Sentera Controls DPS-M-4K0 -2 Mounting Instruction

Type
Mounting Instruction
Montage & gebruiksvoorschriften
DPS-M -2 VERSCHILDRUKTRANSMITTER
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 2 - 16
Inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN 3
PRODUCTBESCHRIJVING 4
ARTIKELCODE 4
GEBRUIKSTOEPASSING 4
TECHNISCHE GEGEVENS 4
NORMEN 5
WERKINGSSCHEMA 5
BEKABELING EN AANSLUITING 5
MONTAGE VOORSCHRIFTEN IN STAPPEN 5
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE 7
WERKINGSINSTRUCTIE 8
MODBUS REGISTER MAPPEN 11
TRANSPORT EN OPSLAG 16
GARANTIE INFORMATIE EN BEPERKINGEN 16
ONDERHOUD 16
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 3 - 16
terug naar inhoudstafel
VEILIGHEIDS - & VOORZORGSMAATREGELEN
Voor u aan het werk gaat met ons product, lees aandachtig de technische fiche,
installatie instructie en het aansluit schema. Om uw persoonlijke veiligheid en die
van het toestel te garanderen, evenals de optimale prestaties van het product,
zorg ervoor dat u de volledige technische inhoud begrijpt voordat u het toestel
installeert, in gebruik neemt, of onderhoud doet.
Omwille van de veiligheid en de homologatie (CE) is het eigenhandig ombouwen en
/ of veranderen van het product niet toegestaan.
Het product mag niet worden blootgesteld aan abnormale omstandigheden
zoals: extreme temperaturen, direct zonlicht of trillingen. Chemische dampen met
een hoge concentratie in combinatie met een lange blootstellingstijd kunnen de
prestaties van het product beïnvloeden. Zorg ervoor dat de werkomgeving zo
droog mogelijk is; controleer daarom ook op condensatie plekken.
Alle installaties moeten voldoen aan de lokale gezondheids- en
veiligheidsvoorschriften evenals de plaatselijke elektrische normen. Dit product
kan enkel worden geïnstalleerd door een ingenieur of technicus die een deskundige
kennis heeft van het product en de veiligheidsvoorschriften.
Vermijd contact met onder spanning staande onderdelen; behandel daarom steeds
het product alsof het onder spanning staat. Schakel steeds de stroombron uit
voordat u de voedingskabels aansluit, onderhoud of reparatie werken uitvoert op
het toestel.
Controleer altijd of u de juiste stroomvoorziening toepast op het product en
gebruik kabels met de juiste diameter en kenmerken. Zorg ervoor dat alle bouten,
moeren en schroeven goed zijn aangedraaid en de zekeringen (indien aanwezig)
goed geplaatst zijn.
Het recycleren van de toestellen of verpakking zou men in overweging moeten
nemen, het weggooien van deze moet volgens nationale wetgeving / regels
gebeuren.
Indien u nog vragen heeft, contacteer dan uw technische dienst of een andere
deskundige.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 4 - 16
terug naar inhoudstafel
PRODUCTBESCHRIJVING
De DPS-M-2 serie zijn hoog resolutie verschildruk opnemers met Modbus RTU
communicatie, deze zijn uitgerust met een volledig digitale drukomvormer
ontwikkelt voor een breed gamma aan toepassingen. Alle aansluitingen gebeuren
via de interne RJ45 connectoren. De Luchtstroomsnelheid uitlezing is beschikbaar
door de externe Pitot buis connectie set aan te sluiten. Alle parameters zijn via
Modbus RTU toegankelijk (3SModbus software of Sensistant)
ARTIKELCODE
Artikelcode Voedingsspan-
ning
Aansluiting Bereik, [Pa]
DPS-M-1K0 -2 24 VDC RJ45 0—1.000 Pa
DPS-M-2K0 -2 24 VDC RJ45 0—2.000 Pa
DPS-M-4K0 -2 24 VDC RJ45 0—4.000 Pa
DPS-M-10K -2 24 VDC RJ45 0—10.000 Pa
GEBRUIKSTOEPASSING
Verschildruk, luchtvolume meeting in HVAC toepassingen
Luchtvolume meeting in HVAC toepassingen
Door het gebruik van een externe PSET-PTX-200 Pitot buis connectieset
Druk / luchtstroom bewaking in clean rooms
Zuivere lucht, niet-agressieve en niet-ontvlambare gassen
