Sentera Controls MVS-1-30CDM Mounting Instruction

Type
Mounting Instruction
Montage & gebruiksvoorschriften
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR,
DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 217
Inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN 3
PRODUCTBESCHRIJVING 4
ARTIKELCODE 4
GEBRUIKSTOEPASSING 4
TECHNISCHE GEGEVENS 4
NORMEN 5
BEKABELING EN AANSLUITING 5
OPERATIONELE DIAGRAMMEN 6
MONTAGE VOORSCHRIFTEN IN STAPPEN 8
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE 10
WERKINGSINSTRUCTIE 11
MODBUS REGISTER MAPPEN 12
TRANSPORT EN BEWAAR INFORMATIE 17
GARANTIE INFORMATIE EN BEPERKINGEN 17
ONDERHOUD 17
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 317
terug naar inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN
Voor u aan het werk gaat met ons product, lees aandachtig de technische fiche,
installatie instructie en het aansluit schema. Om uw persoonlijke veiligheid en die
van het toestel te garanderen, evenals de optimale prestaties van het product, zorg
ervoor dat u de volledige technische inhoud begrijpt voordat u het toestel installeert,
in gebruik neemt, of onderhoud doet.
Omwille van de veiligheid en vergunningverlening (CE) is het eigenhandig ombouwen
en/of veranderen van het product niet toegestaan.
Het product mag niet worden blootgesteld aan abnormale omstandigheden zoals:
extreme temperaturen, direct zonlicht of trillingen. Chemische dampen met een hoge
concentratie in combinatie met een lange blootstellingstijd kunnen de prestaties
van het product beïnvloeden. Zorg ervoor dat de werkomgeving zo droog mogelijk
is; controleer daarom ook op condensatie plekken.
Alle installaties moeten voldoen aan de lokale gezondheids- en
veiligheidsvoorschriften evenals de plaatselijke elektrische normen. Dit product
kan enkel worden geïnstalleerd door een ingenieur of technicus die een deskundige
kennis heeft van het product en de veiligheidsvoorschriften.
Vermijd contact met onder spanning staande onderdelen; behandel daarom steeds
het product alsof het onder spanning staat. Schakel steeds de stroombron uit
voordat u de voedingskabels aansluit, onderhoud of reparatie werken uitvoert op
het toestel.
Controleer altijd of u de juiste stroomvoorziening toepast op het product en gebruik
kabels met de juiste diameter en kenmerken. Zorg ervoor dat alle bouten, moeren en
schroeven goed zijn aangedraaid en de zekeringen (indien aanwezig) goed geplaatst
zijn.
Het recycleren van de toestellen of verpakking zou men in overweging moeten nemen,
het weggooien van deze moet volgens nationale wetgeving / regels gebeuren.
Indien u nog vragen heeft, contacteer dan uw technische dienst of een andere
deskundige.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 417
terug naar inhoudstafel
PRODUCTBESCHRIJVING
De MVS elektronische snelheidsregelaar automatisch de snelheid van monofasige
spanningsregelbare elektromotoren (230 VAC / 50—60 Hz) volgens een standaard
ingang stuursignaal.
ARTIKELCODE
Code Nominale stroom, [A] Zekering
Zekering 1 Zekering 2
MVS-1-15X 1,5
F 0,315 A H 250 V
(5*20 mm)
F 3,15 A H 250 V
(5*20 mm)
MVS-1-30X 3,0 F 5,0 A H 250 V
(5*20 mm)
MVS-1-60X 6,0 F 10,0 A H 250 V
(5*20 mm)
MVS-1100X 10,0 F 16,0 A H 250 V
(6,3*32 mm)
GEBRUIKSTOEPASSING
Ventilator snelheidsregelaar voor ventilatie systemen
Toepassingen waar modbus communicatie of een timerfunctie gewenst is
Uitsluitend voor binnen gebruik
TECHNISCHE GEGEVENS
Voedingsspanning: 230 VAC ±10 %/5060 Hz
Analoge uitgang:
Spanning: 010 VDC
Stroom: 020 mA
Analoge ingang modus: stijgend of dalend
Analoge ingang functionaliteit: Normale modus / logic modus
Extern bedieningsingang: normaal of timer functie
Geregelde uitgang: 30—100 % Us
Max. belasting is afhankelijk van de versie (zie de tabel hierboven)
Niet geregelde uitgang, L1: 230 VAC / 50—60 Hz/max. 2 A
Min. uitgangsspannig instelling, Umin: 30—70 % Us (69—161 VAC), in te stellen via
trimmer of Modbus
Max. uitgangsspannig instelling, Umax: 75—100%Us (173—230 VAC), in te stellen
via trimmer of Modbus
Instelbaar via trimmer of via Modbus:
0—4 VDC / 08 mA in stijgende modus
106 VDC / 2012 mA in dalende modus
Kick start of soft start
Lage spanningsuitgang (+12 VDC / 1 mA) voor externe potentiometer
Modbus RTU communicatie
Bedrijfsindicatie:
continu groen: normale werking
knippert groen: stand-by
Overspanning en overstroom bescherming
Behuizing
DIN-rail-interface module: polyamide - PA UL94V0; groene kleur (RAL 6017)
DIN-rail-interface module afdekking: plexiglas, doorzichtig
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 517
terug naar inhoudstafel
Beschermingsgraad: IP20 (volgens de EN 60529)
Werkingscondities:
temperatuur: -20—40 °C
relatieve vochtigheid: < 80 % rH (niet-condenserend)
Opslagtemperatuur: -40—50 °C
NORMEN
Laagspanning richtlijn 2014/35/EC:
EMC richtlijnen 2014/30/EC
WEEE richtlijn 2012/19/EU
RoHs richtlijn 2011/65/EU
BEKABELING EN AANSLUITING
L Voedingsspanning 230 VAC ±10 % / 5060 Hz
NNulgeleider
PE Aarding
L1 Niet geregelde uitgang (230 VAC / max. 2 A)
U1, U2 Geregelde uitgang naar de motor
SW Extern / timer schakelaar
+V Voedingsuitgang + 12 VDC/1 mA
Ai
Analoge uitgang:
(010 VDC/020 mA) of (100 VDC/200 mA)
Logische ingang (timer functie):
(min 2,5 VDC en > 30 ms )
GND Aarding
A Modbus RTU (RS485), signaal A
/B Modbus RTU (RS485), signaal /B
Aansluiting Kabel diameter: max. 2,5 mm2
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 617
terug naar inhoudstafel
OPERATIONELE DIAGRAMMEN
Normaal / externe operationele modi
Stijgende ingang modus Dalende ingang modus
OFF Level uitgeschakeld
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai ,
[VDC]/[mA]
100
75
70
30
Umax
bereik
Umin
bereik
U
out
,
[%]
10 VDC
20 mA
Umax
Umin
0
Ai ,
[VDC]/[mA]
100
75
70
30
Umax
bereik
Umin
bereik
Oplopend mode
berekeningsformule
Uout=Umin+ Aimax
Ai
(Umax-Umin)
Aflopende modus
berekeningsformule
Uout=Umax- Aimax
Ai
(Umax-Umin)
Umax
Umin
0
,Ai
[VDC]
/
[mA]
4 VDC
8 mA
U,
[%]out
100
75
70
30
10 VDC
20 mA
Umax
bereik
Umin
bereik
OFF level
bereik
Umax
Umin
0
,Ai
[VDC] /
[mA]
10 VDC
20 mA
6 VDC
12 mA
U, [%]out
100
75
70
30
Umax
bereik
Umin
bereik
OFF level
OFF Level uitgeschakeld,
Oplopend mode
berekeningsformule
Uout=Umax+ Aimax-Off level
Ai-Off level (Umax-Umin)
Aflopende modus
berekeningsformule
Uout=Umax- Aimax-Off level
Ai-Off level (Umax-Umin)
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
A
Umax
bereik
Umin
bereik
Kick start tijd
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
bereik
Umin
bereik
Kick start tijd
Kick start is geactiveerd
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
bereik
Umin
bereik
Soft start tijd
OFF level
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
bereik
Umin
bereik
Soft start tijd
OFF level
Soft start is geactiveerd
OFF level
OFF level
bereik
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 717
terug naar inhoudstafel
Stijgende ingang modus Dalende ingang modus
Soft start & OFF level
t [s]
Umax
Umin
0
Uout, [%]
100
75
70
30
10 VDC /
20 mA
Ai,
[VDC]/
[mA]
Umax
bereik
U min
bereik
Soft start tijd
OFF level
t [s]
Umax
Umin
Uout, [%]
100
75
70
30
10 VDC /
20 mA
0 VDC /
0 mA
Ai,
[VDC]/
[mA]
Umax
bereik
Umin
bereik
Soft start tijd
OFF level
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 mA
Uout, [%]
100
75
70
30
0 VDC / 0 m
A
Umax
bereik
Umin
bereik
Kick start tijd
t, [s]
Umax
Umin
0
Ai,10 VDC / 20 m
Uout, [%]
100
75
70
30
0 VDC / 0 mA
Umax
bereik
Umin
bereik
Kick start tijd
Kick start & OFF level
Timer mode Logic mode
0
t, [s]
5 VDC
2,5 VDC
Externe
Schakelaar,
[VDC]
Stand-by Werking
Spanning
amplitude
bereik
Schakelaar controle-signaal
t [s]
0
U
out, [%]
100
75
Umax
bereik
Kick start Tijd Operation timer Controller is UIT
Kick start is geactiveerd
Soft start is geactiveerd
t
t
t
t
SW
ONAAN
Holding
Register
18
Holding
Register
21
Soft Start
duur
Soft Start
duur
Start
Uitgang
Umax
Timer
Soft
start
Stop
Start
Stop
Werking
timer
Werkingstijd
Holding
Register
18
OFF REL UIT
Schakelaar controle-signaal
t
t
t
t
Ai >2,4 VDC
REL AAN REL AAN
Holding
Register
18
Holding
Register
21
Holding
Register
21
Soft Start
duur Soft Start
duur
Start
Uitgang
Umax
Timer
Soft
start
Start Stop
Werking
timer Werking
timer
Holding
Register
18
REL UIT REL UIT
Ai controle-signaal
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 817
terug naar inhoudstafel
MONTAGE VOORSCHRIFTEN IN STAPPEN
Voordat u start aan de installatie van de MVS controller, lees dan zorgvuldig de
Veiligheid en voorzorgsmaatregelen”. Ga vervolgens te werk met volgende
installatie stappen:
1. Schakel de voedingsspanning uit.
2. Verwijder de transparante cover van de DIN-behuizing
3. Verwijder de schroeven aan de zijwanden van de DIN-rail module Schuif de
module langs de geleiders van een standaard 107 mm DIN-rail. Bevestig het
gewenste toestel op de rail door de zijwanden te monteren van de behuizing.
Let op de juiste positie en inbouwmaten in Fig. 1 Bevestiging afmetingen en Fig.
2 Montage positie.
Fig. 1 Bevestiging afmetingen
MVS-1-60CDM
MVS-1100CDM
MVS-1-15CDM
MVS-1-30CDM
H
L
W
Artikel Hoogte [mm] Lengte [mm] Breedte [mm]
MVS-1-15CDM,
MVS-1-30CDM 96 127
112
MVS-1-60CDM,
MVS-1100CDM 128
Fig. 2 Montage positie
DIN rail
4. Sluit de motor / ventilator aan.
5. Sluit L1 uitgang aan voor een 3-draads verbinding, klep sturing, enz … (als
nodig). Zie Fig. 3b 3-draads motor connectie.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 917
terug naar inhoudstafel
Fig.3 Aansluitschema
Extern
schakelaar
Voedingsspanning
230 VAC,
50 / 60 Hz
Modbus RTU A
/B
Analoge ingang
010 VDC / 0–20 mA
Voedingsuitgang
+12 VDC / 1 mA
L
N
PE
Geregelde uitgang
uitgang
230 VAC / max. 2 A
M
1
3a. 2-draads motor connectie
Voedingsspanning
230 VAC,
50 / 60 Hz
Extern
schakelaar
Modbus RTU A
/B
Analoge ingang
010 VDC / 0–20 mA
Voedingsuitgang
+12 VDC / 1 mA
L
N
PE M
1
3b. 3-draads motor connectie
6. Selecteer de benodigde analoge ingangstype en modus, start modus en OFF
level modus via de DIP schakelaar op de PCB. (Zie Fig. 4 Dip schakelaar instelling).
Fig. 4 DIP-schakelaar instelling
Ingang modus selectie
(DIP-schakelaar, positie 1)
ON
1 2 3 4
Aan- dalende modus:
10—0 VDC/20—0 mA
OFF – stijgende modus:
0—10 VDC/0—20 mA
OFF level selectie
(DIP-schakelaar, positie 2)
ON
1 2 3 4
ON - ingeschakeld
UIT - uitgeschakeld
Kick start / soft start selectie
(DIP-schakelaar, positie 3)
ON
1 2 3 4
ON – Kick start
UIT – Soft start
Ingang modus selectie
(DIP-schakelaar, positie 4)
ON
1 2 3 4
ON – Stroom modus
(0—20 mA)
OFF - Ingang
spanningsmodus
(0—10 V DC )
7. Controleer of uw toestel een netwerk start of afsluit ( zie Voorbeeld 1 en
Voorbeeld 2). Als dit het geval is, plaatst u de NBT jumper op de pins. Als dit niet
het geval is, laat u de jumper weg (zie Fig. 5).
