INSTALLATION & MAINTENANCE INSTRUCTIONS
327 - 1/4" Solenoid valves for safety applications
according to the IEC 61508 standard (Suffix SL)
The IEC 61508 standard describes a pack-
age of general requirements for every phase
of the lifecycle of safety systems. The reliabil-
ity analysis performed by the TUV has shown
that these valves are suitable for use in such
systems up to safety class SIL4. For installa-
tion, maintenance, test and commissioning
of these valves, the documents prescribed
by the IEC 61508 standard should be used.
Depending on the determined SIL class,
they also prescribe the required measure
of authority, skills and independence of the
concerning personal. All indications and
prescriptions within the subjoined general
installation and maintenance instructions
are the basis for these above mentioned
documents. In order to warrant the reliability,
the supplemental prescriptions mentioned
below, should be observed as well.
· Please notice, that the correct type of
threading is used during installation,
corresponding the type of threading men-
tioned in the type code on the nameplate
(see the explanation of the type code
mentioned below).
· Possible use of sealing tapes should be
minimised in order to prevent parts from
getting into the valve and block the valve
function.
· These valves may only be used in the
“Normally closed” configuration, in which
case, the de-energising of the valve
blocks the flow through the valve.
· These solenoid valves are intended for
use on clean dry air or inert gas, filtered
to 50 micrometer or better. The dew point
of the media should be at least 10ºC
(18ºF) below the minimum temperature
to which the media could be exposed,
to prevent freezing. If lubricated air is
used, the lubricant must be compatible
with the used elastomers. Instrument air
in compliance with ANSI/ISA Standard
S7.3 (1975) exceeds the above require-
ments and is, therefore, an acceptable
media for these valves.
· The exhaust port should be protected
either by means of the supplied filter or
with the help of a pipe connection to a
central filter system. In both cases, these
protectors should be connected to either
port 1 or 3, depending on the valve type.
(See drawing) When using a different type
of filter element, the determined reliability
of the valve can not be assured. In that
case, please contact Asco joucomatic or
one of its authorised representatives.
De IEC 61508 standaard beschrijft een pak-
ket met algemene eisen, voor elke fase van
de levenscyclus van veiligheidssystemen.
De betrouwbaarheidsanalyse door de
TÜV heeft aangetoond, dat deze ventielen
geschikt zijn voor dergelijke systemen
t/m veiligheidsklasse SIL4. Voor de instal-
latie, onderhoud, test en ingebruikname,
dient men gebruik te maken van de door
de IEC 61508 standaard voorgeschreven
documenten. Afhankelijk van de bepaalde
SIL klasse, beschrijven deze tevens de
vereiste mate van bevoegdheid, specialisatie
en onafhankelijkheid van het betreffende
personeel.Als basis voor bovengenoemde
documenten dienen alle aanwijzingen en
voorschriften in de meegeleverde alge-
mene installatie- en onderhoudsinstructies.
Ter waar-borging van de betrouwbaarheid,
dienen tevens onder-staande aanvullende
voorschriften te worden opgevolgd:
· Let erop, dat tijdens de installatie het
juiste type schroefdraad wordt gebruikt,
conform het draad type aangegeven in
de type code op de naamplaat. (Zie on-
derstaande uitleg van de type code).
· Eventueel gebruik van afdichttapes dient
te worden geminimaliseerd om te voorko-
men dat delen hiervan in de klep geraken
en de ventielfunctie blokkeren.
· Deze ventielen mogen alleen in de
“Normally Closed” configuration worden
toegepast, waar bij het afvallen van het
ventiel de doorstroming wordt geblok-
keerd.
· Deze ventielen zijn geschikt voor gebruikt
met schone droge lucht of neutraal gas,
gefilterd tot 50 micron of beter. Het dauw-
punt van dit medium moet minimaal 10ºC
(18ºF) onder de minimale temperatuur
liggen waaraan het medium kan worden
onderheven om bevriezing te voorkomen.
Bij gebruik van gesmeerde lucht, moet
het smeermiddel verenigbaar zijn met de
interne elastomeren. Instrumenten lucht
overeenkomstig de ANSI/ISA standaard
S7.3 (1975) is beter dan boven-staande
eisen en is derhalve een acceptabel
medium voor deze kleppen.