TECHNISCHE GEGEVENS
Ingebouwde digitale hoog resolutie verschildruksensor
RJ45 connector op de PCB
De luchtsnelheid* kan gemeten worden via de instellingen in Modbus RTU ( door
het gebruik van een externe PSET-PTX-200 pitotbuisconnectieset)
Verscheidenheid aan werkingsgebieden en meetvensters
Reactie tijd: 0,110 s
Geïmplementeerd K-factor
Verschildruk, luchtvolume* of luchtsnelheid uitlezen via Modbus RTU
4-bits 7-segment LED display om de verschildruk of luchtvolumesnelheid weer te
geven
Instelbare minimum en maximum werkingsbereik
Modbus register reset functie (naar fabrieksinstelling)
Vier LEDs die u een licht indicatie
Modbus RTU (RS485) communicatie
Sensor kalibratieprocedure via de tact schakelaar
Maximaal opgenomen vermogen: 1,44 W
Gemiddeld opgenomen vermogen bij normaal gebruik: 1,08 W
Imax: 60 mA
Aluminium aansluit nozzles
Bedrijfsomgevingsvoorwaarden:
temperatuur: -5—65 °C
relatieve vochtigheid: < 95 % rH (niet-condenserend)
Opslagtemperatuur: -20—70 °C
* Enkel van toepassing als de K-factor van de ventilator is gekend. Als de K-factor niet gekend is, kan het luchtdebiet berekend worden via de leiding doorsnede (A) te vermenigvuldigen
met de luchtstroomsnelheid(V) met behulp van volgende formule Q = A * V
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 5 - 16
terug naar inhoudstafel
NORMEN
Laagspanning richtlijn 2006/95/EC:
EMC richtlijnen 2014/30/EC: EN 61000-6-2 2005/AC:2005,
EN 61000-6-3:2007/A1:2011/AC:2012, EN 61326-2-3:2013
WEEE richtlijn 2012/19/EC
RoHs richtlijn 2011/65/EC
WERKINGSSCHEMA
10
20
30
40
50
60
70
80
90
100
Min. druk limiet
Uitgang, [%]
Gemeten waardes (druk, debiet of
luchtsnelheid) t.o.v. uitgang.
Control
range min.
Controllebereik
Max.
Max. pressure
limit
Verschildruk
Lucht volume*
Luchtsnelheid
Buiten bereik
LED4 ON
LED2
ON
Alert
LED3 ON
Alert
LED3 ON
Buiten bereik
LED4 ON
BEKABELING EN AANSLUITING
Voedingsspanning 24 VDC
GND Aarding 
A Modbus RTU (RS485), signaal A
/B Modbus RTU (RS485), signaal /B
Connectie RJ45
MONTAGE VOORSCHRIFTEN IN STAPPEN
Voordat u start aan de installatie van de DPS verschildruk transmitter, lees dan
zorgvuldig deVeiligheid en voorzorgsmaatregelen”. Kies een makkelijke effen
oppervlakte als installatielocatie (een muur, een paneel, etc.):
1. Draai de vier schroeven aan de voorzijde van de behuizing los en verwijder het
deksel.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 6 - 16
terug naar inhoudstafel
2. Bevestig de achterzijde van de behuizing op het oppervlak dit door middel van
geschikte bevestigingsmiddelen te gebruiken volgens de afmetingen en de juiste
montagestand getoond in Fig. 1 Montageafmetingen en Fig. 2 Montage positie.
Fig. 1 Montage Afmetingen Fig. 2 Montage positie
2x Ø 3,
4
49
52
Correct Niet correct
DPS
+_
DPS
+_
DPS
+_
3. Breng de kabel via de wartel naar binnen.
4. Sluit aan zoals aangegeven in Fig. 3 Aansluitingen en die voldoen aan de
informatie in de sectie ”Bekabeling en aansluiting” en Fig. 4 Kabel aansluiting .
Fig. 3 Aansluitingen Fig. 4 Kabel aansluiting
RJ45
24 VDC, A, /B, GND
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
5. Bevestig de slangpilaar met de slangen.
6. Plaats de afdekplaat van de voorzijde terug en bevestig deze.
7. Schakel de voedingsspanning aan.
NOTA Voor de Callibratie en Modbus register reset procedure is meer te vinden in sectie
Werkingsinstructie”.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 7 - 16
terug naar inhoudstafel
Optionele instellingen
Om correcte communicatie te verzekeren, moet de NBT op slechts twee apparaten
op het Modbus RTU-netwerk worden geactiveerd. Schakel indien nodig de NBT-
weerstand in via 3SModbus of Sensistant (Holding register 32).