Voorbeeld 1 Voorbeeld 2 Fig. 5 Netwerk bus weerstand
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
ATTENTIE Als u een AC voeding gebruikt voor deze of andere toestellen in een Modbus
netwerk dan zal de GND connector NIET AANGESLOTEN worden op andere
toestellen binnen dit netwerk of via de CNVT-USB-RS485 omvormer. Dit zal
als gevolg permanente schade aan de communicatie semiconductors en / of
computer toebrengen!
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1017
terug naar inhoudstafel
8. Sluit de voedingspanning en aarding kabels aan.
9. Stel de minimale snelheid in door de kleine trimmer. De standaard instelling is Us
(230 VAC). Zie Fig. 6 Min. snelheid trimmer.
10. Pas de min. snelheid via de trimmer aan (als nodig). Pas de min. snelheid via de
trimmer aan (als nodig). Zie Fig. 7 Min. snelheid trimmer.
11. Pas de OFF level waarde aan via de trimmer (als nodig). De standaard waarde is
0 VAC. Zie Fig. 8 OFF level trimmer.
Fig. 6 Max. snelheid trimmer Fig. 7 Min. snelheid trimmer Fig. 8 OFF level trimmer
12. Sluit de behuizing en monteer het transparante deksel.
13. Schakel de voedingsspanning aan.
14. Pas de fabrieksinstellingen volgens uw gewenste waardes aan, via onze
3SModbus software (als dit nodig is). Om de default fabrieksinstelling te
raadplegen zie Table Modbus register mappen.
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE
Volg de instructies hieronder:
1. Schakel de voedingspanning in.
2. Zet de NBT jumper, DIP schakelaar, Max. trimmer, Min. trimmer en OFF level
trimmer in de gewenste positie / waardes. De fabrieksinstellingen zijn als
volgens:
NBT jumper is open (Netwerk bus eindweerstand is ontkoppeld);
Stijgende modus: 010 VDC / 0–20 mA
OFF level – OFF;
Kick start gedeactiveerd;
Ingang spanningsmodus (0—10 VDC);
Min. instelling van de Min. snelheid trimmer
Max. instelling van de Max. snelheid trimmer;
Min. instelling van de OFF level trimmer.
3. Stel het analoge ingangssignaal in op de maximale waarde 10 VDC of 20 mA.
4. De aangesloten motor zal aan maximale of minimum snelheid lopen afhankelijk
van de analoge ingangsmodi (dalend/ stijgend).
5. Als de OFF level aan staat in de dalende analoge ingangsmodi, zal de motor
stoppen.
6. Stel het analoge ingangssignaal in op de maximum waarde van 0 VDC of 0 mA.
7. De aangesloten motor zal aan minimale of maximum snelheid lopen afhankelijk
van de analoge ingangsmodi (dalend / stijgend).
8. Als de OFF level aan staat in de stijgende analoge ingangsmodi, zal de motor
stoppen.
9. Als de OFF Level aanstaat en het ingangssignaal is gelijk aan de waarde van de
OFF level, zal de snelheid van de motor gelijk zijn aan de minimum snelheid in
stijgende en maximum snelheid in dalende modus.
10. Als de controller niet volgens deze instructies zoals hierboven werkt, moet men
de bedrading als de instelling van het toestel nazien.
11. Controleer als beide LEDs (Fig. 9) kniperen als u het toetsel aan zet. Bij
knipperen, heeft uw toestel een Modbus netwerk gedetecteerd. Als deze niet
knipperen, controleer dan opnieuw de aansluitingen.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1117
terug naar inhoudstafel
Fig. 9 Communicatie detectie indicatie
ATTENTIE De status van de LEDs kan enkel gecontroleerd worden als het toestel aan staat.
Neem de nodige veiligheidsmaatregelen!
WERKINGSINSTRUCTIE
BEDIENMODES
In Modbus modus heeft u invloed op volgende parameters: Umax, Umin, Kick start /
Soft start, OFF level Aan / Uit, timer functie en de OFF level waarde via de Modbus
registers.
In Standalone Modus heeft u invloed op volgende parameters: Umax, Umin, Kick
start / Soft start, OFF level Aan / Uit en de OFF level waarde die via de hardware
instelingen (DIP schakelaar, trimmers, jumpers).
In Normale modus tijdens dat de OFF level uit staat, zal de soft start / Kick start
maar een keer uitgevoerd worden – na dat de controller gestart wordt; de soft start /
kick start wordt enkel uitgevoerd elke keer het toestel gestart wordt.
Wanneer Timer modus geselecteerd is, dan zal de controller zijn controle signaal van
de schakelaar ontvangen. Wanneer de logische modus is geselecteerd, ontvangt de
controller een signaal van ingang Ai.
Tijdens de Timer modus als logic modus moet de ingang puls langer zijn dan 30 ms;
anders zal het signaal weg gefilterd worden.
