ENGLISH
The Blue Power IP20 battery chargers will charge and maintain lead-acid batteries and
supply users connected to the battery.
The DC cables are fitted with battery clamps for mobile use. A pair of ring terminals for
10 mm screw/stud is provided, for permanent installation.
State of the art microprocessor controlled charge algorithm
Adaptive 4-stage charge characteristic: bulk absorption float storage
The Blue Power IP20 charger features a microprocessor controlled ‘adaptive’ battery
management system. The ‘adaptive’ feature will automatically optimise the process
relative to the way the battery is being used.
The right amount of charge: variable absorption time
When only shallow discharges occur, the absorption time is kept short in order to
prevent overcharging of the battery. After a deep discharge the absorption time is
automatically increased to make sure that the battery is completely recharged.
Less maintenance and aging when the battery is not in use: the Storage Mode
After the absorption period, the Blue Power IP20 charger will switch to float charge and
thereafter, if the battery has not been subjected to discharge, the Storage Mode kicks
in. In the storage mode float voltage is reduced to 2,2 V/cell (13,2 V for 12 V battery) to
minimise gassing and corrosion of the positive plates. Once a week the voltage is
raised back to the absorption level to ‘equalize’ the battery. This feature prevents
stratification of the electrolyte and sulphation, a major cause of early battery failure.
Installation and instructions for use
1. The battery charger must be installed in a well-ventilated area close to the battery
(but, due to possible corrosive gas not above the battery!)
2. Connect the battery clamps or ring terminals to the battery: the minus cable (black)
to the minus () pole of the battery, the plus cable (red) to the plus (+) pole of the
battery.
3. Plug the AC mains cable into the wall socket. The charge cycle will now start.
LED indication
The green LED will be on when the charger is connected to an AC source.
The yellow LED will blink at a fast rate during bulk charge and at a slower rate during
absorption charge. The yellow LED will be on continuously after completion of the
charge cycle
Safety regulations and measures
1. Install the charger according to the stated instructions.
2. Never use the chargers at a location where there is danger of gas or dust
explosions.
3. Connections and safety features must be executed according to the locally
applicable regulations.
4. In case of wrong polarity connection, the ATO Blade Fuse will blow. Check the
polarity of the cable and check the correct value before replacing the ATO Blade Fuse.
Learn more about batteries and battery charging
To learn more about batteries and charging batteries, please refer to our book ‘Energy
Unlimited’ (available free of charge from Victron Energy and downloadable from
www.victronenergy.com). For more information about adaptive charging please look
under Technical Information on our website.
NEDERLANDS
De Blue Power IP20 laders zijn bedoeld voor het laden en op spanning houden van
loodaccu’s en het voeden van de op de accu aangesloten gebruikers. De laders zijn
voorzien van krokodilbekklemmen voor mobiel gebruik en voor vast opgestelde
installatie zijn 2 kabelogen bijgeleverd.
Geavanceerd microprocessor gestuurd laadsysteem
Adaptieve 4-traps laadkarakteristiek: Bulk-Absorption-Float-Storage
Het microprocessor gestuurde ‘adaptieve’ accu management systeem past het
laadproces automatisch aan het gebruik van de accu.
De juiste hoeveelheid lading: aangepaste absorptietijd
Bij geringe ontlading van de accu wordt de absorptie tijd kort gehouden om overlading
en overmatig gassen te voorkomen. Na een diepe ontlading wordt de absorptietijd
automatisch verlengd om de accu volledig te laden.
Minder onderhoud en veroudering wanneer de accu niet gebruikt wordt: de opslag
functie
De Blue Power IP20 lader schakelt na de absorptie periode eerst over op
druppellading en daarna, wanneer er gedurende langere tijd geen ontlading
plaatsvindt, over op ‘opslag’. De spanning wordt dan verlaagd tot 2,2 V/cel (13,2 V voor
een 12 V accu). De accu zal dan nauwelijks meer gassen en corrosie van de positieve
platen wordt zoveel mogelijk beperkt. Eens per week wordt de spanning verhoogd tot
absorptie niveau om de accu weer bij te laden; dit voorkomt stratificatie van het
elektrolyt en sulfatering van de platen.
Installatie en gebruiksaanwijzingen
1. De acculader dient in een goed geventileerde ruimte in de omgeving (maar in
verband met corrosieve gassen niet boven!) de accu’s geïnstalleerd te worden.
2. Sluit de krokodilbekklemmen of kabelogen aan op de te laden accu: de min kabel
(zwart) op de min () pool van de accu, de plus kabel (rood) op de plus (+) pool van de
accu.
3. Steek de stekker van het AC netsnoer in het stopcontact. De acculader zal nu de
laadcyclus starten.
Indicaties
De groene LED brandt continu zolang het apparaat op de netspanning is aangesloten.