Voorbeeld 1 Voorbeeld 2
RX
ТX
NBT
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTA Op een Modbus RTU-netwerk moeten twee busterminators (NBT's) worden
geactiveerd.
VERIFICATIE VAN DE INSTALLATIE INSTRUCTIE
Continue groene LED1-indicatie zoals afgebeeld in Fig. 5 Voeding / Modbus-
communicatie indicatie betekent dat het apparaat onder spanning staat. Als LED1
niet brand, controleert de aansluiting opnieuw.
Knipperend groene LED-indicatie zoals afgebeeld in Afb. 5 Voeding / Modbus-
communicatie indicatie betekent dat het apparaat een Modbus-netwerk heeft
gedetecteerd. Als LED1 niet knippert, controleer dan de aansluiting opnieuw.
Voor meer informatie, klik hier om naar de productinformatiepagina te gaan.
Fig. 5 Modbus communicatie indicatie
De status van de LEDs kan enkel gecontroleerd worden als het toestel aan staat.
Neem de nodige veiligheidsmaatregelen!
NOTA
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 8 - 16
terug naar inhoudstafel
WERKINGSINSTRUCTIE
Kalibratie procedure:
1. Koppel de slangpilaren los.
2. Er zijn twee opties om het kalibratieproces te starten:
Schrijf "1" in het hollding register 40 of druk gedurende 4 seconden op de knop
SW1 totdat de groene LED2 en de gele LED3 op de printplaat twee keer knipperen
en laat deze los (zie Fig. 6 Sensor kalibratie en Modbus register reset tact switch
en indicatie).
3. "C" voor 'calibration' verschijnt op het display (zie Fig. 7 a Kalibratie-indicatie ).
4. Na 2 seconden knipperen de groene LED2 en gele LED3 twee keer opnieuw, om
aan te geven dat de kalibratieprocedure is voltooid.
ATTENTIE Zorg dat de slangpilaren vrij en niet aangesloten zijn.
Modbus registers reset procedure:
1. Druk 4 seconden op knop SW1 totdat de groene LED2 en gele LED3 op de
printplaat tweemaal knipperen en houd de knop ingedrukt totdat beide LED's
drie keer knipperen (zie Fig. 6 Sensor kalibratie en Modbus-register reset-
toetsschakelaar en indicatie).
2. De Modbus registers zijn naar hun standaard waardes hersteld
(fabrieksvoorinstellingen).
3. Tijdens de Modbus reset procedure zal de display een “H” aangeven. (Zie Fig. 7 b
Modbus reset jumper)
Fig. 6 Sensor kalibratie en Modbus register
reset tact schakelaar en indicatie Fig. 7 Kalibratie en modbus reset indicatie
7 a Kalibratie-indicatie Fig. 7 b Modbus reset jumper
NOTA Houd de knop ingedrukt totdat beide LED's op de PCB twee keer knipperen en
houd dit vast totdat de LED’s drie keer knipperen. Als de toets wordt losgelaten
voordat de LED’s drie keer knipperde dan heeft de sensor een kalibratie procedure
uitgevoerd in plaats van een Modbus-registers reset procedure.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 9 - 16
terug naar inhoudstafel
Communicatie holding register reset procedure :
1. Plaats de jumper op pennen 1 en 2 van de P4-connector gedurende meer dan
20 seconden terwijl het apparaat onder spanning staat. (Zie Fig. 8 Reset-jumper
Modbus holding-register).
Fig. 8 Reset-jumper Modbus
holding-register
1
2
3
4
5
2. Modbus-communicatie holding-registers van 1 tot 3 worden teruggezet naar
default waarden.
3. Verwijder de jumper.
Verschildruk, luchtstroom volume en luchtsnelheid modus indicaties:
Het display wordt ingeschakeld via het schrijven van "1" in holding register 37
(meetuitlezing). Bij het schrijven van ''0'' wordt het display uitgeschakeld.
Wanneer het display geactiveerd is hangt de modus ervan af van de waarde in
holding register 38 (bedrijfsmodus). Er zijn drie weergavemodi geactiveerd door het
schrijven van de relevante cijfer in holding register 38 - Zie onderstaande tabel:
Meetuitlezing geactiveerd
Waarde in holding
register 38: Weergavemodus:
1 Differential pressure
2Luchtdebiet
3Luchtsnelheid
1. Verschildruk weergavemodus (zie Fig. 9):
1.1 Het LED-display toont het drukverschil met een resolutie van 1 Pa. Een
voorbeeld van het weergeven van 1.000 Pa wordt gegeven in Fig. 9
hieronder.