BEDRIJFSINDICATIE
Wanneer de groene LED (Fig. 10) continu blijft branden, dan is de controller in
werking. Als deze knippert:
Dan is de controller in standby extern control modus, of
De OFF level staat aan en het analoge ingang signaal is onder de OFF level waarde.
Fig. 10 Bedrijfsindicatie
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1217
terug naar inhoudstafel
MODBUS REGISTER MAPPEN
INPUT REGISTERS
Data type Description Data Values
1Analogue input level unsigned int. Analogue input value depending on the selected
analogue input type. 0—100
0 =
100 =
0 =
100 =
0 VDC
10,0 VDC
or
0 mA
20,0 mA
2Current output voltage unsigned int. Actual output voltage 0,
30—100
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
3Analogue input type unsigned int. Type of the selected analogue input 0—1 0 =
1 =
0—20 mA
0—10 VDC
4Ascending/descending
input mode unsigned int. Ascending or descending analogue input mode
depending on the selected analogue input type. 0—1
0 =
1 =
0 =
1 =
100 VDC
0—10 VDC
or
200 mA
0—20 mA
5Maximum output
voltage unsigned int. Maximum output voltage 75—100 75 =
100 =
75 % Us
100 % Us
6Minimum output voltage unsigned int. Minimum output voltage 30 —70 30 =
70 =
30 % Us
70 % Us
7 Enable Off level unsigned int. Enables Off level 0—1 0 =
1 =
Disabled
Enabled
8Off level value unsigned int.
Off level value depending on the selected analogue
input type and ascending / descending analogue input
mode.
0 — 40
60—100
Ascending mode:
0 =
400 =
0 =
200 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
9 Kick start/soft start unsigned int. Selects kick start or soft start 0—1 0 =
1 =
Soft start
Kick start
10 Remote control input unsigned int. Remote control input 0—1 0 =
1 =
Disabled
Enabled
12 L1 control unsigned int. L1 contr ol 0—1 0 =
1 =
Off
On
14 ON/Stand-by LED unsigned int. ON/Stand-by LED 0—2
0 =
1 =
2 =
Off
On
Stand-by
15-20 Reserved, returns 0
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1317
terug naar inhoudstafel
HOLDING REGISTERS
Data type Description Data Default Values
1Device slave
address unsigned int. Modbus device address 1—247 1
2Modbus baud
rate unsigned int. Modbus communication baud rate 1—4 2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.60 0
3Modbus parity unsigned int. Parity check mode 0—2 1
0 =
1 =
2 =
8N1
8E1
8O1
4Device type unsigned int. Device type (Read only) MVSX-DM = 3009
5HW version unsigned int. Hardware version of the device (Read only) XXXX 0 x 0300
=
HW version
3.00
6FW version unsigned int. Firmware version of the device (Read only) XXXX 0 x 0140
=
FW version
1.40
7Operating mode unsigned int. Enables Modbus control and disables the DIP switch
and trimmers 0—1 00 =
1 =
Standalone
mode
Modbus mode
8Output override unsigned int. Enables the direct control over the output. Always
settable. Active only if holding register 7 is set to 1. 0—1 00 =
1 =
Disabled
Enabled
9-10 Reserved, returns 0
11 Analogue input
type unsigned int. Selects the analogue input type of the device. Always
settable. Active only if holding register 7 is set to 1. 0—1 10 =
1 =
0—20 mA
0—10 VDC
12
Ascending/
descending
analogue input
mode
unsigned int.
Ascending/descending analogue input mode. Depends
on the selected analogue input type. Always settable.
Active only if holding register 7 is set to 1.
0—1 1
0 =
1 =
0 =
1 =
100 VDC
010 VDC
or
200 mA
0—20 mA
13 Maximum
output voltage unsigned int. Maximum settable output voltage. Always settable.
Active only if holding register 7 is set to 1. 75—100 100 75 =
100 =
75 % Us
100 % Us
14 Minimum output
voltage unsigned int. Minimum settable output voltage. Always settable.
Active only if holding register 7 is set to 1. 30 —70 30 30 =
70 =
30 % Us
70 % Us
15 Enable Off level unsigned int. Enables Off level. Always settable. Active only if
holding register 7 is set to 1. 0—1 00 =
1 =
Disabled
Enabled
16 Off level value unsigned int.
Off level value. Depends on the selected analogue input
type and ascending/descending analogue input mode.
Always settable. Active only if holding register 7 is set
to 1.