De gele LED knippert snel zolang de maximale laadstroom geleverd wordt (accu
minder dan 80% geladen) en knippert langzaam wanneer de absorptie spanning
bereikt is en de laadstroom af gaat nemen. Wanneer de laadcyclus is voltooid gaat de
lader over op druppellading/opslag, en de gele LED gaat continu branden.
Veiligheidsvoorschriften en - maatregelen
1. Installeer de lader volgens de aangegeven instructies.
2. Gebruik de lader nooit op een locatie met gas of stofontploffingsgevaar.
3. Aansluitingen en beveiligingen moeten in overeenstemming met de plaatselijk
geldende voorschriften worden uitgevoerd.
4. Bij verwisseling van de plus- en min aansluitingen op de accu, zal de ATO
steekzekering smelten. Controleer of alle verbindingen correct zijn aangesloten voordat
er een nieuwe ATO steekzekering met hetzelfde ampèrage wordt geplaatst.
Blue Power Charger IP 20
12/7 12/15
24/8
Input voltage range
90 140Vac
Frequency
45-65 Hz
Charge voltage 'absorption' (V DC)
14,4
28,8
Charge voltage 'float' (V DC)
13,8
27,6
Charge voltage 'storage' (V DC)
13,2
26,4
Charge current (A)
7 / 15
8
Charge characteristic
4-stage adaptive
Minimum battery capacity (Ah)
24 / 55
24
Can be used as power supply
Protection
Battery reverse polarity (ATO Fuse Blade)
Output short circuit Over temperature
DC Fuse - ATO Blade (A)
10 / 20
10
Operating temp. range
-20 to +60°C (full rated output up to 40°C)
Humidity (non condensing)
Max 95 %
ENCLOSURE
Material & Colour
aluminium (blue RAL 5012)
Battery-connection
Black and Red cable of 1,5 meter
120 V AC-connection
Cable of 1,5 meter with NEMA 5-15P
Protection category
IP 20
Weight (kg)
1,1
Dimensions (h x w x d in mm)
50 x 85 x 200
STANDARDS
Safety
EN 60335-1, EN 60335-2-29
Emission
EN 55014-1, EN 61000-3-2
Immunity
EN 55014-2, EN 61000-3-3
U (V)
15
14
13
12
I (%)
100
80
60
40
20
0
bulk
float
(max
24 h)
14,4 V
14,0 V
storage
(1 week)
13,2 V
14,4 V
storage
(1 week)
Fig. 1
13,8

Documenttranscriptie

NEDERLANDS ENGLISH The Blue Power IP20 battery chargers will charge and maintain lead-acid batteries and supply users connected to the battery. The DC cables are fitted with battery clamps for mobile use. A pair of ring terminals for 10 mm screw/stud is provided, for permanent installation. De Blue Power IP20 laders zijn bedoeld voor het laden en op spanning houden van loodaccu’s en het voeden van de op de accu aangesloten gebruikers. De laders zijn voorzien van krokodilbekklemmen voor mobiel gebruik en voor vast opgestelde installatie zijn 2 kabelogen bijgeleverd. State of the art microprocessor controlled charge algorithm Geavanceerd microprocessor gestuurd laadsysteem Adaptive 4-stage charge characteristic: bulk – absorption – float – storage The Blue Power IP20 charger features a microprocessor controlled ‘adaptive’ battery management system. The ‘adaptive’ feature will automatically optimise the process relative to the way the battery is being used. The right amount of charge: variable absorption time When only shallow discharges occur, the absorption time is kept short in order to prevent overcharging of the battery. After a deep discharge the absorption time is automatically increased to make sure that the battery is completely recharged. Less maintenance and aging when the battery is not in use: the Storage Mode After the absorption period, the Blue Power IP20 charger will switch to float charge and thereafter, if the battery has not been subjected to discharge, the Storage Mode kicks in. In the storage mode float voltage is reduced to 2,2 V/cell (13,2 V for 12 V battery) to minimise gassing and corrosion of the positive plates. Once a week the voltage is raised back to the absorption level to ‘equalize’ the battery. This feature prevents stratification of the electrolyte and sulphation, a major cause of early battery failure. Adaptieve 4-traps laadkarakteristiek: Bulk-Absorption-Float-Storage Het microprocessor gestuurde ‘adaptieve’ accu management systeem past het laadproces automatisch aan het gebruik van de accu. De juiste hoeveelheid lading: aangepaste absorptietijd Bij geringe ontlading van de accu wordt de absorptie tijd kort gehouden om overlading en overmatig gassen te voorkomen. Na een diepe ontlading wordt de absorptietijd automatisch verlengd om de accu volledig te laden. Minder onderhoud en veroudering wanneer de accu niet gebruikt wordt: de opslag functie De Blue Power IP20 lader schakelt na de absorptie periode eerst over op druppellading en daarna, wanneer er gedurende langere tijd geen ontlading plaatsvindt, over op ‘opslag’. De spanning wordt dan verlaagd tot 2,2 V/cel (13,2 V voor een 12 V accu). De accu zal dan nauwelijks meer gassen en corrosie van de positieve platen wordt zoveel mogelijk beperkt. Eens per week wordt de spanning verhoogd tot absorptie niveau om de accu weer bij te laden; dit voorkomt stratificatie van het elektrolyt en sulfatering van de platen. Installation and instructions for use 1. The battery charger must be installed in a well-ventilated area close to the battery (but, due to possible corrosive gas not above the battery!) 