Fig. 9 Verschildruk indicaties
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 10 - 16
terug naar inhoudstafel
1.2 Buiten bereik indicatie:
De display duidt “Lo” iedere 3 seconden aan als de gemeten verschildruk
lager is dan de minimum limiet van het controle bereik (zie Fig. 10 a).
In geval de gemeten verschildruk hoger is dan de maximum limiet van het
controle bereik, de display duidt ‘HI’ iedere 3 seconden aan (zie Fig. 10 b) .
Fig. 10 Buiten bereik indicatie:
10 a Onder regelbereik minimum limiet 10 b Hoger regelbereik maximum limiet
2. Luchtdebiet weergavemodus:
2.1 Luchtdebiet binnen het bereik 0-9999 m 3 / u wordt weergegeven met een
resolutie van 1 m3 / u. Een voorbeeld van het weergeven van 100 m3 / h
wordt gegeven in Fig. 11 a hieronder.
2.2 Luchtdebiet boven 10.000 m3 / u wordt weergegeven gedeeld door 1.000.
Een voorbeeld van 10.000 m3 / h weergeven is gegeven in Fig. 11 b hieronder.
Afb. 11 Indicaties luchtdebiet en luchtsnelheidmodus
11 a Luchtdebiet (0-9999 m3/ uur) 11 a Luchtdebiet (10,000 m 3 / uur)
Фи
3. Luchtsnelheid weergavemodus:
3.1 Luchtsnelheid wordt weergegeven met een resolutie van 0,1 m / s. Een
voorbeeld van 1,0 m / s wordt gegeven in Fig. 12 hieronder.
Fig. 12 Luchtsnelheid modus
NOTA Een correcte aflezing van de luchtsnelheid is alleen mogelijk als deze ingeschakeld
is door holding register 34 (Pitot-luchtsnelheid) en een sensor aangesloten is op
de juiste Pitot-set (PSET-PTX-200).
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 11 - 16
terug naar inhoudstafel
4. Sensor element storingsmelding:
Bij defect of verlies van communicatie een 'Err'-bericht wordt weergegeven en de
rode LED4 knippert. Zie Fig. 13
Fig. 13 Sensor foutmeldingen
NOTA De sensorstoring wordt alleen weergegeven als het display niet in de UIT-modus
staat (in en uitschakelen via holding register 37).
MODBUS REGISTER MAPPEN
INPUT REGISTERS
Data type Description Data Values
1Output unsigned int. Output value in percentage 0—1.000 100 = 10,0%
2Differential pressure unsigned int. Measured differential pressure
DPS-M-1K0 -2
DPS-M-2K0 -2
DPS-M-4K0 -2
DPS-M-10K -2
0— 1.000
0— 2.000
0— 4.000
0—10.000*
100 =
100 =
100 =
1000 =
100 Pa
100 Pa
100 Pa
1.000 Pa
3Volume flow rate high unsigned int.
Air Volume flow rate
DPS-M-1K0 -2
DPS-M-2K0 -2 0—25.000
0—40.000 1.000 = 1.000 m3/h
4Volume flow rate low unsigned int. DPS-M-4K0 -2
DPS-M-10K -2 0—100.000**
0—180.000** >1.000 = 10.00 m3/h
5Air velocity unsigned int. Measured air velocity 0—300 100 = 10 m/s
6unsigned int. Reserved, returns 0
7Air pressure/volume/
velocity alert flag unsigned int. e flag indicates that measured data is
outside the set alert values. 0—1
0 = Pressure/Volume/Velocity measurement is OK
1 = Pressure/Volume/Velocity measurement is
too low/high
8Air pressure/volume/
velocity range limit flag unsigned int. e flag indicates that measured data is
outside the set range limit values. 0—1
0 = Pressure/Volume/Velocity range is OK
1 = Pressure/Volume/Velocity range is too low/
high
9Sensor fault unsigned int. Indicates sensor failure 0—1 0 = Sensor OK
1 = Sensor fault (Red LED4 blinks)
10 unsigned int. Reserved, returns 0
* Aangezien DPS tot 4 cijfers kan weergeven, zijn de weergegeven waarden 0 tot 9999, d.w.z. als het gemeten drukverschil = 10.000 Pa, geeft het apparaat 9999 weer. De 3SModbus-software geeft
echter altijd de werkelijke waarde aan.