0—40
60—100 0
Ascending mode:
0 =
40 =
0 =
40 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 mA
17 Kick start/soft
start unsigned int. Selects kick start or soft start. Always settable. Active
only if holding register 7 is set to 1. 0—1 10 =
1 =
Soft start
Kick start
18 Kick start/soft
start duration unsigned int. Sets the duration time. Always settable. Active only if
holding register 7 is set to 1. 060 10 0 =
60 =
0 s
60 s
19 Remote control
functionality unsigned int.
Sets the remote control input mode. Depends on the
selected kick start or soft start mode. Always settable.
Active only if holding register 7 is set to 1.
0—1 00 =
1 =
Normal mode
Timer mode
20 Analogue input
functionality unsigned int.
Sets the analogue input functionality. Depends on
the selected kick start or soft start. Always settable.
Active only if holding register 7 is set to 1.
0—1 00 =
1 =
Normal mode
Logic mode
21 Operation timer unsigned int.
Sets the operation time of the device when Timer mode
by remote control input or Logic mode by the analogue
input is selected. e operation time is additional to the
kick start/soft start duration times. Always settable.
Active only if holding registers 7 and 19 or / and 20
are set to 1.
0—200 60 0 =
200 =
0 s
200 s
22-30 Reserved, returns 0
31 Output override
value unsigned int. Override value for the analogue output. Always
settable. Active only if holding register 8 is set to 1.
0,
30—100 0
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
32-40 Reserved, returns 0
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1417
terug naar inhoudstafel
INPUT REGISTERS (zie Table 1 Modbus register mappen)
De input registers zijn ‘read only. Table 1 is een weergave van hoe de data
georganiseerd is in de input register sector. De gemeten data start bij adres
'1' en stop aan adres '14'. De andere input registers worden niet gebruikt. Als ze
geadresseerd zijn zullen ze een 0 waarde weergeven.
Alle data kan uitgelezen worden door het ‘Read Inputs Registers’ commando
te gebruiken. Table 1 duidt aan welke Type data er wordt weergegeven voor elk
register en de manier waarop deze geïnterpreteerd moet worden. Als voorbeeld
'300' in input register 1 betekend dat de gemeten analoge ingangswaarde 3,0 VDC is
(of 6,0 mA), uitleeswaarde '50' in input register 2 betekend dat de uitgangsspanning
50 % van de Us (115 VAC).
Input register 1 toont de actuele waarde van de gemeten analoge ingang.
Deze waarde hangt af van de geselecteerde analoge ingangstype. Wanneer
spanningsingang geselecteerd is, zal deze waardes variëren tussen 01.000
(0—10,0 VDC). Wanneer de stroomingang geselecteerd is, zal deze waardes
variëren tussen 01.000 (0—20,0 mA).
Input register 2 toont de actuele waarde van de uitgangsspanning. Dit input
register wordt overschreven door holding register 31 als uitgang override controle
(holding register 8) aan staat. Wanner deze override controle uit staat, dit input
register toont de waarde van de uitgangsspanning volgens de geselecteerde
werkingsmodus. De uitgangsspanning waarde varieert tussen volgende 30—100 %
Us (69230 VAC) Uitlees '0' (0 VAC) toont aan dat de controller uit staat.
Input register 3 duidt op het type analoge ingangssignaal. Dit Input register wordt
in holding register 11 gedefinieerd of via de hardware setting van positie 4 op de
DIP switch. De waarde zijn '0' (voor 0—20 mA) of '1' (voor 010 VDC).
Input register 4 toont de geselecteerde modus van het analoge ingangssignaal. Dit
input register wordt gedefinieerd in holding register 12 of via de hardware setting
van positie 1 op de DIP switch (Fig. 4) volgens de geselecteerde werkingsmodus
de waarde zijn '0' (voor dalende modus) of '1' (voor stijgende modus).
Input register 5 toont de waarde van de Maximum uitgangsspanning.
Dit input register wordt gedefinieerd in holding register 13 of via de
hardware setting van de Max. trimmer (Fig. 6) volgens de geselecteerde
werkingsmodus Deze register waardes zijn binnen volgend 75—100
(75100 % Us VAC).
Input register 6 toont de waarde van de Minimum uitgangsspanning. Dit input
register wordt gedefinieerd in holding register 14 of via de hardware setting van
de Min. trimmer (Fig. 7) volgens de geselecteerde werkingsmodus. Deze register
waardes zijn binnen volgend 30—70 % Us.
Input Register 7 geeft informatie over de OFF level waarde. In standalone modus
duidt deze de waarde zoals ingesteld op positie 2 van de Dip switch (Fig. 4). In
Modbus modus bedraagt deze de waarde van het holding register 15. Het kan '0'
(uit) of '1' (aan) aangeven.
