MODBUS REGISTER MAPPEN
INPUT REGISTERS
Data type Description Data Values
1Temperature input unsigned int. Analog temperature input 0—600 0 =
600 = 0,0 °C
60.0 °C
2Vmax unsigned int. Max. motor speed value 170—230 170 =
230 = 170 VAC
230 VAC
3Vmin unsigned int. Min. motor speed value 80—160 80 =
160 = 80 VAC
160 VAC
4Output voltage unsigned int. Current output voltage 0,80—230 0 =
80 =
230 =
0 VAC
80 VAC
230 VAC
5Temperature setpoint unsigned int. Temperature setpoint value GTE21-60-DM
GTE-1-60-DM 50—350
150—350
50 =
150 =
350 =
5,0 °C
15,0 ° C
35,0 °C
6Proportional range unsigned int. Proportional temperature value 1—4
1 =
2 =
3 =
4 =
2 °C
4 °C
6 °C
8 °C
7Hysterisis unsigned int. Hysterisis value 1—4
1 =
2 =
3 =
4 =
0,5 °C
1 °C
2 °C
3 °C
8 Off level unsigned int. Off level value 0, 1 0 =
1 = OFF
ON
9 Sensor status unsigned int. Input sensor status 0, 1 0 =
1 = sensor connected
sensor disconnected
10 Reserved, Returns ‘0’
Nota: De ingangsregisters kunnen gelezen worden via het Modbus commando : “Read input registers”.
HOLDING REGISTERS
Data type Description Data Default Values
1Address unsigned int. Modbus device address 1—247 1
2Modbus baud
rate unsigned int. Modbus communication baud rate 1—4 2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3Modbus parity
mode unsigned int. Parity check mode 0—2 10 =
1 =
2 =
8N1
8E1
8O1
4Device type unsigned int. Device type (Read only) GTE21-60-DM=3013
GTE-1-60-DM=3003
5HW version unsigned int. Hardware version of the device
(Read only) XXXX GTE21-60-DM
GTE-1-60-DM 0x0210 =
0x0200 = HW version 2.10
HW version 2.00
6SW version unsigned int. Software version of the device
(Read only) XXXX GTE21-60-DM 0x0300 = SW version 3.00
GTE-1-60-DM 0x0230 = SW version 2.30
7Operating mode unsigned int. Mode of operation 0—1 00 =
1 = Standalone mode
Modbus mode
8Output overwrite unsigned int. Output overwrite mode 0—1 00 =
1 = Disabled
Enabled
9-10 Reserved, return ‘0’
11 Vmax unsigned int. Max. motor speed value 170 —230 230 170 =
230 = 170 VAC
230 VAC
12 Vmin unsigned int. Min. motor speed value 80—160 80 80 =
160 = 80 VAC
160 VAC
13 Temperature
setpoint unsigned int. Temperature setpoint value GTE21-60-
DM
GTE-1-60-DM
50—350
150—350 150 50 =
150 =
350 =
5,0 °C
15,0 ° C
35,0 °C
14 Proportional
range unsigned int. Proportional range value 1—4 2
1 =
2 =
3 =
4 =
2 °C
4 °C
6 °C
8 °C
15 Hysterisis unsigned int. Hysterisis value 1—4 3
1 =
2 =
3 =
4 =
0,5 °C
1 °C
2 °C
3 °C
16 Off level unsigned int. Off level value 0—1 00 =
1 = OFF
ON
17 Modbus time-out
control unsigned int. Modbus time-out control value 0—1 00 =
1 = Disabled
Enabled
18 Modbust time-
out unsigned int. Modbus time-out value 0—60 11 =
60 = 1 min
60 min.
19 Vout unsigned int. Set override output voltage 0,80—230 00 =
80 =
230 =
0 VAC
80 VAC
230 VAC
20 Reserved, returns ‘0’
Nota: De holding registers kunnen zowel uitgelezen als overschreven worden: “Read Holding Registers”, “Write single register” en “Write Multiple Registers” commandos.
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
ELEKTRONISCHE SNELHEIDSREGELAAR
VOOR VENTILATOREN
GTEX1-60