** Wanneer het debiet hoger is dan 10.0003 / h, wordt deze weergegeven gedeeld door 1.000, b.v. als het gemeten debiet = 10650 is, geeft het apparaat 10.65 weer. De 3SModbus-software geeft echter
altijd de werkelijke waarde aan.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 12 - 16
terug naar inhoudstafel
HOLDING REGISTERS
Data type Description Data Default Values
1Device slave address unsigned int. Modbus device address 1—247 1
2Modbus baud rate unsigned int. Modbus communication baud rate 0—6 2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
4.800
9.600
19.200
38.400
57.600
115.200
230.400
3Modbus parity mode unsigned int. Parity check mode
0 =
1 =
2 =
8N1
8E1
8O1
1
0 =
1 =
2 =
None
Even
Odd
4Device type unsigned int. Device type (Read-only)
DPS-M-1K0 -2 =
DPS-M-2K0 -2 =
DPS-M-4K0 -2 =
DPS-M-10K -2 =
1075
1076
1077
1078
5HW version unsigned int. Hardware version of the device (Read-only) XXX 0x0100 = HW version 1.00
6FW version unsigned int. Firmware version of the device (Read-only) XXX 0x0110 = FW version 1.10
7-10 Reserved, return 0
11 Minimum pressure range unsigned int. Minimum of the pressure range 0 - (Max. pressure range - 50 Pa) 010 = 10 Pa
100 = 100 Pa
12 Maximum pressure range unsigned int. Maximum of the pressure range
DPS-M-1K0 -2
DPS-M-2K0 -2
DPS-M-4K0 -2
DPS-M-10K -2
(Min. pressure range + 50 Pa) - 1.000
(Min. pressure range + 50 Pa) - 2.000
(Min. pressure range + 50 Pa) - 4.000
(Min. pressure range + 50 Pa) - 10.000
1.000
2.000
4.000
10.000
100 = 100 Pa
13 Minimum pressure alert unsigned int. Minimum differential pressure alarm value Min pressure range - max. pressure alarm 0
10 = 10 Pa
100 = 100,0 Pa (DPS-M-
10K -2)
14 Maximum pressure alert unsigned int. Maximum differential pressure alarm value
Min pressure
alarm—max.
pressure
range
DPS-X-1K0 -2
DPS-X-2K0 -2
DPS-X-2K0 -2
DPS-X-10K -2
1.000
2.000
4.000
10.000
100=
1000=
100 Pa
1000 Pa
15 Minimum volume flow range high unsigned int. Minimum volume flow range value 0 - (Maximum volume flow range -10 m³/h) 010 = 10 m³/h
16 Minimum volume flow range low unsigned int.
17 Maximum volume flow range
high unsigned int.
Maximum volume flow range value
DPS-M-1K0 -2
DPS-M-2K0 -2
DPS-M-4K0 -2
DPS-M-10K -2
(Min. vol. flow range + 10 m³/h) - 25.000
(Min. vol. flow range + 10 m³/h) - 40.000
(Min. vol. flow range + 10 m³/h) - 100.000
(Min. vol. flow range + 10 m³/h) - 180.000
25.000
40.000
100.000
180.000
20.000 = 20.000 m³/h
18 Maximum volume flow range low unsigned int.
19 Minimum volume flow alert high unsigned int. Minimum volume flow alarm value Min. volume flow range - max. volume flow alarm 01.000 = 1.000 m³/h
20 Minimum volume flow alert low unsigned int.
21 Maximum volume flow alert
high unsigned int.
Maximum volume flow alarm value Min. volume flow alarm - max.
volume flow range
DPS-X-1K0 -2
DPS-X-2K0 -2
DPS-X-4K0 -2
DPS-X-10K -2
25.000
40.000
100.000
180.000
10.000 = 10.000/h
22 Maximum volume flow alert
low unsigned int.