Input Register 8 geeft informatie over de OFF level waarde. In standalone modus
bedraagt deze de waarde zoals met de OFF level trimmer is ingesteld (Fig. 8). In
Modbus modus bedraagt deze de waarde van het holding register 16. Deze waarde is
afhankelijk van de geselecteerde analoge ingang type en modus. De register waarde
kan tussen volgende variëren 0 tot 40 (04,0 VDC / 0—8,0 mA) en van 60 tot 100
(6,0—10,0 VDC / 12,0—20,0 mA). Deze waarde is afhankelijk van de geselecteerde
analoge ingangstype en modus.
Input Register 9 geeft informatie over de Kick Start of Soft Start selectie. In
standalone modus komt de waarde van de start wijze overeen met de instelling
van positie 3 op de DIP switch. In Modbus modus bedraagt deze de waarde van
het holding register 17. De register waardes zijn '0' (voor soft start) of '1' (voor kick
start).
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1517
terug naar inhoudstafel
Input Register 10 toont de status van de externe ingang. Als de externe controle
ingang aan is, dan staat de controller in stand-by modus. De register waarde is '0'
( voor Uit) of '1' (voor Aan). De register waardes zijn '0' (voor soft start) of '1' (voor
kick start).
Input Register 12 geeft de status van de ongeregelde uitgang L1 weer. Wanneer
het analoge signaal lager is dan de waarde van de OFF Level (bij aan) of wanneer
de externe controle ingang uit is, dan is de uitgangsspanning van de ongeregelde
uitgang L1. In ander geval is deze '1' = ON (230 VAC).
Input Register 14 geeft de werking status van het toestel.
Wanneer het register 0 is OFF, de controller staat uit. De Aan/
stand-by LED aan de voorzijde is uit. Zie Fig. 10 Bedrijfsindicatie.
Wanneer de waarde '1' is, en het analoge ingang signaal is boven het geselecteerde
OFF Level waardes (bij aan), werkt de controller volgens de controlalgoritmes.
De AAN/stand-by LED (Fig. 10) geeft een continu licht . De LED knippert en het
register waarde is 2 (stand-by) wanneer de OFF level aan is en het analoge ingang
signaal lager dan de OFF level waarde is.
HOLDING REGISTERS (zie Table Modbus register maps)
Deze registers zijn ‘read / write’ registers en deze kunnen gemanaged worden via
“Read Holding Registers”, “Write single register” en “Write Multiple Registers
commandos. Ze zijn georganiseerd in delen die een verschillende type van
informatie bevat. De Holding registers die niet worden gebruikt zijn alleen-lezen.
In deze registers schrijven zal geen Modbus fout melding genereren, Dit zal ook
geen wijzigingen aanbrengen.
Part 1:
Deel 1 omvat informatie over de toestellen en Modbus communicatie instellingen.
Holding register 1 bevat het adres waarmee de controller naar het Modbus Master
toestel antwoord. Het standaard adres is ‘1. U kan dit op twee wijze veranderen:
1. Zend commando “Write Single Register” met adres ‘1’ en schrijf de nieuwe
adres waarde.
2. Connecteer enkel uw toestel aan een master controller of PC applicatie en
zend het commando “Write Single Register” naar adres ‘0’ (Modbus broadcast
address) en schrijf een nieuw adres waarde.
De Volgende twee registers (2 en 3) bevatten ook Modbus instellingen.
Veranderingen aan deze registers wijzigt ook de communicatie instellingen. De
standaard Modbus instellingen zijn 19200-E-1 als weergegeven in de Modbus
Protocol Specification.
De volgende drie registers (4, 5 en 6) zijn “Read only. Zij bewaren informatie over
de hardware en firmware versie.
Holding register 7 Hiermee stelt u de werkingsmodus van de controller in. Er
zijn twee opties: Standalone en Modbus Modus. In Standalone modus wordt de
controller volledig bediend door het analoge ingang signaal en de geselecteerde
hardware instelling. In Modbus modus zullen de instellingen via de Modbus Master
controller aangestuurd worden.
Holding register 8 wordt gebruikt als uitgang override controle. De instelling wordt
gebruikt om de uitgangspanningswaarde te overschrijven door een ingestelde
waarde. is value has greater priority then the calculated output voltage of the
integrated control algorithm. Only kick start/soft start can change the output
voltage value.
De volgende vier registers 9 en 10 worden niet gebruikt. De input registers zijn
enkel uitlees.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1617
terug naar inhoudstafel
Part 2:
Holding register 11 stelt het type ingangssignaal in. De standaard waarde is '1'
voor 010 VDC; waarde '0' is 020 mA.
