti2
Ai1
AGND
AGND
A14
Ai2
Ai3
Vergrendelingsclip Vergrendeld
Ontgrendeld
DIN rail
2. Sluit aan zoals aangegeven in Fig. 3 Elektrisch schema en die voldoen aan de
informatie in de sectie ”Bekabeling en aansluiting”.
Fig. 3 Elektrisch schema
DADCM/08 DADCM/44
Ai1
AGND
Ai2
Ai3
AGND
Ai4
Ai5
AGND
Ai6
Ai7
AGND
Ai8
Ai1
AGND
Ai2
Ai3
AGND
Ai4
Ti1
AGND
Ti2
Ti3
AGND
Ti4
3. Sluit de RJ45-aansluitingen aan op de RJ45-connectoren (zie Fig. 4).
Fig. 4 RJ45-connectoren
/B
A
GND
24 VD
C
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Zie de positie van
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 7 - 12
terug naar inhoudstafel
Optionele instellingen
Controleer of uw toestel een netwerk start of afsluit (zie Voorbeeld 1 en Voorbeeld
2). Als uw toestel geen eindapparaat is, laat u de NBT open (standaard Modbus-
instelling).
Voorbeeld 1 Voorbeeld 2
RX
ТX
NBT
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTA Sluit de NBT terminator enkel in de twee verste van elkaar verwijderde eenheden
op het netwerk!
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE
Groen POWER 'ON' geeft aan dat het apparaat onder spanning staat.
Knipperende groene TX- en RX-LED's geven actieve Modbus RTU-communicatie
aan.
Knipperende LED's op de RJ45-connector geven ook actieve Modbus RTU-
communicatie aan.
Als dit niet het geval is, controleer dan de aansluitingen (zie Fig. 5 LED-indicaties
hieronder).
Fig. 5 Communicatie LED indicatie
Fig. 5a Voorpaneel LED indicatie Fig. 5b LED-indicaties
ATTENTIE De status van de LEDs kan enkel gecontroleerd worden als het toestel aan staat.
Neem de nodige veiligheidsmaatregelen!
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 8 - 12
terug naar inhoudstafel
WERKINGSINSTRUCTIE
Modbus register resetprocedure
Om de Modbus-registers naar hun fabrieksinstelling te resetten, plaatst een
jumper op pinnen 1 en 2 gedurende ten minste 20 s. Hold-registers 1-3 zijn
teruggezet naar hun fabrieksinstelling.
Alle Modbus-registers worden gereset via het schrijven van "1" in Modbus-
holdregister 19 (zie de Modbus-registermappen hieronder).
6 - Modbus holding register reset Jumper (P5)
1
2
3
4
5
(geeft de positie van de jumper aan.)
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 9 - 12
terug naar inhoudstafel
MODBUS REGISTER MAPPEN
INPUT REGISTERS - DADCM/08
Data type Description Data Values
1 Analog / modulating sensor type (Ai1) unsigned int. Analog / modulating sensor type (Ai1) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
2Analog / modulating input level (Ai1) signed int. Analog / modulating input level (Ai1) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
3PWM frequency (Ai1) unsigned int. PWM frequency (Ai1) if Ai1 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
4 Analog / modulating sensor type (Ai2) unsigned int. Analog / modulating sensor type (Ai2) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
5Analog / modulating input level (Ai2) signed int. Analog / modulating input level (Ai2) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
6PWM frequency (Ai2) unsigned int. PWM frequency (Ai2) if Ai2 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
7 Analog / modulating sensor type (Ai2) unsigned int. Analog / modulating sensor type (Ai2) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
8Analog / modulating input level (Ai3) signed int. Analog / modulating input level (Ai3) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
9PWM frequency (Ai3) unsigned int. PWM frequency (Ai3) if Ai3 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
10 Analog / modulating sensor type (Ai4) unsigned int. Analog / modulating sensor type (Ai4) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
11 Analog / modulating input level (Ai4) signed int. Analog / modulating input level (Ai4) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