· De ontluchtingspoort dient te worden
beschermd met behulp van het meege-
leverde filter of met een pijp-verbinding
naar een centraal filtersysteem. In beide
gevallen dienen deze te worden aange-
sloten op poort 1 of 3, afhankelijk van het
type ventiel. (Zie tekening) Indien gebruikt
wordt gemaakt van een ander type filter,
kan de vastgestelde betrouwbaarheid niet
meer gewaarborgd worden. Neem in dat
geval contact op met Asco joucomatic of
één van haar geautoriseerde vertegen-
woordigers.
INSTRUCTIONS D'INSTALLATION ET D'ENTRETIEN
Electrovannes 327 – 1/4" pour applications de protection
conformes à la norme IEC 61508 (Suffixe SL)
BETRIEBSANLEITUNG
327 - 1/4"-Magnetventile für Sicherheitsanwendungen
gemäß IEC 61508 (Nachsatz SL)
INSTRUCCIONES DE INSTALACIONY MANTENIMIENTO
327-Válvulas de solenoide de 1/4" para aplicaciones de
seguridad según según el estándar IEC 61508 (Sufijo SL)
ISTRUZIONI DI INSTALLAZIONE E MANUTENZIONE
Valvole a solenoide 327 - 1/4" per applicazioni di
sicurezza secondo la norma CEI 61508 (Suffix SL)
INSTALLATIE- EN ONDERHOUDSINSTRUCTIES
327 - 1/4" magneetventiel voor veiligheidsapplicaties
volgens de IEC 61508 standaard (Suffix SL)
El estándar IEC 61508 describe un conjunto
de requisitos generales para cada una de las
fases del ciclo de vida de los sistemas de
seguridad. El análisis de fiabilidad realizado
por el TÜV ha demostrado que estas válvu-
las son adecuadas para su uso en dichos
sistemas, hasta la clasificación de seguridad
SIL4. Para la instalación, mantenimiento,
pruebas y puesta en servicio de estas
válvulas se deben utilizar los documentos
emitidos por el estándar IEC 61508. Depen-
diendo de la clasificación SIL determinada,
también indican la medida de autoridad re-
querida, los conocimientos e independencia
del personal involucrado. Todas las indica-
ciones y recomendaciones englobadas en
las instrucciones generales de instalación
y mantenimiento constituyen la base de los
documentos anteriormente mencionados.
Para garantizar la fiabilidad deben observar-
se además las indicaciones suplementarias
mencionadas a continuación.
· Por favor observe que se utilice el tipo
adecuado de rosca durante la instalación,
correspondiente al tipo de rosca mencio-
nado en el código del tipo indicado en la
placa de identificación (vea la explicación
del código de tipo a continuación).
· Se debe minimizar en lo posible el uso
de cinta selladora para evitar que entren
partículas en la válvula y bloqueen su
funcionamiento.
· Estas válvulas solamente pueden utili-
zarse en la configuración “normalmente
cerradas”, en cuyo caso, la desenergiza-
ción de la válvula bloquea el flujo a través
de ella.
· Estas válvulas de solenoides están dise-
ñadas para utilizarse solamente en aire
limpio o gas inerte, filtrado a 50 micró-
metros o superior. El punto de rocío del
medio debe estar al menos10º C (18º F)
por debajo de la temperatura mínima a
la que el medio puede exponerse, para
evitar la congelación. Si se emplea aire
lubricado, el lubricante debe ser com-
patible con los elastómeros utilizados.
El aire del instrumento que cumple el
estándar ANSI/ISA S7.3 (1975) supera
los requisitos anteriores y es un medio
adecuado para estas válvulas.
· La puerta de escape debe protegerse
mediante el filtro suministrado o con la
ayuda de una conexión de tubo a un
sistema de filtro central. En ambos casos,
estos protectores deben conectarse a
las puertas 1 o 3, dependiendo del tipo
de válvula (véase el diagrama). Cuando
se utilice un tipo distinto de elemento de
filtrado, no puede asegurarse la fiabilidad
determinada de la válvula. En ese caso,
por favor póngase en contacto con
ASCO/JOUCOMATIC o alguno de sus
representantes autorizados.