2. Connect the battery clamps or ring terminals to the battery: the minus cable (black) to the minus (–) pole of the battery, the plus cable (red) to the plus (+) pole of the battery. 3. Plug the AC mains cable into the wall socket. The charge cycle will now start. LED indication The green LED will be on when the charger is connected to an AC source. The yellow LED will blink at a fast rate during bulk charge and at a slower rate during absorption charge. The yellow LED will be on continuously after completion of the charge cycle Safety regulations and measures 1. Install the charger according to the stated instructions. 2. Never use the chargers at a location where there is danger of gas or dust explosions. 3. Connections and safety features must be executed according to the locally applicable regulations. 4. In case of wrong polarity connection, the ATO Blade Fuse will blow. Check the polarity of the cable and check the correct value before replacing the ATO Blade Fuse. Learn more about batteries and battery charging To learn more about batteries and charging batteries, please refer to our book ‘Energy Unlimited’ (available free of charge from Victron Energy and downloadable from www.victronenergy.com). For more information about adaptive charging please look under Technical Information on our website. Blue Power Charger IP 20 12/7 12/15 Frequency 28,8 Charge voltage 'float' (V DC) 13,8 27,6 Charge voltage 'storage' (V DC) 13,2 26,4 Charge current (A) 7 / 15 24 / 55 24 Can be used as power supply √ √ Battery reverse polarity (ATO Fuse Blade) Output short circuit Over temperature 10 / 20 10 -20 to +60°C (full rated output up to 40°C) Max 95 % Protection category Weight (kg) Dimensions (h x w x d in mm) Black and Red cable of 1,5 meter Cable of 1,5 meter with NEMA 5-15P IP 20 1,1 50 x 85 x 200 STANDARDS Safety EN 60335-1, EN 60335-2-29 Emission EN 55014-1, EN 61000-3-2 Immunity EN 55014-2, EN 61000-3-3 15 14,4 V 14,4 V 14 13 12 I (%) bulk 100 80 60 40 20 0 Fig. 1 13,8 14,0 V 13,2 V float (max 24 h) storage (1 week) absorption (1 h) 120 V AC-connection aluminium (blue RAL 5012) U (V) absorption (max 8 h) ENCLOSURE Battery-connection 1. Installeer de lader volgens de aangegeven instructies. 2. Gebruik de lader nooit op een locatie met gas of stofontploffingsgevaar. 3. Aansluitingen en beveiligingen moeten in overeenstemming met de plaatselijk geldende voorschriften worden uitgevoerd. 4. Bij verwisseling van de plus- en min aansluitingen op de accu, zal de ATO steekzekering smelten. Controleer of alle verbindingen correct zijn aangesloten voordat er een nieuwe ATO steekzekering met hetzelfde ampèrage wordt geplaatst. 8 Minimum battery capacity (Ah) Material & Colour Veiligheidsvoorschriften en - maatregelen 4-stage adaptive Charge characteristic Humidity (non condensing) De groene LED brandt continu zolang het apparaat op de netspanning is aangesloten. De gele LED knippert snel zolang de maximale laadstroom geleverd wordt (accu minder dan 80% geladen) en knippert langzaam wanneer de absorptie spanning bereikt is en de laadstroom af gaat nemen. Wanneer de laadcyclus is voltooid gaat de lader over op druppellading/opslag, en de gele LED gaat continu branden. 45-65 Hz 14,4 Operating temp. range Indicaties 24/8 Charge voltage 'absorption' (V DC) DC Fuse - ATO Blade (A) 1. De acculader dient in een goed geventileerde ruimte in de omgeving (maar in verband met corrosieve gassen niet boven!) de accu’s geïnstalleerd te worden. 2. Sluit de krokodilbekklemmen of kabelogen aan op de te laden accu: de min kabel (zwart) op de min (–) pool van de accu, de plus kabel (rood) op de plus (+) pool van de accu. 3. Steek de stekker van het AC netsnoer in het stopcontact. De acculader zal nu de laadcyclus starten. 90 – 140Vac Input voltage range Protection Installatie en gebruiksaanwijzingen storage (1 week)