12 PWM frequency (Ai4) unsigned int. PWM frequency (Ai4) if Ai4 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
13 Analog sensor type (Ai5) unsigned int. Analog sensor type (Ai5) 0—2 0 =
1 =
2 =
Not in use
Voltage
Current
14 Analog input level (Ai5) signed int. Analog input level (Ai5) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
15 Reserved, returns “0.
16 Analog sensor type (Ai6) unsigned int. Analog sensor type (Ai6) 0—2 0 =
1 =
2 =
Not in use
Voltage
Current
17 Analog input level (Ai6) signed int. Analog input level (Ai6) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
18 Reserved, returns “0.
19 Analog sensor type (Ai7) unsigned int. Analog sensor type (Ai7) 0—2 0 =
1 =
2 =
Not in use
Voltage
Current
20 Analog input level (Ai7) signed int. Analog input level (Ai7) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
21 Reserved, returns “0.
22 Analog sensor type (Ai8) unsigned int. Analog sensor type (Ai8) 0—2 0 =
1 =
2 =
Not in use
Voltage
Current
23 Analog input level (Ai8) signed int. Analog input level (Ai8) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
24-30 Reserved, return “0”.
Nota: De ingangsregisters kunnen worden gelezen via de Modbus-commando: “Read input registers” (Ingangsregisters lezen).
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 10 - 12
terug naar inhoudstafel
INPUT REGISTERS - DADCM/44
Data type Description Data Values
1Analog / modulating sensor type
(Ai1) unsigned int. Analog / modulating sensor type (Ai1) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
2Analog / modulating input level (Ai1) signed int. Analog / modulating input level (Ai1) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
3PWM frequency (Ai1) unsigned int. PWM frequency (Ai1) if Ai1 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
4Analog / modulating sensor type
(Ai2) unsigned int. Analog / modulating sensor type (Ai2) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
5Analog / modulating input level (Ai2) signed int. Analog / modulating input level (Ai2) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
6PWM frequency (Ai2) unsigned int. PWM frequency (Ai2) if Ai2 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
7Analog / modulating sensor type
(Ai2) unsigned int. Analog / modulating sensor type (Ai2) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
8Analog / modulating input level (Ai3) signed int. Analog / modulating input level (Ai3) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
9PWM frequency (Ai3) unsigned int. PWM frequency (Ai3) if Ai3 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
10 Analog / modulating sensor type
(Ai4) unsigned int. Analog / modulating sensor type (Ai4) 0—3
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
11 Analog / modulating input level (Ai4) signed int. Analog / modulating input level (Ai4) 0—1.000 100 =
300 = 1,0 VDC =
3,0 VDC = 2 mA =
6 mA = 10%
30%
12 PWM frequency (Ai4) unsigned int. PWM frequency (Ai4) if Ai4 type is PWM 1.000—5.000 1.000 =
2.000 = 1.000 Hz
2.000 Hz
13-20 Reserved, return “0”.
21 Temperature sensor type (Ti1) unsigned int. Current sensor type connected to Ti1 0—3
0 =
1 =
2 =
3 =
PT500
PT100
Disconnected
Shorted
22 Temperature level (Ti1) signed int. Temperature level (Ti1) 0x8000
-1.000
-300—700
0x8000 =
-1.000 =
500 =
Not connected
Shorted
50,0 º C
23 Temperature sensor type (Ti2) unsigned int. Current sensor type connected to Ti2 0—3
0 =
1 =
2 =
3 =
PT500
PT100
Disconnected
Shorted
24 Temperature level (Ti2) signed int. Temperature level (Ti2) 0x8000
-1.000
-300—700
0x8000 =
-1.000 =
500 =
Not connected
Shorted
50,0 º C
25 Temperature sensor type (Ti3) unsigned int. Current sensor type connected to Ti3 0—3
0 =
1 =
2 =
3 =
PT500
PT100
Disconnected
Shorted
26 Temperature level (Ti3) signed int. Temperature level (Ti3) 0x8000
-1.000
-300—700
0x8000 =
-1.000 =
500 =
Not connected
Shorted
50,0 º C
27 Temperature sensor type (Ti4) unsigned int. Current sensor type connected to Ti4 0—3
0 =
1 =
2 =
3 =
PT500
PT100
Disconnected
Shorted
28 Temperature level (Ti4) signed int. Temperature level (Ti4) 0x8000;
-1.000;
-300—700
0x8000 =
-1.000 =
500 =
Not connected
Shorted
50,0 º C
29-30 Reserved, return “0”.