La norme IEC 61508 décrit un ensemble
d’exigences générales pour chaque phase
du cycle de vie des systèmes de sécurité.
L’analyse de la fiabilité réalisée par le TÜV
a révélé que ces vannes conviennent pour
des systèmes dont la classe de sécurité peut
aller jusque SIL4. Pour l’installation, la main-
tenance, la mise à l’épreuve et la mise en
service de ces vannes, il faudrait utiliser les
documents fournis par la norme IEC 61508.
En fonction de la classe SIL terminée,
ils prescrivent également la mesure requise
concernant l’autorité, les qualifications et l’in-
dépendance du personnel impliqué. Toutes
les indications et prescriptions renfermées
dans les instructions générales d’installation
et de maintenance constituent la base de ces
documents susmentionnés. Afin de garantir
la fiabilité, il conviendrait également d’ob-
server les prescriptions complémentaires
mentionnées ci-après.
· Veuillez noter que le type correct de
taraudage est utilisé durant l’installation,
qui correspond au type de taraudage
mentionné dans le code type figurant sur
la plaque signalétique (voir l’explication
du code type mentionné ci-après).
· Il faudrait réduire au maximum l’utilisa-
tion possible d’un ruban d’étanchéi
afin d’empêcher l’introduction de par-
ticules dans la vanne et son blocage
éventuel.
· Ces vannes peuvent uniquement être
utilisées dans la configuration « Norma-
lement fermée », où la mise hors tension
de la vanne bloque le flux passant dans
la vanne.
· Ces électrovannes doivent être utilisées
avec de l’air sec ou du gaz inerte propre,
filtré jusqu’à 50 micromètres ou mieux
encore. Le point de rosée du média de-
vrait être d’au moins 10 degrés Celsius
(18°F) en dessous de la température
minimale à laquelle le média peut être ex-
posé, afin d’éviter la congélation. En cas
d’utilisation d’air lubrifié, le lubrifiant doit
être compatible avec les élastomères
utilisés. L’instrument air conforme à la
norme ANSI/ISA S7.3 (1975) dépasse
les exigences ci-dessus et constitue, par
conséquent, un média acceptable pour
ces vannes.
· Le port d’évacuation devrait être protégé
soit au moyen du filtre fourni ou à l’aide
d’un raccordement de tuyau vers un sys-
tème de filtre central. Dans les deux cas,
ces protecteurs devraient être raccordés
soit au port 1 ou 3, selon le type de vanne
(voir le dessin). En cas d’utilisation d’un
type d’élément de filtre différent, la fiabilité
déterminée de la vanne ne peut pas être
assurée. Dans ce cas, veuillez contacter
ASCO/JOUCOMATIC ou l’un de ses
représentants officiels.
Die Norm IEC 61508 beschreibt allgemeine
Anforderungen bezogen auf sämtliche
Lebenszyklusphasen von Sicherheits-
systemen. Die vom TÜV durchgehrte
Zuverlässigkeitsanalyse hat ergeben, dass
diese Werte für den Einsatz in solchen Sys-
temen bis Sicherheitsklasse SIL4 geeignet
sind. Bei der Montage, Wartung, Prüfung
und Inbetriebnahme dieser Ventile sollten
die gemäß IEC 61508 auszugebenden
Dokumente verwendet werden. Je nach
festgelegter SIL-Klasse wird auch das erfor-
derliche Ausmaß der Befugnisse, Fähigkei-
ten und Eigenständigkeit des betreffenden
Personals vorgeschrieben. Sämtliche in der
beiliegenden Allgemeinen Betriebsanleitung
enthaltenen Angaben und Vorschriften
bilden die Grundlage r die vorstehend
genannten Dokumente. Zur Gewährleistung
der Zuverlässigkeit sollten die nachfolgend
aufgeführten Zusatzvorschriften ebenfalls
beachtet werden.
