DORMA
DORMA
TS 99 FL EN 2-5
Functional test
Interrupt power supply using manual pushbutton
(e.g. DORMA HT) . The hold-open device is
de-energised and the door is closed .
Clip on end caps .
Break out the tab as marked for the spindle recess in
the cover
Clip on cover .
Ensure that the cables are not damaged in this
process.
Clip on DORMA logo badge .
Clip on slide channel cover .
FINAL INSPECTION AND MAINTENANCE
Instruction sheet relating to the use and application
of hold-open systems.
1)
EN 14600 Appendix C
FURTHER INFORMATION / REGULATIONS
Instruction sheet relating to the use and application
of hold-open systems.
1)
Guidelines for hold-open systems published by the
Institute for Building Technology, Berlin
1)
, or
equivalent national guidelines
FIXING INSTRUCTIONS (Transom mounting)
Technical Data
Operating voltage: 24 V DC ±15%
Power consumption: approx. 2 W
Duty factor: 100% continuous duty
Activation is effected via an external central smoke
detector with integral power pack (e.g. DORMA RMZ).
Note: According to the guidelines for hold-open systems
issued by the Institute for Building Technology, Berlin, it
must be possible to release every hold-open device by
manual means.
If free-swing door closers are used, release must be
initiated by a pushbutton.
The manual release pushbutton used for this must be red
and carry the inscription “Close Door”. The pushbutton
must be in the immediate vicinity of the door (barrier) and
must not be concealed when the door (barrier) is open.
The DORMA TS 99 FL is non-handed.
The following relates to installation for an LH (ISO 6) door.
In the case of RH (ISO 5) doors, apply mirrored
arrangements as applicable.
Drill fixing points for closer and slide channel as per
template.
Lay 24V DC power supply cable from the central
smoke detector.
Fix mounting backplate.
Fix closer to the mounting backplate.
When using the TS99 FL as a replacement unit,
please ensure that the 24V power supply cable is not
damaged.
Connect power supply cable (24V DC from the central
smoke detector) to terminals.
Attach, align and firmly fix slide channel.
Open door .
Position arm at an angle of approx. 80° to the
doorframe and secure with screw .
Close valve for adjusting closing speed .
Preload arm approx. 45° .
Undo screw again , remove arm and, turning 90°,
re-fit and tighten .
Connect arm to slide block.
Adjust spring strength (closing force).
Adjust closing speed 180° - 0° .
Adjust latching action 7° - 0° .
Setting the free-swing function
Setting the free-swing function
Switch on power (24V DC from central smoke
detector). Open the door leaf to the required
hold-open position. The closer spindle is held in
this position by the electro-hydraulic hold-open
device, but the door can be freely moved thanks to
the free-swing arm assembly.
Leave the door open.
1
2
3
4
5
6
7
8
9
10
11
12
13
14