23 Minimum air velocity range unsigned int. Minimum air velocity range value 0 - (Max. air velocity range - 1 m/s) 0100 = 10,0 m/s
24 Maximum air velocity range unsigned int. Maximum air velocity range value (Min. air velocity range +1 m/s) - 300 300 300 = 30,0 m/s
25 Minimum air velocity alert unsigned int. Minimum air velocity alarm value Min. air velocity range—Max. air velocity alarm 0100 = 10,0 m/s
26 Maximum air velocity alert unsigned int. Maximum mum air velocity alarm value Min. velocity alarm—Max. air velocity range 300 300 = 30,0 m/s
27 Reserved, returns 0
28 Response time unsigned int. Response time selection 1—100 10 10 = 1,0 s
29 Power-up timer unsigned int. Power-up timer before setting alert and
range limit flags. 0—1.000 60 s 100 = 100 s
30 K-factor. unsigned int. K-factor according to motor / fan
specifications 0—1.000 0
31 Output type unsigned
int Select analog / digital output type1 1—3 1
1
2
3
0—10 VDC
0—20 mA
0—100% PWM,
32 Modbus network resistance
terminator (NBT) unsigned int. Sets device as an end device on the line 0—1 00 =
1 =
NBT disconnected
NBT connected
33 Altitude unsigned int. Current altitude 0—5.000 01.000 = 1.000 m
34 Pitot air velocity unsigned int. Enables Air Velocity Readout. 0—1 00 =
1 =
Disabled
Enabled
35 Duct cross sectional area [ cm2]unsigned int. Calculation of the Volume Flow Rate when
K-factor is not known 0—32.000 00 =
100 =
Not used
100 cm2
36 Reserved, returns 0
37 Measurement readout unsigned int. 4-digit measurement indication ON / OFF 0—1 10 =
1 =
LED display off
LED display on
38 Operating mode unsigned int. Operating mode selection 1—3 1
1 =
2 =
3 =
Differential
pressure(1)
Volume flow rate(2)
Air velocity(3)
39 Reserved, returns 0
40 Recalibrate sensor unsigned int. Sensor recalibration 0—1 00 =
1 =
Inactive
Active
41-49 Reserved, return 0
50 Modbus registers reset unsigned int. Reset Modbus Holding Registers to
default values 0—1 00 =
1 =
Idle
Reset Modbus
Registers
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
(1)Gebruik de PSET-QF of PSET-PVC-set om het drukverschil te meten;
(2) Om het debiet van de luchtstroom te meten met gebruik van PSET-PTx, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 35. Om het debiet van de
luchtstroom te meten met gebruik van PSET-GF of PSET-PVC, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 30.
(3) Gebruik de PSET-PTx-set om luchtsnelheid te meten.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 13 - 16
terug naar inhoudstafel
INPUT REGISTERS (zie Tabellen Input registers hierboven)
De input registers zijn enkel uitlees. Alle data kan uitgelezen worden door het ‘Read
Inputs Registers’ commando te gebruiken. De twee Input register tabelle hierboven
tonen de data type zoals weergegeven en de wijze hoe die te interpreteren.
Input register 1 bevat de waarde van de uitgang als een percentage van het
geselecteerde uitgangssignaal.
Input register 2 bevat de waarde van de huidige gemeten verschildruk.
Input registers 3 and 4 geven informatie over het huidige luchtdebiet. In input
register 3 wordt het meest belangrijke byte (MBS) gehouden, terwijl input
register 4 het minste belangrijke byte (LBS) houdt. De waarde in deze registers
is gelijk aan de K-factor van de ventilator (input register 30) vermenigvuldigd
met vierkantswortel van het huidige drukverschil. Als de K-factor niet bekend is,
wordt het debiet berekend door het kanaaldoorsnede-oppervlak (input register
35) te vermenigvuldigen met luchtstroom snelheid (d.w.z Pitot-luchtsnelheid
ingeschakeld via holding register 34).
Input register 5 is "Luchtsnelheid". Het is alleen actief wanneer holding register
34 is ingesteld op "1".
Input register 6 wordt niet gebruikt. Wanneer geadresseerd, wordt deze terug '0'.
Input register 7 geeft aan dat de gemeten luchtdruk buiten de ingestelde
alarmwaarden valt. Als de gemeten waarde buiten de druk-, debiet- of
snelheidswaarschuwings waarden valt die worden gedefinieerd door registers 13,
14, 19, 20, 21, 22, 25 en 26, wordt deze '0'. Het is niet actief tijdens opstart,
gedefinieerd in holding register 29.
Input register 8 geeft aan dat de gemeten luchtdruk, debiet of snelheid buiten
de ingestelde waarden ligt. Als de gemeten waarde buiten de druk-, volume- of
snelheidslimietbereikwaarden ligt die zijn gedefinieerd door de registers 11, 12, 15,
16, 17, 18, 23 en 24, wordt deze '1' . Het is niet actief tijdens opstart, gedefinieerd
in holding register 29.
Input register 9 geeft een probleem aan met de sensor.
Input register 10 worden niet gebruikt. Wanneer geadresseerd, wordt deze terug
'0'.
Holding registers (zie Tabel Holding registers hierboven)
Deze registers zijn schrijf / lees registers en deze kunnen gemanaged worden via
“Read Holding Registers”, “Write single register” enWrite Multiple Registers
commandos. De registers die niet gebruikt worden zijn enkel-lees en, daarom, geeft
het schrijven in deze noch een error weer, noch worden de waardes in deze registers
gewijzigd.