· Dabei ist zu beachten, dass bei der Mon-
tage der korrekte Gewindetyp entspre-
chend dem in dem Typenschlüssel auf
dem Typenschild genannten Gewindetyp
verwendet wird (siehe Erläuterung des
Typenschlüssels unten).
· Die Verwendung von Dichtungsband
sollte minimal gehalten werden, um das
Eindringen von Fremdkörpern in das
Ventil und die Blockade der Ventilfunktion
zu verhindern.
· Diese Ventile dürfen nur in der Konfigu-
ration “Normal geschlossen” eingesetzt
werden. In diesem Fall wird der Ventil-
durchfluss beim Ausschalten des Ventils
gesperrt.
· Diese Magnetventile eignen sich für den
Einsatz in Verbindung mit trockener Luft
oder Schutzgas nach Filtration bis auf
50 Mikrometer oder höher. Der Konden-
sationspunkt der Medien sollte mindes-
tens 10°C unter der Mindesttemperatur
liegen, der die Medien glicherweise
ausgesetzt sind, um ein Gefrieren zu
verhindern. Bei Verwendung von schmier-
stoffhaltiger Luft muss der Schmierstoff
mit den verwendeten Elastomeren ver-
träglich sein. Instrumentenluft gemäß der
ANSI/ISA-Norm S7.3 (1975) überschreitet
die obigen Anforderungen und ist daher ein
akzeptables Medium für diese Ventile.
· Die Entlüftungsöffnung sollte entweder
mit Hilfe des mitgelieferten Filters oder
über einen Rohrleitungsanschluss an ein
zentrales Filtersystem geschützt werden.
In beiden Fällen sollten diese Schutzvor-
richtungen je nach Ventiltyp entweder
an Anschluss 1 oder 3 angeschlossen
werden (siehe Zeichnung). Bei Verwen-
dung einer anderen Art von Filterelement
kann die festgelegte Zuverlässigkeit des
Ventils nicht garantiert werden. In diesem
Fall ist mit ASCO/JOUCOMATIC Rück-
sprache zu halten.
La norma CEI 61508 descrive un pacchet-
to di requisiti generali per ciascuna fase
del ciclo di vita dei sistemi di sicurezza.
L’analisi di affidabilità realizzata da TÜV ha
dimostrato che queste valvole sono adatte
per l’uso in sistemi conformi alla classe di
sicurezza SIL4. Per l’installazione, la manu-
tenzione, la prova e la messa in servizio di
queste valvole, si devono usare i documenti
pubblicati relativi alla norma CEI 61508.
In funzione della classe SIL stabilita,
prescrivono anche il criterio di valutazione
necessario dell’autorità, la specializzazio-
ne e l’autonomia del personale coinvolto.
Tutte le indicazioni e le prescrizioni presenti
nelle istruzioni generali di installazione e
manutenzione sono la base dei documenti
sopramenzionati. Per garantire l’affidabilità,
si devono rispettare le prescrizioni aggiuntive
descritte di seguito.
· Si noti, che viene usato il tipo corretto di
filettatura durante l’installazione, corri-
spondente al tipo di filettatura menzionato
nel codice tipo sulla targhetta (consultare
la spiegazione del codice tipo descritta
sotto).
· Si deve ridurre al minimo il possibile uso
del nastro saldante in modo da evitare
l’ingresso di particelle nella valvola e il
conseguente blocco della funzione della
valvola.
· È possibile usare queste valvole nella
sola configurazione Normalmente
chiusa”, nel qual caso, la diseccitazione
della valvola blocca il flusso che passa
attraverso di essa.
· Queste elettrovalvole sono previste per
l’uso con aria asciutta pulita o gas inerte,
filtrata a 50 o più micrometri. Per evitare il
congelamento, il punto di rugiada dei fluidi
deve essere di almeno 10ºC inferiore alla
temperatura minima a cui i fluidi possono
essere esposti. Se viene usata l’aria lubri-
ficata, il lubrificante deve essere compa-
tibile con gli elastomeri usati. L’aria nello
strumento conformemente alla norma
ANSI/ISA S7.3 (1975) supera i requisiti
e pertanto è un supporto accettabile per
queste valvole.