Nota: De ingangsregisters kunnen worden gelezen via de Modbus-commando: “Read input registers” (Ingangsregisters lezen).
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 11 - 12
terug naar inhoudstafel
HOLDING REGISTERS - DADCM/08 and DADCM/44
Data type Description Data Default Values
1Address unsigned
int. Device slave address 1—247 1
2 Modbus baud rate unsigned
int. Modbus communication baud rate 0—6 2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
4.800
9.600
19.200
38.400
57.600
115. 200
230.400
3Modbus parity mode unsigned
int. Parity check mode 0—2 10 =
1 =
2 =
None
Even
Odd
4Device type unsigned
int. Device type (Read only) DADCM/44 =
DADCM/08 = 2.402
2.401
5HW version unsigned
int. Hardware version of the device (Read only) XXX 0x0100 = HW version 1.00
6FW version unsigned
int. Firmware version of the device (Read only) XXX 0x0100 = FW version 1.00
7-10 Reserved, return 0
11 Analog / modulating input
(Ai1) unsigned int Disable or select analog / modulating
input type for Ai1 0—3 1
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
12 Analog / modulating input
(Ai2) unsigned int Disable or select analog / modulating
input type for Ai2 0—3 1
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
13 Analog / modulating input
(Ai3) unsigned int Disable or select analog / modulating
input type for Ai3 0—3 1
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
14 Analog / modulating input
(Ai4) unsigned int Disable or select analog / modulating
input type for Ai4 0—3 1
0 =
1 =
2 =
3 =
Not in use
Voltage
Current
PWM
15-18 Reserved, return 0
19 Modbus registers reset unsigned int Resets the Modbus registers to
their default value. e register is
automatically reset to “0 0—1 00 =
1 = Idle
Reset Modbus registers
20 Modbus network resistor
terminator (NBT) unsigned int When connected sets the device as as end
device on th eline 0—1 00 =
1 = NBT disconnected
NBT connected
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
INPUT REGISTERS (zie Tabellen Input registers hierboven)
De input registers zijn enkel uitleesbare. Alle data kan uitgelezen worden door
het ‘Read Inputs Registers’ commando te gebruiken. Als een register niet wordt
gebruikt dan staat deze gedefinieerd als “reserved” en duid deze “0” wanneer die
wordt uitgelezen.
HOLDING REGISTERS (zie Tabel Holding registers hierboven)
Deze registers zijn schrijf / lees registers en deze kunnen gemanaged worden via
“Read Holding Registers”, “Write single register” en “Write Multiple Registers”
commandos. De registers die niet gebruikt worden zijn enkel uitleesbare en, daarom,
geeft het schrijven in deze noch een error weer, noch worden de waardes in deze
registers gewijzigd.
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
www.sentera.eu
MIW-DADCM-NL-000 - 19 / 12 / 18 12 - 12
terug naar inhoudstafel
TRANSPORT EN BEWAAR INFORMATIE
Vermijd schokken en extreme condities; bewaar in originele verpakking.
GARANTIE INFORMATIE EN BEPERKINGEN
Twee jaar vanaf de leveringsdatum op fabricage fouten. Elke aanpassing of verandering
van het product ontheft de fabrikant van alle mogelijke verantwoordelijkheid. De
fabrikant wijst alle verantwoordelijkheid af voor alle drukfouten of vergissingen
in deze data en aanpassingen of modificaties die zijn aangebracht na de tijd van
publicatie.
ONDERHOUD
Onder normale condities is dit een onderhoudsvrij product. Bij vervuiling, reinig met
een droge of licht vochtige doek. In geval van sterke verontreiniging, reinig met een
niet agressief product. Onder deze omstandigheid koppel het toestel los van de
voeding. Let erop dat geen vloeistoffen het toestel kunnen binnentreden. Enkel
terug aansluiten als het toestel volledig droog is.
ANALOOG NAAR DIGITAAL OMVORMER
VOOR DIN-RAIL MONTAGE
DADCM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Sentera Controls DADCM-44 Mounting Instruction

Type
Mounting Instruction