Holding register 1 omvat het sensoradres op welk de sensor beantwoord binnen
het Modbus netwerk. Het standaard adres is ‘1. Het kan via twee mogelijkheden
aangepast worden.
1. Zend commando “Write Single Register” met adres ‘1’ en schrijf de nieuwe adres
waarde.
2. Connecteer enkel uw toestel aan een master controller of PC applicatie en
zend het commando “Write Single Register” naar adres ‘0’ (Modbus broadcast
address) en schrijf een nieuw adres waarde.
De volgende twee holding registers (2 en 3) bevatten ook Modbus instellingen.
Veranderingen aan deze registers wijzigt ook de communicatie instellingen. De
standaard Modbus instellingen zijn als weergegeven in de Modbus Protocol
Specification.
De volgende drie registers (4, 5 en 6) zijn “Read only. Zij geven informatie terug
over de sensor hardware en software versie.
De volgende vier registers (7, 8,9 en 10) worden niet gebruikt. De input registers
zijn read-only.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 14 - 16
terug naar inhoudstafel
NOTA Het schrijven in deze registers geeft u noch een Modbus fout, noch wijzigingen!
Holding register 11 bepalen het minimale drukbereik. Het kan niet lager worden
ingesteld dan het minimale druk plus het minimale drukbereik (dat wil zeggen 50
Pa).
NOTA De minimum control range kan niet hoger dan de maximum range min 50 Pa
ingesteld worden.
Holding register 12 definieert het maximale drukbereik. Het kan niet lager worden
ingesteld dan het minimale druk plus het minimale drukbereik (dat wil zeggen 50
Pa). Dit register aanvaard waarden als gespecifieerd in de Modbus map. (zie Tabel
Holding registers hierboven) Het schrijven van waarden die niet gespecificeerd zijn
in de Modbus-map verandert niets aan dit register.
NOTA Het maximale drukbereik kan niet worden ingesteld onder het minimale bereik
plus 50 Pa.
Holding registers 13 en 14 bevatten respectievelijk de minimale en maximale
verschildruk alarmwaarde.
Holding registers 15 en 16 houden het minimale debietbereik, dat niet hoger kan
worden ingesteld dan het maximale debietbereik minus het minimale debietbereik
(10 m³ / h ). De luchtdebiet wordt gemeten in m3 / h. Holding register 15 bevat het
meest belangrijke byte (MBS), terwijl holding register 16 het minste belangrijke
byte (LBS) van het minimale debietbereik bevat.
Holding registers 17 en 18 houden de maximale debiet vast, die niet lager kan
worden ingesteld dan het minimale debiet plus de minimale debietbereik (dwz 10
m³ / h ). De luchtdebiet wordt gemeten in m3 / h. Holding register 17 bevat het
meest belangrijke byte (MBS), terwijl holding register 18 het minste belangrijke
byte (LBS) van het maximale debietbereik bevat.
Holding registers 19 en 20 houden de alarmwaarde voor de minimale debiet vast.
De luchtdebiet wordt gemeten in m3 / h. Holding register 19 bevat het meest
belangrijke byte (MBS), terwijl holding register 20 het minste belangrijke byte
(LBS) van het minimale debiet melding bevat.
Holding registers 21 en 22 houden de maximale debiet alarmwaarde vast
De luchtdebiet wordt gemeten in m3 / h. Holding register 21 bevat het meest
belangrijke byte (MBS), terwijl holding register 22 het minste belangrijke byte
(LBS) van het maximale debiet melding bevat.
Holding registers 23 en 24 houden respectievelijk het minimale en maximale
luchtsnelheid bereik. Het minimale luchtsnelheidbereik kan niet hoger worden
ingesteld dan het maximale luchtsnelheid minus minimale luchtsnelheidbereik (1
m / s). Het maximale luchtsnelheidbereik kan niet lager worden ingesteld dan het
minimale luchtsnelheid plus de minimale luchtsnelheidbereik (1 m / s).
NOTA De waarde van het minimum limit kan niet hoger zijn dan die van de maximum
limit. Als een waarde hoger dan de opgegeven maximum wordt ingevoerd in dit
register, zal deze automatisch dezelfde waarde als de maximum limiet weergeven.
Holding registers 25 en 26 houden de minimale en maximale luchtsnelheid
alarmwaarden.