· Il foro di scarico deve essere protetto me-
diante il filtro in dotazione o con l’ausilio di
un raccordo al sistema centrale di filtrag-
gio. In entrambi i casi, queste protezioni
devono essere collegate al foro 1 o 3,
in funzione del tipo di valvola (osservare il
disegno). In caso d’uso di un tipo differente
di filtro, non sarà garantita l’affidabilità
stabilita della valvola. In tal caso, si prega
di contattare ASCO/JOUCOMATIC o uno
dei suoi rappresentanti autorizzati.

Documenttranscriptie

INSTALLATION & MAINTENANCE INSTRUCTIONS 327 - 1/4" Solenoid valves for safety applications according to the IEC 61508 standard (Suffix SL) The IEC 61508 standard describes a package of general requirements for every phase of the lifecycle of safety systems. The reliability analysis performed by the TUV has shown that these valves are suitable for use in such systems up to safety class SIL4. For installation, maintenance, test and commissioning of these valves, the documents prescribed by the IEC 61508 standard should be used. Depending on the determined SIL class, they also prescribe the required measure of authority, skills and independence of the concerning personal. All indications and prescriptions within the subjoined general installation and maintenance instructions are the basis for these above mentioned documents. In order to warrant the reliability, the supplemental prescriptions mentioned below, should be observed as well. · Please notice, that the correct type of threading is used during installation, corresponding the type of threading mentioned in the type code on the nameplate (see the explanation of the type code mentioned below). · Possible use of sealing tapes should be minimised in order to prevent parts from getting into the valve and block the valve function. · These valves may only be used in the “Normally closed” configuration, in which case, the de-energising of the valve blocks the flow through the valve. · · These solenoid valves are intended for use on clean dry air or inert gas, filtered to 50 micrometer or better. The dew point of the media should be at least 10ºC (18ºF) below the minimum temperature to which the media could be exposed, to prevent freezing. If lubricated air is used, the lubricant must be compatible with the used elastomers. Instrument air in compliance with ANSI/ISA Standard S7.3 (1975) exceeds the above requirements and is, therefore, an acceptable media for these valves. The exhaust port should be protected either by means of the supplied filter or with the help of a pipe connection to a central filter system. In both cases, these protectors should be connected to either port 1 or 3, depending on the valve type. (See drawing) When using a different type of filter element, the determined reliability of the valve can not be assured. In that case, please contact Asco joucomatic or one of its authorised representatives. AJN: 123-620-139 INSTRUCCIONES DE INSTALACIONY MANTENIMIENTO 327-Válvulas de solenoide de 1/4" para aplicaciones de seguridad según según el estándar IEC 61508 (Sufijo SL) El estándar IEC 61508 describe un conjunto de requisitos generales para cada una de las fases del ciclo de vida de los sistemas de seguridad. El análisis de fiabilidad realizado por el TÜV ha demostrado que estas válvulas son adecuadas para su uso en dichos sistemas, hasta la clasificación de seguridad SIL4. Para la instalación, mantenimiento, pruebas y puesta en servicio de estas válvulas se deben utilizar los documentos emitidos por el estándar IEC 61508. Dependiendo de la clasificación SIL determinada, también indican la medida de autoridad requerida, los conocimientos e independencia del personal involucrado. Todas las indicaciones y recomendaciones englobadas en las instrucciones generales de instalación y mantenimiento constituyen la base de los documentos anteriormente mencionados. Para garantizar la fiabilidad deben observarse además las indicaciones suplementarias mencionadas a