Holding register 12 definieert de stijgende / dalende analoge ingangsmodus. De
standaard waarde is '1' voor 0—10 VDC (stijgend spanning signaal). De register
waardes zijn '0' voor 100 VDC en '1' voor 010 VDC wanneer spanning signaal is
geselecteerd, en “0” voor 200 mA en '1' voor 0—20 mA wanneer stroom signaal
is geselecteerd.
Holding register 13 stelt de maximum uitgangsspanning in. De standaard waarde
is '100' (100 % Us voor 230 VAC). De register waardes variëren in de bereiken van
75—100 (75 —100 Us).
Holding register 14 stelt de minimum uitgangsspanning in. Standaard is deze '30'
(30 % Us). De register waardes varren in de bereiken van 3070 (3070 % Us).
Holding register 15 stelt de OFF level status in. De standaard waarde is '0' (UIT).
'1' is voor aan.
Holding register 16 definieert de minimum control range. De standaard waarde is
'0' (0 VDC). Deze waarde is afhankelijk van de geselecteerde analoge ingang type
en modus. De register waardes variëren in de bereiken van 0—40 (0—4,0 VDC)
voor stijgende spanning signaal en 60—100 (6,0—10,0 VDC) voor dalende spanning
signaal. Als het stroom signaal geselecteerd is, zijn de register waardes in bereiken
van 0—40 (08,0 mA) voor stijgend signaal en 60100 (12,0—20,0 mA) voor
dalend signaal.
Holding register 17stelt de Kick start of soft start tijdsduur in. De standard
waarde is '1' (kick start); waarde ‘0’ is soft start.
Holding register 18 stelt de Kick start of soft start tijdsduur in. Standaard is deze
‘10’ (10 seconden). De register waarde varieert van '0' tot '60' (060 seconden).
Deze instelling is enkel toegankelijk via Modbus Modus.
Holding register 19 selecteert de externe controle ingangsfunctie. De standard
waarde is '0' voor normale modus. Waarde '1' is voor timer modus. Deze instelling
is enkel toegankelijk via Modbus Modus. OFF level modus wordt niet gebruikt in
timer modus.
Holding register 20 selecteert de analoge ingangsfunctie. De standard waarde
is '0' voor de normale werking; '1' is voor logische modus. Deze instelling is enkel
toegankelijk via Modbus Modus.
Holding register 21 stelt de waarde van de timer in. Dit holding register is enkel
toegankelijk in timer modus en / of logisch modus. Standaard is deze '60' (60
seconden). De register waarde kan variëren van 0 tot 200 (0200 seconden).
Deze instelling is enkel toegankelijk via Modbus Modus. De werkingstijd is gelijk
aan de som van de kick start / soft start tijdsduur en de tijdswaarde van de timer.
Wanneer de werkingstijd gedaan is, kan enkel de externe controle ingang of de
analoge ingang het toestel herstarten.
Volgende holding registers 22—30 worden niet gebruikt. De input registers zijn
enkel uitlees.
Holding register 31overschrijft de uitgangsspanningswaarde in Modbus modus
als de uitgang override aan is. De overschrijf waarde houdt geen rekening met
andere instellingen uitgezonder voor kick of soft start selectie. De standaard
waarde is '0' (VAC). De register waarde kan variëren in volgende bereiken 30100
(30—100 % Us). Het kan ook '0' zijn (0 % Us = uit).
Volgende holding registers 32—40 worden niet gebruikt. De input registers zijn
enkel uitlees.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
www.sentera.eu
- MIW-MVS-NL-00210 / 11 / 22 - 1717
terug naar inhoudstafel
TRANSPORT EN BEWAAR INFORMATIE
Vermijd schokken en extreme condities; bewaar in originele verpakking.
GARANTIE INFORMATIE EN BEPERKINGEN
Twee jaar vanaf de leveringsdatum op fabricage fouten. Elke aanpassing of verandering
van het product ontheft de fabrikant van alle mogelijke verantwoordelijkheid. De
fabrikant wijst alle verantwoordelijkheid af voor alle drukfouten of vergissingen
in deze data en aanpassingen of modificaties die zijn aangebracht na de tijd van
publicatie.
ONDERHOUD
Onder normale condities is dit een onderhoudsvrij product. Bij vervuiling, reinig met
een droge of licht vochtige doek. In geval van sterke verontreiniging, reinig met
een niet agressief product. Onder deze omstandigheid koppel het toestel los van
de voeding. Let erop dat geen vloeistoffen het toestel kunnen binnentreden. Enkel
terug aansluiten als het toestel volledig droog is.
MVS ELECTRONISCHE VENTILATOR
SNELHEIDSREGELAAR, DIN-RAIL
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17

Sentera Controls MVS-1-30CDM Mounting Instruction

Type
Mounting Instruction