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 15 - 16
terug naar inhoudstafel
NOTA Als een waarde lager dan de opgegeven minimum wordt ingevoerd in holding
register 16, zal deze automatisch dezelfde waarde als de minimum limiet
weergeven. (Bijvoorbeeld: wanneer bij min. 200 en max. 1.000, de max. waarde
veranderd wordt naar 150, d.w.z. lager is dan de min. waarde, dan zal het toestel
automatisch de min. waarde op 150 instellen omdat de min. niet hoger kan zijn
dan de max.)
Holding register 27 worden niet gebruikt. Wanneer geadresseerd, wordt deze
terug '0'.
Holding register 28 bevat de responstijd, waarden van 1 tot 100 kan worden
ingegeven, waarbij 10 = 1,0 seconde.
Holding register 29 bevat de waarde van de 'Power-up timer' voordat de
waarschuwing en bereiklimiet meldingen worden ingesteld. Standaard is deze 60
s. Tijdens dit interval worden de alarmen en bereiklimieten niet vergeleken met
de huidige verschiledruk / debiet / -snelheid en de waarschuwings en bereiklimiet
melding registers blijven '0'. U kan de waardes in dit register enkel wijzigen
gedurende de eerste 60 s. nadat u het toestel heeft aan gezet.
Holding register 30 is voor de K-factor. Geef de K-factor van de gebruikte ventilator
/ drive, als deze gekend is (controleer de datafiche van de geselecteerde ventilator
/ drive). De standaard waarde is 0, u kan waardes van 01.000 invoeren. Als u hier
een waarde buiten het bereik schrijft zal er niks gewijzigd worden in dit register.
Holding register 31 worden niet gebruikt. Wanneer geadresseerd, wordt deze
terug '0'.
Holding register 32 geeft aan of het toestel een eindapparaat of niet is via het
verbinden van de NBT.
Holding register 33 bevat informatie over de huidige hoogte, variërend tussen "0"
tot "5.000". De standaard waarde is '0' d.w.z 0 m.
Holding register 34 maakt luchtsnelheid aflezing mogelijk. Als de waarde '0' is,
is luchtsnelheid uitlezing uitgeschakeld. Als de waarde '1' is, wordt luchtsnelheid
uitlezing ingeschakeld en is deze toegankelijk in het input register 5. PSET-
PTX-200 Pitot-buis is noodzakelijk.
Hold-register 35 wordt gebruikt voor de berekening van het debiet wanneer
K-factor niet bekend is. Dit register accepteert waarden van 0 tot 32.000. Wanneer
de waarde 0 is, wordt deze niet gebruikt. Bij gebruik, waarden van 1 tot 32.000
overeenkomen met het doorsnede oppervlak van de buis in cm2 .
Hold register 36 wordt niet gebruikt. Wanneer geadresseerd, wordt deze terug
'0'.
Hold register 37 wordt gebruikt om te bepalen of de LED display aan of uit zal zijn.
Holding register 38 definieert bedrijfsmodi, d.w.z verschildruk, debiet of
luchtsnelheid.
Hold register 39 wordt niet gebruikt. Wanneer geadresseerd, wordt deze terug
'0'.
Holding register 40 wordt gebruikt voor hercalibratie van de sensor.
Holding registers 4149 are not used. When addressed, they return “0”.
Holding register 50 resets all Modbus Holding registers to their default values.
When the process is complete, the value of the register is automatically set to “0”
(Idle).
VERSCHILDRUKTRANSMITTER
DPS-M -2
www.sentera.eu
MIW-DPS-M-2-NL-000 - 20 / 12 / 18 16 - 16
terug naar inhoudstafel
TRANSPORT EN OPSLAG
Vermijd schokken en extreme condities; bewaar in originele verpakking.
GARANTIE INFORMATIE EN BEPERKINGEN
Twee jaar vanaf de leveringsdatum op fabricage fouten. Elke aanpassing of verandering
van het product ontheft de fabrikant van alle mogelijke verantwoordelijkheid. De
fabrikant wijst alle verantwoordelijkheid af voor alle drukfouten of vergissingen
in deze data en aanpassingen of modificaties die zijn aangebracht na de tijd van
publicatie.
ONDERHOUD
Onder normale condities is dit een onderhoudsvrij product. Bij vervuiling, reinig met
een droge of licht vochtige doek. In geval van sterke verontreiniging, reinig met een
niet agressief product. Onder deze omstandigheid koppel het toestel los van de
voeding. Let erop dat geen vloeistoffen het toestel kunnen binnentreden. Enkel
terug aansluiten als het toestel volledig droog is.
VERSCHILDRUKTRANSMITTER