continuación. · Por favor observe que se utilice el tipo adecuado de rosca durante la instalación, correspondiente al tipo de rosca mencionado en el código del tipo indicado en la placa de identificación (vea la explicación del código de tipo a continuación). · Se debe minimizar en lo posible el uso de cinta selladora para evitar que entren partículas en la válvula y bloqueen su funcionamiento. IMGEN-04-X-R0 · · · GB ES Estas válvulas solamente pueden utilizarse en la configuración “normalmente cerradas”, en cuyo caso, la desenergización de la válvula bloquea el flujo a través de ella. Estas válvulas de solenoides están diseñadas para utilizarse solamente en aire limpio o gas inerte, filtrado a 50 micrómetros o superior. El punto de rocío del medio debe estar al menos10º C (18º F) por debajo de la temperatura mínima a la que el medio puede exponerse, para evitar la congelación. Si se emplea aire lubricado, el lubricante debe ser compatible con los elastómeros utilizados. El aire del instrumento que cumple el estándar ANSI/ISA S7.3 (1975) supera los requisitos anteriores y es un medio adecuado para estas válvulas. La puerta de escape debe protegerse mediante el filtro suministrado o con la ayuda de una conexión de tubo a un sistema de filtro central. En ambos casos, estos protectores deben conectarse a las puertas 1 o 3, dependiendo del tipo de válvula (véase el diagrama). Cuando se utilice un tipo distinto de elemento de filtrado, no puede asegurarse la fiabilidad determinada de la válvula. En ese caso, por favor póngase en contacto con ASCO/JOUCOMATIC o alguno de sus representantes autorizados. INSTRUCTIONS D'INSTALLATION ET D'ENTRETIEN Electrovannes 327 – 1/4" pour applications de protection conformes à la norme IEC 61508 (Suffixe SL) La norme IEC 61508 décrit un ensemble d’exigences générales pour chaque phase du cycle de vie des systèmes de sécurité. L’analyse de la fiabilité réalisée par le TÜV a révélé que ces vannes conviennent pour des systèmes dont la classe de sécurité peut aller jusque SIL4. Pour l’installation, la maintenance, la mise à l’épreuve et la mise en service de ces vannes, il faudrait utiliser les documents fournis par la norme IEC 61508. En fonction de la classe SIL déterminée, ils prescrivent également la mesure requise concernant l’autorité, les qualifications et l’indépendance du personnel impliqué. Toutes les indications et prescriptions renfermées dans les instructions générales d’installation et de maintenance constituent la base de ces documents susmentionnés. Afin de garantir la fiabilité, il conviendrait également d’observer les prescriptions complémentaires mentionnées ci-après. · Veuillez noter que le type correct de taraudage est utilisé durant l’installation, qui correspond au type de taraudage mentionné dans le code type figurant sur la plaque signalétique (voir l’explication du code type mentionné ci-après). · Il faudrait réduire au maximum l’utilisation possible d’un ruban d’étanchéité afin d’empêcher l’introduction de particules dans la vanne et son blocage éventuel. · · · Ces vannes peuvent uniquement être utilisées dans la configuration « Normalement fermée », où la mise hors tension de la vanne bloque le flux passant dans la vanne. Ces électrovannes doivent être utilisées avec de l’air sec ou du gaz inerte propre, filtré jusqu’à 50 micromètres ou mieux encore. Le point de rosée du média devrait être d’au moins 10 degrés Celsius (18°F) en dessous de la température minimale à laquelle le média peut être exposé, afin d’éviter la congélation. En cas d’utilisation d’air lubrifié, le lubrifiant doit être compatible avec les élastomères utilisés. L’instrument air conforme à la norme ANSI/ISA S7.3 (1975) dépasse les exigences ci-dessus et constitue, par conséquent, un média acceptable pour ces vannes. Le port d’évacuation devrait être protégé soit au moyen du filtre fourni ou à l’aide d’un raccordement de tuyau vers un système de filtre central. Dans les deux cas, ces protecteurs devraient être raccordés soit au port 1 ou 3, selon le type de vanne (voir le dessin). En cas d’utilisation d’un type d’élément de filtre différent, la fiabilité déterminée de la vanne ne peut pas être assurée. Dans ce cas, veuillez contacter ASCO/JOUCOMATIC ou l’un de ses représentants officiels. ISTRUZIONI DI INSTALLAZIONE E MANUTENZIONE Valvole a solenoide 327 - 1/4" per applicazioni di sicurezza secondo la norma CEI 61508 (Suffix SL) La norma CEI 61508 descrive un pacchetto di requisiti generali per ciascuna fase del ciclo di vita dei sistemi di sicurezza. L’analisi di affidabilità realizzata da TÜV ha dimostrato che queste valvole sono adatte per l’uso in sistemi conformi alla classe di sicurezza SIL4. Per l’installazione, la manutenzione, la prova e la messa in servizio di queste valvole, si devono usare i documenti pubblicati relativi alla norma CEI 61508. In funzione della classe SIL stabilita, prescrivono anche il criterio di valutazione necessario dell’autorità, la specializzazione e l’autonomia del personale coinvolto. Tutte le indicazioni e le prescrizioni presenti nelle istruzioni generali di installazione e manutenzione sono la base dei documenti sopramenzionati. Per garantire l’affidabilità, si devono rispettare le prescrizioni aggiuntive descritte di seguito. · Si noti, che viene usato il tipo corretto di filettatura durante l’installazione, corrispondente al tipo di filettatura menzionato nel codice tipo sulla targhetta (consultare la spiegazione del codice tipo descritta sotto). · Si deve ridurre al minimo il possibile uso del nastro saldante in modo da evitare l’ingresso di particelle nella valvola e il conseguente blocco della funzione della valvola. · · · FR IT È possibile usare queste valvole nella sola configurazione “Normalmente chiusa”, nel qual caso, la diseccitazione della valvola blocca il flusso che passa attraverso di essa. Queste elettrovalvole sono previste per l’uso con aria asciutta pulita o gas inerte, filtrata a 50 o più micrometri. Per evitare il congelamento, il punto di rugiada dei fluidi deve essere di almeno 10ºC inferiore alla temperatura minima a cui i fluidi possono essere esposti. Se viene usata l’aria lubrificata, il lubrificante deve essere compatibile con gli elastomeri usati. L’aria nello strumento conformemente alla norma ANSI/ISA S7.3 (1975) supera i requisiti e pertanto è un supporto accettabile per queste valvole. Il foro di scarico deve essere protetto mediante il filtro in dotazione o con l’ausilio di un raccordo al sistema centrale di filtraggio. In entrambi i casi, queste protezioni devono essere collegate al foro 1 o 3, in funzione del tipo di valvola (osservare il disegno). In caso d’uso di un tipo differente di filtro, non sarà garantita l’affidabilità stabilita della valvola. In tal caso, si prega di contattare ASCO/JOUCOMATIC o uno dei suoi rappresentanti autorizzati. BETRIEBSANLEITUNG 327 - 1/4"-Magnetventile für Sicherheitsanwendungen gemäß IEC 61508 (Nachsatz SL) Die Norm IEC 61508 beschreibt allgemeine Anforderungen bezogen auf sämtliche Lebenszyklusphasen von Sicherheitssystemen. Die vom TÜV durchgeführte Zuverlässigkeitsanalyse hat ergeben, dass diese Werte für den Einsatz in solchen Systemen bis Sicherheitsklasse SIL4 geeignet sind. Bei der Montage, Wartung, Prüfung und Inbetriebnahme dieser Ventile sollten die gemäß IEC 61508 auszugebenden Dokumente verwendet werden. Je nach festgelegter SIL-Klasse wird auch das erforderliche Ausmaß der Befugnisse, Fähigkeiten und Eigenständigkeit des betreffenden Personals vorgeschrieben. Sämtliche in der beiliegenden Allgemeinen Betriebsanleitung enthaltenen Angaben und Vorschriften bilden die Grundlage für die vorstehend genannten Dokumente. Zur Gewährleistung der Zuverlässigkeit sollten die nachfolgend aufgeführten Zusatzvorschriften ebenfalls beachtet werden. · Dabei ist zu beachten, dass bei der Montage der korrekte Gewindetyp entsprechend dem in dem Typenschlüssel auf dem Typenschild genannten Gewindetyp verwendet wird (siehe Erläuterung des Typenschlüssels unten). · Die Verwendung von Dichtungsband sollte minimal gehalten werden, um das Eindringen von Fremdkörpern in das Ventil und die Blockade der Ventilfunktion zu verhindern. · · · Diese Ventile dürfen nur in der Konfiguration “Normal geschlossen” eingesetzt werden. In diesem Fall wird der Ventildurchfluss beim Ausschalten des Ventils gesperrt. Diese Magnetventile eignen sich für den Einsatz in Verbindung mit trockener Luft oder Schutzgas nach Filtration bis auf 50 Mikrometer oder höher. Der Kondensationspunkt der Medien sollte mindestens 10°C unter der Mindesttemperatur liegen, der die Medien möglicherweise ausgesetzt sind, um ein Gefrieren zu verhindern. Bei Verwendung von schmierstoffhaltiger Luft muss der Schmierstoff mit den verwendeten Elastomeren verträglich sein. Instrumentenluft gemäß der ANSI/ISA-Norm S7.3 (1975) überschreitet die obigen Anforderungen und ist daher ein akzeptables Medium für diese Ventile. Die Entlüftungsöffnung sollte entweder mit Hilfe des mitgelieferten Filters oder über einen Rohrleitungsanschluss an ein zentrales Filtersystem geschützt werden. In beiden Fällen sollten diese Schutzvorrichtungen je nach Ventiltyp entweder an Anschluss 1 oder 3 angeschlossen werden (siehe Zeichnung). Bei Verwendung einer anderen Art von Filterelement kann die festgelegte Zuverlässigkeit des Ventils nicht garantiert werden. In diesem Fall ist mit ASCO/JOUCOMATIC Rücksprache zu halten. INSTALLATIE- EN ONDERHOUDSINSTRUCTIES 327 - 1/4" magneetventiel voor veiligheidsapplicaties volgens de IEC 61508 standaard (Suffix SL) De IEC 61508 standaard beschrijft een pakket met algemene eisen, voor elke fase van de levenscyclus van veiligheidssystemen. De betrouwbaarheidsanalyse door de TÜV heeft aangetoond, dat deze ventielen geschikt zijn voor dergelijke systemen t/m veiligheidsklasse SIL4. Voor de installatie, onderhoud, test en ingebruikname, dient men gebruik te maken van de door de IEC 61508 standaard voorgeschreven documenten. Afhankelijk van de bepaalde SIL klasse, beschrijven deze tevens de vereiste mate van bevoegdheid, specialisatie en onafhankelijkheid van het betreffende personeel.Als basis voor bovengenoemde documenten dienen alle aanwijzingen en voorschriften in de meegeleverde algemene installatie- en onderhoudsinstructies. Ter waar-borging van de betrouwbaarheid, dienen tevens onder-staande aanvullende voorschriften te worden opgevolgd: · Let erop, dat tijdens de installatie het juiste type schroefdraad wordt gebruikt, conform het draad type aangegeven in de type code op de naamplaat. (Zie onderstaande uitleg van de type code). · Eventueel gebruik van afdichttapes dient te worden geminimaliseerd om te voorkomen dat delen hiervan in de klep geraken en de ventielfunctie blokkeren. · · · DE NL Deze ventielen mogen alleen in de “Normally Closed” configuration worden toegepast, waar bij het afvallen van het ventiel de doorstroming wordt geblokkeerd. Deze ventielen zijn geschikt voor gebruikt met schone droge lucht of neutraal gas, gefilterd tot 50 micron of beter. Het dauwpunt van dit medium moet minimaal 10ºC (18ºF) onder de minimale temperatuur liggen waaraan het medium kan worden onderheven om bevriezing te voorkomen. Bij gebruik van gesmeerde lucht, moet het smeermiddel verenigbaar zijn met de interne elastomeren. Instrumenten lucht overeenkomstig de ANSI/ISA standaard S7.3 (1975) is beter dan boven-staande eisen en is derhalve een acceptabel medium voor deze kleppen. De ontluchtingspoort dient te worden beschermd met behulp van het meegeleverde filter of met een pijp-verbinding naar een centraal filtersysteem. In beide gevallen dienen deze te worden aangesloten op poort 1 of 3, afhankelijk van het type ventiel. (Zie tekening) Indien gebruikt wordt gemaakt van een ander type filter, kan de vastgestelde betrouwbaarheid niet meer gewaarborgd worden. Neem in dat geval contact op met Asco joucomatic of één van haar geautoriseerde vertegenwoordigers.